1-1999 (2001)
ENERGY STANDARD
FOR BUILDINGS
A REFERENCE GUIDE TO
MEETING THE NEW MINIMUM EFFICIENCY
REQUIREMENTS FOR HVAC EQUIPMENT
WITH CARRIER PRODUCTS
Carrier Corporation
Syracuse, New York
December 2002
TABLE OF CONTENTS
INTRODUCTION ............................................................................................................................................ 3
PART 1 – CROSS-REFERENCE
UNITARY AIR CONDITIONERS AND CONDENSING UNITS (Table 6.2.1A)......................................... 7
Air Conditioners, Air-Cooled ............................................................................................................ 7
Air Conditioners, Water-Cooled......................................................................................................... 9
Condensing Units, Air-Cooled............................................................................................................ 11
Condensing Units, Water-Cooled ....................................................................................................... 11
HEAT PUMPS (Table 6.2.1B) ......................................................................................................................... 12
Air-Cooled .......................................................................................................................................... 12
Water-Source ...................................................................................................................................... 14
Groundwater-Source........................................................................................................................... 15
Ground-Source.................................................................................................................................... 16
WATER CHILLING PACKAGES (Table 6.2.1C) .......................................................................................... 17
Air-Cooled, with Condenser, Electric................................................................................................. 17
Air-Cooled, without Condenser, Electric............................................................................................ 17
Water-Cooled, Electric, Positive Displacement (Reciprocating)........................................................ 17
Water-Cooled, Electric, Positive Displacement (Rotary Screw and Scroll) ....................................... 18
Water-Cooled, Electric, Centrifugal ................................................................................................... 19
Water-Cooled, Absorption, Single Effect ........................................................................................... 19
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS (Table 6.2.1D).............................. 20
Packaged Terminal Air Conditioners.................................................................................................. 20
Packaged Terminal Heat Pumps ......................................................................................................... 21
Room Air Conditioners Without Louvered Sides ............................................................................... 22
HEAT REJECTION EQUIPMENT (Table 6.2.1G)......................................................................................... 23
Air-Cooled Condensers....................................................................................................................... 23
2
INTRODUCTION
ASHRAE Standard 90.1-1999 (2001) defines for equipment that are rated in accordance with an
minimum efficiency requirements for HVAC established test procedure. Equipment not listed in
equipment. This paper is designed to assist to help the ASHRAE Standard 90.1 tables have no minimum
you find the right Carrier product necessary to meet performance requirements.
those requirements.
ASHRAE Standard 90.1 defines minimum efficiency HOW TO USE THIS REFERENCE
requirements in a series of tables in Section 6.2, This paper is divided into two parts. Part 1 is a cross-
Mandatory Provisions. reference between the ASHRAE Standard 90.1
requirements (including current addenda) and Carrier
Table 6.2.1A Air Conditioners and products. Efficiency requirements are grouped and
Condensing Units referenced as they are in Tables 6.2.1A through
Table 6.2.1B Heat Pumps 6.2.1G of the standard. The specific efficiency
Table 6.2.1C Water Chilling Packages requirement for each equipment type, size category,
Table 6.2.1D Packaged Terminal and Room and subcategory is presented as a heading to a table
Air Conditioners and Heat that lists the Carrier products meeting that
Pumps requirement. An example is shown in Figure 1
Table 6.2.1E Furnaces, Duct Furnaces, and below. Part 2 of this paper is a reference guide to
Unit Heaters Carrier commercial products that meet ASHRAE
Table 6.2.1F Boilers Standard 90.1.
Table 6.2.1G Heat Rejection Equipment
Table 6.2.1H The 1999 publication of ASHRAE Standard 90.1
Table 6.2.1I Non-Standard Centrifugal indicated two efficiency requirements: the first
Table 6.2.1J Chillers labeled “Minimum Efficiency,” and the second
labeled, “Efficiency as of 10/29/01.” All equipment
Tables 6.2.1A through 6.2.1G define requirements manufactured after October 29, 2001, must meet the
<65,000 Btu/h
All Split System 10.0 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Console, duct-free split system (with 38CG condensing unit), 1.5 to 2.5
40CG 10.0 39
tons
Satellite, duct-free split system (with 38HDC/HDL condensing unit),
40HD 10.0 – 11.0 40
2 to 4 tons
Under ceiling, duct-free split system (with 38HDC/HDL condensing
40QAB 10.1 – 12.0 40
unit), 1.5 to 5 tons
Cassette, duct-free split system (with 38HDC/HDL condensing unit),
40QKB 10.5 – 11.8 41
1.5 to 3 tons
Fig. 1. Example of the cross-reference between one ASHRAE Standard 90.1 Table 6.2.1A
requirement and appropriate Carrier product model numbers
3
second requirement. Equipment manufactured before factory-installed options and field-installed
October 29, 2001 must meet the first requirement, accessories available. To obtain a complete
even if it is installed after the indicated date. In most description of all features and options for a specific
tables, addenda to the standard have deleted the time model, please review the listed catalog, or consult
distinction, and now show only the requirement for your local Carrier sales representative.
equipment after October 29, 2001, labeled
“Minimum Efficiency”. This document follows the In all cases, performance data listed are for 60 Hz
pattern of the amended ASHRAE tables, showing products at ARI standard conditions.
only one column labeled “Minimum Efficiency.” In
all cases, the minimum efficiency indicated is for
equipment manufactured after October 29, 2001. DEFINITIONS
The following definitions are taken from ASHRAE
If multiple performance requirements are listed, the Standard 90.1-1999 (2001).
equipment must meet all requirements unless
otherwise exempted by footnotes in the table. Coefficient of performance (COP) – cooling: the
ratio of the rate of heat removal to the rate of energy
To find the available equipment options, begin by input, in consistent units, for a complete refrigerating
determining the requirement from the appropriate system or some specific portion of that system under
table (or amended table) in ASHRAE Standard 90.1. designated operating conditions.
Next, enter the Part 1 Cross-Reference of this paper Coefficient of performance (COP), heat pump –
by finding the same ASHRAE Standard 90.1 table heating: the ratio of the rate of heat delivered to the
number, equipment type, size category, and rate of energy input, in consistent units, for a
subcategory. The Carrier equipment options are complete heat pump system, including the
listed in order of model number with a short compressor and, if applicable, auxiliary heat, under
description of the product. After each listed Carrier designated operating conditions.
product there is a page number that indicates where
to find more information in the Part 2 Reference Energy efficiency ratio (EER): the ratio of net
Guide. cooling capacity in Btu/h to the total rate of electric
input in watts under designated operating conditions.
In Part 2, the Reference Guide is arranged by model
number and presents a brief snapshot of the product Heating seasonal performance factor (HSPF): the
including expanded efficiency information, major total heating output of a heat pump during its normal
features, and options. In each case, the current annual usage period for heating (in Btu) divided by
applicable Carrier catalog is listed. Please refer to the total electric energy input during the same period.
the catalog for a more complete description of the
features, benefits, and options of each product. Integrated part-load value (IPLV): a single-
number figure of merit based on part-load EER,
COP, or kW/ton, expressing part-load efficiency for
REFERENCE GUIDE air-conditioning and heat pump equipment on the
Every effort has been made to present the most up to basis of weighted operation at various load capacities
date information in the Reference Guide to Carrier for the equipment.
Commercial Products. But, because Carrier
continually improves its products, model NAECA: National Appliance Energy Conservation
specifications and designs may be changed or Act of 1987.
discontinued at any time without notice or obligation.
The most up to date product catalogs and literature Seasonal energy efficiency ratio (SEER): the total
are always available from your local Carrier sales cooling output of an air conditioner during its normal
representative, or at Carrier’s web site, annual usage period for cooling (in Btu) divided by
http://www.commercial.carrier.com. This document the total electric energy input during the same period
is updated regularly. (in watt-hours).
