1
2
INDICE
Index
Pág.
INTRODUCCION
Introduction ................................................................................................................................... 5
LABORATORIO
Laboratory ..................................................................................................................................... 97
TABLA DE CONVERSION
Conversion Table ............................................................................................................................ 105
RECOMENDACIONES PARA EL MANEJO Y ALMACENAMIENTO
DE LOS CABLES
Handling and Shipping Recomendations for Aluminun Cables ........................................................... 107
3
INTRODUCCION
Introduction
CONAL, es la empresa líder en Latinoamérica en la CONAL is the leader company in Latin America in the
fabricación y comercialización a nivel nacional e production and commercialization of electrical aluminum
internacional de conductores eléctricos de aluminio. conductors.
Su ubicación estratégica, muy cerca del puerto naviero Its strategic position, very close to the most important
más importante de Venezuela (Puerto Cabello), país port in Venezuela (Puerto Cabello) a traditional
tradicionalmente exportador de productos mineros y su country exporting mining products; and its proximity to
cercanía a Guayana, región que produce el 4% de la Guayana, region that produces 4% of the worldwide
producción mundial de aluminio; la colocan en una situación production of aluminum, sets CONAL in a privilege
privilegiada para responder competitivamente a las nece- place to respond to the international business and
sidades comerciales y de needs in an competitive
negocios del mercado way.
internacional. CONAL top of the line
CONAL, en la actua- technology in the industry
lidad posee una infra- permits to produce
estructura con la más al- aluminum conductors for
ta tecnología en la the transmission of high,
industria para producir medium and low voltage,
conductores de alu- and for regional electrical
minio para la transmi- distribution net. As part
sión de energía eléctri- of the PD WIRE & CABLE,
ca de alto, medio y ba- CONAL relies on the
jo voltaje, así como re- most specialized
des de distribución eléc- technical department,
trica. CONAL, como parte de PHELPS DODGE Wire and this is due to the different operations for electrical and
Cable Group, cuenta con el más especializado soporte y telecommunications conductors that Phelps Dodge
apoyo técnico, ya que este reconocido Grupo posee plantas owns around the world.
para la fabricación de conductores de energía eléctrica y CONAL is located in the city of Valencia, Carabobos
telecomunicaciones alrededor del mundo. Para ello se state (the industrial center of the country), with an
cuenta con la Unidad Técnica de Aluminio con la finalidad extension of 64.000 square meter in which is located
de asistir a las compañías asociadas a PD WIRE & CABLE, a the areas of production, storage and labs.
los clientes y proveedores en la realización de cálculos,
pruebas y ensayos especiales, dotada con equipos
sofisticados de la más alta tecnología. Sus instalaciones se
encuentran ubicadas en Valencia, Edo. Carabobo, centro
industrial del país, sobre una extensión de 64.000 m2 en
las que se ubican las áreas de producción, laboratorios,
almacenes y vías perimetrales.
4
PARTE I
ALAMBRON Y ALAMBRES
DE ALUMINIO
Aluminum Rod and Wires
5
SECCION I
ALAMBRON DE ALUMINIO
Aluminum Rod
6
Alambrón de Aluminio
Aluminum Rod
ALAMBRON DE ALUMINIO Y ALUMINUM AND ALUMINUM
ALEACIONES DE ALUMINIO ALLOY ROD FOR ELECTRICAL
PARA USO ELECTRICO Y AND MECHANICAL
MECANICO. APPLICATION.
7
Alambrón de Aluminio
Aluminum Rod
Resistividad Conductividad
Carga de Rotura a 20ºC a 20ºC
Tensile Strength Resistivity Conductivity
(as-rolled) at 20ºC at 20ºC
8
Alambrón de Aluminio
Aluminum Rod
EMBALAJE Y TAMAÑOS NORMALES STANDARD FORMS AND PACKAGING
El despacho normal se realiza en rollos, con pesos y tamaños The standard method of shipping is in coils, with coil weights
según se indica en la siguiente tabla. El material del embalaje and sizes as indicated in the following table.
y su aplicación están diseñados para proteger el alambrón The packaging material and its application are designed to
contra daños bajo condiciones de un manejo y embarque protect the rod from damage under normal handling and
normales. shipping conditions.
