MEETING ASHRAE 90.

1-1999 (2001)
ENERGY STANDARD
FOR BUILDINGS

A REFERENCE GUIDE TO
MEETING THE NEW MINIMUM EFFICIENCY
REQUIREMENTS FOR HVAC EQUIPMENT
WITH CARRIER PRODUCTS

Carrier Corporation
Syracuse, New York

December 2002
TABLE OF CONTENTS
INTRODUCTION ............................................................................................................................................ 3

PART 1 – CROSS-REFERENCE
UNITARY AIR CONDITIONERS AND CONDENSING UNITS (Table 6.2.1A)......................................... 7
Air Conditioners, Air-Cooled ............................................................................................................ 7
Air Conditioners, Water-Cooled......................................................................................................... 9
Condensing Units, Air-Cooled............................................................................................................ 11
Condensing Units, Water-Cooled ....................................................................................................... 11
HEAT PUMPS (Table 6.2.1B) ......................................................................................................................... 12
Air-Cooled .......................................................................................................................................... 12
Water-Source ...................................................................................................................................... 14
Groundwater-Source........................................................................................................................... 15
Ground-Source.................................................................................................................................... 16
WATER CHILLING PACKAGES (Table 6.2.1C) .......................................................................................... 17
Air-Cooled, with Condenser, Electric................................................................................................. 17
Air-Cooled, without Condenser, Electric............................................................................................ 17
Water-Cooled, Electric, Positive Displacement (Reciprocating)........................................................ 17
Water-Cooled, Electric, Positive Displacement (Rotary Screw and Scroll) ....................................... 18
Water-Cooled, Electric, Centrifugal ................................................................................................... 19
Water-Cooled, Absorption, Single Effect ........................................................................................... 19
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS (Table 6.2.1D).............................. 20
Packaged Terminal Air Conditioners.................................................................................................. 20
Packaged Terminal Heat Pumps ......................................................................................................... 21
Room Air Conditioners Without Louvered Sides ............................................................................... 22
HEAT REJECTION EQUIPMENT (Table 6.2.1G)......................................................................................... 23
Air-Cooled Condensers....................................................................................................................... 23

PART 2 – REFERENCE GUIDE


Model No. Page Model No. Page Model No. Page
07D, E........................................25 38SB..........................................43 50GS..........................................55
09AW, AZ .................................25 38SC..........................................43 50GX .........................................55
09DE, DK..................................26 40CG .........................................39 50HG .........................................56
16JB...........................................26 40CS..........................................39 50HJ .................................... 56-57
19XR .........................................27 40HD .........................................40 50HJQ ................................. 57-58
23XL..........................................27 40QAB ......................................40 50HQL.......................................58
30GTN, GTR.............................28 40QAE.......................................41 50HX .........................................59
30GUN, GUR ............................29 40QKB ......................................41 50JS...........................................59
30GXN, GXR............................29 40QKE.......................................42 50JX ..........................................60
30HK .........................................30 40QNB ......................................42 50JZ...........................................60
30HL..........................................30 40QNE, QNH ............................43 50KQA, KQD............................61
30HWA .....................................30 40-Series Multi-Zone.................43 50RHC, RVC ............................61
30HWB, HWC ..........................30 48AJ, AW..................................44 50RHR, RVR ...................... 62-63
30HXA ......................................31 48AK, AY .................................44 50RHS, RVS, RDS....................64
30HXC ......................................31 48GP, GPN................................45 50RTG.......................................65
30RA .........................................32 48GS, GSN................................45 50RWS ......................................65
38AH ................................... 32-33 48GX, GXN...............................46 50SX..........................................66
38AKS.......................................34 48HG .........................................46 50TFF........................................66
38AN .........................................42 48HJ ..........................................47 50TFQ .......................................67
38AQ .........................................35 48JZ, JZN ..................................48 50TM................................... 67-68
38AQS.......................................35 48TF ..........................................49 50VQA, VQD............................68
38ARD ................................ 35-36 48TM................................... 49-50 50XJ ..........................................69
38ARQ ......................................36 48Z ............................................50 50Z ............................................69
38ARS .......................................37 50AH .........................................51 50ZH .........................................70
38ARZ.......................................38 50AJ, AW..................................51 50ZP ..........................................70
38BK .........................................43 50AK, AY .................................52 52CE..........................................71
38CG .........................................39 50BRN.......................................52 52CQ .........................................71
38CS..........................................39 50BYN ......................................53 52FC, FE ...................................72
38HDC, HDL ...................... 40-44 50BZN.......................................53 52PC, PE ...................................72
38HDS.......................................43 50EJQ, EWQ .............................54 52PQ..........................................73
38QR ................................... 41-42 50GL .........................................54 90MA, MF.................................73
90MU ........................................74

2
INTRODUCTION

ASHRAE Standard 90.1-1999 (2001) defines for equipment that are rated in accordance with an
minimum efficiency requirements for HVAC established test procedure. Equipment not listed in
equipment. This paper is designed to assist to help the ASHRAE Standard 90.1 tables have no minimum
you find the right Carrier product necessary to meet performance requirements.
those requirements.

ASHRAE Standard 90.1 defines minimum efficiency HOW TO USE THIS REFERENCE
requirements in a series of tables in Section 6.2, This paper is divided into two parts. Part 1 is a cross-
Mandatory Provisions. reference between the ASHRAE Standard 90.1
requirements (including current addenda) and Carrier
Table 6.2.1A Air Conditioners and products. Efficiency requirements are grouped and
Condensing Units referenced as they are in Tables 6.2.1A through
Table 6.2.1B Heat Pumps 6.2.1G of the standard. The specific efficiency
Table 6.2.1C Water Chilling Packages requirement for each equipment type, size category,
Table 6.2.1D Packaged Terminal and Room and subcategory is presented as a heading to a table
Air Conditioners and Heat that lists the Carrier products meeting that
Pumps requirement. An example is shown in Figure 1
Table 6.2.1E Furnaces, Duct Furnaces, and below. Part 2 of this paper is a reference guide to
Unit Heaters Carrier commercial products that meet ASHRAE
Table 6.2.1F Boilers Standard 90.1.
Table 6.2.1G Heat Rejection Equipment
Table 6.2.1H The 1999 publication of ASHRAE Standard 90.1
Table 6.2.1I Non-Standard Centrifugal indicated two efficiency requirements: the first
Table 6.2.1J Chillers labeled “Minimum Efficiency,” and the second
labeled, “Efficiency as of 10/29/01.” All equipment
Tables 6.2.1A through 6.2.1G define requirements manufactured after October 29, 2001, must meet the

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

<65,000 Btu/h
All Split System 10.0 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Console, duct-free split system (with 38CG condensing unit), 1.5 to 2.5
40CG 10.0 39
tons
Satellite, duct-free split system (with 38HDC/HDL condensing unit),
40HD 10.0 – 11.0 40
2 to 4 tons
Under ceiling, duct-free split system (with 38HDC/HDL condensing
40QAB 10.1 – 12.0 40
unit), 1.5 to 5 tons
Cassette, duct-free split system (with 38HDC/HDL condensing unit),
40QKB 10.5 – 11.8 41
1.5 to 3 tons

Fig. 1. Example of the cross-reference between one ASHRAE Standard 90.1 Table 6.2.1A
requirement and appropriate Carrier product model numbers

3
second requirement. Equipment manufactured before factory-installed options and field-installed
October 29, 2001 must meet the first requirement, accessories available. To obtain a complete
even if it is installed after the indicated date. In most description of all features and options for a specific
tables, addenda to the standard have deleted the time model, please review the listed catalog, or consult
distinction, and now show only the requirement for your local Carrier sales representative.
equipment after October 29, 2001, labeled
“Minimum Efficiency”. This document follows the In all cases, performance data listed are for 60 Hz
pattern of the amended ASHRAE tables, showing products at ARI standard conditions.
only one column labeled “Minimum Efficiency.” In
all cases, the minimum efficiency indicated is for
equipment manufactured after October 29, 2001. DEFINITIONS
The following definitions are taken from ASHRAE
If multiple performance requirements are listed, the Standard 90.1-1999 (2001).
equipment must meet all requirements unless
otherwise exempted by footnotes in the table. Coefficient of performance (COP) – cooling: the
ratio of the rate of heat removal to the rate of energy
To find the available equipment options, begin by input, in consistent units, for a complete refrigerating
determining the requirement from the appropriate system or some specific portion of that system under
table (or amended table) in ASHRAE Standard 90.1. designated operating conditions.

Next, enter the Part 1 Cross-Reference of this paper Coefficient of performance (COP), heat pump –
by finding the same ASHRAE Standard 90.1 table heating: the ratio of the rate of heat delivered to the
number, equipment type, size category, and rate of energy input, in consistent units, for a
subcategory. The Carrier equipment options are complete heat pump system, including the
listed in order of model number with a short compressor and, if applicable, auxiliary heat, under
description of the product. After each listed Carrier designated operating conditions.
product there is a page number that indicates where
to find more information in the Part 2 Reference Energy efficiency ratio (EER): the ratio of net
Guide. cooling capacity in Btu/h to the total rate of electric
input in watts under designated operating conditions.
In Part 2, the Reference Guide is arranged by model
number and presents a brief snapshot of the product Heating seasonal performance factor (HSPF): the
including expanded efficiency information, major total heating output of a heat pump during its normal
features, and options. In each case, the current annual usage period for heating (in Btu) divided by
applicable Carrier catalog is listed. Please refer to the total electric energy input during the same period.
the catalog for a more complete description of the
features, benefits, and options of each product. Integrated part-load value (IPLV): a single-
number figure of merit based on part-load EER,
COP, or kW/ton, expressing part-load efficiency for
REFERENCE GUIDE air-conditioning and heat pump equipment on the
Every effort has been made to present the most up to basis of weighted operation at various load capacities
date information in the Reference Guide to Carrier for the equipment.
Commercial Products. But, because Carrier
continually improves its products, model NAECA: National Appliance Energy Conservation
specifications and designs may be changed or Act of 1987.
discontinued at any time without notice or obligation.
The most up to date product catalogs and literature Seasonal energy efficiency ratio (SEER): the total
are always available from your local Carrier sales cooling output of an air conditioner during its normal
representative, or at Carrier’s web site, annual usage period for cooling (in Btu) divided by
http://www.commercial.carrier.com. This document the total electric energy input during the same period
is updated regularly. (in watt-hours).

The Features and Options listed in the Reference


Guide are a sampling of the many standard attributes,

4
PART 1

CROSS-REFERENCE
BETWEEN ASHRAE STANDARD 90.1
MINIMUM EFFICIENCY REQUIREMENTS AND
CARRIER COMMERCIAL PRODUCTS

5
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

<65,000 Btu/h
All Split System 10.0 SEER ARI 210/240
(Note 1)

Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.

CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.

40CG Console, duct-free split system (with 38CG condensing unit), 1.5 to 2.5 tons 10.0 39
Satellite, duct-free split system (with 38HDC/HDL condensing unit), 2 to 4
40HD 10.0 – 11.0 40
tons
Under ceiling, duct-free split system (with 38HDC/HDL condensing unit), 1.5
40QAB 10.1 – 12.0 40
to 5 tons
Cassette, duct-free split system (with 38HDC/HDL condensing unit), 1.5 to 3
40QKB 10.5 – 11.8 41
tons
High wall, duct-free split system (with 38AN & 38HDC/HDL condensing
40QNB 10.5 – 12.0 42
unit), 0.75 to 2 tons
40-Series Multi-zone, duct-free split system, 2 to 5 tons 10.0 – 12.0 43
Indoor, single-package cooling units with remote air-cooled condenser, 5 to 15
50BZN 10.0 53
tons
90MU Single-package, condenserless electric cooling unit, 3 to 10 tons (Available in 2002) 74

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

<65,000 Btu/h
All Single Package 9.7 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.

CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Single-package unit, gas heating or low NOx gas heating, electric cooling,
48GP, GPN 12.0 – 13.0 45
optional variable-speed blower, Puron refrigerant, 2 to 5 tons
Single-package unit, gas heating or low NOx gas heating, electric cooling, 1.5
48GS, GSN 10.0 45
to 5 tons
Single-package unit, gas heating or low NOx gas heating, electric cooling, 2 to
48GX, GXN 12.0 46
5 tons
48HJ Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 13.0 47
48TF Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 10.0 49
48TM Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 10.0 49
Indoor unit, horizontal, single-package, electric cooling, optional electric
50AH 9.75 – 10.8 51
heating, 2 to 5 tons
Indoor unit, air-cooled, single-package, vertical, electric cooling, optional hot
50BYN 10.0 53
water or steam heating, 5 to 20 tons
Single-package unit, electric cooling, optional electric heating, optional
50GL 12.0 – 13.0 54
variable-speed blower, Puron refrigerant, 2 to 5 tons
50GS Single-package unit, electric cooling, optional electric heating, 1.5 to 5 tons 10.0 55
50GX Single-package unit, electric cooling, optional electric heating, 2 to 5 tons 12.0 55
Rooftop unit, single-package, high-efficiency, electric cooling, optional electric
50HJ 13.0 56
heating, 3 to 12.5 tons
Single-package unit, high-efficiency, electric cooling, optional electric heating,
50SX 11.0 – 12.0 66
2 to 5 tons

6
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

AIR CONDITIONERS, AIR-COOLED (continued)


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

<65,000 Btu/h
All Single Package 9.7 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.

CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TFF 9.7 – 10.0 66
12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TM 10.0 67
12.5 tons
50ZP Single-package unit, electric cooling, optional electric heating, 2 to 5 tons 10.0 70

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single


10.3 EER
≥65,000 Btu/h and (or None) Package
ARI 210/240
<135,000 Btu/h Split System and Single
All Other 10.1 EER
Package

CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.

38ARD Split system, air-cooled, 10 to 20 tons 10.3 – 10.9 36


38ARS Split system, air-cooled, 10 tons 10.3 – 10.4 37
38ARZ Split system, air-cooled, 6 to 10 tons 10.3 – 11.3 38
48HJ Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 11.0 – 11.6 47
48HJ Rooftop unit, single-package, electric cooling, gas heating, 12 to 15 tons 10.6 47
48TM Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 10.1 49
Rooftop unit, single-package, high efficiency, electric cooling, optional electric
50HJ 11.0 – 11.8 56
heating, 3 to 12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 12 to
50HJ 10.7 57
15 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TM 10.2 – 10.3 67
12.5 tons
90MU Single-package, condenserless electric cooling unit, 3 to 10 tons (Available in 2002) 74

7
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single


9.7 EER
≥135,000 Btu/h and (or None) Package
ARI 340/360
<240,000 Btu/h Split System and Single
All Other 9.5 EER
Package

CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.

38AKS Split system, air-cooled, 12.5 to 20 tons 9.7 – 10.8 34


38ARD Split system, air-cooled, 10 to 20 tons 9.7 – 11.3 36
Consult Carrier
48AJ, AW Rooftop unit, single-package, electric cooling, gas heating, 20 to 60 tons sales representative 44
Rooftop unit, single-package, variable volume, electric cooling, gas heating, 20 Consult Carrier
48AK, AY 44
to 60 tons sales representative

48HG Rooftop unit, single-package, electric cooling, gas heating, 12.5 to 25 tons 11.2 – 11.6 46
48HJ Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 9.6 47
48HJ Rooftop unit, single-package, electric cooling, gas heating, 12 to 15 tons 10.5 47
48TM Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 9.5 49
48TM Rooftop unit, single-package, electric cooling, gas heating, 15 to 25 tons 9.5 – 9.7 50
Rooftop unit, single-package, electric cooling, optional electric heating, 20 to Consult Carrier
50AJ, AW 51
60 tons sales representative
Rooftop unit, single-package, variable volume, electric cooling, electric Consult Carrier
50AK, AY 52
heating, 20 to 60 tons sales representative
Rooftop unit, single-package, electric cooling, optional electric heating, 12.5 to
50HG 11.2 – 11.6 56
25 tons
Rooftop unit, single-package, high efficiency, electric cooling, optional electric
50HJ 9.8 56
heating, 3 to 12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 12 to
50HJ 10.8 57
15 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TM 9.7 67
12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 15 to
50TM 9.7 – 10.0 68
25 tons

AIR CONDITIONERS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single 9.5 EER


≥240,000 Btu/h and (or None) Package 9.7 IPLV
ARI 340/360
<760,000 Btu/h Split System and Single 9.3 EER
All Other
Package 9.5 IPLV

CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.

38AH Split system, air-cooled, 20 to 30 tons 9.4 – 10.2 9.5 – 10.3 33


38AKS Split system, air-cooled, 12.5 to 20 tons 9.5 11.8 34
38ARD Split system, air-cooled, 10 to 20 tons 9.6 – 9.7 9.8 – 9.9 36
Rooftop unit, single-package, electric cooling, gas heating, 20
48AJ, AW Consult Carrier sales representative 44
to 60 tons

8
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

AIR CONDITIONERS, AIR-COOLED (continued)


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single 9.5 EER


≥240,000 Btu/h and (or None) Package 9.7 IPLV
ARI 340/360
<760,000 Btu/h Split System and Single 9.3 EER
All Other
Package 9.5 IPLV

CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.
Rooftop unit, single-package, variable volume, electric
48AK, AY Consult Carrier sales representative 44
cooling, gas heating, 20 to 60 tons
Rooftop unit, single-package, electric cooling, gas heating,
48HG 10.4 11.0 46
12.5 to 25 tons
Rooftop unit, single-package, electric cooling, gas heating, 15
48TM 9.5 – 9.7 10.0 – 10.4 50
to 25 tons
Rooftop unit, single-package, constant or variable volume,
48Z Consult Carrier sales representative 50
electric cooling, gas heating, 30 to 90 tons
Rooftop unit, single-package, electric cooling, electric
50AJ, AW Consult Carrier sales representative 51
heating, 20 to 60 tons
Rooftop unit, single-package, variable volume, electric
50AK, AY Consult Carrier sales representative 52
cooling, electric heating, 20 to 60 tons
50HG Rooftop unit, single-package, electric cooling, 12.5 to 25 tons 10.4 11.0 56
Rooftop unit, single-package, electric cooling, optional
50TM 9.8 10.5 68
electric heating, 15 to 25 tons
Rooftop unit, single-package, constant or variable volume,
50Z Consult Carrier sales representative 69
electric cooling, electric heating, 30 to 90 tons

AIR CONDITIONERS, WATER-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Split System and Single


<65,000 Btu/h All 12.1 SEER ARI 210/240
Package

CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 13.1 52
heating, 5 to 20 tons
Single-package unit, water-cooled, electric cooling, optional hot water or steam
90MA, MF 12.4 73
heating, 3 to 10 tons

9
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

AIR CONDITIONERS, WATER-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single


11.5 EER
≥65,000 Btu/h and (or None) Package
ARI 210/240
<135,000 Btu/h Split System and Single
All Other 11.3 EER
Package

CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 11.5 52
heating, 5 to 20 tons
Single-package unit, water-cooled, electric cooling, optional hot water or steam
90MA, MF 11.9 – 12.1 7473
heating, 3 to 10 tons

AIR CONDITIONERS, WATER-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single


11.0 EER
≥135,000 Btu/h and (or None) Package
ARI 340/360
<240,000 Btu/h Split System and Single
All Other 10.8 EER
Package

CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 11.5 – 12.0 52
heating, 5 to 20 tons

AIR CONDITIONERS, WATER-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Electric Resistance Split System and Single 11.0 EER


(or None) Package 10.3 IPLV
≥240,000 Btu/h ARI 340/360
Split System and Single 10.8 EER
All Other
Package 10.1 IPLV

CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.
Indoor unit, single-package, water-cooled, variable volume,
50XJ 12.4 – 13.5 (Available in 2002) 69
electric cooling, 55 to 100 tons

10
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units

CONDENSING UNITS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

10.1 EER
≥135,000 Btu/h — — ARI 365
11.2 IPLV (Note 1)
Notes:
1. IPLVs are only applicable to equipment with capacity modulation.

CARRIER PRODUCTS
Reference Guide Page
Model No. Description EER IPLV
No.

38AH Air-cooled condensing unit, 20 to 30 tons 11.1 – 11.7 12.9 – 13.7 32


38AH Air-cooled condensing unit, 40 to 130 tons 10.1 – 10.7 12.5 – 13.8 33
38AKS Air-cooled condensing unit, 12.5 to 40 tons 10.1 – 12.1 12.1 – 15.8 34
38ARD Air-cooled condensing unit, 10 to 20 tons 11.2 – 12.5 13.1 – 15.1 35

CONDENSING UNITS, WATER-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

13.1 EER
≥135,000 Btu/h — — ARI 365
13.1 IPLV (Note 1)
Notes:
1. IPLVs are only applicable to equipment with capacity modulation.