4
PART 1
CROSS-REFERENCE
BETWEEN ASHRAE STANDARD 90.1
MINIMUM EFFICIENCY REQUIREMENTS AND
CARRIER COMMERCIAL PRODUCTS
5
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
<65,000 Btu/h
All Split System 10.0 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
40CG Console, duct-free split system (with 38CG condensing unit), 1.5 to 2.5 tons 10.0 39
Satellite, duct-free split system (with 38HDC/HDL condensing unit), 2 to 4
40HD 10.0 – 11.0 40
tons
Under ceiling, duct-free split system (with 38HDC/HDL condensing unit), 1.5
40QAB 10.1 – 12.0 40
to 5 tons
Cassette, duct-free split system (with 38HDC/HDL condensing unit), 1.5 to 3
40QKB 10.5 – 11.8 41
tons
High wall, duct-free split system (with 38AN & 38HDC/HDL condensing
40QNB 10.5 – 12.0 42
unit), 0.75 to 2 tons
40-Series Multi-zone, duct-free split system, 2 to 5 tons 10.0 – 12.0 43
Indoor, single-package cooling units with remote air-cooled condenser, 5 to 15
50BZN 10.0 53
tons
90MU Single-package, condenserless electric cooling unit, 3 to 10 tons (Available in 2002) 74
<65,000 Btu/h
All Single Package 9.7 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Single-package unit, gas heating or low NOx gas heating, electric cooling,
48GP, GPN 12.0 – 13.0 45
optional variable-speed blower, Puron refrigerant, 2 to 5 tons
Single-package unit, gas heating or low NOx gas heating, electric cooling, 1.5
48GS, GSN 10.0 45
to 5 tons
Single-package unit, gas heating or low NOx gas heating, electric cooling, 2 to
48GX, GXN 12.0 46
5 tons
48HJ Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 13.0 47
48TF Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 10.0 49
48TM Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 10.0 49
Indoor unit, horizontal, single-package, electric cooling, optional electric
50AH 9.75 – 10.8 51
heating, 2 to 5 tons
Indoor unit, air-cooled, single-package, vertical, electric cooling, optional hot
50BYN 10.0 53
water or steam heating, 5 to 20 tons
Single-package unit, electric cooling, optional electric heating, optional
50GL 12.0 – 13.0 54
variable-speed blower, Puron refrigerant, 2 to 5 tons
50GS Single-package unit, electric cooling, optional electric heating, 1.5 to 5 tons 10.0 55
50GX Single-package unit, electric cooling, optional electric heating, 2 to 5 tons 12.0 55
Rooftop unit, single-package, high-efficiency, electric cooling, optional electric
50HJ 13.0 56
heating, 3 to 12.5 tons
Single-package unit, high-efficiency, electric cooling, optional electric heating,
50SX 11.0 – 12.0 66
2 to 5 tons
6
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
<65,000 Btu/h
All Single Package 9.7 SEER ARI 210/240
(Note 1)
Notes:
1. Single-phase air-cooled air conditioners <65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TFF 9.7 – 10.0 66
12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TM 10.0 67
12.5 tons
50ZP Single-package unit, electric cooling, optional electric heating, 2 to 5 tons 10.0 70
CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
7
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
48HG Rooftop unit, single-package, electric cooling, gas heating, 12.5 to 25 tons 11.2 – 11.6 46
48HJ Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 9.6 47
48HJ Rooftop unit, single-package, electric cooling, gas heating, 12 to 15 tons 10.5 47
48TM Rooftop unit, single-package, electric cooling, gas heating, 3 to 12.5 tons 9.5 49
48TM Rooftop unit, single-package, electric cooling, gas heating, 15 to 25 tons 9.5 – 9.7 50
Rooftop unit, single-package, electric cooling, optional electric heating, 20 to Consult Carrier
50AJ, AW 51
60 tons sales representative
Rooftop unit, single-package, variable volume, electric cooling, electric Consult Carrier
50AK, AY 52
heating, 20 to 60 tons sales representative
Rooftop unit, single-package, electric cooling, optional electric heating, 12.5 to
50HG 11.2 – 11.6 56
25 tons
Rooftop unit, single-package, high efficiency, electric cooling, optional electric
50HJ 9.8 56
heating, 3 to 12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 12 to
50HJ 10.8 57
15 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 3 to
50TM 9.7 67
12.5 tons
Rooftop unit, single-package, electric cooling, optional electric heating, 15 to
50TM 9.7 – 10.0 68
25 tons
CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.
8
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.
Rooftop unit, single-package, variable volume, electric
48AK, AY Consult Carrier sales representative 44
cooling, gas heating, 20 to 60 tons
Rooftop unit, single-package, electric cooling, gas heating,
48HG 10.4 11.0 46
12.5 to 25 tons
Rooftop unit, single-package, electric cooling, gas heating, 15
48TM 9.5 – 9.7 10.0 – 10.4 50
to 25 tons
Rooftop unit, single-package, constant or variable volume,
48Z Consult Carrier sales representative 50
electric cooling, gas heating, 30 to 90 tons
Rooftop unit, single-package, electric cooling, electric
50AJ, AW Consult Carrier sales representative 51
heating, 20 to 60 tons
Rooftop unit, single-package, variable volume, electric
50AK, AY Consult Carrier sales representative 52
cooling, electric heating, 20 to 60 tons
50HG Rooftop unit, single-package, electric cooling, 12.5 to 25 tons 10.4 11.0 56
Rooftop unit, single-package, electric cooling, optional
50TM 9.8 10.5 68
electric heating, 15 to 25 tons
Rooftop unit, single-package, constant or variable volume,
50Z Consult Carrier sales representative 69
electric cooling, electric heating, 30 to 90 tons
CARRIER PRODUCTS
Reference Guide
Model No. Description SEER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 13.1 52
heating, 5 to 20 tons
Single-package unit, water-cooled, electric cooling, optional hot water or steam
90MA, MF 12.4 73
heating, 3 to 10 tons
9
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 11.5 52
heating, 5 to 20 tons
Single-package unit, water-cooled, electric cooling, optional hot water or steam
90MA, MF 11.9 – 12.1 7473
heating, 3 to 10 tons
CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
Indoor unit, single-package, electric cooling, optional hot water or steam
50BRN 11.5 – 12.0 52
heating, 5 to 20 tons
CARRIER PRODUCTS
Reference Guide
Model No. Description EER IPLV
Page No.
Indoor unit, single-package, water-cooled, variable volume,
50XJ 12.4 – 13.5 (Available in 2002) 69
electric cooling, 55 to 100 tons
10
Table 6.2.1A
Electrically Operated Unitary Air Conditioners and Condensing Units
10.1 EER
≥135,000 Btu/h — — ARI 365
11.2 IPLV (Note 1)
Notes:
1. IPLVs are only applicable to equipment with capacity modulation.
CARRIER PRODUCTS
Reference Guide Page
Model No. Description EER IPLV
No.
13.1 EER
≥135,000 Btu/h — — ARI 365
13.1 IPLV (Note 1)
Notes:
1. IPLVs are only applicable to equipment with capacity modulation.
CARRIER PRODUCTS
Reference Guide Page
Model No. Description EER IPLV
No.
Consult Carrier
07D, E Water-cooled condensing unit, 5 to 40 tons 13.2 – 14.4 sales representative 25
11
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
SEER HSPF Page No.
Console, duct-free split system heat pump (with 38CS
40CS 10.0 6.8 – 6.9 39
condensing unit), 1.5 to 2.5 tons
Under ceiling, duct-free split system heat pump (with 38QR
40QAE 10.2 – 11.5 7.2 – 7.4 41
condensing unit), 2 to 5 tons
Cassette, duct-free split system heat pump (with 38QR
40QKE 10.0 – 11.5 6.8 – 7.6 42
condensing unit), 1.5 to 3 tons
High wall, duct-free split system heat pump (with 38BK
40QNE, QNH 10.0 – 11.0 6.8 43
condensing unit), 0.75 to 2 tons
40-Series Multi-zone, duct-free split system heat pump, 2 to 2.5 tons 10.0 6.8 43
Cooling Mode
<65,000 Btu/h All Single Package 9.7 SEER
(Cooling Capacity) ARI 210/240
(Note 1) Heating Mode
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
SEER HSPF Page No.