9
SECCION II
ALAMBRES DE ALUMINIO
Aluminum Wires
10
Alambre de Atar
Tie Wire
APLICACION: El alambre de atar se utiliza para Application: The Tie Wire is used to join the
unir el conductor a los aisladores, conductor to the insulator. It can be
puede aplicarse en el conductor o applied over the conductor or over
sobre las varillas de armar. the armour rods.
6 4,11 90,7 36
4 5,18 145 57
2 6,55 235 91
11
Alambres de Aluminio
Aluminum Wires
C A R G A D E R O T U R A
R A T E D S T R E N G H T
Calibre Sección Diámetro Pe s o Resistencia corriente
Duro 3/4 Duro 1/2 Duro contínua a 20ºC
AWG
EC - H19 EC - H26 EC - H24
EC - H16 EC - H14
Size Section Diameter Weight Maximum
Hard 3/4 Hard 1/2 Hard Resistance at 20ºC
EC - H19 EC - H26 EC - H24
EC - H16 EC - H14
AWG mm2 mm kg/km kg kg kg ohms/km
12
PARTE II
CONDUCTORES DE
ALUMINIO DESNUDOS
Bare Aluminum Conductors
13
SECCION I
CABLES DE ALEACION
DE ALUMINIO 1350 (AAC)
All Aluminum Conductor (AAC)
14
CABLES DE ALEACION DE ALL ALUMINUM
ALUMINIO 1350 CONDUCTORS
El cable AAC es un conductor cableado concéntrico que se This bare concentric-lay stranded conductor is constructed with a
compone de una o de varias capas de alambres de aluminio straight round central wire surrounded by one or more layers of
1350, que puede ser suministrado con diversas clases de helically layed wires. These wires are of aluminum 1350 and can
cableado y de temple para atender mejor a los requisitos de be provided in different classes of stranding and tempers that fit
aplicación. best the requirements of the client.
Los cables de aluminio que aparecen en esta sección son The aluminum conductors that appear in this section are classified,
clasificados, de acuerdo con la clase de cableado, de la siguiente regarding the class of stranding, as follow:
manera: Class AA: For bare conductors usually used in overhead lines
Clase AA - Cables conductores desnudos utilizados normalmente Class A: For conductors to be covered with weather-resistant
para instalaciones aéreas. materials, and for bare conductors where greater flexibility than
Clase A - Cables conductores destinados a ser recubiertos con is afforded by Class AA is required.
materiales resistentes a las intemperies y cables conductores Next page is an illustration of the combinations of stranding of
desnudos para aplicaciones que exigen mayor flexibilidad que these conductors.
la que es proporcionada por los cables de clase AA.
A continuación, una ilustración de las combinaciones de cableado
y formación de los cables AAC.
15
Cables de Aleación de Aluminio 1350 AAC
All Aluminum Conductors AAC
Código Calibre Sección Nº de hilos Diámetro Peso total Carga de Resistencia corriente
x diámetro total rotura contínua a 20ºC
16
Cables de Aleación de Aluminio1350 AAC
All Aluminum Conductors AAC
Código Calibre Sección Nº de hilos Diámetro Peso total Carga de Resistencia corriente
x diámetro total rotura contínua a 20ºC
17
Cables de Aleación de Aluminio1350 AAC
All Aluminum Conductors AAC
NORMA ASTM B231M
Calibre Clase de No. de Diámetro de Diámetro del Masa Carga de Resistencia corriente
cableado hilos cada hilo conductor del cable rotura continua a 20 o C
18
Cables de Aluminio 1350 AAC
All Aluminum Conductors AAC
19
Cables de Aluminio Compactado 1350
Compact Aluminum Conductor AAC
Calibre Sección Nº de hilos Diámetro Diámetro Peso total Carga de Resistencia corriente
x diámetro total compactado rotura contínua a 20ºC
20
SECCION II
CABLES DE ALEACIÓN
DE ALUMINIO 6201 (AAAC)
All Aluminum Alloy Conductors 6201 (AAAC)
21
CABLES DE ALEACION DE ALUMINIO varilla, estas varillas se someten a un tratamiento térmico en
6201 solución y una vez trefilado el alambre se somete a un
envejecimiento artificial. El envejecimiento artificial y el
El Cable de Aleación de Aluminio es un conductor cableado tratamiento térmico son esenciales para obtener
concéntrico que se compone de una o de varias capas de óptimas propiedades mecánicas y eléctricas.