CARRIER PRODUCTS
Reference Guide Page
Model No. Description EER IPLV
No.
Consult Carrier
07D, E Water-cooled condensing unit, 5 to 40 tons 13.2 – 14.4 sales representative 25

11
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps

HEAT PUMPS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition
Cooling Mode
<65,000 Btu/h All Split System 10.0 SEER
(Cooling Capacity) ARI 210/240
(Note 1) Heating Mode

— Split System 6.8 HSPF


Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
SEER HSPF Page No.
Console, duct-free split system heat pump (with 38CS
40CS 10.0 6.8 – 6.9 39
condensing unit), 1.5 to 2.5 tons
Under ceiling, duct-free split system heat pump (with 38QR
40QAE 10.2 – 11.5 7.2 – 7.4 41
condensing unit), 2 to 5 tons
Cassette, duct-free split system heat pump (with 38QR
40QKE 10.0 – 11.5 6.8 – 7.6 42
condensing unit), 1.5 to 3 tons
High wall, duct-free split system heat pump (with 38BK
40QNE, QNH 10.0 – 11.0 6.8 43
condensing unit), 0.75 to 2 tons
40-Series Multi-zone, duct-free split system heat pump, 2 to 2.5 tons 10.0 6.8 43

HEAT PUMPS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Cooling Mode
<65,000 Btu/h All Single Package 9.7 SEER
(Cooling Capacity) ARI 210/240
(Note 1) Heating Mode

— Single Package 6.6 HSPF


Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
SEER HSPF Page No.
Rooftop heat pump unit, single-package, gas heating,
48JZ, JZN 12.0 – 12.7 7.0 – 7.2 48
2 to 5 tons
Rooftop heat pump unit, single-package, high-efficiency,
50HJQ 11.9 – 12.0 7.6 57
optional electric heating, 3 to 10 tons
Single-package heat pump, optional electric heating, 2 to 5
50HX 11.0 – 12.0 6.9 – 7.2 59
tons
Single-package heat pump, optional electric heating, 1.5 to 5
50JS 10.0 6.6 – 7.0 59
tons
Single-package heat pump, optional electric heating, 2 to 5
50JX 12.0 7.1 – 7.2 60
tons
Single-package heat pump, optional electric heating,
50JZ 12.0 – 12.7 7.0 – 7.2 60
optional variable-speed blower, Puron, 2 to 5 tons
Rooftop heat pump unit, single-package, optional electric
50TFQ 9.7 – 10.2 6.7 – 7.5 67
heating, 3 to 10 tons
Single-package heat pump unit, optional electric heating, 2
50ZH 10.0 – 10.5 6.8 70
to 5 tons

12
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps

HEAT PUMPS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Cooling Mode

Electric Resistance Split System and


10.1 EER
(or None) Single Package

Split System and


All Other 9.9 EER
Single Package
≥65,000 Btu/h and ARI 210/240
<135,000Btu/h Heating Mode
(Cooling Capacity) 47°Fdb/43°Fwb
3.2 COP
— Outdoor Air

17°Fdb/15°Fwb
2.2 COP
Outdoor Air

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

38AQ Split system heat pump, air-cooled, 6 tons 10.3 3.2 35


38ARQ Split system heat pump, air-cooled, 7.5 to 10 tons 10.1 – 10.4 3.2 36
Rooftop heat pump unit, single package, optional electric
50HJQ 10.3 – 10.5 3.3 – 3.4 57
heat, 3 to 10 tons

HEAT PUMPS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Cooling Mode

Electric Resistance Split System and


9.3 EER
(or None) Single Package

Split System and


All Other 9.1 EER
Single Package
≥135,000Btu/h and ARI 340/360
<240,000 Btu/h Heating Mode
(Cooling Capacity) 47°Fdb/43°Fwb
3.1 COP
— Outdoor Air

17°Fdb/15°Fwb
2.0 COP
Outdoor Air

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

38AQS Split system heat pump, air-cooled, 15 tons 9.3 3.1 35


Rooftop heat pump unit, single-package, optional electric
50EJQ, EWQ 9.8 3.3 54
heating, 20 and 25 tons
Rooftop heat pump unit, single-package, optional electric
50HJQ 9.3 – 9.8 3.2 – 3.3 58
heat, 13 and 15 tons

13
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps

HEAT PUMPS, AIR-COOLED


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition
Cooling Mode

Electric Resistance Split System and Single 9.0 EER


(or None) Package 9.2 IPLV

Split System and Single 8.8 EER


All Other
Package 9.0 IPLV
≥240,000 Btu/h ARI 340/360
(Cooling Capacity) Heating Mode

47°Fdb/43°Fwb
3.1 COP
Outdoor Air

17°Fdb/15°Fwb
2.0 COP
Outdoor Air

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
Rooftop heat pump unit, single-package, optional electric
50EJQ, EWQ 9.2 3.3 54
heating, 20 and 25 tons

HEAT PUMPS, WATER-SOURCE


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Cooling Mode

All 86°F Entering Water 11.2 EER


<17,000 Btu/h ARI/ISO-13256-1
(Cooling Capacity) Heating Mode

— 68°F Entering Water 4.2 COP

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

50KQA, KQD Console heat pump unit, water-source, 0.5 to 1.5 tons 12.2 – 12.6 4.2 – 4.3 61
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 12.8 – 13.3 4.2 – 4.6 62-63
5 tons
50RHS, RVS, Horizontal and vertical heat pump unit, high-efficiency,
16.0 5.3 64
RDS water-source, 1.25 to 6 tons

14
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps

HEAT PUMPS, WATER-SOURCE


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition
Cooling Mode
≥17,000 Btu/h and All 86°F Entering Water 12.0 EER
<135,000 Btu/h ARI/ISO-13256-1
(Cooling Capacity) Heating Mode

— 68°F Entering Water 4.2 COP

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 12.7 – 12.8 4.2 – 4.4 58
Horizontal and vertical heat pump unit, water-source,
50RHC, RVC 12.0 – 13.0 4.2 – 4.6 61
1.5 to 5 tons
Horizontal and vertical, high-efficiency heat pump unit,
50RHR, RVR 12.3 – 13.2 4.2 – 4.4 62-63
water-source, 0.5 to 5 tons
50RHS, RVS, Horizontal and vertical, premium-efficiency heat pump unit,
12.4 – 15.1 4.4 – 5.0 64
RDS water-source, 1.25 to 6 tons
Rooftop heat pump unit, single-package, water-source,
50RTG 13.0 – 14.7 4.2 – 5.0 65
3 to 20 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 12.0 – 14.3 4.2 – 5.0 65
Single-package heat pump, vertical, water-source, 6.5 to 25
50VQA, VQD 14.0 4.2 68
tons

HEAT PUMPS, GROUNDWATER-SOURCE


Subcategory or Rating
Size Category Heating Section Type Minimum Efficiency Test Procedure
Condition

Cooling Mode

<135,000 Btu/h All 59°F Entering Water 16.2 EER


ARI/ISO-13256-1
(Cooling Capacity) Heating Mode

— 50°F Entering Water 3.6 COP

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 17.2 – 17.4 3.9 – 4.0 58
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 16.8 – 18.6 3.6 – 4.1 62-63
5 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 20.6 4.0 65

15
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps

HEAT PUMPS, GROUND-SOURCE


Subcategory or Rating
Size Category Minimum Efficiency Test Procedure
Condition

Cooling Mode

<135,000 Btu/h 77°F Entering Water 13.4 EER


ARI/ISO-13256-1
(Cooling Capacity) Heating Mode

— 32°F Entering Water 3.1 COP

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 14.1 – 14.2 3.2 – 3.4 58
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 13.3 – 15.0 3.2 – 3.5 62-63
5 tons
50RHS, RVS, Horizontal and vertical heat pump unit, high-efficiency,
13.4 – 18.5 3.3 – 3.8 64
RDS water-source, 1.25 to 6 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 16.2 3.3 65

16
Table 6.2.1C
Water Chilling Packages

CHILLERS, AIR-COOLED WITH CONDENSER, ELECTRICALLY-OPERATED


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

2.80 COP
All capacities ARI 550/590
3.05 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference Guide
Model No. Description COP IPLV
Page No.

30GTN Packaged, air-cooled, reciprocating liquid chiller, 15 to 35 tons 2.83 – 2.90 3.34 – 3.78 28
30GTN, GTR Packaged, air-cooled, reciprocating liquid chiller, 36 to 410 tons 2.80 – 2.92 3.49 – 4.31 28
30GUN, GUR Packaged, air-cooled, reciprocating liquid chiller, 25 to 280 tons 2.82 – 3.06 3.16 – 4.07 29
Consult Carrier
30GXN, GXR Packaged, air-cooled, rotary screw liquid chiller, 80 to 450 tons 2.80 – 3.06 sales representative 29
Hermetic scroll liquid chiller, packaged, air-cooled, 9.6 to 54.3
30RA 2.81 – 2.96 3.73 – 4.44 32
tons

CHILLERS, AIR-COOLED WITHOUT CONDENSER, ELECTRICALLY-OPERATED


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

3.10 COP
All capacities ARI 550/590
3.45 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference Guide
Model No. Description COP IPLV
Page No.

30HL Condenserless, reciprocating liquid chiller, 50 to 60 tons 3.11 — 30


30HWA Condenserless, reciprocating liquid chiller, 15 to 40 tons 3.10 – 3.11 — 30
30HXA Condenserless, rotary screw liquid chiller, 75 to 265 tons 3.12 – 3.24 — 31

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, POSITIVE DISPLACEMENT (RECIPROCATING)


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

4.20 COP
All capacities ARI 550/590
5.05 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

30HK Reciprocating liquid chillers, water-cooled, 40 to 60 tons 4.23 5.92 30


30HWB, HWC Reciprocating liquid chillers, water-cooled, 15 to 40 tons 4.20 – 4.31 5.37 – 5.90 30

17
Table 6.2.1C
Water Chilling Packages

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, POSITIVE DISPLACEMENT, (ROTARY SCREW AND SCROLL)


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

4.45 COP
<150 tons ARI 550/590
5.20 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

30HXC Rotary screw liquid chillers, fluid-cooled, 75 to 265 tons 4.84 – 5.00 6.60 – 6.91 31

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, POSITIVE DISPLACEMENT, (ROTARY SCREW AND SCROLL)


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

≥150 tons and 4.90 COP


ARI 550/590
<300 tons 5.60 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

23XL Rotary screw liquid chiller, hermetic, water-cooled, 150 to 360 tons 5.89 – 5.94 7.59 – 7.86 27
30HXC Rotary screw liquid chillers, fluid-cooled, 75 to 265 tons 4.92 – 5.08 6.26 – 6.89 31

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, POSITIVE DISPLACEMENT, (ROTARY SCREW AND SCROLL)


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

5.50 COP
≥300 tons ARI 550/590
6.15 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

23XL Rotary screw liquid chiller, hermetic, water-cooled, 150 to 360 tons 5.98 – 6.12 7.47 – 7.67 27

18
Table 6.2.1C
Water Chilling Packages

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, CENTRIFUGAL


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

≥150 tons and 5.55 COP


ARI 550/590
<300 tons 5.90 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

19XR High-efficiency, hermetic, centrifugal liquid chiller, 200 to 1,500 tons 5.59 5.94 27

CHILLERS, WATER-COOLED, ELECTRICALLY-OPERATED, CENTRIFUGAL


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

6.10 COP
≥300 tons ARI 550/590
6.40 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.

19XR High-efficiency, hermetic, centrifugal liquid chiller, 200 to 1,500 tons 6.10 – 6.45 6.41 – 6.79 27

CHILLERS, WATER-COOLED, ABSORPTION, SINGLE EFFECT


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

All capacities 0.70 COP ARI 560

Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.

CARRIER PRODUCTS
Reference Guide
Model No. Description COP
Page No.

16JB Steam/hot water, single effect, absorption liquid chiller, 108 to 680 tons 0.70 – 0.71 26

19
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps

PACKAGED TERMINAL AIR CONDITIONERS (COOLING MODE)


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

All capacities 95°Fdb 12.5 – (0.213 x Cap/1000)


EER (Note 2 and 3)
ARI 310
New Construction Outdoor air

All capacities 95°Fdb 10.9 – (0.213 x Cap/1000)


EER (Note 2 and 3)
ARI 310
Replacements (Note 1) Outdoor air

Notes:
1. Replacement units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE
INSTALLED IN NEW CONSTRUCTION PROJECTS.” Replacement efficiencies apply only to units with existing sleeves less than 16 inches high
and less than 42 inches wide.
2. Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the
unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
3. See table below for typical PTAC sizes and efficiency requirements based on the ASHRAE 90.1-1999 (2001) equations indicated in Table 6.2.1D.

CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.

52CE Comfort Series packaged terminal air conditioners 9.4 – 11.1 71


52PC, PE Premier Series packaged terminal air conditioners 9.4 – 12.7 72

PTAC EFFICIENCY REQUIREMENTS FOR TYPICAL UNIT CAPACITIES


NEW CONSTRUCTION Minimum Efficiency REPLACEMENT UNITS Minimum Efficiency

Factor 0.213 Factor 0.213

Actual Capacity Calculation Capacity Actual Capacity Calculation Capacity


EER EER
(Btu/h) (Btu/h) (Btu/h) (Btu/h)
5,000 7,000 11.01 5,000 7,000 9.41
6,000 7,000 11.01 6,000 7,000 9.41
7,000 7,000 11.01 7,000 7,000 9.41
8,000 8,000 10.80 8,000 8,000 9.20
9,000 9,000 10.58 9,000 9,000 8.98
10,000 10,000 10.37 10,000 10,000 8.77
11,000 11,000 10.16 11,000 11,000 8.56
12,000 12,000 9.94 12,000 12,000 8.34
13,000 13,000 9.73 13,000 13,000 8.13
14,000 14,000 9.52 14,000 14,000 7.92
15,000 15,000 9.31 15,000 15,000 7.71
16,000 15,000 9.31 16,000 15,000 7.71
17,000 15,000 9.31 17,000 15,000 7.71
18,000 15,000 9.31 18,000 15,000 7.71

20
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps

PACKAGED TERMINAL HEAT PUMPS


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

Cooling Mode
95°Fdb 12.3 – (0.213 x Cap/1000)
Outdoor air EER (Note 2 and 3)
All capacities ARI 380
New Construction Heating Mode

3.2 – (0.026 x Cap/1000)


COP (Note 2 and 3)
Cooling Mode
95°Fdb 10.8 – (0.213 x Cap/1000)
Outdoor air EER (Note 2 and 3)
All capacities ARI 380
Replacements Heating Mode
(Note 1) 2.9 – (0.026 x Cap/1000)
COP (Note 2 and 3)

Notes:
1. Replacement units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE
INSTALLED IN NEW CONSTRUCTION PROJECTS.” Replacement efficiencies apply only to units with existing sleeves less than 16 inches high
and less than 42 inches wide.
2. Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the
unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
3. See table below for typical PTAC sizes and efficiency requirements based on the ASHRAE 90.1-1999 (2001) equations indicated in Table 6.2.1D.

CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.

52CQ Comfort Series packaged terminal heat pumps 9.4 – 11.1 2.9 – 3.1 71
52PQ Premier Series packaged terminal heat pumps 9.4 – 12.7 2.9 – 3.4 73

PTHP EFFICIENCY REQUIREMENTS FOR TYPICAL UNIT CAPACITIES


Cooling Mode Heating Mode Cooling Mode Heating Mode
NEW CONSTRUCTION Minimum Efficiency Minimum Efficiency
REPLACEMENTS Minimum Efficiency Minimum Efficiency

Factor 0.213 0.026 Factor 0.213 0.026

Actual Capacity Calculation Actual Capacity Calculation


EER COP EER COP
(Btu/h) Capacity (Btu/h) (Btu/h) Capacity (Btu/h)
5,000 7,000 11.01 3.02 5,000 7,000 9.41 2.72
6,000 7,000 11.01 3.02 6,000 7,000 9.41 2.72
7,000 7,000 11.01 3.02 7,000 7,000 9.41 2.72
8,000 8,000 10.80 2.99 8,000 8,000 9.20 2.69
9,000 9,000 10.58 2.97 9,000 9,000 8.98 2.67
10,000 10,000 10.37 2.94 10,000 10,000 8.77 2.64
11,000 11,000 10.16 2.91 11,000 11,000 8.56 2.61
12,000 12,000 9.94 2.89 12,000 12,000 8.34 2.59
13,000 13,000 9.73 2.86 13,000 13,000 8.13 2.56
14,000 14,000 9.52 2.84 14,000 14,000 7.92 2.54
15,000 15,000 9.31 2.81 15,000 15,000 7.71 2.51
16,000 15,000 9.31 2.81 16,000 15,000 7.71 2.51
17,000 15,000 9.31 2.81 17,000 15,000 7.71 2.51
18,000 15,000 9.31 2.81 18,000 15,000 7.71 2.51

21
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps

ROOM AIR CONDITIONERS, WITHOUT LOUVERED SIDES


Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

<8,000 Btu/h 9.0 EER ANSI/AHAM RAC-1

≥8,000 Btu/h 8.5 EER ANSI/AHAM RAC-1

CARRIER PRODUCTS
Model No. Description EER Reference Guide Page No.

52FC, FE Room air conditioner, solid side 8.5 – 9.0 72

22
Table 6.2.1G
Heat Rejection Equipment

AIR-COOLED CONDENSERS
Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure

125°F condensing temperature


R-22 test fluid
All capacities 190°F entering gas temperature ≥176,000 Btu/h-hp ARI 460
15°F subcooling
95°Fdb entering air
Notes:
1. Air-cooled condenser performance is defined by ASHRAE Standard 90.1-1999 (2001) as the heat rejected from the refrigerant divided by the fan
nameplate rated motor power.

CARRIER PRODUCTS
Reference Guide
Model No. Description Performance
Page No.

09AW, AZ Air-cooled condensers, 1 to 20 tons 180,000 – 266,000 Btu/h-hp 25


09DE, DK Air-cooled condensers, 15 to 90 tons 190,800 – 235,800 Btu/h-hp 26

23
REFERENCE GUIDE

PART 2

REFERENCE GUIDE
TO CARRIER COMMERCIAL PRODUCTS

24
REFERENCE GUIDE

07D, E, WATER-COOLED CONDENSING UNITS, 5 TO 40 TONS


Cooling Capacity
Unit 07 Input kW COP EER IPLV
(Tons)

DB215 15.59 14.2 3.86 13.2


EA022 21.60 18.3 4.15 14.2 (Note 3)
EB027 28.60 23.9 4.21 14.4
EB033 32.00 26.8 4.20 14.3
Notes:
1. ARI standard ratings for R-22 refrigerant units are shown.
2. Rated in accordance with ARI Standard 520.
3. Consult local Carrier sales representative for IPLV data.
4. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Suitable for R-12, -22, -500 and -502 refrigerants Shell-and-coil condenser (15 tons and smaller)
Semi-hermetic, reciprocating compressors Shell-and-tube condenser (sizes larger than 15 tons)
Suction cutoff unloading Integral finned copper tubes
Time Guard anti-short-cycling device Subcooling circuit (sizes larger than 15 tons)

OPTIONS: Electric actuated unloaders Discharge muffler

CATALOG NO. 520-700

09AW, AZ, AIR-COOLED CONDENSERS, 1 TO 20 TONS


Unit 09 Total Motor Performance
Nominal Capacity Heat Rejection
Outdoor CFM Nameplate (Btu/hr-hp)
(Tons) (Btu/h)
Arrangement Unit Size Horsepower (Note 1)

003 3 2,850 47,000 0.25 188,000


004 4 2,740 60,500 0.25 242,000
006 5 5,700 93,700 0.5 187,400
008 7.5 5,480 121,000 0.5 242,000
AWL, AWW 012 10 5,110 133,000 0.5 266,000
014 12 11,600 190,000 1 190,000
016 15 11,400 206,000 1 206,000
018 17 11,500 246,000 1 246,000
020 20 11,300 265,000 1 265,000
008 7.5 5,300 112,000 0.5 224,000
012 10 11,070 180,000 1 180,000
AZL, AZW
014 12 10,872 219,000 1 219,000
016 15 10,566 254,000 1 254,000
Notes:
1. ASHRAE 90.1 defines air-cooled condenser performance as the total heat rejected from the refrigerant divided by the fan nameplate rated motor
horsepower.
2. ARI capacities shown.
3. AWL Direct-drive, general purpose, horizontal, low sound motor.
AWW Direct-drive, general purpose, vertical, low sound motor.
AZL Direct-drive, sized to work best with 50BZN, horizontal, low sound motor.
AZW Direct-drive, sized to work best with 50BZN, vertical (sizes 014 to 020 only), low sound motor.
4. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Designed for R-22 or R-134a Vertical and horizontal airflow configurations
Single or multiple refrigerant circuits Low sound levels
Copper tubes with aluminum fins standard Direct-drive propeller fans

OPTIONS: Aluminum cabinet Motor and motor control options


Corrosion-resistant coil options Control transformer
Fused disconnect

CATALOG NO. 520-921

25
REFERENCE GUIDE

09DE, DK, AIR-COOLED CONDENSERS, 15 TO 90 TONS


Unit 09 Nominal Heat Total Motor Performance
Nominal Capacity
Outdoor CFM Rejection (Btu/h) Nameplate (Btu/hr-hp)
(Tons)
Arrangement Unit Size (Note 2) Horsepower (Note 1)

DE 016 15 9,600 220,800 1 220,800


024 20 13,500 310,800 1.5 207,200
028 25 15,700 399,600 2 199,800
034 30 21,100 576,000 3 192,000
044 40 23,700 674,400 3 224,800
DK 054 50 35,000 789,600 4 197,400
064 60 35,000 943,200 4 235,800
074 70 52,000 1,144,800 6 190,800
084 80 51,000 1,242,000 6 207,000
094 90 57,000 1,395,600 6 232,600
Notes:
1. ASHRAE 90.1 defines performance as the total heat rejected from the refrigerant divided by the fan nameplate rated motor power.
2. Nominal heat rejection is based on optimum refrigerant charge of R-22 with 15°F subcooling.