Rooftop heat pump unit, single-package, gas heating,
48JZ, JZN 12.0 – 12.7 7.0 – 7.2 48
2 to 5 tons
Rooftop heat pump unit, single-package, high-efficiency,
50HJQ 11.9 – 12.0 7.6 57
optional electric heating, 3 to 10 tons
Single-package heat pump, optional electric heating, 2 to 5
50HX 11.0 – 12.0 6.9 – 7.2 59
tons
Single-package heat pump, optional electric heating, 1.5 to 5
50JS 10.0 6.6 – 7.0 59
tons
Single-package heat pump, optional electric heating, 2 to 5
50JX 12.0 7.1 – 7.2 60
tons
Single-package heat pump, optional electric heating,
50JZ 12.0 – 12.7 7.0 – 7.2 60
optional variable-speed blower, Puron, 2 to 5 tons
Rooftop heat pump unit, single-package, optional electric
50TFQ 9.7 – 10.2 6.7 – 7.5 67
heating, 3 to 10 tons
Single-package heat pump unit, optional electric heating, 2
50ZH 10.0 – 10.5 6.8 70
to 5 tons
12
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps
Cooling Mode
17°Fdb/15°Fwb
2.2 COP
Outdoor Air
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
Cooling Mode
17°Fdb/15°Fwb
2.0 COP
Outdoor Air
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
13
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps
47°Fdb/43°Fwb
3.1 COP
Outdoor Air
—
17°Fdb/15°Fwb
2.0 COP
Outdoor Air
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
Rooftop heat pump unit, single-package, optional electric
50EJQ, EWQ 9.2 3.3 54
heating, 20 and 25 tons
Cooling Mode
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
50KQA, KQD Console heat pump unit, water-source, 0.5 to 1.5 tons 12.2 – 12.6 4.2 – 4.3 61
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 12.8 – 13.3 4.2 – 4.6 62-63
5 tons
50RHS, RVS, Horizontal and vertical heat pump unit, high-efficiency,
16.0 5.3 64
RDS water-source, 1.25 to 6 tons
14
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 12.7 – 12.8 4.2 – 4.4 58
Horizontal and vertical heat pump unit, water-source,
50RHC, RVC 12.0 – 13.0 4.2 – 4.6 61
1.5 to 5 tons
Horizontal and vertical, high-efficiency heat pump unit,
50RHR, RVR 12.3 – 13.2 4.2 – 4.4 62-63
water-source, 0.5 to 5 tons
50RHS, RVS, Horizontal and vertical, premium-efficiency heat pump unit,
12.4 – 15.1 4.4 – 5.0 64
RDS water-source, 1.25 to 6 tons
Rooftop heat pump unit, single-package, water-source,
50RTG 13.0 – 14.7 4.2 – 5.0 65
3 to 20 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 12.0 – 14.3 4.2 – 5.0 65
Single-package heat pump, vertical, water-source, 6.5 to 25
50VQA, VQD 14.0 4.2 68
tons
Cooling Mode
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 17.2 – 17.4 3.9 – 4.0 58
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 16.8 – 18.6 3.6 – 4.1 62-63
5 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 20.6 4.0 65
15
Table 6.2.1B
Electrically Operated Unitary and Applied Heat Pumps
Cooling Mode
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
50HQL Heat pump unit, horizontal, water-source, 6 to 10 tons 14.1 – 14.2 3.2 – 3.4 58
Horizontal and vertical heat pump unit, water-source, 0.5 to
50RHR, RVR 13.3 – 15.0 3.2 – 3.5 62-63
5 tons
50RHS, RVS, Horizontal and vertical heat pump unit, high-efficiency,
13.4 – 18.5 3.3 – 3.8 64
RDS water-source, 1.25 to 6 tons
50RWS Heat pump unit, water-source, 3 to 10 tons 16.2 3.3 65
16
Table 6.2.1C
Water Chilling Packages
2.80 COP
All capacities ARI 550/590
3.05 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference Guide
Model No. Description COP IPLV
Page No.
30GTN Packaged, air-cooled, reciprocating liquid chiller, 15 to 35 tons 2.83 – 2.90 3.34 – 3.78 28
30GTN, GTR Packaged, air-cooled, reciprocating liquid chiller, 36 to 410 tons 2.80 – 2.92 3.49 – 4.31 28
30GUN, GUR Packaged, air-cooled, reciprocating liquid chiller, 25 to 280 tons 2.82 – 3.06 3.16 – 4.07 29
Consult Carrier
30GXN, GXR Packaged, air-cooled, rotary screw liquid chiller, 80 to 450 tons 2.80 – 3.06 sales representative 29
Hermetic scroll liquid chiller, packaged, air-cooled, 9.6 to 54.3
30RA 2.81 – 2.96 3.73 – 4.44 32
tons
3.10 COP
All capacities ARI 550/590
3.45 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference Guide
Model No. Description COP IPLV
Page No.
4.20 COP
All capacities ARI 550/590
5.05 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
17
Table 6.2.1C
Water Chilling Packages
4.45 COP
<150 tons ARI 550/590
5.20 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
30HXC Rotary screw liquid chillers, fluid-cooled, 75 to 265 tons 4.84 – 5.00 6.60 – 6.91 31
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
23XL Rotary screw liquid chiller, hermetic, water-cooled, 150 to 360 tons 5.89 – 5.94 7.59 – 7.86 27
30HXC Rotary screw liquid chillers, fluid-cooled, 75 to 265 tons 4.92 – 5.08 6.26 – 6.89 31
5.50 COP
≥300 tons ARI 550/590
6.15 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
23XL Rotary screw liquid chiller, hermetic, water-cooled, 150 to 360 tons 5.98 – 6.12 7.47 – 7.67 27
18
Table 6.2.1C
Water Chilling Packages
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
19XR High-efficiency, hermetic, centrifugal liquid chiller, 200 to 1,500 tons 5.59 5.94 27
6.10 COP
≥300 tons ARI 550/590
6.40 IPLV
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference
Model No. Description COP IPLV
Guide Page No.
19XR High-efficiency, hermetic, centrifugal liquid chiller, 200 to 1,500 tons 6.10 – 6.45 6.41 – 6.79 27
Notes:
1. Chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is ≤40°F.
CARRIER PRODUCTS
Reference Guide
Model No. Description COP
Page No.
16JB Steam/hot water, single effect, absorption liquid chiller, 108 to 680 tons 0.70 – 0.71 26
19
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps
Notes:
1. Replacement units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE
INSTALLED IN NEW CONSTRUCTION PROJECTS.” Replacement efficiencies apply only to units with existing sleeves less than 16 inches high
and less than 42 inches wide.
2. Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the
unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
3. See table below for typical PTAC sizes and efficiency requirements based on the ASHRAE 90.1-1999 (2001) equations indicated in Table 6.2.1D.
CARRIER PRODUCTS
Reference Guide
Model No. Description EER
Page No.
20
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps
Cooling Mode
95°Fdb 12.3 – (0.213 x Cap/1000)
Outdoor air EER (Note 2 and 3)
All capacities ARI 380
New Construction Heating Mode
Notes:
1. Replacement units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE
INSTALLED IN NEW CONSTRUCTION PROJECTS.” Replacement efficiencies apply only to units with existing sleeves less than 16 inches high
and less than 42 inches wide.
2. Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the
unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
3. See table below for typical PTAC sizes and efficiency requirements based on the ASHRAE 90.1-1999 (2001) equations indicated in Table 6.2.1D.
CARRIER PRODUCTS
Cooling Mode Heating Mode Reference Guide
Model No. Description
EER COP Page No.