alambres de aleación de aluminio 6201-T81. Fue desarrollado FABRICACION DEL CABLE
para atender a las necesidades de un conductor económico para Se usan las mismas cableadoras que fabrican los cables de
aplicaciones en circuitos aéreos que requieren una resistencia aluminio. Las especificaciones del paso y cambio de dirección
mecánica mayor que la que es proporcionada por el conductor de las capas son aplicables a los cables de aleación de
de aluminio AAC, y mayor resistencia a la corrosión que la que aluminio. En las aleaciones se requiere una operación de
es proporcionada por el cable de aluminio con alma de acero conformación al cablear los alambres para asegurar máxima
ACSR. Los Conductores de Aleación de Aluminio 6201-T81 son estabilidad del cable y buenas características de manejo.
más duros y tienen, por lo tanto, mayor resistencia a la abrasión VENTAJAS QUE OFRECEN LOS CABLES AAC, AAAC
que los conductores de aluminio 1350-H19. Sin embargo, al Y ACAR
manipular los Conductores de Aleación de Aluminio hay que A. Permite el empleo de postes de construcción más ligera.
tomar las mismas precauciones que para manipular los B. Buena conductividad eléctrica.
conductores AAC y ACSR. C. Elevadas sobrecargas.
Las combinaciones de cableado de los cables de aleación de D. Bajas pérdidas de corona.
aluminio son muy semejantes a las de los cables AAC. E. Alta resistencia térmica.
En las tablas a continuación, presentamos varias características F. Resistente a las influencias atmosféricas.
normalizadas de los Cables de Aleación de Aluminio. G. Buen comportamiento a las variaciones de temperaturas.
Mayores informaciones son suministradas bajo consulta. H. Cables homogéneos con accesorios sencillos.
Los cables no se seleccionan como un rubro separado de una I. No presentan problemas electromagnéticos.
línea aérea, se seleccionan por consideraciones económicas que J. Los cables AAC, AAAC (6201) y ACAR pesan
implican el costo instalado de la línea, conjuntamente con los aproximadamente la mitad de un conductor de cobre de
requerimientos financieros relacionados con su operación, tales la misma conductividad.
como las pérdidas de energía, intereses sobre capital, DISEÑO DE LOS CONDUCTORES
depreciación. Para calcular todos los parámetros de los cables, se debe de
Los cables de aleación de aluminio tratados térmicamente no disponer de la siguiente información:
son cosa nueva. En el año 1925 ya estos cables se usaban en 1.- Diseño del cable mensajero (o cable portante) que sostiene
Europa para los sistemas aéreos de transmisión y distribución. el peso de los cables aislados, este diseño abarca:
Las aleaciones de magnesio han sido usadas por mucho tiempo a. El módulo de elasticidad.
con éxito, en planchas y como refuerzo en forma de cinta o b. El coeficiente de dilatación lineal.
alambre de cables aislados; también para refuerzos de cables c. El peso por metro total (kg/m).
submarinos y cables armados con aleación 6201. Puede decirse d.- El diámetro total.
que la aleación de aluminio ya tiene años de haber probado sus e.- La velocidad del viento en zona.
características en aplicaciones eléctricas. f.- Temperatura promedio diaria en la zona.
g.- Tipo de aleación.
FABRICACION DE LOS HILOS (ALAMBRES)
h.- Calibre del cable mensajero o cable portante.