FEATURES: Designed for R-12, -22, -500, -502 and R-134a Direct-drive propeller fans
Single or multiple refrigerant circuits Copper tubes with aluminum fins standard

OPTIONS: Corrosion-resistant coil options Head pressure control


Sound reduction kit (sizes 054 to 094) Fan cycling control

CATALOG NO. 520-920

16JB, STEAM/HOT WATER, SINGLE EFFECT, HERMETIC, ABSORPTION LIQUID CHILLER, 108 TO 680 TONS
Chiller Model 16JB Nominal Capacity (Tons) COP

010 108 0.71


012 122 0.71
014 137 0.70
018 186 0.70
021 211 0.70
024 245 0.70
028 279 0.70
032 326 0.70
036 362 0.70
041 413 0.70
047 479 0.70
054 539 0.70
Notes:
1. Rated in accordance with ARI Standard 560.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Single-effect, lithium bromide Removable waterbox covers on both ends


Leak-proof hermetic pumps Non-clogging corrosion-proof spray nozzles
Automatic motorless purge 90/10 Cu-Ni generator tubes
Cycle-Guard anti-crystallization controls Factory-insulated evaporator surfaces

OPTIONS: Marine waterboxes (rated for 150 psig or 250 psig) Absorber-condenser crossover piping
ASME Section VIII, Div. 1, generator (up to 250 psig) Steam demand limiter
Non-standard tubing materials Part-load economizer
Flanged or Victaulic nozzles Chilled and condenser water flow switches

CATALOG NO. 521-612

26
REFERENCE GUIDE

19XR, HIGH-EFFICIENCY, HERMETIC, CENTRIFUGAL LIQUID CHILLER, 200 TO 1,500 TONS


Chiller Model 19XR Capacity (Tons) COP IPLV

19XR 32 32 223 BEH64 200 5.59 5.94


19XR 37 37 2ZZ BGS64 300 6.10 6.41
19XR 40 42 352 CLS64 400 6.11 6.50
19XR 47 47 383 CNS64 500 6.11 6.57
19XR 56 57 434 DBS64 600 6.12 6.68
19XR 65 66 453 DDS64 700 6.19 6.56
19XR 65 65 465 DGH64 800 6.29 6.77
19XR 71 70 475 DHS64 900 6.14 6.76
19XR 71 72 4K4 DKS64 1,000 6.10 6.45
19XR 80 80 574 EJS64 1,100 6.34 6.53
19XR 81 82 564 ELS64 1,200 6.27 6.57
19XR 85 85 594 EMS64 1,300 6.37 6.49
19XR 86 87 594 ENS64 1,400 6.45 6.65
19XR 87 87 594 ENS64 1,500 6.41 6.79
Notes:
1. Rated in accordance with ARI Standard 550/590. Ratings are shown in 100-ton increments for illustration purposes only.

FEATURES: Single-stage, hermetic, centrifugal compressor, R-134a Modular construction


Variable inlet guide vanes ASME certified heat exchangers
Electrically-driven oil pump Internally and externally enhanced tubing
Microprocessor-controlled oil heater Double-grooved tube sheet holes
Refrigerant-cooled oil cooler Condenser baffle
Direct digital product integrated controls Refrigerant filter isolation valves
AccuMeter refrigerant flow control system Flash subcooler

OPTIONS: 1-, 2-, or 3-pass cooler or condenser (water side) Unit-mounted or stand-alone pumpout unit
Marine waterboxes Hot gas bypass
Cooler and condenser tube material options Sensor kit
Refrigerant isolation valves Factory performance testing
Unit-mounted starter or VFD

CATALOG NO. 521-912

23XL, HERMETIC, ROTARY SCREW LIQUID CHILLER, 150 TO 360 TONS


Chiller Model 23XL Capacity (Tons) COP IPLV

23XL 21 21 E C4 0 200 5.89 7.59


23XL 21 21 E C6 0 250 5.94 7.86
23XL 48 48 E D4 0 300 5.98 7.47
23XL 48 48 E D6 0 350 6.12 7.67
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. Ratings are shown in 50-ton increments for illustration purposes only. Other ASHRAE 90.1-compliant sizes are available.

FEATURES: Hermetic, twin-screw compressor, R-22 or R-134a Direct digital product integrated controls
Bottom-mounted capacity control slide valve ASME certified heat exchangers
Microprocessor-controlled oil heater Internally and externally enhanced tubing
External thermal economizer Double-grooved tube sheet holes

OPTIONS: One, 2, or 3-pass cooler or condenser (water side) Stand-alone pumpout unit
Marine waterboxes Hot gas bypass
Cooler and condenser tube options Full insulation (except waterbox covers)
Refrigerant isolation valves Control module options
Spring isolators Unit-mounted or remote-mounted motor starter

CATALOG NO. 522-304

27
REFERENCE GUIDE

30GTN, PACKAGED, AIR-COOLED, RECIPROCATING LIQUID CHILLERS, 15 TO 35 TONS


Cooling Capacity
Unit 30GTN Input kW COP EER IPLV
Tons kW

015 14.3 50.4 17.4 2.90 9.9 3.78


020 17.4 61.2 21.6 2.83 9.7 3.34
025 24.4 85.7 30.1 2.85 9.7 3.75
030 27.1 95.4 33.6 2.84 9.7 3.63
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: R-22 refrigerant ComfortLink controls


Semi-hermetic reciprocating compressors Suction cutoff unloading
Crankcase heater Shell-and-tube cooler with seamless copper tubes

OPTIONS: Medium temperature brine operation Energy management module


Compressor ground fault sensor Part-winding start
Oil safety switch Chilled water flow switch
Corrosion-resistant condenser coil options Pressure gage panel
Hot gas bypass Head pressure control package

CATALOG NO. 523-059

30GTN, GTR, PACKAGED, AIR-COOLED, RECIPROCATING LIQUID CHILLERS, 36 TO 410 TONS


Cooling Capacity
Unit 30GTN Input kW COP EER IPLV
Tons kW

040 36.2 127.3 38.7 2.84 9.7 3.49


050 50.9 179.1 56.4 2.86 9.8 3.63
080 82.6 290.5 94.1 2.81 9.6 3.75
090 88.2 310.4 99.0 2.86 9.8 4.31
100 100.5 353.5 108.4 2.92 10.0 4.13
110 108.7 382.3 123.7 2.80 9.6 4.01
150 141.4 497.3 162.5 2.80 9.5 3.95
170 158.4 557.1 181.8 2.82 9.6 4.22
190 173.9 611.5 200.2 2.80 9.5 4.22
230 224.0 787.9 256.6 2.80 9.6 3.81
245 229.7 807.7 261.4 2.82 9.6 4.01
255 242.1 851.3 270.9 2.85 9.7 3.95
270 259.0 911.0 290.2 2.86 9.8 4.10
290 282.6 993.8 323.9 2.80 9.5 4.07
315 311.3 1094.9 360.2 2.80 9.5 4.04
330 316.8 1114.0 363.5 2.82 9.6 4.22
360 347.8 1223.0 400.4 2.80 9.5 4.22
390 376.8 1325.3 436.9 2.80 9.5 4.13
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: R-22 refrigerant Designed for variable chilled water flow


Semi-hermetic reciprocating compressors ComfortLink controls
Dual independent refrigeration circuits Shell-and-tube cooler with seamless copper tubes
Crankcase heater Electronic expansion valves

OPTIONS: Brine operation Energy management module


Compressor ground fault sensor Part-winding start
Additional electric suction cutoff unloaders Head pressure control package
Corrosion-resistant condenser coil options Sound reduction package

CATALOG NO. 523-062

28
REFERENCE GUIDE

30GUN, GUR, PACKAGED, AIR-COOLED, RECIPROCATING LIQUID CHILLERS, 25 TO 280 TONS


Cooling Capacity
Unit 30GUN, GUR Input kW COP EER IPLV
Tons kW

040, 045, 050,


24.0 – 49.9 84.5 – 175.5 29.8 – 61.5 2.82 – 2.98 9.6 – 10.2 3.16 – 3.54
060, 070,
080, 090, 100,
56.2 – 82.9 197.6 – 291.7 67.1 – 100.9 2.89 – 3.02 9.9 – 10.3 3.51 – 3.92
110, 130,
150, 170, 190,
95.6 – 137.3 336.1 – 482.8 114.8 – 160.4 2.93 – 3.06 10.0 – 10.4 3.63 – 4.07
210
230, 245, 255,
151.8 – 191.2 533.7 – 672.5 181.9 – 225.2 2.93 – 3.05 10.0 – 10.4 3.54 – 3.84
270, 290
315, 330, 360,
209.8 – 274.5 737.8 – 965.4 247.8 – 320.9 2.98 – 3.06 10.2 – 10.4 3.78 – 4.07
390, 420
Notes:
1. Ratings are summarized. See catalog for complete list of ratings at ARI conditions. Rated in accordance with ARI Standard 550/590.

FEATURES: R-134a refrigerant Designed for variable chilled water flow


Semi-hermetic reciprocating compressors ComfortLink controls
Dual independent refrigeration circuits Shell-and-tube cooler with seamless copper tubes
Crankcase heater Electronic expansion valves

OPTIONS: Brine operation Energy management module


Compressor ground fault sensor Part-winding start
Additional electric suction cutoff unloaders Head pressure control package
Corrosion-resistant condenser coil options Sound reduction package

CATALOG NO. 523-063

30GXN, GXR, PACKAGED, AIR-COOLED, ROTARY SCREW LIQUID CHILLERS, 80 TO 450 TONS
Cooling Capacity
Unit 30GXN, GXR Input kW COP EER IPLV
Tons kW

080, 090, 106, 114, 125,


75.9 – 139.8 267 – 492 92.3 – 173.0 2.80 – 2.89 9.56 – 9.86
135, 150
160, 174, 204, 225, 249, (Note 2)
151.5 – 286.7 533 – 1,009 190.2 – 353.9 2.80 – 2.89 9.56 – 9.88
264, 281, 301
325, 370, 390, 415, 450,
308.7 – 502.7 1,087 – 1,770 387.5 – 621.1 2.80 – 2.86 9.56 – 9.75
475, 500, 525
HIGH-EFFICIENCY UNIT
083, 093, 108, 118, 128,
77.1 – 141.0 271 – 496 88.9 – 164.8 2.99 – 3.05 10.19 – 10.41
138, 153
163, 178, 208, 228, 253,
153.1 – 287.4 539 – 1,012 179.1 – 332.1 2.93 – 3.06 10.00 – 10.43 (Note 2)
268, 283, 303
328, 353, 373, 393, 418,
316.8 – 516.5 1,115 – 1,817 366.9 – 611.3 2.97 – 3.05 10.14 – 10.41
453, 473, 503, 528
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. Consult Carrier sales representative for IPLV data.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: R-134a refrigerant Designed for variable chilled water flow


Semi-hermetic, rotary screw compressors ComfortLink controls
Dual independent refrigeration circuits Shell-and-tube cooler with seamless copper tubes
Across-the-line starter (30GXN) Wye-delta starter (30GXR)

OPTIONS: Medium-temperature brine operation Energy management module


Corrosion-resistant condenser coil options Low ambient control
Cooler heater and low ambient protection Minimum load control
Cooler design options Multi-chiller control

CATALOG NO. 523-068

29
REFERENCE GUIDE

30HK, HWB, HWC, RECIPROCATING LIQUID CHILLERS, 15 TO 60 TONS


Unit Cooling Capacity (Tons) Input kW COP IPLV

30HK-040 41.2 34.2 4.23 5.92


30HWB-018 16.3 13.6 4.20 5.79
30HWB-025 20.3 16.9 4.22 5.66
30HWB-028 27.1 22.6 4.21 5.59
30HWB-035 30.4 25.4 4.21 5.37
30HWC-018 15.8 13.2 4.22 5.79
30HWC-025 19.9 16.2 4.31 5.90
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. 30HK fluid-cooled reciprocating liquid chiller; 30HWB brazed-plate cooler and condenser; 30HWC brazed-plate cooler and shell-and-tube condenser.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Water-cooled ComfortLink controls


Semi-hermetic reciprocating compressors Stainless steel, brazed plate cooler (30HWB, HWC)
Dual refrigeration circuits (30HK) Stainless steel, brazed plate condenser (30HWB)
Crankcase heater Single-pass, shell-and-tube cooler (30HK)
Suction cutoff unloading Shell-and-tube condenser (30HK, 30HWC)

OPTIONS: Medium temperature brine operation (30HWB, HWC) Energy management module
Sound enclosure panels Part-winding start
Compressor ground fault sensor Hot gas bypass
Oil safety switch Pressure gage panel

CATALOG NO. 523-057 (New catalog available in 2002)

30HL, HWA, CONDENSERLESS, RECIPROCATING LIQUID CHILLERS, 15 TO 60 TONS


Unit Cooling Capacity (Tons) Input kW COP IPLV

30HL-050 44.9 50.8 3.11 —


30HWA-018 14.0 15.8 3.11 —
30HWA-025 17.2 19.5 3.10 —
30HWA-028 22.5 25.5 3.10 —
30HWA-035 25.9 29.4 3.10 —
Notes:
1. Rated in accordance with ARI Standard 550/590.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Condenserless ComfortLink controls


Semi-hermetic reciprocating compressors Suction cutoff unloading
Dual refrigeration circuits (30HL) Stainless steel, brazed plate cooler (30HWA)
Crankcase heater Single-pass, shell-and-tube cooler (30HL)

OPTIONS: Medium temperature brine operation (30HW) Energy management module


Sound enclosure panels Part-winding start
Compressor ground fault sensor Hot gas bypass
Oil safety switch Pressure gage panel

CATALOG NO. 523-057 (New catalog available in 2002)

30
REFERENCE GUIDE

30HXA, CONDENSERLESS, ROTARY SCREW LIQUID CHILLERS, 75 TO 265 TONS


Unit 30HXA Cooling Capacity (Tons) Input kW COP IPLV
076 67.7 76.2 3.12 —
086 76.0 84.4 3.16 —
096 85.8 95.1 3.17 —
106 96.9 106.9 3.19 —
116 104.9 115.0 3.21 —
126 113.9 125.3 3.19 —
136 127.0 138.5 3.22 —
146 137.2 150.0 3.21 —
161 147.3 159.9 3.24 —
171 159.0 173.8 3.22 —
186 174.3 192.7 3.18 —
206 198.5 216.4 3.23 —
246 231.9 252.4 3.23 —
261 244.1 267.5 3.21 —
271 257.9 283.9 3.19 —
Notes:
1. Rated in accordance with ARI Standard 550/590.

FEATURES: R-134a refrigerant Navigator hand-held display module


Semi-hermetic, twin-screw compressors Microprocessor-based controls
Dual independent refrigeration circuits Shell-and-tube cooler
Compact design Internally enhanced seamless copper tubes

OPTIONS: Brine operation Energy management module


Cooler options Minimum load control
Suction service valves Multi-chiller control
Sound reduction package Wye-delta starter

CATALOG NO. 523-064 (New catalog available in 2002)

30HXC, FLUID-COOLED, SCREW LIQUID CHILLERS, 75 TO 265 TONS


Unit 30HXC Cooling Capacity (Tons) Input kW COP IPLV
076 75.4 53.7 4.94 6.87
086 83.1 60.4 4.84 6.72
096 94.0 67.0 4.93 6.85
106 104.3 75.3 4.87 6.75
116 113.6 79.9 5.00 6.91
126 123.0 86.8 4.98 6.91
136 136.5 97.0 4.95 6.67
146 145.9 105.1 4.88 6.60
161 156.5 111.7 4.93 6.76
171 165.9 118.2 4.93 6.54
186 177.2 126.7 4.92 6.26
206 211.6 146.4 5.08 6.89
246 248.6 172.4 5.07 6.74
261 257.2 180.5 5.01 6.72
271 267.4 189.5 4.96 6.70
Notes:
1. Rated in accordance with ARI Standard 550/590.

FEATURES: R-134a refrigerant Navigator hand-held display module


Semi-hermetic, twin-screw compressors Microprocessor-based controls
Dual independent refrigeration circuits Shell-and-tube cooler and condenser
Compact design Internally enhanced seamless copper tubes

OPTIONS: Brine operation Energy management module


Cooler options Minimum load control
Suction service valves Multi-chiller control
Sound reduction package Wye-delta starter

CATALOG NO. 523-064 (New catalog available in 2002)

31
REFERENCE GUIDE

30RA, AIR-COOLED LIQUID CHILLERS, 9.6 TO 54.3 TONS


Cooling Capacity
Unit 30RA Input kW COP IPLV
Tons kW

010 9.6 33.8 11.6 2.87 3.77


015 13.7 48.2 16.7 2.87 3.73
018 15.9 55.9 19.9 2.81 3.93
022 21.6 76.0 25.5 2.96 4.20
025 23.8 83.7 29.7 2.81 4.08
030 27.2 95.7 33.4 2.87 4.10
035 34.8 122.4 41.4 2.93 4.24
040 37.7 132.6 46.4 2.84 3.97
045 43.1 151.6 50.8 2.96 4.44
050 47.4 166.7 59.1 2.81 4.13
055 54.3 191.0 66.7 2.84 4.14
Notes:
1. Rated in accordance with ARI Standard 550/590.

FEATURES: R-22 refrigerant ComfortLink controls


Fully hermetic scroll compressors AeroAcoustic condenser fans for quiet operation
Independent refrigeration circuits (sizes 035 to 055) Stainless steel brazed plate-type cooler
Single or dual hydronic pumps Low profile design

OPTIONS: Medium-temperature brine operation Navigator hand-held display module


Corrosion-resistant condenser coil options Energy management module
Cooler heater and low ambient protection package Low ambient control
Hydronic pump package Minimum load control
Chilled water storage tank Interface device options

CATALOG NO. 523-067

38AH, AIR-COOLED CONDENSING UNITS, 20 TO 30 TONS


Condensing Unit 38AH Nominal Capacity (Tons) Net Capacity (Btu/h) EER (Note 1) IPLV

024 20 250,000 11.7 13.7


028 25 290,000 11.2 12.9
034 30 344,000 11.1 12.9
Notes:
1. Rated in accordance with ARI Standard 360/365.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: Semi-hermetic compressors Low oil pressure safety switch


Suction cutoff unloading on lead compressor Refrigerant high- and low-pressure switches
Independent refrigerant circuits Calibrated circuit breakers
Time Guard anti-short-cycling device

OPTIONS: Corrosion-resistant coil options Accessory control (for VAV applications)


Additional electric unloader package Low ambient control
Additional pressure unloader package Gage panel package

CATALOG NO. 523-80022

32
REFERENCE GUIDE

38AH, SPLIT SYSTEMS WITH AIR-COOLED CONDENSING UNITS, 20 TO 30 TONS


Condensing Unit 38AH Nominal Capacity Indoor Air Handler System Net Capacity
System EER System IPLV
(Note 3) (Tons) (Note 2) (Btu/h)

40RM024H 240,000 9.6 9.7


024 20
40RM028H 250,000 10.2 10.3
40RM024H 268,000 9.4 (Note 4) 9.5 (Note 4)
028 25
40RM028H 282,000 9.6 9.5 (Note 4)
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. Carrier model 40RM is a commercial packaged air-handling unit with a direct expansion coil.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.
4. Meets ASHRAE Std. 90.1 when used with heating section other than electric resistance heat.