52CQ Comfort Series packaged terminal heat pumps 9.4 – 11.1 2.9 – 3.1 71
52PQ Premier Series packaged terminal heat pumps 9.4 – 12.7 2.9 – 3.4 73
21
Table 6.2.1D
Packaged Terminal Air Conditioners and Heat Pumps
Room Air Conditioners and Heat Pumps
CARRIER PRODUCTS
Model No. Description EER Reference Guide Page No.
22
Table 6.2.1G
Heat Rejection Equipment
AIR-COOLED CONDENSERS
Size Category Subcategory or Rating Condition Minimum Efficiency Test Procedure
CARRIER PRODUCTS
Reference Guide
Model No. Description Performance
Page No.
23
REFERENCE GUIDE
PART 2
REFERENCE GUIDE
TO CARRIER COMMERCIAL PRODUCTS
24
REFERENCE GUIDE
FEATURES: Suitable for R-12, -22, -500 and -502 refrigerants Shell-and-coil condenser (15 tons and smaller)
Semi-hermetic, reciprocating compressors Shell-and-tube condenser (sizes larger than 15 tons)
Suction cutoff unloading Integral finned copper tubes
Time Guard anti-short-cycling device Subcooling circuit (sizes larger than 15 tons)
FEATURES: Designed for R-22 or R-134a Vertical and horizontal airflow configurations
Single or multiple refrigerant circuits Low sound levels
Copper tubes with aluminum fins standard Direct-drive propeller fans
25
REFERENCE GUIDE
FEATURES: Designed for R-12, -22, -500, -502 and R-134a Direct-drive propeller fans
Single or multiple refrigerant circuits Copper tubes with aluminum fins standard
16JB, STEAM/HOT WATER, SINGLE EFFECT, HERMETIC, ABSORPTION LIQUID CHILLER, 108 TO 680 TONS
Chiller Model 16JB Nominal Capacity (Tons) COP
OPTIONS: Marine waterboxes (rated for 150 psig or 250 psig) Absorber-condenser crossover piping
ASME Section VIII, Div. 1, generator (up to 250 psig) Steam demand limiter
Non-standard tubing materials Part-load economizer
Flanged or Victaulic nozzles Chilled and condenser water flow switches
26
REFERENCE GUIDE
OPTIONS: 1-, 2-, or 3-pass cooler or condenser (water side) Unit-mounted or stand-alone pumpout unit
Marine waterboxes Hot gas bypass
Cooler and condenser tube material options Sensor kit
Refrigerant isolation valves Factory performance testing
Unit-mounted starter or VFD
FEATURES: Hermetic, twin-screw compressor, R-22 or R-134a Direct digital product integrated controls
Bottom-mounted capacity control slide valve ASME certified heat exchangers
Microprocessor-controlled oil heater Internally and externally enhanced tubing
External thermal economizer Double-grooved tube sheet holes
OPTIONS: One, 2, or 3-pass cooler or condenser (water side) Stand-alone pumpout unit
Marine waterboxes Hot gas bypass
Cooler and condenser tube options Full insulation (except waterbox covers)
Refrigerant isolation valves Control module options
Spring isolators Unit-mounted or remote-mounted motor starter
27
REFERENCE GUIDE
28
REFERENCE GUIDE
30GXN, GXR, PACKAGED, AIR-COOLED, ROTARY SCREW LIQUID CHILLERS, 80 TO 450 TONS
Cooling Capacity
Unit 30GXN, GXR Input kW COP EER IPLV
Tons kW
29
REFERENCE GUIDE
OPTIONS: Medium temperature brine operation (30HWB, HWC) Energy management module
Sound enclosure panels Part-winding start
Compressor ground fault sensor Hot gas bypass
Oil safety switch Pressure gage panel
30
REFERENCE GUIDE
31
REFERENCE GUIDE
32
REFERENCE GUIDE
33
REFERENCE GUIDE
34
REFERENCE GUIDE
38AQ, SPLIT SYSTEM HEAT PUMP WITH AIR-COOLED CONDENSING UNIT, 6 TONS
Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Outdoor Unit Indoor Unit
Capacity
38AQ 40RMQ Capacity Capacity Capacity
(Tons) EER COP COP
(Btu/h) (Btu/h) (Btu/h)
38AQS, SPLIT SYSTEM HEAT PUMP WITH AIR-COOLED CONDENSING UNIT, 15 TONS
Heating
Nominal Cooling Heating (High-Temp.)
Outdoor Unit Indoor Unit (Low-Temp.)
Capacity
38AS 40RMQ
(Tons) Capacity Capacity Capacity
EER IPLV COP COP
(Btu/h) (Btu/h) (Btu/h)
35
REFERENCE GUIDE
38ARQ, SPLIT SYSTEM HEAT PUMPS WITH AIR-COOLED CONDENSING UNITS, 7.5 TO 10 TONS
Nominal Cooling Heating (High-Temp.) Heating (Low-Temp.)
Outdoor Unit Indoor Unit
Capacity Capacity Capacity Capacity
38ARQ 40RMQ
(Tons) EER COP COP
(Btu/h) (Btu/h) (Btu/h)
36
REFERENCE GUIDE
37
REFERENCE GUIDE
38
REFERENCE GUIDE
40CG, CONSOLE (WITH 38CG CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 2.5 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure
1.5 40CG-018-3 38CG-018-3 18,000 650 10.0 9.0 55.0 38.0 79.0 49.0 2.0
2 40CG-024-3 38CG-024-3 23,400 800 10.0 9.1 56.0 40.0 74.0 49.0 2.6
2.5 40CG-030-3 38CG-030-3 30,000 800 10.0 9.0 55.0 40.0 78.0 49.0 3.3
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
40CS, CONSOLE (WITH 38CS CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 1.5 TO 2.5 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit
1.5 40CS-018-3 38CS-018-3 650 18,000 10.0 9.0 19,000 6.8 55.0 79.0 2.0
2 40CS-024-3 38CS-024-3 800 23,400 10.0 9.1 29,000 6.9 56.0 74.0 2.6
2.5 40CS-030-3 38CS-030-3 800 30,000 10.0 9.0 33,000 6.8 55.0 78.0 3.3
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
39
REFERENCE GUIDE
40HD, SATELLITE (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 2 TO 4 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
40QAB, UNDER CEILING (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 5 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure
38HDC018-3 18,000 500 12.0 11.0 57.2 48.9 66.1 57.8 1.6
1.5 40QAB024-331
38HDL018-3 18,000 500 11.6 10.5 57.2 48.9 59.5 51.2 1.7
38HDC024-3 22,800 600 12.0 11.0 58.4 50.1 65.5 57.2 2.1
2 40QAB024-331
38HDL024-3 23,000 600 11.0 11.2 58.4 50.1 63.2 54.9 2.2
38HDC030-3 30,000 840 12.0 11.0 68.4 60.1 63.0 54.7 2.7
2.5 40QAB036-321
38HDL030-3 29,000 840 10.3 9.7 68.4 60.1 59.5 51.2 2.9
38HDC036-3, 5, 6 34,000 840 12.0 10.5 68.4 60.1 64.5 56.2 3.2
3 40QAB036-321
38HDL036-3 34,000 840 10.1 9.6 68.4 60.1 64.7 56.4 3.2
38HDC048-3, 5, 6 47,000 1,200 12.0 10.8 67.3 59.0 70.1 61.8 4.4
4 40QAB048-321
38HDL048-3 45,500 1,200 10.8 9.9 67.3 59.0 65.4 57.1 4.5
