Manufacturer assumes no responsibility for a hazard or 1.

Features
damage caused by incorrect or non-application of any of the · Accuracy class 1 as per IEC 62053-21, class 0.5 as per IEC 62053-22
instructions attached herein. Under no circumstance shall
Larsen & Toubro be liable for any consequential or resulting · True RMS measurement
injury or for loss, damage or expense directly or indirectly from · Simultaneous sampling of Volts & Amps
the use of this product. Sufficient care is taken to provide all · Positive accumulation of active energy even with CT polarity reversal, reverse lock programmable
INSTRUCTION MANUAL information regarding the product but Larsen & Toubro does
not claim any responsibility for the damage caused by using the · User programmable password protection
product directly or indirectly. Use according to the operating · Auto scrolling
Digital Panel Meter instructions, professional practices, wiring rules, codes, safety · Auto-scaling of Kilo, Mega, Giga
regulations applicable to the given installation.
· Low PT, CT burden
Energy Meter
· Programmable PT, CT ratio
4000 LED Series During normal operation of this instrument ,hazardous · Field programmable 3 Phase 4 Wire, 3 Phase 3 Wire, 1 Phase configuration
voltages are present at the rear terminals, which can cause
injury or death. Installation ,disconnection or removal of the · OLD register to store the previously cleared energy value
meter should be carried out only by qualified, trained · Wide operating range of 80 to 300 V AC/DC auxiliary supply
personnel, after de-energizing connected circuits. Improper · Site selectable 1A/5A
installation , including improper grounding will void warranty.
Product warranty void if seal is broken. · Energy display format programmable-counter based or resolution based

2. LED Indication WL 4000 3.Technical Specification

3 Ph 4 W, 3 Ph 3 W, 1 Ph
Lag (ON) Type of measurement Type
True RMS, 64 samples per cycle
M Mega ON Both ON 1 sec update time
41 5.0 P.P -
K Kilo ON
} Giga
Reverse
REV
Communication Class 1 as per IEC 62053-21
ON Measurement Accuracy
PRG
Pulse ON Class 0.5 as per IEC 62053-22
(only for Wh parameter
ENERGY METER
is selected)
To edit the To select the value
Display type and resolution LED 4 digit for instantaneous and 6 digits for cumulative
value/Parameter or accept the value
in programming in programming
mode mode