La aleación de aluminio se trefila a partir del alambrón o
22
ALL ALUMINUM ALLOY CONDUCTORS
6201 (AAAC)
23
Cables de Aleación de Aluminio 6201 AAAC
All Aluminum Alloy Conductors 6201 AAAC
CALIBRES NORMALES
24
Cables de Aleación de Aluminio 6201 AAAC
All Aluminum Alloy Conductors 6201 AAAC
Código del Calibre del Sección Calibres y Cableados de los Nº de hilos por Diámetro Peso Carga de Resistencia
cable de cable de cables ACSR del mismo diámetro de Total Total Rotura corriente
aleación 6201 aleación 6201 diámetro que los de aleación cada hilo continua a 20ºC
Code of Size of 6201 Section Size Stranding Nº of Strands X Total Total Rated Maximum
6201 cable cable Diameter Diameter Weight Strenght Resistance at 20ºC
25
Cables de Aleación de Aluminio 6201 AAAC
All Aluminum Alloy Conductors 6201 AAAC
Normas DIN/IRAM
26
Cables de Aleación de Aluminio 6201 AAAC
All Aluminum Alloy Conductors 6201 AAAC
Normas IEC
mm 2 mm kg/km kg ohms/km
27
SECCION III
28
CABLES DE ALUMINIO REFORZADO ALUMINUM CONDUCTORS STEEL
CON ACERO REINFORCED (ACSR)
El cable ACSR es un conductor cableado concéntrico que se This bare concentric-lay-stranded conductor is made from round
compone de una o de varias capas de alambres de aluminio aluminum 1350-H19 (extra hard) wires and round zinc-coated or
1350 de temple duro (H19) y de un núcleo (alma) de acero aluminum-coated steel core wire(s) to be used as overhead
galvanizado de elevada resistencia mecánica. electrical conductors.
Según las dimensiones del cable, el alma puede ser formada por Depending on the dimensions of the conductor, the steel core can
un solo alambre de acero o por varios alambres de acero be made of one or more wires.
cableados. Thanks to the great number of combinations that can be made
Gracias a las innumerables combinaciones de alambres de between the wires of aluminum and the wires of steel, the
aluminio y de acero que son posibles, se puede variar las proportions can vary among them to obtain the best relation
proporciones entre los mismos de modo que se obtenga la mejor between the mechanical resistance and the current-carrying
relación entre capacidad de transporte de corriente eléctrica y capacity for each type of application.
resistencia mecánica para cada tipo de aplicación. El núcleo For a better protection in an atmosphere of extreme corrosion,
(alma) de acero puede ser suministrado con tres tipos de CONAL division recommends to use Class B or C galvanized
recubrimiento de galvanización: Clases A, B y C. Para una steel core (zinc-coated). It produces a small reduction on the total
protección mejor en ambientes de extrema corrosión, mechanical resistance when using these types of galvanization.
recomendamos la utilización de galvanización Clase B o C. CONAL division can produce special orders if desired.
Se produce una cierta reducción de la resistencia mecánica total Its not practical to show all the types of combinations and
cuando se utilizan estos tipos de galvanización. Las tablas que dimensions of the cables. The following tables presents the
presentamos a continuación muestran las dimensiones y los dimensions and stranding most used.
cableados más usuales. Podemos elaborar otros proyectos para
requisitos especiales. No es práctico, sin embargo, inscribir aquí
todas las combinaciones de cableado y dimensiones posibles.
Presentamos a continuación una ilustración de las combinaciones
de cableado y formación de los cables ACSR.