38HDC060-3, 5, 6 58,000 1,600 12.0 11.2 70.1 61.8 69.4 61.1 5.2
5 40QAB060-311
38HDL060-3 58,500 1,600 10.8 9.9 70.1 61.8 65.8 57.5 5.7
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
40
REFERENCE GUIDE
40QAE, UNDER CEILING (WITH 38QR CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 2 TO 5 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit
38QR-018C-3 500 19,000 11.0 10.0 17,000 7.2 57.2 67.2 1.9
2 40QAE024-331
38QR-024C-3 525 24,000 11.0 10.0 22,600 7.3 57.2 66.3 2.4
38QR-030C-3 870 30,000 11.0 10.2 28,000 7.4 68.4 65.9 2.7
3 40QAE036-321 38QR-036C-3 870 34,600 11.5 10.2 33,000 6.8 68.4 66.2 3.4
38QR-036C-5, 6 870 35,000 10.1 9.8 33,400 6.8 68.4 71.5 3.4
4 40QAE048-321 38QR-048C-3, 5, 6 1,100 48,000 10.2 9.6 45,500 7.3 67.3 73.0 4.8
5 40QAE060-311 38QR-060C-3, 5, 6 1,600 58,000 10.5 9.9 57,500 7.4 70.1 73.6 5.9
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
40QKB, CASSETTE (WITH 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 1.5 TO 3 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure
38HDC018-3 18,300 525 11.0 10.4 56.3 48.0 66.1 57.8 1.8
1.5 40QKB024-3
38HDL018-3 17,800 525 11.4 10.6 56.3 48.0 59.5 51.2 1.6
38HDC024-3 24,000 915 11.0 10.9 54.8 46.5 65.5 57.2 2.1
2 40QKB036-3
38HDL024-3 24,000 915 11.8 11.3 54.8 46.5 63.2 54.9 2.1
38HDC030-3 30,000 915 10.8 9.6 54.8 46.5 63.0 54.7 2.8
2.5 40QKB036-3
38HDL030-3 29,000 915 11.1 10.1 54.8 46.5 59.5 51.2 2.8
38HDC036-3, 5, 6 33,000 915 10.8 10.5 54.8 46.5 64.5 56.2 3.1
3 40QKB036-3
38HDL036-3 34,400 915 10.5 9.7 54.8 46.5 64.7 56.4 3.5
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
41
REFERENCE GUIDE
40QKE, CASSETTE (WITH 38QR CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 1.5 TO 3 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit
1.5 40QKE024-3 38QR-018C-3 525 18,000 10.0 9.0 17,600 6.8 56.3 67.2 2.0
38QR-024C-3 980 25,000 10.7 10.2 23,800 7.6 54.8 66.3 2.4
2 40QKE036-3
38QR-030C-3 980 29,000 11.5 11.1 27,000 7.6 54.8 65.9 2.6
38QR-036C-3 1,100 33,000 10.5 9.5 33,000 6.8 59.1 66.2 3.5
3 40QKE048-3
38QR-036C-5, 6 1,100 34,400 10.0 9.2 34,000 6.8 59.1 71.5 3.7
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
40QNB, HIGH WALL (WITH 38AN & 38HDC/HDL CONDENSING UNIT), DUCT-FREE SPLIT SYSTEMS, 0.75 TO 2 TONS
Nominal Net Sound Ratings (dBa)
Standard Total
Capacity Indoor Unit Outdoor Unit Cooling SEER EER
CFM Indoor Indoor Outdoor Outdoor kW
(Tons) (Btu/h) Power Pressure Power Pressure
0.75 40QNB009-1 38AN-009-1 8,500 215 10.5 9.7 50.4 42.1 62.3 54.0 0.9
1 40QNB012-1 38AN-012-1 11,000 300 10.5 9.3 54.0 45.7 63.1 54.8 1.2
40QNB012-3 38AN-012-3 11,600 300 11.0 10.1 54.0 45.7 63.1 54.8 1.1
38HDC018-3 17,300 480 11.3 10.4 57.6 49.3 66.1 57.8 1.7
1.5 40QNB018-3
38HDL018-3 16,200 480 11.0 9.7 57.6 49.3 59.5 51.2 1.7
38HDL018-3 17,600 550 11.7 10.4 62.5 54.2 59.5 51.2 1.6
2 40QNB024-3 38HDC024-3 23,600 550 12.0 10.8 62.5 54.2 65.5 57.2 2.2
38HDL024-3 22,600 550 11.3 11.3 62.5 54.2 63.2 54.9 2.2
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
42
REFERENCE GUIDE
40QNE, QNH, HIGH WALL (WITH 38BK CONDENSING UNIT), DUCT-FREE HEAT PUMP SYSTEMS, 0.75 TO 2 TONS
High Heating Sound Power
Nominal Cooling
Standard (Note 4) Ratings (dBa) Total
Capacity Indoor Unit Outdoor Unit CFM
Capacity Capacity
kW
(Tons) SEER EER HSPF
Indoor Outdoor
(Btu/h) (Btu/h) Unit Unit
0.75 40QNE009-1 38BK-009-1 252 8,700 10.0 9.2 9,000 6.8 50.6 63.4 1.0
1 40QNH012-3 38BK-012-3 300 11,100 10.0 9.5 11,700 6.8 54.0 62.8 1.2
1.5 40QNH018-3 38BK-018-3 485 17,300 11.0 10.1 16,400 6.8 58.6 67.2 1.7
2 40QNH024-3 38BK-024-3 520 23,000 11.0 10.4 21,000 6.8 61.7 63.3 2.2
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. Total kW is for total system, including compressor, outdoor fan, and indoor fan.
3. Ratings are based on 25 feet of interconnecting refrigerant line and fan coil unit operating at high fan speed.
4. High heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
5 40CS-030---3 2 38SB-030---3 800 60,000 10.0 9.0 64,500 6.8 55.0 80.0 3.3 × 2
Notes:
1. Multi-zone system operating with condensing unit 38HDS024 has a maximum of two zones and may use any combination of high wall, under ceiling
or cassette style fan coil units.
2. Multi-zone heat pump high heating ratings are based on 47°Fdb and 43°Fwb air entering the outdoor unit.
3. Standard CFM indicated for console units are for each indoor coil.
CATALOG NO. On-line Product Data Digest Catalog 853-030 (print) and 853-023 (CD-ROM)
43
REFERENCE GUIDE
44
REFERENCE GUIDE
FEATURES: Electric cooling, Puron® (R-410A) refrigerant Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Natural gas or LP gas heating
Horizontal or vertical duct configuration Low NOx design (48GPN)
Rust-free composite base Direct spark ignition
45
REFERENCE GUIDE
46
REFERENCE GUIDE
FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Integrated gas control with diagnostics
Single-stage or 2-stage natural gas (or LP gas) heating Vertical or horizontal duct configurations
Fully hermetic scroll compressors
47
REFERENCE GUIDE
48JZ, JZN, SINGLE-PACKAGE, GAS HEATING, ELECTRIC HEAT PUMP UNITS, 2 TO 5 TONS
STANDARD UNIT
Cooling (Note 3) Heating Capacities and Efficiencies
024 2 800 24,000 12.0 10.5 23,800 3.0 13,000 2.0 7.0 72
030 2.5 1,000 29,000 12.0 10.4 28,200 3.2 15,600 2.1 7.0 72
036 3 1,200 36,000 12.0 10.5 34,400 3.2 18,000 2.0 7.2 77
042 3.5 1,400 41,000 12.0 10.6 40,000 3.2 22,000 2.0 7.2 73
048 4 1,600 47,500 12.0 10.5 44,000 3.1 23,600 2.0 7.2 79
060 5 1,750 59,000 12.0 10.0 55,000 3.1 31,000 2.0 7.2 79
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
Cooling (Note 3) Heating Capacities and Efficiencies
Nominal High
Unit 48JZ Capacity Low Heating
Net Capacity Heating COP at 47°F COP at
(Tons) SEER EER Capacity at HSPF
(Btu/h) Capacity at (Btu/h) 17°F (Btu/h)
17°F (Btu/h)
47°F (Btu/h)