FEATURES: Semi-hermetic compressors Low oil pressure safety switch


Suction cutoff unloading on lead compressor Refrigerant high- and low-pressure switches
Independent refrigerant circuits Calibrated circuit breakers
Time Guard anti-short-cycling device

OPTIONS: Corrosion-resistant coil options Accessory control (for VAV applications)


Additional electric unloader package Low ambient control
Additional pressure unloader package Gage panel package

CATALOG NO. 523-80022

38AH, AIR-COOLED CONDENSING UNITS, 40 TO 130 TONS


Condensing Unit 38AH Nominal Capacity (Tons) Net Cooling (Btu/h) EER IPLV

044 40 502,000 10.7 13.0


054 50 583,000 10.5 13.0
064 60 699,000 10.5 13.3
074 70 882,100 10.1 12.6
084 80 1,022,400 10.1 12.5
094 90 1,091,000 10.2 13.4
104 100 1,220,000 10.4 13.8
124 120 1,402,000 10.5 13.6
134 130 1,557,000 10.2 12.5
Notes:
1. Rated in accordance with ARI Standard 365.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: Up to 4 compressors and 2 refrigeration circuits Time Guard anti-short-cycling device


Can supply single or 2 separate air handlers Low oil pressure safety switch
Semi-hermetic compressors Refrigerant high- and low-pressure switches
Suction cutoff unloading on lead compressor Calibrated circuit breakers

OPTIONS: Corrosion-resistant coil options Accessory control (for VAV applications)


Additional electric unloader package Low ambient control
Additional pressure unloader package Thermostat options
Sound reduction package Single-circuit options

CATALOG NO. 523-80019

33
REFERENCE GUIDE

38AKS, AIR-COOLED CONDENSING UNITS, 12.5 TO 40 TONS


Condensing Unit 38AKS Nominal Capacity (Tons) Net Cooling (Btu/h) EER IPLV

014 12.5 150,000 12.1 15.8


016 15 198,000 11.0 14.9
024 20 248,000 10.5 13.9
028 25 330,000 10.2 12.1
034 30 370,000 10.1 13.1
044 40 506,000 10.1 13.0
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Semi-hermetic reciprocating compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Non-fused disconnect switch Thermostat options
Gage panel package Low ambient control
Electric unloader package Winter start package

CATALOG NO. 523-80021 (sizes 014-024); 523-80022 (sizes 028-044)

38AKS, SPLIT SYSTEMS WITH AIR-COOLED CONDENSING UNITS, 12.5 TO 20 TONS


Condensing Unit Nominal Capacity Indoor Air Handler System Net Cooling
System EER System IPLV
38AKS (Tons) (Note 2) (Btu/h)

40RM014 138,000 10.4 12.7


40RM014H 144,000 10.6 13.0
014 12.5
40RM016 144,000 10.6 11.6
40RM016H 146,000 10.8 13.1
40RM016 176,000 9.8 12.3
40RM016H 182,000 9.7 12.1
016 15
40RM024 184,000 9.8 12.2
40RM024H 196,000 10.0 12.5
024 20 40RM028H 244,000 9.5 11.8
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. Carrier model 40RM is a commercial packaged air-handling unit with a direct expansion coil.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Semi-hermetic reciprocating compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Non-fused disconnect switch Thermostat options
Gage panel package Low ambient control
Electric unloader package Winter start package

CATALOG NO. 523-80021

34
REFERENCE GUIDE

38AQ, SPLIT SYSTEM HEAT PUMP WITH AIR-COOLED CONDENSING UNIT, 6 TONS
Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Outdoor Unit Indoor Unit
Capacity
38AQ 40RMQ Capacity Capacity Capacity
(Tons) EER COP COP
(Btu/h) (Btu/h) (Btu/h)

007 008 6 75,000 10.3 71,000 3.2 46,000 2.3


Notes:
1. Rated in accordance with ARI Standard 210/240.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
3. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.

FEATURES: Electric cooling and heating, R-22 Thermostatic expansion valves


Constant volume Field-configurable defrost system
Hermetic scroll compressors Low sound levels
High- and low-pressure switches Anti-short-cycling protection

OPTIONS: Outdoor Unit: Indoor Unit:


Enhanced coil grille High-static fan motor and drive options
Indoor thermostat options Heater coil options: electric, steam, hot water
Gage panel package Enthalpy-controlled economizer
CO2 sensors and UV-C germicidal lamps

CATALOG NO. 523-80023

38AQS, SPLIT SYSTEM HEAT PUMP WITH AIR-COOLED CONDENSING UNIT, 15 TONS
Heating
Nominal Cooling Heating (High-Temp.)
Outdoor Unit Indoor Unit (Low-Temp.)
Capacity
38AS 40RMQ
(Tons) Capacity Capacity Capacity
EER IPLV COP COP
(Btu/h) (Btu/h) (Btu/h)

016 016 15 174,000 9.3 11.3 172,000 3.1 100,000 2.1


Notes:
1. Rated in accordance with ARI Standard 340/360.

FEATURES: R-22 refrigerant Anti-short-cycling protection


Semi-hermetic reciprocating compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Refrigerant high- and low-pressure protection

OPTIONS: Corrosion resistant coil options Low ambient control


Gage panel package Condenser coil grille

CATALOG NO. 523-80023

38ARD, AIR-COOLED CONDENSING UNITS, 10 TO 20 TONS


Condensing Unit 38ARD Nominal Capacity (Tons) Net Capacity (Btu/h) EER IPLV

012 10 123,000 12.3 16.0


014 12.5 158,000 12.5 15.1
016 15 204,000 11.9 13.9
024 20 259,000 11.2 13.1
Notes:
1. Rated in accordance with ARI Standard 210/240 or 360.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Hermetic scroll compressors Compressor overload protection
Dual refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Convenience outlet (115 volt) and non-fused disconnect switch Low ambient control
Hail guard package (size 012) Gage panel package

CATALOG NO. 523-80021

35
REFERENCE GUIDE

38ARD, SPLIT SYSTEMS WITH AIR-COOLED CONDENSING UNITS, 10 TO 20 TONS


Condensing Unit Nominal Capacity System Net Capacity
Indoor Air Handler System EER System IPLV
38ARD (Tons) (Btu/h)

40RM012 113,000 10.3 11.7


40RM012H 118,000 10.5 12.4
012 10
40RM014 118,000 10.5 12.8
40RM014H 124,000 10.9 13.2
40RM012 135,000 9.7 9.9
40RM012H 143,000 10.2 10.3
40RM014 145,000 10.5 10.9
014 12.5
40RM014H 153,000 11.1 11.5
40RM016 152,000 10.8 11.0
40RM016H 161,000 11.3 11.5
40RM014 176,000 10.0 10.4
40RM014H 185,000 10.3 10.8
40RM016 187,000 10.2 10.5
016 15
40RM016H 198,000 10.6 10.9
40RM024 194,000 10.1 10.2
40RM024H 204,000 10.4 10.4
40RM024H 243,000 9.6 9.8
024 20 40RM028 242,000 9.6 9.9
40RM028H 252,000 9.7 9.9
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Carrier model 40RM is a commercial packaged air-handling unit with a direct expansion coil.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Hermetic scroll compressors Compressor overload protection
Dual refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Convenience outlet (115 volt) Low ambient control
Non-fused disconnect switch Gage panel package
Hail guard package (size 012)

CATALOG NO. 523-80021

38ARQ, SPLIT SYSTEM HEAT PUMPS WITH AIR-COOLED CONDENSING UNITS, 7.5 TO 10 TONS
Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Outdoor Unit Indoor Unit
Capacity Capacity Capacity Capacity
38ARQ 40RMQ
(Tons) EER COP COP
(Btu/h) (Btu/h) (Btu/h)

008 008 7.5 88,000 10.4 93,000 3.2 57,000 2.2


012 012 10 105,000 10.1 100,000 3.2 67,000 2.2
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
3. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.

FEATURES: R-22 refrigerant Anti-short-cycling protection


Hermetic scroll compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Refrigerant high- and low-pressure switches

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Convenience outlet (115 volt) Low ambient control
Non-fused disconnect switch Gage panel package
Hail guard package Condenser coil grille

CATALOG NO. 523-80023

36
REFERENCE GUIDE

38ARS, AIR-COOLED CONDENSING UNITS, 7.5 TO 10 TONS


Condensing Unit 38ARS Nominal Capacity (Tons) Net Capacity (Btu/h) EER IPLV

012 10 124,000 12.0 16.5


Notes:
1. Rated in accordance with ARI Standard 210/240 or 360.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Semi-hermetic reciprocating compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Electric unloader package (size 012) Low ambient control
Convenience outlet (115 volt) Gage panel package
Non-fused disconnect switch Condenser coil grille
Hail guard package

CATALOG NO. 523-80021

38ARS, SPLIT SYSTEMS WITH AIR-COOLED CONDENSING UNITS, 7.5 TO 10 TONS


Condensing Unit Nominal Capacity Indoor Air Handler System Net Capacity
System EER System IPLV
38ARS (Tons) (Note 2) (Btu/h)

40RM012 114,000 10.3 13.1


40RM012H 119,000 10.3 13.6
012 10
40RM014 118,000 10.4 14.1
40RM014H 125,000 10.3 14.5
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Carrier model 40RM is a commercial packaged air-handling unit with a direct expansion coil.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Semi-hermetic reciprocating compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Electric unloader package (size 012) Low ambient control
Convenience outlet (115 volt) Gage panel package
Non-fused disconnect switch Condenser coil grille
Hail guard package

CATALOG NO. 523-80021

37
REFERENCE GUIDE

38ARZ, AIR-COOLED CONDENSING UNITS, 6 TO 10 TONS


Condensing Unit 38ARZ Nominal Capacity (Tons) Net Capacity (Btu/h) EER

007 6 72,000 12.4


008 7.5 100,000 12.7
012 10 133,000 12.4
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Condensing unit ratings are at 45°F saturated suction temperature and 95°Fdb entering outdoor air temperature.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Hermetic scroll compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Convenience outlet (115 volt) Low ambient control
Non-fused disconnect switch Gage panel package
Hail guard package Condenser coil grille

CATALOG NO. 523-80021

38ARZ, SPLIT SYSTEMS WITH AIR-COOLED CONDENSING UNITS, 6 TO 10 TONS


Indoor Air Handler
Condensing Unit 38ARZ Nominal Capacity (Tons) System Net Capacity (Btu/h) System EER
(Note 2)

28LA008 66,000 10.3


40RM007 69,000 11.0
007 6 40RM007H 72,000 11.2
40RM008 71,000 10.8
40RM008H 74,000 11.0
40RM007 87,000 10.6
40RM007H 91,000 11.3
40RM008 90,000 10.6
008 7.5
40RM008H 94,000 11.2
40RM012 93,000 10.6
40RM012H 98,000 10.8
40RM012 118,000 10.3
40RM012H 125,000 10.4
012 10
40RM014 123,000 10.4
40RM014H 130,000 10.4
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Carrier model 40RM is a commercial packaged air-handling unit with a direct expansion coil.

FEATURES: R-22 refrigerant Refrigerant high- and low-pressure switches


Hermetic scroll compressors Compressor overload protection
Single refrigerant circuit Crankcase heater
Anti-short-cycling protection

OPTIONS: Corrosion-resistant coil options PremierLink Controller


Convenience outlet (115 volt) Low ambient control
Non-fused disconnect switch Gage panel package
Hail guard package Condenser coil grille

CATALOG NO. 523-80021

38
REFERENCE GUIDE

40CG, CONSOLE (WITH 38CG CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 2.5 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure

1.5 40CG-018-3 38CG-018-3 18,000 650 10.0 9.0 55.0 38.0 79.0 49.0 2.0
2 40CG-024-3 38CG-024-3 23,400 800 10.0 9.1 56.0 40.0 74.0 49.0 2.6
2.5 40CG-030-3 38CG-030-3 30,000 800 10.0 9.0 55.0 40.0 78.0 49.0 3.3
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.

FEATURES: Refrigerant: R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection

OPTIONS: Low ambient control Crankcase heater

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40CS, CONSOLE (WITH 38CS CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 1.5 TO 2.5 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit

1.5 40CS-018-3 38CS-018-3 650 18,000 10.0 9.0 19,000 6.8 55.0 79.0 2.0
2 40CS-024-3 38CS-024-3 800 23,400 10.0 9.1 29,000 6.9 56.0 74.0 2.6
2.5 40CS-030-3 38CS-030-3 800 30,000 10.0 9.0 33,000 6.8 55.0 78.0 3.3
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.

FEATURES: Refrigerant: R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection

OPTIONS: Low ambient control Crankcase heater

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

39
REFERENCE GUIDE

40HD, SATELLITE (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 2 TO 4 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure

38HDC024-3 24,000 800 11.0 10.2 (Note 2) 65.5 57.2


2 40HD024-3
38HDL024-3 24,000 800 11.0 9.8 (Note 2) 63.2 54.9
38HDC036-3, 5, 6 34,400 1,226 11.0 10.5 68.6 64.5 56.2
3 40HD036-3 (Note 2) (Note 2)
38HDL036-3 35,000 1,226 10.0 10.0 68.6 64.7 56.4
38HDC048-3, 5, 6 47,000 1,610 11.0 10.4 (Note 2) 70.1 61.8
4 40HD048-3
38HDL048-3 46,400 1,610 10.5 10.0 (Note 2) 65.4 57.1
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Information is not available at this time.

FEATURES: Electric cooling, R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection

OPTIONS: Internal condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40QAB, UNDER CEILING (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 5 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure

38HDC018-3 18,000 500 12.0 11.0 57.2 48.9 66.1 57.8 1.6
1.5 40QAB024-331
38HDL018-3 18,000 500 11.6 10.5 57.2 48.9 59.5 51.2 1.7
38HDC024-3 22,800 600 12.0 11.0 58.4 50.1 65.5 57.2 2.1
2 40QAB024-331
38HDL024-3 23,000 600 11.0 11.2 58.4 50.1 63.2 54.9 2.2
38HDC030-3 30,000 840 12.0 11.0 68.4 60.1 63.0 54.7 2.7
2.5 40QAB036-321
38HDL030-3 29,000 840 10.3 9.7 68.4 60.1 59.5 51.2 2.9
38HDC036-3, 5, 6 34,000 840 12.0 10.5 68.4 60.1 64.5 56.2 3.2
3 40QAB036-321
38HDL036-3 34,000 840 10.1 9.6 68.4 60.1 64.7 56.4 3.2
38HDC048-3, 5, 6 47,000 1,200 12.0 10.8 67.3 59.0 70.1 61.8 4.4
4 40QAB048-321
38HDL048-3 45,500 1,200 10.8 9.9 67.3 59.0 65.4 57.1 4.5
38HDC060-3, 5, 6 58,000 1,600 12.0 11.2 70.1 61.8 69.4 61.1 5.2
5 40QAB060-311
38HDL060-3 58,500 1,600 10.8 9.9 70.1 61.8 65.8 57.5 5.7
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.

FEATURES: Electric cooling, R-22 Low sound levels


Fully hermetic compressors Fully insulated indoor cabinet
3-speed indoor fan motor Freeze protection

OPTIONS: Internal condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40
REFERENCE GUIDE

40QAE, UNDER CEILING (WITH 38QR CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 2 TO 5 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit

38QR-018C-3 500 19,000 11.0 10.0 17,000 7.2 57.2 67.2 1.9
2 40QAE024-331
38QR-024C-3 525 24,000 11.0 10.0 22,600 7.3 57.2 66.3 2.4
38QR-030C-3 870 30,000 11.0 10.2 28,000 7.4 68.4 65.9 2.7
3 40QAE036-321 38QR-036C-3 870 34,600 11.5 10.2 33,000 6.8 68.4 66.2 3.4
38QR-036C-5, 6 870 35,000 10.1 9.8 33,400 6.8 68.4 71.5 3.4
4 40QAE048-321 38QR-048C-3, 5, 6 1,100 48,000 10.2 9.6 45,500 7.3 67.3 73.0 4.8
5 40QAE060-311 38QR-060C-3, 5, 6 1,600 58,000 10.5 9.9 57,500 7.4 70.1 73.6 5.9
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.

FEATURES: Electric cooling and heating, R-22 Low sound levels


Fully hermetic compressors Fully insulated indoor cabinet
3-speed indoor fan motor Freeze protection

OPTIONS: Internal condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40QKB, CASSETTE (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 3 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure

38HDC018-3 18,300 525 11.0 10.4 56.3 48.0 66.1 57.8 1.8
1.5 40QKB024-3
38HDL018-3 17,800 525 11.4 10.6 56.3 48.0 59.5 51.2 1.6
38HDC024-3 24,000 915 11.0 10.9 54.8 46.5 65.5 57.2 2.1
2 40QKB036-3
38HDL024-3 24,000 915 11.8 11.3 54.8 46.5 63.2 54.9 2.1
38HDC030-3 30,000 915 10.8 9.6 54.8 46.5 63.0 54.7 2.8
2.5 40QKB036-3
38HDL030-3 29,000 915 11.1 10.1 54.8 46.5 59.5 51.2 2.8
38HDC036-3, 5, 6 33,000 915 10.8 10.5 54.8 46.5 64.5 56.2 3.1
3 40QKB036-3
38HDL036-3 34,400 915 10.5 9.7 54.8 46.5 64.7 56.4 3.5
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.

FEATURES: Electric cooling, R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection Internal condensate pump

OPTIONS: Crankcase heater Winter start control


Low ambient control Liquid line solenoid valve

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

41
REFERENCE GUIDE

40QKE, CASSETTE (WITH 38QR CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 1.5 TO 3 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit

1.5 40QKE024-3 38QR-018C-3 525 18,000 10.0 9.0 17,600 6.8 56.3 67.2 2.0
38QR-024C-3 980 25,000 10.7 10.2 23,800 7.6 54.8 66.3 2.4
2 40QKE036-3
38QR-030C-3 980 29,000 11.5 11.1 27,000 7.6 54.8 65.9 2.6
38QR-036C-3 1,100 33,000 10.5 9.5 33,000 6.8 59.1 66.2 3.5
3 40QKE048-3
38QR-036C-5, 6 1,100 34,400 10.0 9.2 34,000 6.8 59.1 71.5 3.7
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.

FEATURES: Electric cooling and heating, R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection Internal condensate pump

OPTIONS: Crankcase heater Winter start control


Low ambient control Liquid line solenoid valve

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40QNB, HIGH WALL (WITH 38AN & 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 0.75 TO 2 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure

0.75 40QNB009-1 38AN-009-1 8,500 215 10.5 9.7 50.4 42.1 62.3 54.0 0.9
1 40QNB012-1 38AN-012-1 11,000 300 10.5 9.3 54.0 45.7 63.1 54.8 1.2
40QNB012-3 38AN-012-3 11,600 300 11.0 10.1 54.0 45.7 63.1 54.8 1.1
38HDC018-3 17,300 480 11.3 10.4 57.6 49.3 66.1 57.8 1.7
1.5 40QNB018-3
38HDL018-3 16,200 480 11.0 9.7 57.6 49.3 59.5 51.2 1.7
38HDL018-3 17,600 550 11.7 10.4 62.5 54.2 59.5 51.2 1.6
2 40QNB024-3 38HDC024-3 23,600 550 12.0 10.8 62.5 54.2 65.5 57.2 2.2
38HDL024-3 22,600 550 11.3 11.3 62.5 54.2 63.2 54.9 2.2
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.

FEATURES: Electric cooling, R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet
Freeze protection

OPTIONS: Condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

42
REFERENCE GUIDE

40QNE, QNH, HIGH WALL (WITH 38BK CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 0.75 TO 2 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit

0.75 40QNE009-1 38BK-009-1 252 8,700 10.0 9.2 9,000 6.8 50.6 63.4 1.0
1 40QNH012-3 38BK-012-3 300 11,100 10.0 9.5 11,700 6.8 54.0 62.8 1.2
1.5 40QNH018-3 38BK-018-3 485 17,300 11.0 10.1 16,400 6.8 58.6 67.2 1.7
2 40QNH024-3 38BK-024-3 520 23,000 11.0 10.4 21,000 6.8 61.7 63.3 2.2
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.

FEATURES: Electric cooling and heating, R-22 Low sound levels


Fully hermetic compressors Diagnostics
3-speed indoor fan motor Fully insulated indoor cabinet

OPTIONS: Condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

40-SERIES, MULTI-ZONE, DUCT-FREE, SPLIT SYSTEMS, 2 TO 5 TONS


HIGH WALL, UNDER CEILING AND CASSETTE, COOLING ONLY
Nominal Indoor Unit Net Sound Ratings (dBa)
Standard
Capacity Outdoor Unit Cooling SEER EER Total kW
Fan Coil No. of CFM Indoor Outdoor
(Tons) (Btu/h) Power Power
(Note 1) Circuits

40QNB018-3 2 38HDS024-3 23,000 862 12.0 11.3 57.6 68.0 2.0


2 40QAB024-3 2 38HDS024-3 23,000 862 12.0 10.8 57.2 68.0 2.1
40QKB024-3 2 38HDS024-3 23,000 862 12.0 10.8 56.3 68.0 2.1
CONSOLE, COOLING ONLY
Nominal Indoor Unit Net Standard Sound Ratings (dBa)
Capacity Outdoor Unit Cooling CFM SEER EER Total kW
No. of Indoor Outdoor
(Tons) Fan Coil (Btu/h) (Note 3) Power Power
Circuits

5 40CG-030---3 2 38SC-030---3 60,000 800 10.0 9.0 55.0 80.0 3.3 × 2


CONSOLE, HEAT PUMP
High Heating Sound Power
Nominal Indoor Unit Standard Cooling
(Note 2) Ratings (dBa) Total
Capacity Outdoor Unit CFM
No. of (Note 3) Capacity Capacity kW
(Tons) Indoor Outdoor
Fan Coil (Btu/h)
SEER EER
(Btu/h)
HSPF Unit Unit
Circuits

5 40CS-030---3 2 38SB-030---3 800 60,000 10.0 9.0 64,500 6.8 55.0 80.0 3.3 × 2
Notes:
1. Multi-zone system operating with condensing unit 38HDS024 has a maximum of two zones and may use any combination of high wall, under ceiling
or cassette style fan coil units.
2. Multi-zone heat pump high heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
3. Standard CFM indicated for console units are for each indoor coil.