29
Cables de Aluminio Reforzado con Acero ACSR
Aluminum Conductors Steel Reinforced (ACSR)
*Wren 8 8,37 9,81 6 x 1,33 1 x 1,33 3,99 1,33 33,8 340 3,4017
Turkey 6 13,30 15,48 6 x 1,68 1 x 1,68 5,03 1,68 53,7 540 2,1135
Swan 4 21,15 24,71 6 x 2,12 1 x 2,12 6,35 2,12 85,4 846 1,3278
Swanate 4 21,15 26,52 7 x 1,96 1 x 2,61 6,53 2,61 99,7 1.067 1,3133
Sparrow 2 33,62 39,23 6 x 2,67 1 x 2,67 8,03 2,67 136 1.289 0,8343
Sparate 2 33,62 42,13 7 x 2,47 1 x 3,30 8,26 3,30 159 1.650 0,8251
Robin 1 42,41 49,48 6 x 3,00 1 x 3,00 9,02 3,00 171 1.612 0,6621
Raven 1/0 53,51 62,39 6 x 3,37 1 x 3,37 10,11 3,37 216 1.987 0,5243
Quail 2/0 67,44 78,65 6 x 3,78 1 x 3,78 11,35 3,78 273 2.401 0,4160
Pigeon 3/0 85,02 99,23 6 x 4,25 1 x 4,25 12,75 4,25 344 3.006 0,3304
Penguin 4/0 107 125 6 x 4,77 1 x 4,77 14,30 4,77 433 3.787 0,2618
*Owl 266,8 135 153 6 x 5,36 7 x 1,79 16,09 5,37 507 4.330 0,2109
Waxwing 266,8 135 143 18 x 3,09 1 x 3,09 15,47 3,09 431 3.117 0,2119
Partridge 266,8 135 157 26 x 2,57 7 x 2,00 16,31 5,98 547 5.113 0,2100
Ostrich 300 152 177 26 x 2,73 7 x 2,12 17,27 6,36 614 5.755 0,1867
*Piper 300 152 188 30 x 2,54 7 x 2,54 17,78 7,62 697 7.000 0,1902
Merlin 336,4 171 180 18 x 3,47 1 x 3,47 17,37 3,47 544 3.931 0,1680
Linnet 336,4 171 198 26 x 2,89 7 x 2,25 18,31 6,74 689 6.730 0,1663
Oriole 336,4 171 210 30 x 2,69 7 x 2,69 18,82 8,07 784 7.865 0,1654
Chickadee 397,5 201 213 18 x 3,77 1 x 3,77 18,87 3,77 642 4.499 0,1421
Ibis 397,5 201 234 26 x 3,14 7 x 2,44 19,89 7,32 814 7.488 0,1411
Lark 397,5 201 248 30 x 2,92 7 x 2,92 20,47 8,77 927 9.202 0,1401
Pelican 477 242 255 18 x 4,14 1 x 4,14 20,68 4,14 771 5.347 0,1184
Flicker 477 242 273 24 x 3,58 7 x 2,39 21,49 7,16 914 7.790 0,1178
Hawk 477 242 281 26 x 3,44 7 x 2,67 21,79 8,03 977 8.880 0,1171
Hen 477 242 298 30 x 3,20 7 x 3,20 22,43 9,61 1.112 10.783 0,1165
*Heron 500 253 312 30 x 3,28 7 x 3,28 22,96 9,84 1.162 11.090 0,1141
Osprey 556,5 282 298 18 x 4,47 1 x 4,47 22,33 4,47 899 6.233 0,1014
Parakeet 556,5 282 319 24 x 3,87 7 x 2,58 23,22 7,73 1.067 8.999 0,1010
Dove 556,5 282 328 26 x 3,72 7 x 2,89 23,55 8,66 1.140 10.019 0,1007
Eagle 556,5 282 348 30 x 3,46 7 x 3,46 24,21 10,39 1.298 12.606 0,1001
Peacock 605 307 346 24 x 4,03 7 x 2,69 24,21 8,03 1.161 9.771 0,0928
Squab 605 307 357 26 x 3,87 7 x 3,01 24,54 9,04 1.240 11.018 0,0925
Teal 605 307 376 30 x 3,61 19 x 2,16 25,25 10,82 1.398 13.567 0,0919
*Duck 605 307 346 54 x 2,69 7 x 2,69 24,21 8,07 1.158 10.210 0,0944
Kingbird 636 322 340 18 x 4,78 1 x 4,78 23,88 4,78 1.028 7.128 0,0895
Rook 636 322 364 24 x 4,14 7 x 2,76 24,82 8,28 1.219 10.298 0,0883
Grosbeak 636 322 375 26 x 3,97 7 x 3,09 25,15 9,27 1.302 11.427 0,0879
* No especificados por Normas ASTM.