024040
40,000 31,000 20-50 80.1
030040
030060 46,000 35-65 78.4
036060 60,000 46,000 25-55 78.7
042060 47,000 20-50 78.7
036090 70,000 45-75 79.9
042090 71,000 35-65 79.9
90,000
048090 70,000 25-55 78.6
060090 70,000 25-55 78.6
048115
115,000 92,000 35-65 81.1
060115
048130 104,000
130,000 40-70 80.3
060130 103,000
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
2. Units are equipped with factory-installed ICM motors to provide variable-speed blower operation.
3. Cooling capacity, EER and SEER values shown are at 80°Fdb and 67°Fwb indoors, and 95°Fdb outdoors.
4. AFUE – Annual Fuel Utilization Efficiency.
FEATURES: Electric cooling and heating, Puron (R-410A) Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base High- and low-pressure switches
Low-NOx design (48JZN) Direct spark ignition
Integrated gas control with diagnostics Turbo-tubular aluminized steel heat exchanger
48
REFERENCE GUIDE
FEATURES: Electric cooling, R-22 Low NOx design (Models 48TML, M and N)
Constant volume Independent refrigerant circuits (sizes 008 to 014)
Single-stage or 2-stage natural gas (or LP gas) heating Integrated gas control with diagnostics
Fully hermetic reciprocating or scroll compressors Vertical or horizontal duct configurations
49
REFERENCE GUIDE
030 30 6,000-15,000
040 40 8,000-20,000
050 50 9,000-20,000 All 48Z models are All 48Z models are
ASHRAE Std. 90.1 ASHRAE Std. 90.1
055 55 10,000-25,000 compliant. See local Carrier compliant. See local Carrier
060 60 12,000-30,000 sales representative for sales representative for
070 70 14,000-30,000 ratings. ratings.
075 75 15,000-30,000
090 90 17,000-34,000
Notes:
1. Units are rated in accordance with ARI Standard 340/360..
50
REFERENCE GUIDE
FEATURES: Electric cooling, R-22 Low profile design (installs above ceiling)
Fully hermetic scroll compressor Removable access panels
51
REFERENCE GUIDE
OPTIONS: Hot water or steam heating coil Ducted return-air filter rack (sizes 006 to 014)
Discharge plenum Thermostat options
52
REFERENCE GUIDE
09BYN006
006 5 2,000 59,000 10.0 (Note 2)
09AZ006
Notes:
1. Capacities shown are at ARI standard conditions.
2. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.
OPTIONS: Hot water or steam heating coil Ducted return-air filter rack (sizes 006 to 014)
Discharge plenum Thermostat options
53
REFERENCE GUIDE
024 20 6,800 230,000 9.8 23.4 228,000 3.3 20.0 116,000 2.0 16.7
028 25 7,500 262,000 9.2 28.6 266,000 3.3 23.7 140,000 2.1 19.5
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. 50EJQ vertical discharge unit; 50EWQ horizontal discharge unit.
3. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
4. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.
OPTIONS: Electric resistance heater coil (36 or 72 kW) Electronic expansion board
Power exhaust Enthalpy controls
Corrosion-resistant coil options Head pressure control package
Field-installed control interface device CO2 sensor
FEATURES: Electric cooling, Puron (R-410A) refrigerant Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels
OPTIONS: Electronic variable-speed blower motor Electric resistance heater coil (5 to 20 kW)
Economizer with solid-state controls Low-ambient kit
Manual outdoor air damper Crankcase heater
Time Guard® II anti-short-cycling device Corrosion-resistant coil options
54
REFERENCE GUIDE
OPTIONS: Economizer with solid-state controls Electric resistance heater coil (5 to 20 kW)
Manual outdoor air damper Low-ambient kit
Time Guard® II anti-short-cycling device Crankcase heater
Controls upgrade kit Corrosion-resistant coil options
55
REFERENCE GUIDE
FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Vertical or horizontal duct configurations
Fully hermetic scroll compressors Direct- or belt-driven evaporator fan
2-inch filter rack
56
REFERENCE GUIDE
Heating (High-
Nominal Capacity Cooling Sound Rating
Unit 50HJQ Temp.)
(Tons) (decibels)
Capacity (Btu/h) EER Capacity (Btu/h) COP
007 6 71,000 10.5 69,000 3.4 80
008 7.5 88,000 10.3 85,000 3.3 82
012 10 116,000 10.3 114,000 3.3 84
Notes:
1. Rated in accordance with ARI Standard 340/360.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Defrost system
Fully hermetic scroll compressors Low sound levels
Dual independent refrigerant circuits (sizes 008 and 012) Non-corrosive condensate drain pan
57
REFERENCE GUIDE
014 13 4,500 140,000 9.8 14.3 136,000 3.2 12.4 72,000 2.1 10.0 87
016 15 5,200 172,000 9.3 18.5 172,000 3.3 15.3 90,000 2.2 12.5 88
Notes:
1. Rated in accordance with ARI Standard 210/240.
2. High-temperature heating conditions: 70°Fdb indoor entering air, 47°Fdb and 43°Fwb outdoor entering air.
3. Low-temperature heating conditions: 70°Fdb indoor entering air, 17°Fdb and 15°Fwb outdoor entering air.
FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Belt-driven fans with variable-pitch sheaves
Semi-hermetic, reciprocating compressors Defrost system
Dual independent refrigerant circuits (size 016) Electric unloaders (size 014)
58
REFERENCE GUIDE
024 2 800 23,400 12.0 10.2 23,800 3.2 12,400 2.0 6.9 78
030 2.5 1,000 28,600 12.0 10.0 28,200 3.2 15,400 1.9 7.1 78
036 3 1,200 35,000 12.0 10.0 33,000 3.2 18,000 1.9 7.0 80
042 3.5 1,400 41,500 12.0 10.1 40,000 3.3 21,000 1.9 7.0 80
048 4 1,600 47,500 12.0 10.1 44,000 3.5 23,600 2.0 7.0 82
060 5 1,800 57,000 11.0 9.2 57,000 3.5 31,800 2.0 7.2 82
Notes:
1. Rated in accordance with the latest revision of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor (sizes 024 to 042)
Constant volume Electronic, variable-speed blower motor (sizes 048 & 060)
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Chronotemp defrost system Time Guard® II anti-short-cycling device
OPTIONS: Manual outdoor air damper Electric resistance heater coil (5 to 20 kW)
Copper-fin coils Low-ambient kit
Controls upgrade kit Filter rack
Thermostat options
018 1.5 700 19,000 10.0 17,600 2.9 8,600 1.8 6.6 73
024 2 800 24,000 10.0 23,600 2.9 12,400 1.8 6.8 73
030 2.5 1,000 29,000 10.0 29,000 3.0 15,000 1.9 6.9 75
036 3 1,200 35,000 10.0 35,000 3.0 18,000 1.9 7.0 79
042 3.5 1,250 42,000 10.0 40,500 3.0 22,000 1.9 7.0 73
048 4 1,600 47,000 10.0 47,000 3.0 27,000 2.0 7.0 80
060 5 2,000 57,500 10.0 57,000 3.2 32,000 2.0 7.0 78
Notes:
1. Rated in accordance with the latest edition of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic compressors Vertical or horizontal duct configuration
Time Guard® II anti-short-cycling device Low sound levels
Rust-free composite base
59
REFERENCE GUIDE
024 2 800 23,200 12.0 10.5 22,400 3.2 13,000 2.0 7.1 72
030 2.5 1,000 29,000 12.0 10.5 28,200 3.2 15,600 2.0 7.1 72
036 3 1,200 35,000 12.0 10.5 34,000 3.2 19,000 1.9 7.1 77
042 3.5 1,400 41,500 12.0 10.5 40,000 3.2 22,000 2.0 7.2 73
048 4 1,450 47,000 12.0 10.5 44,000 3.1 23,600 2.0 7.1 79
060 5 1,750 60,000 12.0 10.5 57,000 3.3 32,000 2.0 7.2 79
Notes:
1. Rated in accordance with the latest edition of ARI Standard 210/240 and/or U.S. Government DOE test procedures.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Vertical or horizontal duct configuration
Rust-free composite base Low sound levels
024 2 800 24,000 12.0 10.5 23,800 3.0 13,000 2.0 7.0 72
030 2.5 1,000 29,000 12.0 10.4 28,200 3.1 15,600 2.0 7.1 72
036 3 1,200 36,000 12.0 10.5 34,400 3.2 18,000 2.0 7.2 77
042 3.5 1,400 41,000 12.0 10.6 40,000 3.2 22,000 2.0 7.2 73
048 4 1,600 47,500 12.0 10.5 44,000 3.1 23,600 2.0 7.2 79
060 5 1,750 59,000 12.0 10.0 55,000 3.1 31,000 2.0 7.2 79
INTEGRATED CONTROL MOTOR (VARIABLE-SPEED) UNIT
High
Nominal Net Cooling Low Heating
Heating COP at 47°F COP at
Unit 50JZ Capacity Capacity at EER SEER Capacity at HSPF
Capacity at (Btu/h) 17°F (Btu/h)
(Tons) 95°F (Btu/h) 17°F (Btu/h)
47°F (Btu/h)
FEATURES: Electric cooling and heating, Puron (R-410A) Direct-drive, multi-speed blower motor
Fully hermetic compressors Vertical or horizontal duct configuration
Rust-free composite base High- and low-pressure switches
OPTIONS: Electronic variable-speed blower motor Electric resistance heater coil (5 to 20 kW)
Economizer with solid-state controls Low-ambient kit
Manual outdoor air damper Crankcase heater
Corrosion-resistant coil options Filter rack
60
REFERENCE GUIDE
50KQA, KQD, CONSOLE, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 1.5 TONS
Cooling (Note 2) Heating (Note 3) Water
Unit Nominal
Nominal Water Flow Pressure
50KQA, Capacity
CFM Capacity Capacity GPM Drop
KQD (Tons) EER Total kW COP Total kW
(Btu/h) (Btu/h) (Ft wg)
007 0.5 275 6,800 12.2 0.531 8,600 4.3 0.548 1.7 2.3
009 0.75 275 9,000 12.6 0.744 11,600 4.2 0.791 2.3 4.2
Notes:
1. Rated in accordance with ARI Standard 320.
2. Cooling standard: 85°F entering water temperature.
3. Heating standard: 70°F entering water temperature.
4. 50KQA standard temperature range unit; 50KQD low temperature range unit.
5. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.
50RHC, RVC, HORIZONTAL & VERTICAL, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
WATER-SOURCE APPLICATIONS
Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)
018 1.5 600 18,200 12.3 22,000 4.2 4.5 3.9 9.1
024 2 800 23,800 13.0 27,800 4.6 6.0 6.0 13.8
030 2.5 1,000 28,000 12.2 33,500 4.4 7.5 4.0 9.3
036 3 1,200 35,000 12.0 45,500 4.2 9.5 4.7 10.9
041 3.5 1,325 37,700 12.0 47,500 4.2 10.5 3.7 8.6
042 3.5 1,350 41,000 12.0 52,600 4.2 11.0 5.1 11.8
048 4 1,600 47,100 12.2 58,200 4.4 12.0 4.9 11.3
060 5 2,000 58,000 12.0 76,800 4.2 15.0 10.7 24.6
Notes:
1. 50RHC horizontal unit; 50RVC vertical unit.
2. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
3. The temperature of the water or brine loop is usually controlled within a temperature range of 60°F to 90°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
5. EWT – Entering Water Temperature.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Capillary metering device
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations
61
REFERENCE GUIDE
50RHR, RVR, HORIZ. & VERT. HIGH-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
WATER-SOURCE APPLICATIONS
Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)
006 0.5 180 6,200 12.8 7,400 4.2 1.50 1.7 3.9
009 0.75 300 8,100 12.8 10,300 4.3 2.25 2.9 6.7
015 1.25 500 14,100 13.3 16,800 4.6 3.75 6.8 15.7
019 1.5 600 18,900 12.5 22,500 4.2 4.50 5.6 12.8
024 2 800 23,000 12.3 27,600 4.2 6.00 5.8 13.5
030 2.5 1,000 28,500 13.2 33,300 4.4 7.50 3.3 7.6
036 3 1,200 34,000 13.0 41,700 4.2 9.00 2.9 6.8
042 3.5 1,400 40,000 13.0 46,700 4.3 10.50 3.8 8.8
048 4 1,600 47,000 12.8 58,000 4.2 12.00 5.4 12.4
060 5 2,000 59,000 12.8 68,000 4.2 15.00 7.9 18.2
Notes:
6. 50RHR horizontal unit; 50RVR vertical unit.
7. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
8. The temperature of the water or brine loop is usually mechanically controlled within a temperature range of 60°F to 90°F.
9. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
10. Size 006 available as a RHR (horizontal) model only.
11. EWT – Entering Water Temperature.
GROUND-SOURCE APPLICATIONS
Unit Nominal Cooling (77°F EWT) Heating (32°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)
006 0.5 180 5,600 14.3 4,400 3.4 1.50 1.7 3.9
009 0.75 300 8,300 14.2 6,200 3.4 2.25 2.9 6.7
012 1 375 12,100 14.2 8,700 3.4 3.00 8.1 18.7
015 1.25 500 14,500 14.8 10,700 3.5 3.75 6.8 15.7
019 1.5 600 19,100 13.4 11,800 3.2 4.50 5.6 12.8
024 2 800 23,000 13.3 16,700 3.3 6.00 5.8 13.5
030 2.5 1,000 28,700 14.4 20,100 3.4 7.50 3.3 7.6
036 3 1,200 35,200 14.7 25,500 3.4 9.00 2.9 6.8
042 3.5 1,400 42,000 15.0 29,400 3.4 10.50 3.8 8.8
048 4 1,600 48,500 14.3 35,300 3.3 12.00 5.4 12.4
060 5 2,000 60,600 14.1 44,000 3.2 15.00 7.9 18.2
Notes:
1. 50RHR horizontal unit; 50RVR vertical unit.
2. A brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink.
3. The heat exchange loop may be placed in horizontal trenches or vertical bores, or be submerged in a body of surface water.
4. The temperature of the brine is related to the climatic conditions and may vary from 20°F to 110°F.
5. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 330).
6. Size 006 available as RHR (horizontal) model only.
7. EWT – Entering Water Temperature.
62
REFERENCE GUIDE
50RHR, RVR, HORIZ. & VERT. HIGH-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 0.5 TO 5 TONS
(continued)
GROUNDWATER-SOURCE APPLICATIONS
Unit Nominal Cooling (59°F EWT) Heating (50°F EWT) Water Pressure Drop
Nominal Water Flow
50RHR, Capacity
CFM Capacity Capacity GPM
RVR (Tons) EER COP (Psi) (Ft wg)
(Btu/h) (Btu/h)
006 0.5 180 5,900 17.6 5,500 3.8 1.50 1.7 3.9
009 0.75 300 8,800 17.6 7,700 3.8 2.25 2.9 6.7
012 1 375 12,500 17.6 11,000 3.6 3.00 8.1 18.7
015 1.25 500 15,200 17.6 13,500 4.1 3.75 6.8 15.7
019 1.5 600 20,100 17.6 16,700 3.6 4.50 5.6 12.8
024 2 800 26,100 18.2 21,300 3.7 6.00 5.8 13.5
030 2.5 1,000 31,100 18.6 27,000 3.9 7.50 3.3 7.6
036 3 1,200 37,500 18.2 33,400 3.9 9.00 2.9 6.8
042 3.5 1,400 48,500 18.6 38,300 3.9 10.50 3.8 8.8
048 4 1,600 54,000 18.1 46,000 3.8 12.00 5.4 12.4
060 5 2,000 64,500 16.8 56,000 3.8 15.00 7.9 18.2
Notes:
1. 50RHR horizontal unit; 50RVR vertical unit.
