Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Synchronous Generator
1 Introduction
The main aim of Electronic load controller is to reduce the cost of Hydropower in-
stallation by replacing speed controlled mechanical Governor System. A mechanical
governor maintains constant frequency on generator by controlling the flow of water.
Mostly, two things were required for the installation of this device.
2 Literature Review
In this section various work performed by different authors are presented. Shailendra
Kumar Rai , et al have proposed the Simulation on Pulse width modulation based
ELC’S. There are several components to sense voltage current and frequency. When-
ever there is change or fluctuation in the users load, the blast load is triggered which
helps to calculate pulse width modulation. Also, the driver circuit dissipate excessive
power in order to gain steady state. In this system DC based control switching is used
[1].
Nan Win Aung and Aung Ze Ya have proposed an ELC which is based on Binary
load action. In this concept many dummy loads are connected with different power
rating of various electric load. Whenever there is a change in an electric load, frequency
will be varied and at a time microcontroller will calculates the required amount of
power which is necessary to maintain the stability of the system. So, with the help of
switching devices dummy loads are trigged [10].
Binary load regulation is a technique where dummy load is made up of several series
and parallel combination of resistive loads arranged in a binary pattern. Whenever there
is a change in customers load there is a proportional change in frequency of the power
system, microcontroller calculates required combination of blast load required to make
system’s frequency constant. Therefore switching operation is followed during transi-
ent period only. In stable condition switching is in “OFF” state, so full voltage is applied
to the new combination of blast load. In this proposed system harmonics are not intro-
duced in the steady state condition [11].
Hardware required:
─ . . Rectifier
─ Driver Circuit( thyristor is used )
─ Frequency Sensing Circuit
─ Notch Detection Circuit
─ Current sensing Circuit
─ Microcontroller Board
Software required:
─ . PROTEUS
─ ARDUINO
─ ISIS 7 PROFESSIONAL
Function of this circuit is to detect zero crossing of waveform whenever there is zero
cross it gives high output. This circuit has huge importance to calculate exact timing
for firing angle of thyristor.
U1
7
1
3
6
2
4
5
LM741 D1
DIODE
TO PIC
B
R2
15K C
R3
2R2
Current transformer is connected to the main supply and shunt resistance is connected
in parallel to CT refer Fig.3.
We have selected VCC as 10V.Therefore resistance is so selected if it is 10V it should
give 10 mA.
VS=I ×R (2)
10=10mA × R
𝑅2
Vout=VS (1+ ) (3)
𝑅3
Atmega328p contains 10-bit analog to digital converter, which means that we can map
input Voltage from 0 to Operating voltages, either 3.3 or 5 into integer value from 0 to
1024.
In this proposed system frequency sensor has been used for the real time measurement
of frequency variation. For this circuit, a step down transformer is used for the conver-
sion of high voltage into low voltage. Also, a transistor is used to convert sine wave
into square wave refer Fig. 6. A Frequency has been calculated with following set of
code.
duration1= pulseIn(freqpin, HIGH); // when the wave has
on waveforem
duration2= pulseIn(freqpin, LOW); //when the wave has low
or off waveform
sum=duration1+duration2; //sum of both the duration for
one complete cycle
freq=(1/sum*1000000); //time is being converted into
second so that we can get frequency
Frequency (f) = 1/time
R3
2k2
TR1 D1 R1 Q1
2N2222
2k2
DIODE
V1
VSINE +88.8
AC Volts
R2 A
1k
B
TRAN-2P2S
C
T
R2
220R
U3
1 6
TO PIC Heater
U1 OV1
Q4010L5 OVEN
2 4
MOC3021
V1
VSINE
In order to achieve the stated objective, the following methodologies were adopted:
5 Proposed System
Fig.8 shows the proposed scheme of Electronic load controller. The main function of
proposed scheme is that, it has the ability to draw different current from different phase
of the generator terminals which allow it to compensate for the unbalanced consumer
current. Therefore the frequency of the system is balanced. This feature results in gen-
erator currents being balanced even when consumer loads are unbalanced .Thus over-
loading of generator is also reduced. The proposed system is embedded with variety of
sensors like Zero cross detector, Triac gate driver circuit, Frequency sensor, Current
sensor, Notch detection sensor. The function of frequency sensor is to sense change in
frequency at any instance of time. Current Sensor is used to calculate current in each
phase. zero cross circuit is used to detect correct timing for firing of TRIAC at certain
delay or firing angle. Notch detecting circuit is used to calculate waveform’s ON and
OFF time period to calculate exact firing delay.
Fig. 8. Proposed proteus schematic circuit diagram
6 Results
Table 1. Gate driver Circuit
The proposed scheme is tested for various conditions refer Fig.8 and there output is
noted as mentioned above refer Table 1. In condition first, we didn’t apply any con-
sumer’s load therefore all power is drained to the blast load. The microcontroller detect
no load and hence frequency is increased. Microcontroller calculates the require amount
of firing angle and fires TRIAC. Total power of the generator was drained to the dummy
load in first condition.