30
Cables de Aluminio Reforzado con Acero ACSR
Aluminum Conductors Steel Reinforced (ACSR)
Egret 636 322 396 30 x 3,70 19 x 2,22 25,88 11,10 1.471 14.302 0,0876
*Goose 636 322 364 54 x 2,76 7 x 2,76 24,84 8,28 1.218 10.730 0,0898
Flamingo 666,6 338 382 24 x 4,23 7 x 2,82 25,40 8,46 1.278 10.751 0,0843
*Gull 666,6 338 382 54 x 2,82 7 x 2,82 25,38 8,46 1.276 11.140 0,0857
Starling 715,5 363 422 26 x 4,21 7 x 3,28 26,70 9,83 1.465 12.865 0,0781
Redwing 715,5 363 445 30 x 3,92 19 x 2,35 27,46 11,76 1.653 15.649 0,0778
*Crow 715,5 363 410 54 x 2,92 7 x 2,92 26,28 8,76 1.370 11.950 0,0787
Cuckoo 795 403 455 24 x 4,62 7 x 3,08 27,74 9,25 1.524 12.649 0,0719
Drake 795 403 468 26 x 4,44 7 x 3,45 28,14 10,36 1.628 14.359 0,0705
Mallard 795 403 495 30 x 4,14 19 x 2,48 28,96 12,42 1.838 18.390 0,0699
Tern 795 403 431 45 x 3,38 7 x 2,25 27,00 6,76 1.333 10.027 0,0712
Condor 795 403 455 54 x 3,08 7 x 3,08 27,76 9,25 1.524 12.770 0,0705
*Crane 874,5 443 501 54 x 3,23 7 x 3,23 29,11 9,69 1.674 14.245 0,0643
Canary 900 456 515 54 x 3,28 7 x 3,28 29,51 9,83 1.725 14.483 0,0623
Rail 954 483 517 45 x 3,70 7 x 2,47 29,59 7,39 1.600 11.771 0,0594
Cardinal 954 483 546 54 x 3,38 7 x 3,38 30,38 10,13 1.829 16.323 0,0591
Ortolan 1.033,5 524 560 45 x 3,85 7 x 2,57 30,81 7,70 1.734 12.577 0,0548
Curlew 1.033,5 524 592 54 x 3,51 7 x 3,51 31,65 10,54 1.981 16.680 0,0545
Bluejay 1.113 564 603 45 x 4,00 7 x 2,66 31,98 8,00 1.867 13.540 0,0509
Finch 1.113 564 635 54 x 3,65 19 x 2,19 32,84 10,95 2.129 17.746 0,0509
Bunting 1.192,5 604 646 45 x 4,14 7 x 2,76 33,07 8,28 2.000 14.530 0,0476
Grackle 1.192,5 604 681 54 x 3,77 19 x 2,27 33,99 11,33 2.281 18.999 0,0472
Bittern 1.272 645 689 45 x 4,27 7 x 2,85 34,16 8,53 2.134 15.470 0,0446
Pheasant 1.272 645 726 54 x 3,90 19 x 2,34 35,10 11,71 2.433 19.788 0,0443
Dipper 1.351,5 685 732 45 x 4,40 7 x 2,93 35,20 8,81 2.265 16.359 0,0420
Martin 1.351,5 685 772 54 x 4,02 19 x 2,41 36,17 12,07 2.585 21.007 0,0417
Bobolink 1.431 725 775 45 x 4,53 7 x 3,02 36,25 9,07 2.400 17.396 0,0397
Plover 1.431 725 817 54 x 4,14 19 x 2,48 37,21 12,42 2.738 22.262 0,0394
Nuthatch 1.510,5 765 818 45 x 4,65 7 x 3,10 37,24 9,30 2.533 18.152 0,0374
Parrot 1.510,5 765 863 54 x 4,25 19 x 2,55 38,25 12,75 2.890 23.499 0,0374
Lapwing 1.590 806 861 45 x 4,77 7 x 3,18 38,15 9,55 2.667 19,101 0,0358
Falcon 1.590 806 908 54 x 4,36 19 x 2,62 39,24 13,08 3.041 24.769 0,0354
*Chukar 1.780 902 975 84 x 3,70 19 x 2,22 40,69 11,10 3.086 23.291 0,0318
*Bluebird 2.156 1.092 1.181 84 x 4,07 19 x 2,44 44,75 12,22 3.736 27.526 0,0262
*Kiwi 2.167 1.098 1.146 72 x 4,41 7 x 2,94 44,12 8,81 3.427 22.819 0,0263
* No especificados por Normas ASTM.