2. A water-to-air heat pump using water pumped from a well, lake or stream functioning as a heat source/heat sink.
3. The temperature of the water is related to the climatic conditions and may vary from 40°F to 80°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 325).
5. Size 006 available as RHR (horizontal) model only.
6. EWT – Entering Water Temperature.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Thermostatic expansion valves
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations
63
REFERENCE GUIDE
50RHS, RVS, RDS, PREMIUM-EFFICIENCY, WATER-SOURCE HEAT PUMP UNITS, 1.25 TO 6 TONS
WATER-SOURCE APPLICATIONS
Unit Nominal Cooling (86°F EWT) Heating (68°F EWT) Water Pressure Drop
Nominal Water Flow
50RHS, Capacity
CFM Capacity EER Capacity COP GPM
RVS (Tons) (Psi) (Ft wg)
(Btu/h) (Vert/Horiz) (Btu/h) (Vert/Horiz)
015 1.25 500 14,100 16.0 / 16.0 16,300 5.3 / 5.3 3.8 1.3 3.0
018 1.5 600 17,100 14.8 / 14.4 20,900 5.0 / 4.8 4.5 1.6 3.7
024 2 800 24,200 14.9 / 14.5 30,100 4.8 / 4.7 6.0 1.5 3.5
030 2.5 1,000 28,900 15.1 / 14.7 35,000 4.8 / 4.7 8.0 2.2 5.1
036 3 1,150 33,800 14.9 / 14.5 40,400 4.6 / 4.4 9.0 3.4 7.9
042 3.5 1,400 41,000 14.5 / 14.1 49,800 4.8 / 4.7 10.5 4.4 10.2
048 4 1,600 45,800 14.6 / 14.2 54,100 4.9 / 4.8 12.0 5.5 12.7
060 5 2,000 56,800 13.4 / 13.0 74,900 4.7 / 4.6 15.0 3.1 7.2
070 6 2,300 63,700 12.4 / 12.4 78,300 4.5 / 4.5 18.0 4.3 9.9
Notes:
1. 50RHS horizontal unit; 50RVS vertical (up flow) unit; 50RDS vertical (down flow) unit.
2. A water-to-air heat pump using water or brine circulating in a common piping loop functioning as a heat source/heat sink.
3. The temperature of the water or brine loop is usually mechanically controlled within a temperature range of 60°F to 90°F.
4. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 320).
5. EWT – Entering Water Temperature.
GROUND-SOURCE APPLICATIONS
Unit Nominal Cooling (77°F EWT) Heating (32°F EWT) Water Pressure Drop
Nominal Water Flow
50RHS, Capacity
CFM Capacity EER Capacity COP GPM
RVS (Tons) Psi Ft wg
(Btu/h) (Vert/Horiz) (Btu/h) (Vert/Horiz)
015 1.25 500 14,900 18.5 / 18.5 11,200 3.8 / 3.8 3.8 1.5 3.5
018 1.5 600 18,300 16.7 / 16.2 13,200 3.6 / 3.5 4.5 1.8 4.2
024 2 800 26,000 17.1 / 16.6 19,200 3.6 / 3.5 6.0 1.8 4.2
030 2.5 1,000 30,700 16.9 / 16.4 22,200 3.6 / 3.5 8.0 2.6 6.0
036 3 1,150 35,800 16.4 / 15.9 26,700 3.4 / 3.3 9.0 3.9 9.0
042 3.5 1,400 43,300 16.0 / 15.5 32,700 3.7 / 3.6 10.5 5.1 11.8
048 4 1,600 48,900 16.4 / 15.9 36,900 3.7 / 3.6 12.0 6.4 14.8
060 5 2,000 59,400 14.6 / 14.2 48,700 3.6 / 3.5 15.0 3.6 8.3
070 6 2,300 67,100 13.4 / 13.4 53,400 3.6 / 3.6 18.0 5.0 11.6
Notes:
1. 50RHS horizontal unit; 50RVS vertical unit.
2. A brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink.
3. The heat exchange loop may be placed in horizontal trenches or vertical bores, or be submerged in a body of surface water.
4. The temperature of the brine is related to the climatic conditions and may vary from 20°F to 110°F.
5. Certified in accordance with ARI/ISO Standard 13256-1 Certification Program (replaces ARI Standard 330).
6. EWT – Entering Water Temperature.
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Hermetic compressors Thermostatic expansion valves
Steel/copper tube-in-tube heat exchanger Multiple airflow configurations
64
REFERENCE GUIDE
65
REFERENCE GUIDE
OPTIONS: Electric resistance heater coil (4.4 to 51 kW) Direct digital controls
Integrated economizer Head pressure control package
Power exhaust Corrosion-resistant coil options
High-static indoor fan motor and drive Energy$Recycler heat recovery
Time Guard® II anti-short-cycling device CO2 sensor
66
REFERENCE GUIDE
FEATURES: Electric cooling and heating, R-22 Vertical or horizontal duct configurations
Constant volume Acutrol refrigerant metering system
Fully hermetic compressors Corrosion-resistant sloped condensate pan
FEATURES: Electric cooling, R-22 Independent refrigerant circuits (sizes 008 to 014)
Constant volume Vertical or horizontal duct configurations
Fully hermetic reciprocating or scroll compressors Direct- or belt-driven evaporator fan
2-inch filter rack
67
REFERENCE GUIDE
080 6.5 2,600 74,000 14.0 5.29 83,000 4.2 5.79 18.0 8.2
160 13 5,200 148,000 14.0 10.57 166,000 4.2 11.58 36.0 8.2
Notes:
1. Rated in accordance with ARI Standard 320.
2. Cooling standard: 85°F entering water temperature.
3. Heating standard: 70°F entering water temperature.
4. 50VQA standard temperature range unit; 50VQD low temperature range unit.
5. All of the unit sizes listed meet ASHRAE Standard 90.1. Sizes not listed may soon be upgraded or are in the process of being upgraded. For the latest
information, go to Carrier’s web site at http://www.commercial.carrier.com or consult your local Carrier sales representative.
FEATURES: Electric cooling and heating, R-22 Designed for vertical installation
Standard and low temperature models Condensate overflow switch
Fully hermetic or scroll compressors Anti-short cycle timer
Steel/copper tube-in-tube heat exchanger Thermostatic expansion valves
68
REFERENCE GUIDE
OPTIONS: Waterside economizer with control valves Control options for system integration
Acoustical discharge plenum Factory-mounted disconnect
Water regulating valve package VFD bypass
Hot water heating Water flow switch
030 30 6,000-15,000
040 40 8,000-20,000
050 50 9,000-20,000 All 50Z models are All 50Z models are
ASHRAE Std. 90.1 ASHRAE Std. 90.1
055 55 10,000-25,000 compliant. See local Carrier compliant. See local Carrier
060 60 12,000-30,000 sales representative for sales representative for
070 70 14,000-30,000 ratings. ratings.
075 75 15,000-30,000
090 90 17,000-34,000
Notes:
1. Units are rated in accordance with ARI Standard 340/360..
69
REFERENCE GUIDE
FEATURES: Electric cooling and heating, R-22 Direct-drive, multi-speed blower motor
Fully hermetic scroll compressors Horizontal duct configuration
Chronotemp defrost system Composite material base
70
REFERENCE GUIDE
FEATURES: Electric resistance heater coil (2.3, 3.4, or 5.0 kW) Low sound levels
Slide-out chassis Fits in standard 42” x 16” wall sleeve
71
REFERENCE GUIDE
FEATURES: Electric resistance heater coil (2.3, 3.4, or 5.0 kW) Low sound levels
Slide-out chassis Fits in standard 42” x 16” wall sleeve
72
REFERENCE GUIDE
73
REFERENCE GUIDE
74
CARRIER CORPORATION