FEATURES: R-22 refrigerant Low sound levels


Fully hermetic compressors Choice of 4 fan coil types
3-speed indoor fan motor Diagnostics
Freeze protection Fully insulated indoor cabinet

OPTIONS: Condensate pump Winter start control


Crankcase heater Liquid line solenoid valve
Low ambient control

CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)

43
REFERENCE GUIDE

48AJ, AW, SINGLE-PACKAGE ROOFTOP UNITS, 20 TO 60 TONS


Cooling CFM
Unit 48AJ, AW Net Capacity (Tons) EER IPLV
Operating range

020 20 6,000-10,000 9.3 (Note 3) 9.5 (Note 3)


025 25 7,500-12,500
027 27.5 8,100-13,500 All 48AJ, AW models are All 48AJ, AW models are
030 30 9,000-15,000 ASHRAE Std. 90.1 ASHRAE Std. 90.1
035 35 10,500-17,500 compliant. See local Carrier compliant. See local Carrier
040 40 12,000-20,000 sales representative for sales representative for
050 50 13,500-20,000 ratings. ratings.
060 60 18,000-27,000
Notes:
1. 48AJ constant volume, vertical configuration; 48AW constant volume, horizontal configuration.
2. 48AJD and 48AWD are low heating capacity units; 48AJE and 48AWE are high heating capacity units.
3. Preliminary rating.

FEATURES: Electric cooling, R-22 Direct digital controls


Constant volume Integrated economizer
Reciprocating, semi-hermetic compressors Independent refrigeration circuits
Electric-operated compressor unloaders Horizontal or vertical discharge configuration

OPTIONS: Corrosion-resistant coil options Double-wall airstream


Power exhaust options CO2 sensor
Electric- or pressure-operated compressor unloaders Smoke detectors
High-efficiency evaporator fan motor Stainless steel heat exchanger
2-stage natural gas or LP gas heating Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80029

48AK, AY, SINGLE-PACKAGE, VARIABLE VOLUME ROOFTOP UNITS, 20 TO 60 TONS


Cooling CFM
Unit 48AK, AY Nominal Capacity (Tons) EER IPLV
Operating range

020 20 4,000-10,000 9.3 (Note 3) 9.5 (Note 3)


025 25 5,000-12,500
027 27.5 5,400-13,500 All 48AK, AY models are All 48AK, AY models are
030 30 6,000-15,000 ASHRAE Std. 90.1 ASHRAE Std. 90.1
035 35 7,000-17,500 compliant. See local Carrier compliant. See local Carrier
040 40 8,000-20,000 sales representative for sales representative for
050 50 10,000-20,000 ratings. ratings.
060 60 12,000-27,000
Notes:
1. 48AK variable volume, vertical configuration; 48AY variable volume, horizontal configuration.
2. 48AKD and 48AYD are low heating capacity units; 48AKE and 48AYE are high heating capacity units.
3. Preliminary rating.

FEATURES: Electric cooling, R-22 Direct digital controls


Variable volume, variable frequency drive Integrated economizer
Reciprocating, semi-hermetic compressors Independent refrigeration circuits
Electric-operated compressor unloaders Horizontal or vertical discharge configuration

OPTIONS: Corrosion-resistant coil options Double-wall airstream


Power exhaust options CO2 sensor
Electric- or pressure-operated compressor unloaders Smoke detectors
High-efficiency evaporator fan motor Stainless steel heat exchanger
2-stage natural gas or LP gas heating Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80029

44
REFERENCE GUIDE

48GP, GPN, SINGLE-PACKAGE, GAS HEATING/ELECTRIC COOLING UNITS, 2 TO 5 TONS


STANDARD UNIT
Nominal Capacity Sound Rating
Unit 48GP, GPN Standard CFM Net Cooling (Btu/h) SEER EER
(Tons) (decibels)

024 2 800 24,000 12.0 10.2 72


030 2.5 1,000 29,000 12.0 10.3 72
036 3 1,200 35,000 12.0 10.3 72
042 3.5 1,400 41,000 12.0 10.5 73
048 4 1,600 48,000 12.0 10.6 78
060 5 1,750 59,000 12.0 10.2 76
Notes:
1. 48GP is standard unit; 48GPN is a low NOx rated unit.
2. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
Unit 48GP, GPN Nominal Capacity (Tons) Net Cooling (Btu/h) SEER EER

024 2 24,000 13.0 10.8


030 2.5 29,000 12.7 10.9
036 3 35,000 12.5 10.6
042 3.5 41,000 12.5 10.7
048 4 48,000 12.3 10.8
060 5 59,000 12.3 10.5
Notes:
1. Units are equipped with factory-installed ICM motors to provide variable-speed blower operation.
2. Capacity and performance values shown are at 80°Fdb and 67°Fwb indoors, and 95°Fdb outdoors.

FEATURES: Electric cooling, Puron® (R-410A) refrigerant Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Natural gas or LP gas heating
Horizontal or vertical duct configuration Low NOx design (48GPN)
Rust-free composite base Direct spark ignition

OPTIONS: Electronic, variable-speed blower motor Low-ambient kit


Economizer with solid-state controls High altitude kit
Manual outdoor air damper Crankcase heater
Time Guard® II anti-short-cycling device Corrosion-resistant coil options

CATALOG NO. 524-80014

48GS, GSN, SINGLE-PACKAGE, GAS HEATING/ELECTRIC COOLING UNITS, 1.5 TO 5 TONS


Unit 48GS, GSN Nominal Capacity (Tons) Standard CFM Net Cooling (Btu/h) SEER Sound Rating (decibels)

018 1.5 600 18,000 10.0 75


024 2 800 24,600 10.0 75
030 2.5 1,000 28,800 10.0 75
036 3 1,200 34,400 10.0 80
042 3.5 1,400 42,000 10.0 80
048 4 1,600 46,500 10.0 80
060 5 2,000 60,000 10.0 80
Notes:
1. 48GS is standard unit; 48GSN is a low NOx rated unit.
2. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling, R-22 Natural gas or LP gas heating


Fully hermetic compressors Low NOx design (48GSN)
Horizontal or vertical duct configuration Direct spark ignition
Rust-free composite base Integrated gas control with diagnostics

OPTIONS: Economizer with solid-state controls Low-ambient kit


Manual outdoor air damper High altitude kit
Time Guard® II anti-short-cycling device Crankcase heater
Corrosion-resistant coil options Controls upgrade kit

CATALOG NO. 524-80003

45
REFERENCE GUIDE

48GX, GXN, SINGLE-PACKAGE, GAS HEATING/ELECTRIC COOLING UNITS, 2 TO 5 TONS


Nominal Capacity Sound Rating
Unit 48GX Standard CFM Net Cooling (Btu/h) SEER EER
(Tons) (decibels)

024 2 800 24,000 12.0 10.5 72


030 2.5 1,000 30,000 12.0 10.5 72
036 3 1,200 35,000 12.0 10.5 74
042 3.5 1,400 42,000 12.0 10.5 74
048 4 1,450 48,000 12.0 10.5 80
060 5 1,750 58,000 12.0 10.5 78
Notes:
1. 48GX is standard unit; 48GXN is a low NOx rated unit.
2. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling, R-22 Natural gas or LP gas heating


Fully hermetic scroll compressors Low NOx design (48GXN)
Rust-free composite base Direct spark ignition
Horizontal or vertical duct configuration Integrated gas control with diagnostics

OPTIONS: Economizer with solid-state controls Low-ambient kit


Manual outdoor air damper High altitude kit
Time Guard® II anti-short-cycling device Crankcase heater
Corrosion-resistant coil options Controls upgrade kit

CATALOG NO. 524-80028

48HG, SINGLE-PACKAGE, HIGH-PERFORMANCE ROOFTOP UNITS, 12.5 TO 25 TONS


Nominal Net Cooling Sound Rating
Unit 48HG Standard CFM EER IPLV Total kW
Capacity (Tons) (Btu/h) (decibels)

014 12.5 3,800 156,000 11.6 13.2 13.4 81.7


016 15 4,500 182,000 11.5 13.7 15.8 81.7
020 18 5,500 202,000 11.2 12.8 18.0 81.7
024 20 6,000 238,000 11.2 12.4 21.2 81.7
028 25 7,500 283,600 10.4 11.0 27.3 84.0
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. 48HGD low heating capacity; 48HGF high heating capacity

FEATURES: Electric cooling, R-22 ComfortLink controls


Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Multiple independent refrigerant circuits
2-stage natural gas or LP gas heating Hinged service access panels

OPTIONS: Integrated economizer Power exhaust


Corrosion-resistant coil options Enthalpy sensor
Indoor fan motor and drive options Smoke detector
CO2 sensor Stainless steel heat exchanger

CATALOG NO. 524-80022

46
REFERENCE GUIDE

48HJ, SINGLE-PACKAGE, HIGH-EFFICIENCY ROOFTOP UNITS, 3 TO 12.5 TONS


Nominal Capacity Sound Rating
Unit 48HJ Net Cooling (Btu/h) SEER EER Total kW
(Tons) (decibels)

004 3 36,000 13.0 11.2 3.2 76


005 4 46,000 13.0 11.1 4.1 76
006 5 61,000 13.0 11.0 5.5 80

Nominal Capacity Sound Rating


Unit 48HJ Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

007 6 74,000 11.0 (Note 2) 6.7 80


008 7.5 90,000 11.0 11.6 8.2 82
009 8.5 102,000 11.6 (Note 5) (Note 5) (Note 5)
012 10 120,000 11.0 11.4 10.9 84
014 12.5 138,000 9.6 10.3 14.4 86
Notes:
1. Rated in accordance with ARI Standard 210/240 or 360 (size 014).
2. IPLV is not applicable to single-compressor units.
3. 48HJD low heating capacity unit; 48HJE medium/high heating capacity unit; 48HJF high heating capacity unit.
4. California compliant: 48HJG, H and K are non-NOx units; 48HJL, M and N are low-NOx units.
5. Data available in November, 2002.

FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Integrated gas control with diagnostics
Single-stage or 2-stage natural gas (or LP gas) heating Vertical or horizontal duct configurations
Fully hermetic scroll compressors

OPTIONS: EconoMi$er microprocessor-controlled economizer PremierLink controls


Power exhaust options Direct digital controls
MoistureMi$er dehumidification package CO2 sensor
Energy$Recycler heat recovery Corrosion-resistant coil options
High-static indoor fan motor and drive Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80025

48HJ, SINGLE-PACKAGE ROOFTOP UNITS, 12 AND 15 TONS


Nominal Capacity Sound Rating
Unit 48HJD Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

015 12 134,000 10.6 11.4 12.2 88


017 15 180,000 10.5 11.4 17.1 88

Nominal Capacity Sound Rating


Unit 48HJF Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

015 12 134,000 10.6 11.4 12.2 88


017 15 180,000 10.5 11.1 17.2 88
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. 48HJD low heating capacity unit; 48HJF high heating capacity unit.

FEATURES: Electric cooling, R-22 Thermostatic expansion valves


Constant volume 2-stage natural gas (or LP gas) heating
Fully hermetic scroll compressors Direct spark ignition
Independent refrigerant circuits Vertical or horizontal duct configurations

OPTIONS: EconoMi$er2 microprocessor-controlled economizer PremierLink controls


Power exhaust Direct digital controls
Corrosion-resistant coil options Head pressure control package
MoistureMi$er dehumidification package Stainless steel heat exchanger

CATALOG NO. 524-80025

47
REFERENCE GUIDE

48JZ, JZN, SINGLE-PACKAGE, GAS HEATING, ELECTRIC HEAT PUMP UNITS, 2 TO 5 TONS
STANDARD UNIT
Cooling (Note 3) Heating Capacities and Efficiencies

Nominal High Low Sound


Standard
Unit 48JZ Capacity Net Heating COP at Heating COP at Rating
CFM SEER EER HSPF
(Tons) Capacity Capacity 47°F Capacity 17°F (decibels)
(Btu/h) at 47°F (Btu/h) at 17°F (Btu/h)
(Btu/h) (Btu/h)

024 2 800 24,000 12.0 10.5 23,800 3.0 13,000 2.0 7.0 72
030 2.5 1,000 29,000 12.0 10.4 28,200 3.2 15,600 2.1 7.0 72
036 3 1,200 36,000 12.0 10.5 34,400 3.2 18,000 2.0 7.2 77
042 3.5 1,400 41,000 12.0 10.6 40,000 3.2 22,000 2.0 7.2 73
048 4 1,600 47,500 12.0 10.5 44,000 3.1 23,600 2.0 7.2 79
060 5 1,750 59,000 12.0 10.0 55,000 3.1 31,000 2.0 7.2 79
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
Cooling (Note 3) Heating Capacities and Efficiencies
Nominal High
Unit 48JZ Capacity Low Heating
Net Capacity Heating COP at 47°F COP at
(Tons) SEER EER Capacity at HSPF
(Btu/h) Capacity at (Btu/h) 17°F (Btu/h)
17°F (Btu/h)
47°F (Btu/h)

024 2 24,000 12.7 11.3 23,800 3.2 13,000 2.1 7.0


030 2.5 29,000 12.7 11.3 27,400 3.2 15,400 2.1 7.0
036 3 36,000 12.3 11.2 34,400 3.2 18,000 2.0 7.2
042 3.5 41,000 12.5 10.7 39,000 3.2 21,400 2.0 7.2
048 4 47,500 12.3 11.0 41,500 3.2 23,000 2.1 7.2
060 5 59,000 12.1 10.6 54,800 3.1 30,800 2.0 7.2
GAS HEATING CAPACITIES AND EFFICIENCIES
Temperature Rise Range
Unit 48JZ Heating Input (Btu/h) Heating Capacity (Btu/h) AFUE (Note 4)
(°F)

024040
40,000 31,000 20-50 80.1
030040
030060 46,000 35-65 78.4
036060 60,000 46,000 25-55 78.7
042060 47,000 20-50 78.7
036090 70,000 45-75 79.9
042090 71,000 35-65 79.9
90,000
048090 70,000 25-55 78.6
060090 70,000 25-55 78.6
048115
115,000 92,000 35-65 81.1
060115
048130 104,000
130,000 40-70 80.3
060130 103,000
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
2. Units are equipped with factory-installed ICM motors to provide variable-speed blower operation.
3. Cooling capacity, EER and SEER values shown are at 80°Fdb and 67°Fwb indoors, and 95°Fdb outdoors.
4. AFUE – Annual Fuel Utilization Efficiency.

FEATURES: Electric cooling and heating, Puron (R-410A) Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base High- and low-pressure switches
Low-NOx design (48JZN) Direct spark ignition
Integrated gas control with diagnostics Turbo-tubular aluminized steel heat exchanger

OPTIONS: Electronic variable-speed blower motor High altitude kit


Economizer with solid-state controls Low-ambient kit
Manual outdoor air damper Compressor hard start kit
Corrosion-resistant coil options Crankcase heater
Liquid propane conversion kit Filter rack

CATALOG NO. 524-80020

48
REFERENCE GUIDE

48TF, SINGLE-PACKAGE ROOFTOP UNITS, 3 TO 12.5 TONS


Nominal Net Cooling SEER SEER Sound Rating
Unit 48TF Standard CFM Total kW
Capacity (Tons) (Btu/h) Belt Drive Direct-drive (decibels)

004 3 1,200 35,000 10.0 9.7 4.0 81


005 4 1,600 47,000 10.0 9.7 5.5 81
006 5 2,000 57,000 10.0 9.7 6.7 81
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. 48TFD low heating capacity unit; 48TFE medium heating capacity unit; 48TFF high heating capacity unit.
3. California compliant: 48TFG, H and K are non-NOx units; 48TFL, M and N are low-NOx units.
4. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 Natural gas or LP gas heating


Constant volume Integrated gas control with diagnostics
Independent refrigeration circuits (sizes 008 to 014) Vertical and horizontal duct configurations
Fully hermetic compressors

OPTIONS: EconoMi$er2 microprocessor controlled economizer PremierLink controls


Corrosion-resistant coil options Direct digital controls
High-static fan motor and drive Enthalpy controls
Power exhaust options Head pressure control package
CO2 sensor Energy$Recycler heat recovery
Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80023

48TM, SINGLE-PACKAGE, ROOFTOP UNITS, 3 TO 12.5 TONS


Nominal Capacity Sound Rating
Unit 48TM Net Cooling (Btu/h) SEER EER Total kW
(Tons) (decibels)

004 3 35,000 10.0 8.7 4.0 81


005 4 47,000 10.0 8.8 5.3 81
006 5 57,000 10.0 8.5 6.7 81

Nominal Capacity Sound Rating


Unit 48TM Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

007 6 71,000 10.1 (Note 2) 7.0 80


008 7.5 88,000 10.1 10.5 8.7 82
009 8.5 100,000 10.1 10.4 9.9 82
012 10 114,000 10.1 11.0 11.3 84
014 12.5 136,000 9.5 9.7 14.3 86
Notes:
1. Rated in accordance with ARI Standard 210/240 or 360 (size 014).
2. IPLV is not applicable to single-compressor units.
3. 48TMD low heating capacity unit; 48TME medium heating capacity unit; 48TMF high heating capacity unit.

FEATURES: Electric cooling, R-22 Low NOx design (Models 48TML, M and N)
Constant volume Independent refrigerant circuits (sizes 008 to 014)
Single-stage or 2-stage natural gas (or LP gas) heating Integrated gas control with diagnostics
Fully hermetic reciprocating or scroll compressors Vertical or horizontal duct configurations

OPTIONS: Integrated economizer PremierLink controls


Power exhaust options Direct digital controls
Energy$Recycler heat recovery CO2 sensor
High-static indoor fan motor and drive Ultraviolet (UV-C) germicidal lamps
Corrosion-resistant coil options

CATALOG NO. 524-80025

49
REFERENCE GUIDE

48TM, SINGLE-PACKAGE ROOFTOP UNITS, 15 TO 25 TONS


Nominal Capacity Sound Rating
Unit 48TMD Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

016 15 176,000 9.5 9.5 17.1 88


020 18 202,000 9.7 10.2 21.2 88
025 20 236,000 9.5 10.1 24.8 94
028 25 278,000 9.7 10.4 28.5 94

Nominal Capacity Sound Rating


Unit 48TMF Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

016 15 176,000 9.5 9.5 17.2 88


020 18 202,000 9.7 10.1 21.3 88
025 20 236,000 9.5 10.0 24.8 94
028 25 278,000 9.5 10.0 29.0 94
Notes:
1. Rated in accordance with ARI Standard 360.
2. 48TMD low heating capacity unit; 48TMF high heating capacity unit.

FEATURES: Electric cooling, R-22 Thermostatic expansion valves


Constant volume 2-stage natural gas (or LP gas) heating
Fully hermetic scroll compressors Direct spark ignition
Independent refrigerant circuits Vertical or horizontal duct configurations

OPTIONS: Integrated economizer PremierLink controls


Power exhaust Direct digital controls
High-static indoor fan motor and drive Head pressure control package
Corrosion-resistant coil options Ultraviolet (UV-C) germicidal lamps
Stainless steel condensate pan

CATALOG NO. 524-80025

48Z, SINGLE-PACKAGE, CONSTANT OR VARIABLE VOLUME ROOFTOP UNITS, 30 TO 90 TONS


Cooling CFM
Unit 48AK, AY Nominal Capacity (Tons) EER IPLV
Operating range

030 30 6,000-15,000
040 40 8,000-20,000
050 50 9,000-20,000 All 48Z models are All 48Z models are
ASHRAE Std. 90.1 ASHRAE Std. 90.1
055 55 10,000-25,000 compliant. See local Carrier compliant. See local Carrier
060 60 12,000-30,000 sales representative for sales representative for
070 70 14,000-30,000 ratings. ratings.
075 75 15,000-30,000
090 90 17,000-34,000
Notes:
1. Units are rated in accordance with ARI Standard 340/360..

FEATURES: Electric cooling, R-22 Product integrated controls


Variable volume, variable frequency drive Integrated economizer
Reciprocating, semi-hermetic compressors Natural gas or LP gas heating
Electrically-controlled compressor unloaders Vertical discharge configuration

OPTIONS: Corrosion-resistant coil options Enthalpy control


Staged gas control CO2 sensor
Inlet guide vanes or VFD volume control Stainless steel heat exchanger
Modulating power exhaust Extended chassis
Return fan and building pressure control system (sizes 075 to 105) Outdoor airflow sensor

CATALOG NO. 524-80024

50
REFERENCE GUIDE

50AH, INDOOR, SINGLE-PACKAGE, HORIZONTAL COOLING UNITS, 2 TO 5 TONS


Nominal Net Cooling SEER (with Time Sound Rating
Unit 50AH Nominal CFM SEER Total kW
Capacity (Tons) (Btu/h) Delay Relay) (decibels)

024 2 800 25,000 10.80 11.00 2.6 78


036 3 1,200 36,000 10.00 10.05 4.3 82
048 4 1,600 49,500 10.20 10.40 5.5 82
060 5 2,000 58,500 9.75 10.05 6.9 82
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Unit is designed for indoor installation.