50 - 550 VLL Impulse voltage test ±6 kV as per IEC 62052-11


Insulation
PT Primary and Secondary user programmable AC voltage test 4 kV double insulation as per IEC 62053-21
Input voltage properties
for LT and HT applications Insulation resistance 500 V DC as per IS 13779
Burden : 0.2VA max per phase Operating temperature
O O
-10 C to +55 C
Measuring -/5A and -/1A site selectable O O
circuit Operating Storage temperature -25 C to +70 C
Current range from 10% to 120% of In (50mA-6A), conditions Humidity 5% to 95% relative humidity non-condensing
Input current Starting current : 0.4% of full scale
CT Primary and Secondary user programmable Recommended wire 2.5 sq mm
for LT and HT applications Shock As per standard IEC 60068-2
Frequency 40 - 70 Hz Mechanical
Vibration 10 to 55 Hz, 0.15 mm amplitude
conditions
Aux voltage 80 - 300V AC/DC Casing Plastic mould protected to IP51 from front side
Auxilliary
Aux burden <5VA Measurement category CAT III
circuit
Freq range 40 - 70 Hz Safety Pollution degree 2
Test of power consumption as per IEC 62053-21
Electrical Protection IP20 at terminals, IP51 on front
Voltage dips and interrupts as per IEC 62053-21
requirements Product weight 300 gms
Short time over current protection 10A max continuous, 20 times of In for 3 sec Weight &
dimensions Bezel dimension (W x H x D) 96 x 96 x 58 mm
Fast transients burst test ±4 kV as per IEC 61000-4-4
Panel cutout 92 x 92 mm +0.8
- 0.0
Immunity to electrostatic discharge ±8 kV air discharge, ±6 kV contact discharge
as per IEC 61000-4-2 Outputs Meter constant : 1250/ (external CT ratio x PT ratio)
Electro- Radiated, radio-frequency, 10 V/m as per 61000-4-3 Type Rs485 port Modbus RTU
magnetic electromagnetic field immunity test
Baud rate 2400, 4800, 9600, 19200 bps (site selectable)
compatibility Immunity to electromagnetic 10 V/m as per IEC 61000-4-6 Communica-
(EMC) HF fields through conducted lines tion Parity Odd, Even, None
Surge immunity test ±6 kV as per IEC 61000-4-5 Slave id 1 to 247 (programmable)
Rated power frequency magnetic fields 1 A/m as per IEC 61000-4-8 Isolation 2 kVAC isolation for 1 min between communication & other circuits
Emission Class B as per CISPR 22 Certifications CE, RoHS
4. Programming Mode 4.2.2. Programming Mode PT Secondary 4150P.S 415.0 50V to 550V
4.1 Programming keys · Press Down To Enter Programming Mode CT Primary 5000C.P 5.000 0.5A - 99KA
· Press UP key to select the Edit Mode
To select Edit Mode and save parameter  Blink indicates Edit Mode is ON CT Secondary 5000C.S 5.000 0.5A - 6A
DOWN to decrement value or parameter · Press DOWN to decrement values or Yes/No
to select from available options Reverse lock No If YES it blocks energy accumulation in
case the CT polarity reverse.
4.2 General Programming Guide · Press UP to accept the value of the parameter
· Press UP + Down to enter Programming Mode Method of VA Selection:
· Press DOWN to edit next parameters till end VA Selection UE C.H UA. VEC.Har Arithmetic /Vector harmonics /Vector
· Enter Password (default value 0000) after the configuration of last parameter display
· Blink indicates Edit Mode is ON Parameter options Wh Options: Wh/PF/W/VA
screen will prompt “SAVE”, Display reads “Y” (YES)
· Press DOWN to decrement value · Press DOWN to change to “ ” (NO) Baud rate 9600 2400, 4800, 9600 19.2k
0/9/8/7/6/5/4/3/2/1 · Press UP to save. Parity Even Even/Odd/none
· Press UP to move to the next digit till 4th digit
4.3.Display Slave Id 1000SL 1.000 1 to 247
If Password is correct, meter display reads I First four digit : Parameter value
For Clear Mode move to step 4.2.1 41 5.0 P.P 5th & 6th digit : Parameter to edit PASSWORD 0000 0000 to 9999
For Programming Mode move to step 4.2.2 Energy
Programming Resolution Resolution/Counter
Default Option/Range
4.2.1.Clear Mode Parameter Energy Selection Wh Wh/VAh
· Press UP to Enter Clear Mode Display reads “ I” ConFIG.
· Press UP to clear parameter. Display prompts “ ” (Defines the 3P 4W 4.4. Enabling and Disabling Auto Scrolling
power system Press DOWN for 6 secs
· Press DOWN to change for “y” (yes) to clear values configuration.)
3P 4W 3P 3W
· Press UP to clear 1 Phase Display Shows: EnbL. Au.
Again press DOWN for 6 sec
100V-999kv Display Shows: dSbL. Au.
If password is incorrect, meter will display next To set 11.10kV Set first four digits
parameter but cannot be edited. PT Primary (1110) as explained above press
415 UP/DOWN key to place decimal point
4150P.P
at appropriate location.
M & K both LED will glow for Giga

5. Memory Map 6. Display Parameters


Data Data 6.1 Display of Parameters in meter 6.2 Energy Value Interpretation
Address Parameter type Address Parameter type
Display Meaning Display Meaning Programming mode
40101 Watts Total float 40123 PF B phase float
Active Energy Power Factor b-phase Sl.No. Display Parameter Energy
40103 Watts R phase float 40125 VA total float
Active Energy Old Watts r-phase on Meter selection selection
40105 Watts Y phase float 40127 VA R phase float
Apparent Energy Watts y-phase 1. Wh Wh Wh
40107 Watts B phase float 40129 VA Y phase float
Apparent Energy Old Watts b-phase 2. VAh Wh VAh
40117 PF Avg (inst) float 40131 VA B phase float
Power Factor Watts Total
40119 PF R phase float 40159 Wh float In auto scroll mode, the parameter name (eg. Wh)
Apparent Power Apparent Power r-phase will be displayed for 1 sec. after which the energy
40121 PF Y phase float 40161 VAh float
Power Factor r-phase Apparent Power y-phase value will be displayed for next 4 sec.
Power Factor y-phase Apparent Power b-phase

7. Wiring Diagram 8. Mounting Dimensions


In case of complaint please contact

WL40000501A
90 +2.0 Steps for Mounting
- 0.0
Received (Import) Delivered (Export) Received (Import) Delivered (Export) Received (Import) Delivered (Export) Insert meter to panel CUSTOMER INTERACTION CENTRE (CIC)
1
without clamps TOLL-Free: 1800 233 5858, 1800 200 5858
2 Telephone : 022 6774 5858
Load Line Load Line Load Line Insert both clamps email: cic@LNTEBG.com
2 1 3

+2.0
90 - 0.0

AMF IP AMF IP AMF IP


L&T Electrical & Automation
240V AC 240V AC 240V AC

Electrical Standard Products


L&T Business Park, Tower 'B' / 3rd Floor
3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System 54mm
3 Saki Vihar Road, Powai Mumbai 400 072
4mm
Website: www.Lntebg.com