Fig. 9. Oscilloscope reading and practical Implementation circuit
In second condition, Consumer’s current was 4.6Amp but the generator was rated as
7.2Amp.threrfore the required amount of firing angle is calculated by microcontroller
and dummy current was 2.6 Amp. Thus generated current and consumers current is
balanced by the application of proposed scheme. Therefore frequency of the system is
remained constant
In third condition consumer’s current was 7.2 Amp. Therefore generated current and
consumers current is equal so there is no firing of TRIAC. In condition four, consumer’s
current is more than generated current which is main cause of overloading of generator,
therefore system is shutdown to prevent damage to the power system.
Firing angle calculation
One complete cycle =50Hz (Asia region)
Time taken to complete once complete cycle = 1/ (Frequency)
1 full 50Hz wave is equals to 1/50=20ms
Every zero crossing thus can be represented as: (50Hz) -> 10ms (1/2 Cycle) or
10ms=10000 Micro Seconds
Therefore at 0 microseconds the firing is full and at 10000 microseconds TRIAC is
completely OFF.
By the use of PID based Electronic load controller we can easily control and monitor
frequency of the generator. We can reduce worse case of overloading on generator.
Therefore there is very less risk of damage of generator which is very costly. Thus,
Frequency can be maintained constant with least error.
Since this is an era of science and technology, we will make better monitoring and
controlling by the implementation of IOT. So that people from another location can
control manage and update the system. We can also use excess drained power to charge
up street light batteries
Acknowledgment
An Author would like to express sincere gratitude to Amritsar group of colleges and
Professor Dr. Narinder Sharma, HOD Gurjeet Singh for their guidance, support and
valuable suggestions to proceed on the project during research. He also wants to thanks
to his guider Lochan Basyal for his support and help.
I want to express my appreciation to my wonderful parents. My parents deserve spe-
cial thanks for giving me the very best that they could. Thanks to my father Er. Aftab
alam and brother irfan alam, for all the interest that he has shown in my education ever
since I was a child. Thanks to my mother and sister for her affection and gentleness
towards me
References
1. Shailendra Kumar Rai, O. P. Rahi , Sunil Kumar “Implementation of Electronic Load Con-
troller for Control of Micro Hydro Power Plant”,IEEE 2015
2. B. Singh, S.S. Murthy, M. Goel and A.K.Tandon, “A Steady State Analysis on Voltage and
Frequency Control of Self-Excited Induction Generator in Micro-Hydro System,” Interna-
tional conference on power electronics, Drives and Energy Systems, pp. 1-6, 2006.
3. O.P. Rahi, A.K. Chandel, M.G. Sharma, “Simulation Studies for Refurbishment and Uprating
of Hydro Power Plants,” International Journal of Advances in Engineering, Science and Tech-
nology (IJAEST), vol. 1, no. 2, pp. 200-208, 2012.
4. O.P. Rahi, A.K. Chandel, M.G. Sharma, “Fuzzy Logic Based Approach for Condition Moni-
toring of Hydro Generator,” International Journal of Soft Computing, vol. 6, no. 41, pp. 85-
90, 2011.
5. B. Singh, S.S. Murthy and S. Gupta, “Analysis and Design of Electronic Load Controller for
Self-Excited Induction Generators,” IEEE Transactions on Energy Conversion, vol. 21, pp.
285-293, 2006.
6. Pankaj Kapoor, L. Phunchock, S. Kumar, and O.P. Rahi, “Frequency Control of Micro Hydro
Power Plant using Electronic Load Controller,” International Journal of Engineering Research
and Application(IJERA),vol. 2, no. 4, pp.733-737, 2012.
7. O.P. Rahi, Sanjeev Kumar Gagrai, and Sumit Kumar Rawat, “Simulation of Turbine Govern-
ing in Hydro Power Plants,” International Conference on Future Trends in Electronics and
Electrical Engineering (FTEE – 2013) Bangkok, Thailand, 13 -14 July, 2013, pp. 34-37.
8. O.P. Rahi, A.K. Chandel, M.G. Sharma, “Investigations into the design of a hydro power
plants,” Indian Journal of Power and River Valley Development, pp. 132-144, 2014.
9. O.P. Rahi and G. Kumar, “Simulation Studies for Refurbishment and Uprating of Hydro
Power Plants,” IEEE Power & Energy Society General Meeting 2014 at the Gaylord National
Resort and Convention Center located in National Harbor, Washington, DC, pp. 1-5, 27-31
July, 2014.
10. Nan Win Aung and Aung Ze Ya, “Microcontroller Based Electrical Parameter Monitoring
11. D. Henderson, ”An advanced electronic load governor for control of micro hydroelectric gen-
eration,” IEEE Transactions on Energy Conversion, vol. 13, no. 3, pp. 300-304, 1998.