FEATURES: Electric cooling, R-22 Low profile design (installs above ceiling)
Fully hermetic scroll compressor Removable access panels

OPTIONS: Electric resistance heater coil (5 to 30 kW) Condensate pump


Time Guard II anti-short-cycling device Head pressure control damper
Vibration isolation package Thermostat and subbase assembly

CATALOG NO. 525-00001

50AJ, AW, SINGLE-PACKAGE ROOFTOP UNITS, 20 TO 60 TONS


Cooling CFM
Unit 50AJ, AW Net Capacity (Tons) EER IPLV
Operating range

020 20 6,000-10,000 9.5 (Note 3) 9.7 (Note 3)


025 25 7,500-12,500
027 27.5 8,100-13,500 All 50AJ/AW models are All 50AJ/AW models are
030 30 9,000-15,000 ASHRAE Std. 90.1 ASHRAE Std. 90.1
035 35 10,500-17,500 compliant. See local Carrier compliant. See local Carrier
040 40 12,000-20,000 sales representative for sales representative for
050 50 13,500-20,000 ratings. ratings.
060 60 18,000-27,000
Notes:
1. 50AJ constant volume, vertical configuration; 50AW constant volume, horizontal configuration.
2. 50AJD and 50AWD are low heating capacity units; 50AJE and 50AWE are high heating capacity units.
3. Preliminary rating.

FEATURES: Electric cooling, R-22 Direct digital controls


Constant volume Integrated economizer
Reciprocating, semi-hermetic compressors Independent refrigeration circuits
Electric-operated compressor unloaders Horizontal or vertical discharge configuration

OPTIONS: Electric resistance heater coil Double-wall airstream


Corrosion-resistant coil options CO2 sensor
Power exhaust options Smoke detectors
Electric- or pressure-operated compressor unloaders Stainless steel heat exchanger
High-efficiency evaporator fan motor Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80029

51
REFERENCE GUIDE

50AK, AY, SINGLE-PACKAGE, VARIABLE VOLUME ROOFTOP UNITS, 20 TO 60 TONS


Cooling CFM
Unit 50AK, AY Nominal Capacity (Tons) EER IPLV
Operating range

020 20 4,000-10,000 9.3 (Note 3) 9.5 (Note 3)


025 25 5,000-12,500
027 27.5 5,400-13,500 All 50AK, AY models are All 50AK, AY models are
030 30 6,000-15,000 ASHRAE Std. 90.1 ASHRAE Std. 90.1
035 35 7,000-17,500 compliant. See local Carrier compliant. See local Carrier
040 40 8,000-20,000 sales representative for sales representative for
050 50 10,000-20,000 ratings. ratings.
060 60 12,000-27,000
Notes:
1. 50AK variable volume, vertical configuration; 50AY variable volume, horizontal configuration.
2. 50AKD and 50AYD are low heating capacity units; 50AKE and 50AYE are high heating capacity units.
3. Preliminary rating.

FEATURES: Electric cooling, R-22 Direct digital controls


Variable volume, variable frequency drive Integrated economizer
Reciprocating, semi-hermetic compressors Independent refrigeration circuits
Electric-operated compressor unloaders Horizontal or vertical discharge configuration

OPTIONS: Electric resistance heater coil Double-wall airstream


Corrosion-resistant coil options CO2 sensor
Power exhaust options Smoke detectors
Electric- or pressure-operated compressor unloaders Stainless steel heat exchanger
High-efficiency evaporator fan motor Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 524-80029

50BRN, INDOOR, WATER-COOLED, SINGLE-PACKAGE COOLING UNITS, NOMINAL 5 TO 20 TONS


Unit 50BRN Nominal Capacity (Tons) Nominal CFM Net Cooling (Btu/h) EER

006 5 2,000 62,000 13.1 (SEER)


008 7.5 3,000 82,000 11.5
014 12 4,800 136,000 11.5
016 15 6,000 168,000 11.5
024 20 8,000 224,000 12.0
Notes:
1. Capacities shown are at ARI standard conditions.

FEATURES: Electric cooling, R-22 Vertical or horizontal supply air discharge


Constant volume High-efficiency tube-in-tube heat exchanger (condenser)
Hermetic scroll compressors Dual independent refrigeration circuits (sizes 012 to 024)
Sloped drain pan Removable front access panels

OPTIONS: Hot water or steam heating coil Ducted return-air filter rack (sizes 006 to 014)
Discharge plenum Thermostat options

CATALOG NO. 525-075

52
REFERENCE GUIDE

50BYN, INDOOR, AIR-COOLED, SINGLE-PACKAGE, VERTICAL COOLING UNITS, 5 TO 20 TONS


Nominal Capacity
Unit 50BYN Evaporator CFM Net Cooling (Btu/h) SEER EER Total kW
(Tons)

006 5 2,000 59,000 10.0 — 6.6


Notes:
1. Rated in accordance with ARI Standard 210/240.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 Vertical or horizontal supply air discharge


Constant volume Belt-driven centrifugal condenser fan
Fully hermetic scroll compressors Dual independent refrigeration circuits (sizes 012 and 024)
Sloped drain pan Removable front access panels

OPTIONS: Hot water or steam heating coil Defrost thermostat kit


Low-ambient damper Thermostat options
Discharge plenum CO2 sensor
Winter start kit (time delay and low-pressure switch)

CATALOG NO. 525-051

50BZN, INDOOR, SINGLE-PACKAGE COOLING UNITS (WITH REMOTE CONDENSER), 5 TO 15 TONS


Nominal Capacity
Unit 50BZN Air-Cooled Condenser Nominal CFM Net Cooling (Btu/h) SEER
(Tons)

09BYN006
006 5 2,000 59,000 10.0 (Note 2)
09AZ006
Notes:
1. Capacities shown are at ARI standard conditions.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 Vertical or horizontal supply air discharge


Constant volume High-efficiency tube-in-tube heat exchanger (condenser)
Hermetic scroll compressors Dual independent refrigeration circuits (sizes 012 to 016)
Sloped drain pan Removable front access panels

OPTIONS: Hot water or steam heating coil Ducted return-air filter rack (sizes 006 to 014)
Discharge plenum Thermostat options

CATALOG NO. 525-075

53
REFERENCE GUIDE

50EJQ, EWQ, SINGLE-PACKAGE, ROOFTOP HEAT PUMP UNITS, 20 AND 25 TONS


Unit Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Standard
50EJQ, Capacity
CFM Capacity Capacity Capacity
EWQ (Tons) EER Total kW COP Total kW COP Total kW
(Btu/h) (Btu/h) (Btu/h)

024 20 6,800 230,000 9.8 23.4 228,000 3.3 20.0 116,000 2.0 16.7
028 25 7,500 262,000 9.2 28.6 266,000 3.3 23.7 140,000 2.1 19.5
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. 50EJQ vertical discharge unit; 50EWQ horizontal discharge unit.
3. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
4. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.

FEATURES: Electric cooling and heating, R-22 Direct digital controls


Constant volume Integrated economizer
Semi-hermetic, reciprocating compressors Dual independent refrigerant circuits
Hinged access panels Dedicated horizontal or vertical units

OPTIONS: Electric resistance heater coil (36 or 72 kW) Electronic expansion board
Power exhaust Enthalpy controls
Corrosion-resistant coil options Head pressure control package
Field-installed control interface device CO2 sensor

CATALOG NO. 525-072

50GL, SINGLE-PACKAGE, ELECTRIC COOLING UNITS, 2 TO 5 TONS


STANDARD UNIT
Nominal Capacity Sound Rating
Unit 50GL Standard CFM Net Cooling (Btu/h) SEER EER
(Tons) (decibels)

024 2 800 24,000 12.0 10.2 72


030 2.5 1,000 29,000 12.0 10.3 72
036 3 1,200 35,000 12.0 10.3 72
042 3.5 1,400 41,000 12.0 10.5 73
048 4 1,600 48,000 12.0 10.6 78
060 5 1,750 59,000 12.0 10.2 76
Notes:
1. ARI capacities shown.
2. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
Nominal Capacity Cooling Capacity
Unit 50GL SEER EER Sound Rating (decibels)
(Tons) (Btu/h)

024 2 24,000 13.0 10.8 72


030 2.5 29,000 12.7 10.9 72
036 3 35,000 12.5 10.6 72
042 3.5 41,000 12.5 10.7 73
048 4 48,000 12.3 10.8 78
060 5 59,000 12.3 10.5 76
Notes:
1. Units are equipped with factory-installed ICM motors to provide variable-speed blower operation.
2. Capacity and SEER values shown are at 80°Fdb and 67°Fwb indoors, and 95°Fdb outdoors.

FEATURES: Electric cooling, Puron (R-410A) refrigerant Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels

OPTIONS: Electronic variable-speed blower motor Electric resistance heater coil (5 to 20 kW)
Economizer with solid-state controls Low-ambient kit
Manual outdoor air damper Crankcase heater
Time Guard® II anti-short-cycling device Corrosion-resistant coil options

CATALOG NO. 525-00013

54
REFERENCE GUIDE

50GS, SINGLE-PACKAGE, ELECTRIC COOLING UNITS, 1.5 TO 5 TONS


Unit 50GS Nominal Capacity (Tons) Standard CFM Net Cooling (Btu/h) SEER Sound Rating (decibels)

018 1.5 600 18,000 10.0 75


024 2 800 24,600 10.0 75
030 2.5 1,000 28,800 10.0 75
036 3 1,200 34,400 10.0 80
042 3.5 1,400 42,000 10.0 80
048 4 1,600 46,500 10.0 80
060 5 2,000 60,000 10.0 80
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling, R-22 Direct-drive, multi-speed blower motor


Fully hermetic compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels

OPTIONS: Economizer with solid-state controls Electric resistance heater coil (5 to 20 kW)
Manual outdoor air damper Low-ambient kit
Time Guard® II anti-short-cycling device Crankcase heater
Controls upgrade kit Corrosion-resistant coil options

CATALOG NO. 525-00034

50GX, SINGLE-PACKAGE, ELECTRIC COOLING UNITS, 2 TO 5 TONS


Nominal Capacity Sound Rating
Unit 50GX Standard CFM Net Cooling (Btu/h) SEER EER
(Tons) (decibels)

024 2 800 24,000 12.0 10.5 72


030 2.5 1,000 30,000 12.0 10.5 72
036 3 1,200 35,000 12.0 10.5 74
042 3.5 1,400 42,000 12.0 10.5 74
048 4 1,450 48,000 12.0 10.5 80
060 5 1,750 58,000 12.0 10.5 78
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling, R-22 Direct-drive, multi-speed blower motor


Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels

OPTIONS: Economizer with solid-state controls Controls upgrade kit


Manual outdoor air damper Low-ambient kit
Time Guard® II anti-short-cycling device Crankcase heater
Electric resistance heater coil (5 to 20 kW) Corrosion-resistant coil options

CATALOG NO. 525-00036

55
REFERENCE GUIDE

50HG, SINGLE-PACKAGE, HIGH-EFFICIENCY ROOFTOP UNITS, 12.5 TO 25 TONS


Nominal Net Cooling Sound Rating
Unit 50HG Standard CFM EER IPLV Total kW
Capacity (Tons) (Btu/h) (decibels)

014 12.5 3,800 156,000 11.6 13.2 13.4 81.7


016 15 4,500 182,000 11.5 13.7 15.8 81.7
020 18 5,500 202,000 11.2 12.8 18.0 81.7
024 20 6,000 238,000 11.2 12.4 21.2 81.7
028 25 7,500 283,600 10.4 11.0 27.3 84.0
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. 50HG no heating, 50HGA low electric heating capacity; 50HGB medium electric heating capacity; 50HGC high electric heating capacity.

FEATURES: Electric cooling, R-22 ComfortLink controls


Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Multiple independent refrigerant circuits
Hinged service access panels

OPTIONS: Integrated economizer Electric resistance heater coil (12 to 78 kW)


Power exhaust Enthalpy sensor
Indoor fan motor and drive options Smoke detector
Corrosion-resistant coil options CO2 sensor

CATALOG NO. 524-80022

50HJ, SINGLE-PACKAGE, HIGH-EFFICIENCY ROOFTOP UNITS, 3 TO 12.5 TONS


Nominal Net Cooling Sound Rating
Unit 50HJ Standard CFM SEER EER Total kW
Capacity (Tons) (Btu/h) (decibels)

004 3 1,200 36,000 13.0 11.2 3.21 76


005 4 1,450 47,000 13.0 11.1 4.25 76
006 5 1,750 61,000 13.0 11.0 5.55 80

Nominal Net Cooling Sound Rating


Unit 50HJ Standard CFM EER IPLV Total kW
Capacity (Tons) (Btu/h) (decibels)

007 6 2,100 74,000 11.0 (Note 2) 6.70 80


008 7.5 3,000 90,000 11.0 11.6 8.18 82
009 8.5 3,000 102,000 11.8 (Note 3) (Note 3) (Note 3)
012 10 3,200 120,000 11.0 11.4 10.91 84
014 12.5 4,300 139,000 9.8 10.5 14.04 86
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. IPLV is not applicable to single-compressor units.
3. Data available in November 2002.

FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Direct- or belt-driven evaporator fan
2-inch filter rack

OPTIONS: EconoMi$er2 microprocessor-controlled economizer Direct digital controls


Power exhaust options PremierLink controls
High-static indoor fan motor and drive Enthalpy control
MoistureMi$er dehumidification package CO2 sensor
Energy$Recycler heat recovery Corrosion-resistant coil options
Electric resistance heater coil or hydronic (glycol) coil Stainless steel drain pan
Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00031

56
REFERENCE GUIDE

50HJ, SINGLE-PACKAGE ROOFTOP UNITS, 12 TO 15 TONS


Nominal Net Cooling Sound Rating
Unit 50HJ Standard CFM EER IPLV Total kW
Capacity (Tons) (Btu/h) (decibels)

015 12 3,600 134,000 10.70 11.6 12.13 88


017 15 5,300 180,000 10.80 11.7 16.83 88
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 Independent refrigerant circuits


Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Direct- or belt-driven evaporator fan
Thermostatic expansion valves 2-inch filter rack

OPTIONS: EconoMi$er microprocessor-controlled economizer Direct digital controls


Power exhaust options PremierLink controls
High-static indoor fan motor and drive Enthalpy control
MoistureMi$er dehumidification package CO2 sensor
Energy$Recycler heat recovery Corrosion-resistant coil options
Electric resistance heater coil or hydronic (glycol) coil Stainless steel drain pan
Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00031

50HJQ, SINGLE-PACKAGE, HIGH-EFFICIENCY, ROOFTOP HEAT PUMP UNITS, 3 TO 10 TONS


Heating (High-
Nominal Capacity Cooling Sound Rating
Unit 50HJQ Temp.)
(Tons) (decibels)
Capacity (Btu/h) SEER Capacity (Btu/h) HSPF

004 3 36,000 12.0 34,000 7.6 76


005 4 46,000 12.0 46,000 7.6 76
006 5 60,000 11.9 60,000 7.6 80

Heating (High-
Nominal Capacity Cooling Sound Rating
Unit 50HJQ Temp.)
(Tons) (decibels)
Capacity (Btu/h) EER Capacity (Btu/h) COP
007 6 71,000 10.5 69,000 3.4 80
008 7.5 88,000 10.3 85,000 3.3 82
012 10 116,000 10.3 114,000 3.3 84
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.

FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Defrost system
Fully hermetic scroll compressors Low sound levels
Dual independent refrigerant circuits (sizes 008 and 012) Non-corrosive condensate drain pan

OPTIONS: EconoMi$er microprocessor-controlled economizer Direct digital controls


Power exhaust options PremierLink controls
High-static indoor fan motor and drive Enthalpy control
Energy$Recycler heat recovery CO2 sensor
Electric resistance heater coil Stainless steel drain pan
Corrosion-resistant coil options Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00027

57
REFERENCE GUIDE

50HJQ, SINGLE-PACKAGE, ROOFTOP HEAT PUMP UNITS, 13 AND 15 TONS


Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Unit Standard Sound
Capacity Rating
50HJQ CFM Capacity Total Capacity Total Capacity Total
(Tons) EER COP COP (decibels)
(Btu/h) kW (Btu/h) kW (Btu/h) kW

014 13 4,500 140,000 9.8 14.3 136,000 3.2 12.4 72,000 2.1 10.0 87
016 15 5,200 172,000 9.3 18.5 172,000 3.3 15.3 90,000 2.2 12.5 88
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
3. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.

FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Belt-driven fans with variable-pitch sheaves
Semi-hermetic, reciprocating compressors Defrost system
Dual independent refrigerant circuits (size 016) Electric unloaders (size 014)

OPTIONS: Electric resistance heater coil Direct digital controls


Integrated economizer PremierLink controls
Power exhaust options Enthalpy controls
Hydronic (glycol) heating coil Head pressure control package
Corrosion-resistant coil options CO2 sensor
High static pressure indoor fan motor and drive Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00022

50HQL, HORIZONTAL, WATER-SOURCE HEAT PUMP UNITS, 6 TO 10 TONS


WATER-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (86°F EWT) Heating (68°F EWT)


Nominal CFM
50HQL (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

096 8 3,200 94,600 12.8 108,700 4.4


120 10 4,000 120,000 12.7 137,800 4.2
GROUND-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (77°F EWT) Heating (32°F EWT)


Nominal CFM
50HQL (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

096 8 3,200 96,700 14.2 72,600 3.4


120 10 4,000 122,200 14.1 90,500 3.2
GROUNDWATER-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (59°F EWT) Heating (50°F EWT)


Nominal CFM
50HQL (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

096 8 3,200 101,900 17.4 91,000 4.0


120 10 4,000 127,600 17.2 114,000 3.9
Notes:
1. Ratings certified in accordance with ARI/ISO Standard 13256-1.
2. EWT – Entering Water Temperature.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling and heating, R-22 Thermostatic expansion valves


Standard and low-temperature models Dual refrigeration circuits
Fully hermetic or scroll compressors Condensate overflow sensor
Steel/copper tube-in-tube heat exchanger Anti-short cycle timer

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Deluxe control option


Sound attenuation package PremierLink controls
High-static blower and drive Loop controller
Thermostat options CO2 sensor

CATALOG NO. 525-00023

58
REFERENCE GUIDE

50HX, SINGLE-PACKAGE, HIGH EFFICIENCY HEAT PUMP UNITS, 2 TO 5 TONS


Net Net Net
Nominal Cooling Heating COP at Heating COP at Sound
Standard
Unit 50HX Capacity Capacity SEER EER Capacity 47°F Capacity 17°F HSPF Rating
CFM
(Tons) at 95°F at 47°F (Btu/h) at 17°F (Btu/h) (decibels)
(Btu/h) (Btu/h) (Btu/h)

024 2 800 23,400 12.0 10.2 23,800 3.2 12,400 2.0 6.9 78
030 2.5 1,000 28,600 12.0 10.0 28,200 3.2 15,400 1.9 7.1 78
036 3 1,200 35,000 12.0 10.0 33,000 3.2 18,000 1.9 7.0 80
042 3.5 1,400 41,500 12.0 10.1 40,000 3.3 21,000 1.9 7.0 80
048 4 1,600 47,500 12.0 10.1 44,000 3.5 23,600 2.0 7.0 82
060 5 1,800 57,000 11.0 9.2 57,000 3.5 31,800 2.0 7.2 82
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor (sizes 024 to 042)
Constant volume Electronic, variable-speed blower motor (sizes 048 & 060)
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Chronotemp defrost system Time Guard® II anti-short-cycling device

OPTIONS: Manual outdoor air damper Electric resistance heater coil (5 to 20 kW)
Copper-fin coils Low-ambient kit
Controls upgrade kit Filter rack
Thermostat options

CATALOG NO. 525-076

50JS, SINGLE-PACKAGE HEAT PUMP UNITS, 1.5 TO 5 TONS


Net Net Net
Nominal Sound
Standard Cooling Heating COP at Heating COP at
Unit 50JS Capacity SEER HSPF Rating
CFM Capacity at Capacity at 47°F (Btu/h) Capacity at 17°F (Btu/h)
(Tons) (decibels)
95°F (Btu/h) 47°F (Btu/h) 17°F (Btu/h)

018 1.5 700 19,000 10.0 17,600 2.9 8,600 1.8 6.6 73
024 2 800 24,000 10.0 23,600 2.9 12,400 1.8 6.8 73
030 2.5 1,000 29,000 10.0 29,000 3.0 15,000 1.9 6.9 75
036 3 1,200 35,000 10.0 35,000 3.0 18,000 1.9 7.0 79
042 3.5 1,250 42,000 10.0 40,500 3.0 22,000 1.9 7.0 73
048 4 1,600 47,000 10.0 47,000 3.0 27,000 2.0 7.0 80
060 5 2,000 57,500 10.0 57,000 3.2 32,000 2.0 7.0 78
Notes:
1. Rated in accordance with the latest edition of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic compressors Vertical or horizontal duct configuration
Time Guard® II anti-short-cycling device Low sound levels
Rust-free composite base

OPTIONS: Electric resistance heater coil (5 to 20 kW) Low-ambient kit


Economizer with solid-state controls Controls upgrade kit
Manual outdoor air damper Crankcase heater
Corrosion-resistant coil options Filter rack

CATALOG NO. 525-00046

59
REFERENCE GUIDE

50JX, SINGLE-PACKAGE HEAT PUMP UNITS, 2 TO 5 TONS


Nominal Net Cooling Net Heating COP at Net Heating COP at Sound
Unit Standard
Capacity Capacity at SEER EER Capacity at 47°F Capacity at 17°F HSPF Rating
50JX CFM
(Tons) 95°F (Btu/h) 47°F (Btu/h) (Btu/h) 17°F (Btu/h) (Btu/h) (decibels)

024 2 800 23,200 12.0 10.5 22,400 3.2 13,000 2.0 7.1 72
030 2.5 1,000 29,000 12.0 10.5 28,200 3.2 15,600 2.0 7.1 72
036 3 1,200 35,000 12.0 10.5 34,000 3.2 19,000 1.9 7.1 77
042 3.5 1,400 41,500 12.0 10.5 40,000 3.2 22,000 2.0 7.2 73
048 4 1,450 47,000 12.0 10.5 44,000 3.1 23,600 2.0 7.1 79
060 5 1,750 60,000 12.0 10.5 57,000 3.3 32,000 2.0 7.2 79
Notes:
1. Rated in accordance with the latest edition of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels

OPTIONS: Electric resistance heater coil (5 to 20 kW) Low-ambient kit


Economizer with solid-state controls Controls upgrade kit
Manual outdoor air damper Crankcase heater
Corrosion-resistant coil options Filter rack

CATALOG NO. 525-00037

50JZ, SINGLE-PACKAGE HEAT PUMP UNITS, 2 TO 5 TONS


STANDARD UNIT
Net High Low
Nominal COP at COP at Sound
Standard Cooling Heating Heating
Unit 50JZ Capacity SEER EER 47°F 17°F HSPF Rating
CFM Capacity at Capacity at Capacity at
(Tons) (Btu/h) (Btu/h) (decibels)
95°F (Btu/h) 47°F (Btu/h) 17°F (Btu/h)

024 2 800 24,000 12.0 10.5 23,800 3.0 13,000 2.0 7.0 72
030 2.5 1,000 29,000 12.0 10.4 28,200 3.1 15,600 2.0 7.1 72
036 3 1,200 36,000 12.0 10.5 34,400 3.2 18,000 2.0 7.2 77
042 3.5 1,400 41,000 12.0 10.6 40,000 3.2 22,000 2.0 7.2 73
048 4 1,600 47,500 12.0 10.5 44,000 3.1 23,600 2.0 7.2 79
060 5 1,750 59,000 12.0 10.0 55,000 3.1 31,000 2.0 7.2 79
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
High
Nominal Net Cooling Low Heating
Heating COP at 47°F COP at
Unit 50JZ Capacity Capacity at EER SEER Capacity at HSPF
Capacity at (Btu/h) 17°F (Btu/h)
(Tons) 95°F (Btu/h) 17°F (Btu/h)
47°F (Btu/h)

024 2 24,000 11.3 12.7 23,800 3.2 13,000 2.1 7.0


030 2.5 29,000 11.3 12.7 28,000 3.2 15,400 2.1 7.0
036 3 36,000 11.2 12.3 34,400 3.2 18,000 2.0 7.2
042 3.5 41,000 10.7 12.5 39,400 3.2 21,400 2.0 7.2
048 4 47,500 11.0 12.3 43,600 3.2 23,000 2.1 7.2
060 5 59,000 10.6 12.1 54,800 3.2 30,800 2.1 7.2
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
2. Units are equipped with factory-installed ICM motors to provide variable-speed blower operation.
3. Capacity, EER and SEER values shown are at 80°Fdb and 67°Fwb indoors, and 95°Fdb outdoors.

FEATURES: Electric cooling and heating, Puron (R-410A) Direct-drive, multi-speed blower motor
Fully hermetic compressors Vertical or horizontal duct configuration
Rust-free composite base High- and low-pressure switches

OPTIONS: Electronic variable-speed blower motor Electric resistance heater coil (5 to 20 kW)
Economizer with solid-state controls Low-ambient kit
Manual outdoor air damper Crankcase heater
Corrosion-resistant coil options Filter rack

CATALOG NO. 525-00014

60
REFERENCE GUIDE

50KQA, KQD, CONSOLE, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 1.5 TONS
Cooling (Note 2) Heating (Note 3) Water
Unit Nominal
Nominal Water Flow Pressure
50KQA, Capacity
CFM Capacity Capacity GPM Drop
KQD (Tons) EER Total kW COP Total kW
(Btu/h) (Btu/h) (Ft wg)

007 0.5 275 6,800 12.2 0.531 8,600 4.3 0.548 1.7 2.3
009 0.75 275 9,000 12.6 0.744 11,600 4.2 0.791 2.3 4.2
Notes:
1. Rated in accordance with ARI Standard 320.
2. Cooling standard: 85°F entering water temperature.
3. Heating standard: 70°F entering water temperature.
4. 50KQA standard temperature range unit; 50KQD low temperature range unit.
5. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling and heating, R-22 Removable console cabinet


Standard and low temperature models Control section access door
Hermetic compressors Low sound levels
Steel/copper tube-in-tube heat exchanger Microprocessor-based controls (CMX)

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Deluxe control option (DMX)


Motorized water valve Cabinet options
Motorized fresh air damper Thermostat options

CATALOG NO. 525-011

50RHC, RVC, HORIZONTAL & VERTICAL, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
WATER-SOURCE APPLICATIONS

Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)

018 1.5 600 18,200 12.3 22,000 4.2 4.5 3.9 9.1
024 2 800 23,800 13.0 27,800 4.6 6.0 6.0 13.8
030 2.5 1,000 28,000 12.2 33,500 4.4 7.5 4.0 9.3
036 3 1,200 35,000 12.0 45,500 4.2 9.5 4.7 10.9
041 3.5 1,325 37,700 12.0 47,500 4.2 10.5 3.7 8.6
042 3.5 1,350 41,000 12.0 52,600 4.2 11.0 5.1 11.8
048 4 1,600 47,100 12.2 58,200 4.4 12.0 4.9 11.3
060 5 2,000 58,000 12.0 76,800 4.2 15.0 10.7 24.6
Notes:
1. 50RHC horizontal unit; 50RVC vertical unit.
2. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
3. The temperature of the water or brine loop is usually controlled within a temperature range of 60°F to 90°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
5. EWT – Entering Water Temperature.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Capillary metering device
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Sound attenuation package


High-static blower Deluxe control system
2-inch filter rack Carrier Comfort Network (CCN) controller
Fire-rated hoses

CATALOG NO. 525-00029

61
REFERENCE GUIDE

50RHR, RVR, HORIZ. & VERT. HIGH-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
WATER-SOURCE APPLICATIONS

Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)

006 0.5 180 6,200 12.8 7,400 4.2 1.50 1.7 3.9
009 0.75 300 8,100 12.8 10,300 4.3 2.25 2.9 6.7
015 1.25 500 14,100 13.3 16,800 4.6 3.75 6.8 15.7
019 1.5 600 18,900 12.5 22,500 4.2 4.50 5.6 12.8
024 2 800 23,000 12.3 27,600 4.2 6.00 5.8 13.5
030 2.5 1,000 28,500 13.2 33,300 4.4 7.50 3.3 7.6
036 3 1,200 34,000 13.0 41,700 4.2 9.00 2.9 6.8
042 3.5 1,400 40,000 13.0 46,700 4.3 10.50 3.8 8.8
048 4 1,600 47,000 12.8 58,000 4.2 12.00 5.4 12.4
060 5 2,000 59,000 12.8 68,000 4.2 15.00 7.9 18.2
Notes:
6. 50RHR horizontal unit; 50RVR vertical unit.
7. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
8. The temperature of the water or brine loop is usually mechanically controlled within a temperature range of 60°F to 90°F.
9. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
10. Size 006 available as a RHR (horizontal) model only.
11. EWT – Entering Water Temperature.
GROUND-SOURCE APPLICATIONS

Unit Nominal Cooling (77°F EWT) Heating (32°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)

006 0.5 180 5,600 14.3 4,400 3.4 1.50 1.7 3.9
009 0.75 300 8,300 14.2 6,200 3.4 2.25 2.9 6.7
012 1 375 12,100 14.2 8,700 3.4 3.00 8.1 18.7
015 1.25 500 14,500 14.8 10,700 3.5 3.75 6.8 15.7
019 1.5 600 19,100 13.4 11,800 3.2 4.50 5.6 12.8
024 2 800 23,000 13.3 16,700 3.3 6.00 5.8 13.5
030 2.5 1,000 28,700 14.4 20,100 3.4 7.50 3.3 7.6
036 3 1,200 35,200 14.7 25,500 3.4 9.00 2.9 6.8
042 3.5 1,400 42,000 15.0 29,400 3.4 10.50 3.8 8.8
048 4 1,600 48,500 14.3 35,300 3.3 12.00 5.4 12.4
060 5 2,000 60,600 14.1 44,000 3.2 15.00 7.9 18.2
Notes:
1. 50RHR horizontal unit; 50RVR vertical unit.
2. A brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink.
3. The heat exchange loop may be placed in horizontal trenches or vertical bores, or be submerged in a body of surface water.
4. The temperature of the brine is related to the climatic conditions and may vary from 20°F to 110°F.
5. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 330).
6. Size 006 available as RHR (horizontal) model only.
7. EWT – Entering Water Temperature.

62
REFERENCE GUIDE

50RHR, RVR, HORIZ. & VERT. HIGH-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
(continued)

GROUNDWATER-SOURCE APPLICATIONS

Unit Nominal Cooling (59°F EWT) Heating (50°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)

006 0.5 180 5,900 17.6 5,500 3.8 1.50 1.7 3.9
009 0.75 300 8,800 17.6 7,700 3.8 2.25 2.9 6.7
012 1 375 12,500 17.6 11,000 3.6 3.00 8.1 18.7
015 1.25 500 15,200 17.6 13,500 4.1 3.75 6.8 15.7
019 1.5 600 20,100 17.6 16,700 3.6 4.50 5.6 12.8
024 2 800 26,100 18.2 21,300 3.7 6.00 5.8 13.5
030 2.5 1,000 31,100 18.6 27,000 3.9 7.50 3.3 7.6
036 3 1,200 37,500 18.2 33,400 3.9 9.00 2.9 6.8
042 3.5 1,400 48,500 18.6 38,300 3.9 10.50 3.8 8.8
048 4 1,600 54,000 18.1 46,000 3.8 12.00 5.4 12.4
060 5 2,000 64,500 16.8 56,000 3.8 15.00 7.9 18.2
Notes:
1. 50RHR horizontal unit; 50RVR vertical unit.
2. A water-to-air heat pump using water pumped from a well, lake or stream functioning as a heat source/heat sink.
3. The temperature of the water is related to the climatic conditions and may vary from 40°F to 80°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 325).
5. Size 006 available as RHR (horizontal) model only.
6. EWT – Entering Water Temperature.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Thermostatic expansion valves
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Sound attenuation package


High-static blower (size 048) Deluxe control system
2-inch filter rack Thermostat options
Fire-rated hoses Loop controller
Ball valves and strainers Carrier Comfort Network (CCN) controller

CATALOG NO. 525-040

63
REFERENCE GUIDE

50RHS, RVS, RDS, PREMIUM-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 1.25 TO 6 TONS
WATER-SOURCE APPLICATIONS

Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHS, Capacity
CFM Capacity EER Capacity COP GPM
RVS (Tons) (Psi) (Ft wg)
(Btu/h) (Vert/Horiz) (Btu/h) (Vert/Horiz)

015 1.25 500 14,100 16.0 / 16.0 16,300 5.3 / 5.3 3.8 1.3 3.0
018 1.5 600 17,100 14.8 / 14.4 20,900 5.0 / 4.8 4.5 1.6 3.7
024 2 800 24,200 14.9 / 14.5 30,100 4.8 / 4.7 6.0 1.5 3.5
030 2.5 1,000 28,900 15.1 / 14.7 35,000 4.8 / 4.7 8.0 2.2 5.1
036 3 1,150 33,800 14.9 / 14.5 40,400 4.6 / 4.4 9.0 3.4 7.9
042 3.5 1,400 41,000 14.5 / 14.1 49,800 4.8 / 4.7 10.5 4.4 10.2
048 4 1,600 45,800 14.6 / 14.2 54,100 4.9 / 4.8 12.0 5.5 12.7
060 5 2,000 56,800 13.4 / 13.0 74,900 4.7 / 4.6 15.0 3.1 7.2
070 6 2,300 63,700 12.4 / 12.4 78,300 4.5 / 4.5 18.0 4.3 9.9
Notes:
1. 50RHS horizontal unit; 50RVS vertical (up flow) unit; 50RDS vertical (down flow) unit.
2. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
3. The temperature of the water or brine loop is usually mechanically controlled within a temperature range of 60°F to 90°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
5. EWT – Entering Water Temperature.
GROUND-SOURCE APPLICATIONS

Unit Nominal Cooling (77°F EWT) Heating (32°F EWT) Water Pressure Drop
Nominal Water Flow
50RHS, Capacity
CFM Capacity EER Capacity COP GPM
RVS (Tons) Psi Ft wg
(Btu/h) (Vert/Horiz) (Btu/h) (Vert/Horiz)

015 1.25 500 14,900 18.5 / 18.5 11,200 3.8 / 3.8 3.8 1.5 3.5
018 1.5 600 18,300 16.7 / 16.2 13,200 3.6 / 3.5 4.5 1.8 4.2
024 2 800 26,000 17.1 / 16.6 19,200 3.6 / 3.5 6.0 1.8 4.2
030 2.5 1,000 30,700 16.9 / 16.4 22,200 3.6 / 3.5 8.0 2.6 6.0
036 3 1,150 35,800 16.4 / 15.9 26,700 3.4 / 3.3 9.0 3.9 9.0
042 3.5 1,400 43,300 16.0 / 15.5 32,700 3.7 / 3.6 10.5 5.1 11.8
048 4 1,600 48,900 16.4 / 15.9 36,900 3.7 / 3.6 12.0 6.4 14.8
060 5 2,000 59,400 14.6 / 14.2 48,700 3.6 / 3.5 15.0 3.6 8.3
070 6 2,300 67,100 13.4 / 13.4 53,400 3.6 / 3.6 18.0 5.0 11.6
Notes:
1. 50RHS horizontal unit; 50RVS vertical unit.
2. A brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink.
3. The heat exchange loop may be placed in horizontal trenches or vertical bores, or be submerged in a body of surface water.
4. The temperature of the brine is related to the climatic conditions and may vary from 20°F to 110°F.
5. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 330).
6. EWT – Entering Water Temperature.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Thermostatic expansion valves
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Sound attenuation package


High-static blower (sizes 030 and 036) Deluxe control system
2-inch filter rack Thermostat options
Fire-rated hoses Loop controller
Ball valves and strainers Carrier Comfort Network (CCN) controller

CATALOG NO. 525-040

64
REFERENCE GUIDE

50RTG, SINGLE-PACKAGE, ROOFTOP WATER-SOURCE HEAT PUMP UNITS, 3 TO 20 TONS


Nominal Cooling (86°F EWT) Heating (68°F EWT) Water
Unit Water Flow
Capacity Nominal CFM Pressure Drop
50RTG Capacity Capacity GPM
(Tons) EER COP (Ft wg)
(Btu/h) (Btu/h)

03 3 1,200 33,400 13.6 38,300 4.7 8.4 9.5


04 4 1,600 45,600 14.7 52,200 5.0 11.2 12.7
05 5 2,000 58,100 13.6 68,000 4.5 14.7 18.3
07 7 2,600 78,800 13.2 90,900 4.3 19.9 10.5
08 8 3,200 91,900 14.6 96,700 4.6 22.7 13.4
12 12 4,800 133,100 13.0 148,200 4.2 33.2 10.1
15 15 6,000 175,700 15.0 175,700 4.9 43.0 12.2
20 20 8,000 249,700 13.9 267,100 4.5 62.0 20.8
Notes:
1. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard-320).

FEATURES: Electric cooling and heating, R-22 Microprocessor-based controls (CMX)


Fully hermetic scroll compressors Variable-pitch sheaves
Steel/copper tube-in-tube heat exchanger Thermostatic expansion valves
ABS gear-driven dampers (direct-drive) Slide-out blower assembly

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Deluxe control system (DMX)


Enthalpy controlled economizer 2-inch or 4-inch pleated 30% efficient filters
Two-position motorized outdoor air damper

CATALOG NO. 525-026

50RWS, WATER-SOURCE HEAT PUMP UNITS, 3 TO 10 TONS


WATER-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (86°F EWT) Heating (68°F EWT)


Water Flow GPM
50RWS (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

036 3 9.0 29,000 14.3 43,000 5.0


060 5 15.0 44,400 12.0 63,300 4.2
GROUND-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (77°F EWT) Heating (32°F EWT)


Water Flow GPM
50RWS (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

036 3 9.0 29,800 16.2 27,200 3.3


GROUNDWATER-SOURCE APPLICATIONS

Unit Nominal Capacity Cooling (59°F EWT) Heating (50°F EWT)


Water Flow GPM
50RWS (Tons)
Capacity (Btu/h) EER Capacity (Btu/h) COP

036 3 9.0 31,200 20.6 33,400 4.0


Notes:
1. Ratings certified in accordance with ARI/ISO Standard 13256-2.
2. EWT – Entering Water Temperature.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling and heating, R-22 Thermostatic expansion valves


Standard and low-temperature models Dual refrigeration circuits
Scroll compressors Condensate overflow sensor
Steel/copper tube-in-tube heat exchanger Anti-short cycle timer

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Deluxe control option


Sound attenuation package PremierLink controls
Thermostat options Loop controller
CO2 sensor

CATALOG NO. 525-00030

65
REFERENCE GUIDE

50SX, SINGLE-PACKAGE, HIGH-EFFICIENCY ELECTRIC COOLING UNITS, 2 TO 5 TONS


Nominal Capacity Sound Rating
Unit 50SX Standard CFM Net Cooling (Btu/h) SEER (Note 3) EER
(Tons) (decibels)

024 2 785 23,400 12.0 10.6 80


030 2.5 990 29,800 12.0 10.5 80
036 3 1,225 36,800 12.0 10.5 80
042 3.5 1,400 41,500 12.0 10.3 80
048 4 1,585 47,500 12.0 10.2 82
060 5 1,995 60,000 11.0 9.4 82
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
2. All units have factory-installed time-delay relay.

FEATURES: Electric cooling, R-22 Direct-drive, multi-speed blower motor


Constant volume Vertical or horizontal duct configuration
Fully hermetic scroll compressors Low sound levels

OPTIONS: Manual outdoor air damper Thermostat options


Time Guard® II anti-short-cycling device Low-ambient kit
Electric resistance heater coil (5 to 20 kW) High- and low-pressure switches
Filter rack

CATALOG NO. 525-093

50TFF, SINGLE-PACKAGE ROOFTOP UNITS, 3.0 TO 12.5 TONS


Nominal Net Cooling SEER SEER Sound Rating
Unit 50TFF Standard CFM Total kW
Capacity (Tons) (Btu/h) Belt Drive Direct-drive (decibels)

004 3 1,200 35,000 10.0 9.7 4.0 81


005 4 1,600 47,000 10.0 9.7 5.5 81
006 5 2,000 57,000 10.0 9.7 6.7 81
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 Vertical or horizontal duct configuration


Constant volume Non-corrosive sloped condensate pan
Fully hermetic, reciprocating compressors 2-inch filters
Acutrol refrigerant metering system Independent refrigeration circuits (sizes 008 to 014)

OPTIONS: Electric resistance heater coil (4.4 to 51 kW) Direct digital controls
Integrated economizer Head pressure control package
Power exhaust Corrosion-resistant coil options
High-static indoor fan motor and drive Energy$Recycler heat recovery
Time Guard® II anti-short-cycling device CO2 sensor

CATALOG NO. 525-00028

66
REFERENCE GUIDE

50TFQ, SINGLE-PACKAGE, ROOFTOP HEAT PUMP UNITS, 3 TO 10 TONS


Cooling Heating (High-Temp.) Sound Rating
Nominal (decibels)
Unit 50TFQ Capacity Standard CFM Capacity SEER Capacity
(Tons) HSPF
(Btu/h) (Btu/h)
Belt Drive Direct-drive

004 3 1,200 35,600 10.2 10.0 34,400 6.7 84


005 4 1,600 46,500 10.0 9.7 46,500 7.0 80
006 5 2,000 57,000 10.0 9.9 57,000 7.5 82
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
3. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Acutrol refrigerant metering system
Fully hermetic compressors Corrosion-resistant sloped condensate pan

OPTIONS: Electric resistance heater coil Direct digital controls


EconoMi$er microprocessor-controlled economizer PremierLink controls
Power exhaust options Enthalpy controls
High-static indoor fan motor and drive Head pressure control package
Corrosion-resistant coil options CO2 sensor
Energy$Recycler heat recovery Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00022

50TM, SINGLE-PACKAGE, ROOFTOP UNITS, 3 TO 12.5 TONS


Nominal Capacity Sound Rating
Unit 50TM Net Cooling (Btu/h) SEER (Note 2) EER Total kW
(Tons) (decibels)

004 3 35,000 10.00 8.7 4.0 81


005 4 47,000 10.00 8.8 5.3 81
006 5 57,000 10.00 8.5 6.7 81

Nominal Capacity Sound Rating


Unit 50TM Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

007 6 71,000 10.3 (Note 3) 6.9 80


008 7.5 89,000 10.3 10.6 8.6 82
009 8.5 100,000 10.2 10.6 9.7 82
012 10 115,000 10.3 11.1 11.2 84
014 12.5 136,000 9.7 10.1 14.0 86
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. SEER values are for units with optional belt-drive motors; units with standard direct-drive motors have an SEER of 9.7.
3. IPLV is not applicable to single-compressor units.

FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Vertical or horizontal duct configurations
Fully hermetic reciprocating or scroll compressors Direct- or belt-driven evaporator fan
2-inch filter rack

OPTIONS: EconoMi$er2 microprocessor-controlled economizer Direct digital controls


Energy$Recycler heat recovery PremierLink controls
Power exhaust options Enthalpy control
High-static indoor fan motor and drive Electric resistance heater coil
Corrosion-resistant coil options Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00031

67
REFERENCE GUIDE

50TM, SINGLE-PACKAGE ROOFTOP UNITS, 15 TO 25 TONS


Nominal Capacity Sound Rating
Unit 50TM Net Cooling (Btu/h) EER IPLV Total kW
(Tons) (decibels)

016 15 178,000 9.7 9.9 16.8 88


020 18 204,000 10.0 10.5 20.6 88
025 20 236,000 9.7 10.4 24.6 94
028 25 278,000 9.8 10.5 28.3 94
Notes:
1. Rated in accordance with ARI Standard 340/360.

FEATURES: Electric cooling, R-22 Independent refrigerant circuits


Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Belt-driven evaporator fan
Thermostatic expansion valves 2-inch filter rack

OPTIONS: EconoMi$er microprocessor-controlled economizer Direct digital controls


Power exhaust PremierLink controls
High-static indoor fan motor and drive Enthalpy control
Electric resistance heater coil or hydronic (glycol) coil Stainless steel drain pan
Corrosion-resistant coil options Ultraviolet (UV-C) germicidal lamps

CATALOG NO. 525-00031

50VQA, VQD, VERTICAL, WATER-SOURCE HEAT PUMP UNITS, 6.5 TO 25 TONS


Cooling (Note 2) Heating (Note 3) Water
Unit Nominal
Nominal Water Flow Pressure
50VQA, Capacity
CFM Capacity Capacity GPM Drop
VQD (Tons) EER Total kW COP Total kW
(Btu/h) (Btu/h) (Ft wg)

080 6.5 2,600 74,000 14.0 5.29 83,000 4.2 5.79 18.0 8.2
160 13 5,200 148,000 14.0 10.57 166,000 4.2 11.58 36.0 8.2
Notes:
1. Rated in accordance with ARI Standard 320.
2. Cooling standard: 85°F entering water temperature.
3. Heating standard: 70°F entering water temperature.
4. 50VQA standard temperature range unit; 50VQD low temperature range unit.
5. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling and heating, R-22 Designed for vertical installation
Standard and low temperature models Condensate overflow switch
Fully hermetic or scroll compressors Anti-short cycle timer
Steel/copper tube-in-tube heat exchanger Thermostatic expansion valves

OPTIONS: Steel/cupronickel tube-in-tube heat exchanger Deluxe control system


Sound attenuation package PowerLink controls
Supply and return air configuration options Thermostat options
High-static blower and drive CO2 sensor

CATALOG NO. 525-00023

68
REFERENCE GUIDE

50XJ, SINGLE-PACKAGE, INDOOR, WATER-COOLED VAV UNITS, 55 TO 100 TONS


Unit 50XJ Nominal Capacity (Tons) Standard CFM Net Cooling (Btu/h) EER

50XJA074 55 15,240 534,000 13.5


50XJB074 60 15,240 582,000 13.2
50XJC074 65 15,240 635,000 13.3
50XJD074 70 15,240 680,000 12.9
50XJC084 75 19,320 720,000 12.6
50XJD084 80 19,320 775,000 12.4
50XJA094 85 20,400 795,000 13.0
50XJD094 90 20,400 895,000 12.8
50XJD104 95 22,280 920,000 12.8
50XJE104 100 22,280 965,000 12.5
Notes:
1. Rated in accordance with ARI Standard 340/360.

FEATURES: Electric cooling, R-22 Microprocessor controls


Variable air volume Factory-mounted VFD
Multiple scroll compressors Double-wall panels in evaporator section
Independent refrigeration circuits Double-slope stainless steel drain pan

OPTIONS: Waterside economizer with control valves Control options for system integration
Acoustical discharge plenum Factory-mounted disconnect
Water regulating valve package VFD bypass
Hot water heating Water flow switch

CATALOG NO. (Available in 2002)

50Z, SINGLE-PACKAGE, CONSTANT OR VARIABLE VOLUME ROOFTOP UNITS, 30 TO 90 TONS


Cooling CFM
Unit 48AK, AY Nominal Capacity (Tons) EER IPLV
Operating range

030 30 6,000-15,000
040 40 8,000-20,000
050 50 9,000-20,000 All 50Z models are All 50Z models are
ASHRAE Std. 90.1 ASHRAE Std. 90.1
055 55 10,000-25,000 compliant. See local Carrier compliant. See local Carrier
060 60 12,000-30,000 sales representative for sales representative for
070 70 14,000-30,000 ratings. ratings.
075 75 15,000-30,000
090 90 17,000-34,000
Notes:
1. Units are rated in accordance with ARI Standard 340/360..

FEATURES: Electric cooling, R-22 Product integrated controls


Variable volume, variable frequency drive Integrated economizer
Reciprocating, semi-hermetic compressors Vertical discharge configuration
Electrically controlled compressor unloaders Horizontal discharge configuration (cooling only units)

OPTIONS: Corrosion-resistant coil options Enthalpy control


Optional electric heating section CO2 sensor
Optional hydronic heating section Inlet guide vanes or VFD volume control
Modulating power exhaust Extended chassis
Return fan and building pressure control system (sizes 075 to 105) Outdoor airflow sensor

CATALOG NO. 524-80024

69
REFERENCE GUIDE

50ZH, SINGLE-PACKAGE HEAT PUMP UNITS, 2 TO 5 TONS


Net Cooling Net Heating
Nominal Sound Rating
Unit 50ZH Standard CFM Capacity at 95°F SEER Capacity at 47°F HSPF
Capacity (Tons) (decibels)
(Btu/h) (Btu/h)

024 2 800 22,800 10.0 21,800 6.8 76


030 2.5 1,000 28,200 10.0 27,200 6.8 81
036 3 1,200 34,200 10.0 33,800 6.8 78
042 3.5 1,400 40,000 10.0 40,000 6.8 78
048 4 1,600 46,000 10.0 45,000 6.8 80
060 5 2,000 55,000 10.5 52,500 6.8 84
Notes:
1. Rated in accordance with the latest edition of ARI Standard 210/240 and/or U.S. Government DOE test procedures.

FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Horizontal duct configuration
Chronotemp defrost system Composite material base

OPTIONS: Electric resistance heater coil (5 to 20 kW) Outdoor thermostat


Thermostat options

CATALOG NO. 525-00015

50ZP, SINGLE-PACKAGE, ELECTRIC COOLING UNITS, 2 TO 5 TONS


Unit 50ZP Nominal Capacity (Tons) Standard CFM Net Cooling (Btu/h) SEER (Note 3) Sound Rating (decibels)

024 2 800 22,800 10.0 77


030 2.5 1,000 30,000 10.0 81
036 3 1,200 34,200 10.0 81
042 3.5 1,400 40,000 10.0 81
048 4 1,600 46,000 10.0 81
060 5 2,000 57,000 10.0 83
Notes:
1. ARI capacities shown.
2. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
3. All units have factory-installed time-delay relay.

FEATURES: Electric cooling, R-22 Small, compact, easy to handle


Constant volume Direct-drive, multi-speed blower motor
Fully hermetic reciprocating compressors Composite material base

OPTIONS: Time Guard® II anti-short-cycling device Thermostat options


Electric resistance heater coil (5 to 20 kW) Controls upgrade kit
Low-ambient kit Crankcase heater

CATALOG NO. 525-00016

70
REFERENCE GUIDE

52CE, PACKAGED TERMINAL AIR CONDITIONERS, COMFORT MODEL


Operating Voltage
Unit 52CE Evaporator Fan (Cfm) Cooling (Btu/h) Electric Heat (Btu/h) EER
(1-phase, 60 Hz.)
52CE-207---3 230/208 260/250 7,000/6,900 7,800/6,400 11.1/11.1
52CE-307---3 230/208 260/250 7,000/6,900 11,600/9,700 11.1/11.1
52CE-209---3 230/208 260/250 9,000/8,900 7,800/6,400 10.7/10.7
52CE-309---3 230/208 260/250 9,000/8,900 11,600/9,700 10.7/10.7
52CE-212---3 230/208 350/320 12,000/11,900 7,800/6,400 10.1/10.1
52CE-312---3 230/208 350/320 12,000/11,900 11,600/9,700 10.1/10.1
52CE-512---3 230/208 350/320 12,000/11,900 17,000/13,600 10.1/10.1
52CE-215---3 230/208 350/320 14,500/14,000 7,800/6,400 9.4/9.5
52CE-315---3 230/208 350/320 14,500/14,000 11,600/9,700 9.4/9.5
52CE-515---3 230/208 350/320 14,500/14,000 17,000/13,600 9.4/9.5
52CE-207---4 265 260 7,000 7,800 11.1
52CE-307---4 265 260 7,000 11,600 11.1
52CE-209---4 265 260 8,900 7,800 10.7
52CE-309---4 265 260 8,900 11,600 10.7
52CE-212---4 265 340 12,000 7,800 10.1
52CE-312---4 265 340 12,000 11,600 10.1
52CE-512---4 265 340 12,000 17,000 10.1
52CE-215---4 265 340 14,500 7,800 9.4
52CE-315---4 265 340 14,500 11,600 9.4
52CE-515---4 265 340 14,500 17,000 9.4

FEATURES: Electric resistance heater coil (2.3, 3.4, or 5.0 kW) Low sound levels
Slide-out chassis Fits in standard 42” x 16” wall sleeve

OPTIONS: Corrosion protection chassis option Wall thermostat options


Lateral air deflector Lateral duct kit
Wall sleeve (polymer and metal) Architectural outdoor air grille (polymer and metal)
Drain kit (internal and external mount) Subbase (non-electrical and electrical)
Security door kit Energy management interface

CATALOG NO. See Carrier’s web site at http://www.commercial.carrier.com

52CQ, PACKAGED TERMINAL HEAT PUMPS, COMFORT MODEL


Operating Voltage Evaporator Fan Reverse Cycle
Unit 52CQ Cooling (Btu/h) EER COP
(1-phase, 60 Hz.) (Cfm) Heating (Btu/h)
52CQ-207---3 230/208 260/250 7,000/6,900 11.1/11.1 6,100/6,000 3.1/3.1
52CQ-307---3 230/208 260/250 7,000/6,900 11.1/11.1 6,100/6,000 3.1/3.1
52CQ-209---3 230/208 260/250 9,000/8,900 10.7/10.7 7,900/7,800 3.1/3.1
52CQ-309---3 230/208 260/250 9,000/8,900 10.7/10.7 7,900/7,800 3.1/3.1
52CQ-212---3 230/208 350/320 12,000/11,900 10.1/10.1 10,800/10,700 3.0/3.0
52CQ-312---3 230/208 350/320 12,000/11,900 10.1/10.1 10,800/10,700 3.0/3.0
52CQ-512---3 230/208 350/320 12,000/11,900 10.1/10.1 10,800/10,700 3.0/3.0
52CQ-215---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52CQ-315---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52CQ-515---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52CQ-207---4 265 260 7,000 11.1 6,100 3.1
52CQ-307---4 265 260 7,000 11.1 6,100 3.1
52CQ-209---4 265 260 8,900 10.7 7,700 3.1
52CQ-309---4 265 260 8,900 10.7 7,700 3.1
52CQ-212---4 265 340 12,000 10.1 10,800 3.0
52CQ-312---4 265 340 12,000 10.1 10,800 3.0
52CQ-512---4 265 340 12,000 10.1 10,800 3.0
52CQ-215---4 265 340 14,500 9.4 13,400 2.9
52CQ-315---4 265 340 14,500 9.4 13,400 2.9
52CQ-515---4 265 340 14,500 9.4 13,400 2.9

FEATURES: Slide-out chassis Low sound levels


Electric resistance heater coil Fits in standard 42” x 16” wall sleeve

OPTIONS: Corrosion protection chassis option Wall thermostat options


Lateral air deflector Lateral duct kit
Wall sleeve (polymer and metal) Architectural outdoor air grille (polymer and metal)
Drain kit (internal and external mount) Subbase (non-electrical and electrical)
Security door kit Energy management interface

CATALOG NO. See Carrier’s web site at http://www.commercial.carrier.com

71
REFERENCE GUIDE

52FC, FE, ROOM AIR CONDITIONERS, SOLID SIDE


Operating Voltage
Unit 52FC, FE Cooling (Btu/h) Electric Heat (Btu/h) EER
(1-phase, 60 Hz.)

52FC009-3 230/208 8,500/8,300 — 9.0


52FC010-1 115 10,000 — 8.7
52FC012-3 230/208 12,000/11,700 — 8.5
52FE108-1 115 8,000 4,200 9.0
52FE310-3 230/208 10,000/9,800 10,600/8,600 9.0
52FE312-3 230/208 12,000/11,700 10,600/8,600 8.5

FEATURES: Electric resistance heater coil (52FE) Adjustable fan speed


Four-way airflow Easy-out filter

OPTIONS: Aluminum architectural air grille Metal wall sleeve


Window mounting kit

CATALOG NO. See Carrier’s web site at http://www.commercial.carrier.com

52PC, PE, PACKAGED TERMINAL AIR CONDITIONERS, PREMIER MODEL


Operating Voltage
Unit 52PC, PE Evaporator Fan (Cfm) Cooling (Btu/h) Electric Heat (Btu/h) EER
(1-phase, 60 Hz.)

52PE-207---3 230/208 260/250 7,200/7,100 7,800/6,400 12.7/12.7


52PE-307---3 230/208 260/250 7,200/7,100 11,600/9,700 12.7/12.7
52PE-209---3 230/208 260/250 9,100/9,000 7,800/6,400 11.5/11.5
52PE-309---3 230/208 260/250 9,100/9,000 11,600/9,700 11.5/11.5
52PE-212---3 230/208 350/320 12,100/12,000 7,800/6,400 11.1/10.7
52PE-312---3 230/208 350/320 12,100/12,000 11,600/9,700 11.1/10.7
52PE-512---3 230/208 350/320 12,100/12,000 17,000/13,600 11.1/10.7
52PE-215---3 230/208 350/320 14,500/14,000 7,800/6,400 9.4/9.5
52PE-315---3 230/208 350/320 14,500/14,000 11,600/9,700 9.4/9.5
52PE-515---3 230/208 350/320 14,500/14,000 17,000/13,600 9.4/9.5
52PE-207---4 265 260 7,200 7,800 12.7
52PE-307---4 265 260 7,200 11,600 12.7
52PE-209---4 265 260 9,100 7,800 11.5
52PE-309---4 265 260 9,100 11,600 11.5
52PE-212---4 265 340 12,100 7,800 11.1
52PE-312---4 265 340 12,100 11,600 11.1
52PE-512---4 265 340 12,100 17,000 11.1
52PE-215---4 265 340 14,500 7,800 9.4
52PE-315---4 265 340 14,500 11,600 9.4
52PE-515---4 265 340 14,500 17,000 9.4
Notes:
1. 52PC cooling only model; 52PE cooling with electric heat.
2. 52PC models have the same cooling ratings and do not have electric heat.

FEATURES: Electric resistance heater coil (2.3, 3.4, or 5.0 kW) Low sound levels
Slide-out chassis Fits in standard 42” x 16” wall sleeve

OPTIONS: Corrosion protection chassis option Wall thermostat options


Lateral air deflector Lateral duct kit
Wall sleeve (polymer and metal) Architectural outdoor air grille (polymer and metal)
Drain kit (internal and external mount) Subbase (non-electrical and electrical)
Security door kit Energy management interface

CATALOG NO. See Carrier’s web site at http://www.commercial.carrier.com

72
REFERENCE GUIDE

52PQ, PACKAGED TERMINAL HEAT PUMPS, PREMIER MODEL


Operating Voltage Evaporator Fan Reverse Cycle
Unit 52PQ Cooling (Btu/h) EER COP
(1-phase, 60 Hz.) (Cfm) Heating (Btu/h)

52PQ-207---3 230/208 260/250 7,200/7,100 12.7/12.7 6,300/6,300 3.4/3.4


52PQ-307---3 230/208 260/250 7,200/7,100 12.7/12.7 6,300/6,300 3.4/3.4
52PQ-209---3 230/208 260/250 9,100/9,000 11.5/11.5 7,900/7,900 3.2/3.2
52PQ-309---3 230/208 260/250 9,100/9,000 11.5/11.5 7,900/7,900 3.2/3.2
52PQ-212---3 230/208 350/320 12,100/12,000 11.1/10.7 11,000/11,000 3.2/3.2
52PQ-312---3 230/208 350/320 12,100/12,000 11.1/10.7 11,000/11,000 3.2/3.2
52PQ-512---3 230/208 350/320 12,100/12,000 11.1/10.7 11,000/11,000 3.2/3.2
52PQ-215---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52PQ-315---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52PQ-515---3 230/208 350/320 14,500/14,000 9.4/9.5 13,400/13,200 2.9/2.9
52PQ-207---4 265 260 7,200 12.7 6,300 3.4
52PQ-307---4 265 260 7,200 12.7 6,300 3.4
52PQ-209---4 265 260 9,100 11.5 7,700 3.2
52PQ-309---4 265 260 9,100 11.5 7,700 3.2
52PQ-212---4 265 340 12,100 11.1 10,800 3.2
52PQ-312---4 265 340 12,100 11.1 10,800 3.2
52PQ-512---4 265 340 12,100 11.1 10,800 3.2
52PQ-215---4 265 340 14,500 9.4 13,400 2.9
52PQ-315---4 265 340 14,500 9.4 13,400 2.9
52PQ-515---4 265 340 14,500 9.4 13,400 2.9

FEATURES: Slide-out chassis Low sound levels


Electric resistance heater coil Fits in standard 42” x 16” wall sleeve

OPTIONS: Corrosion protection chassis option Wall thermostat options


Lateral air deflector Lateral duct kit
Wall sleeve (polymer and metal) Architectural outdoor air grille (polymer and metal)
Drain kit (internal and external mount) Subbase (non-electrical and electrical)
Security door kit Energy management interface

CATALOG NO. See Carrier’s web site at http://www.commercial.carrier.com

90MA, MF, SINGLE-PACKAGE, WATER-COOLED, ELECTRIC COOLING UNITS, 3 TO 10 TONS


Unit 90MA, MF Nominal Capacity (Tons) Nominal CFM Net Cooling (Btu/h) EER Refrigerant

208 7.5 3,000 89,675 12.1 R-22


308 5.5 2,200 62,733 12.4 R-134a
312 8 3,200 83,648 11.9 R-134a
Notes:
1. 90MA uses 90-10 Cu-Ni condenser for sea water service; 90MF uses copper condenser.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.

FEATURES: Electric cooling, R-22 or R-134a Ducted or free-blow applications


Constant volume Water regulating valve (field installed)
Hermetic or semi-hermetic compressors Crankcase heaters
Coaxial (tube-in-tube) heat exchanger Thermostatic expansion valves and filter drier

OPTIONS: Alternate HP motors Copper or cupronickel heat exchanger tubes


Electric heaters Remote monitor relays
Steam or hot water heating coils Non-standard drive package

CATALOG NO. See Carrier’s web site at: www.commercial.carrier.com

73
REFERENCE GUIDE

90MU, SINGLE-PACKAGE, CONDENSERLESS, ELECTRIC COOLING UNITS, 3 TO 10 TONS


Unit 90MU Nominal Capacity (Tons) Nominal CFM Net Cooling (Btu/h) EER Refrigerant

204 3 1,200 36,300 R-22


206 5 2,000 59,000 R-22
208 7.5 3,000 89,700 R-22
(Note 2)
212 10 4,000 116,700 R-22
308 5.5 2,200 62,700 R-134a
312 8 3,200 83,600 R-134a
Notes:
1. For the latest information go to Carrier’s web site at http://www.commercial.carrier.com.
2. Updated ratings available in 2002.

FEATURES: Electric cooling, R-22 or R-134a Ducted or free-blow applications


Constant volume Crankcase heaters
Semi-hermetic compressors Thermostatic expansion valves and filter drier

OPTIONS: Alternate HP motors Remote monitor relays


Electric heaters Non-standard drive package
Steam or hot water heating coils

CATALOG NO. Available in 2002

74

CARRIER CORPORATION

SYRACUSE, NEW YORK