31
Cables de Aluminio Reforzado con Acero ACSR
Aluminum Conductors Steel Reinforced (ACSR)
EXTRA RESISTENTE
EXTRA RESISTANT
*Bantan 13,125 6,65 15,48 3 x 1,68 4 x 1,68 5,03 __ 87,8 1.190 4,305
*Magpie 20,87 10,57 24,71 3 x 2,12 4 x 2,12 6,35 __ 140 1.895 2,707
*Shrike 33,185 16,81 39,29 3 x 2,67 4 x 2,67 8,03 __ 222 2.910 1,703
*Snipe 52,77 26,73 62,39 3 x 3,37 4 x 3,37 10,11 __ 354 4.480 1,071
*Loon 66,54 33,72 78,71 3 x 3,79 4 x 3,79 11,35 __ 446 5.640 0,849
Grouse 80 40,52 54,65 8 x 2,54 1 x 4,24 9,32 4,24 222 2.359 0,6798
Petrel 96,9 51,6 81,68 12 x 2,34 7 x 2,34 11,70 7,02 378 4.703 0,5217
Minorca 110,8 56,1 88,90 12 x 2,44 7 x 2,44 12,22 7,32 412 5.106 0,4792
Leghorn 134,6 68,2 108,00 12 x 2,69 7 x 2,69 13,46 8,07 500 6.167 0,3947
Guinea 159 80,5 127,55 12 x 2,92 7 x 2,92 14,63 8,77 590 7.239 0,3340
Dotterel 176,9 89,6 141,94 12 x 3,08 7 x 3,08 15,42 9,25 657 7.847 0,3002
Dorking 190,8 96,7 153,10 12 x 3,20 7 x 3,20 16,03 9,61 709 8.467 0,2782
*Auk 203 102,8 130,60 8 x 4,05 7 x 2,25 14,83 6,74 499 5.060 0,2789
Brahma 203,2 102,8 194,84 16 x 2,86 19 x 2,48 18,14 12,41 1.007 12.814 0,2520
Cochin 211,3 107 169,55 12 x 3,37 7 x 3,37 16,84 10,11 785 9.393 0,2513
32
CONDUCTORES DE ALUMINIO ALUMINUM CONDUCTORS,
REFORZADOS CON ACERO ALUMINUM-CLAD STEEL REINFORCED,
ALUMINIZADO (ACSR/AW) BARE (ACSR/AW)
Se usa en líneas aéreas de transmisión y distribución. Tiene Used as bare overhead transmission cable and as primary
un comportamiento mecánico y eléctrico similar al ACSR. and secondary distribution cable. ACSR/AW offers the same
Es recomendado para usos de alta corrosión. strength characteristics as ACSR, along with slightly greater
ampacity and resistance to corrosion due to the aluminum
cladding of the steel core wires. It provides greater protection
where corrosive condition are severe.
Diámetro Carga
Código C a l i b r e Formación AC @ C a p a c i d a d
Peso por 1000 pies de Resistencia
Alambre Indiv. Aw Completo 75ºC de
Rotura
Corriente
Code Word Size Stranding Diameter (inches)
Rated Resistance AC @
Weight Per 1000 ft Current Rating
Indiv. Wires Aw Complete Strenght DC@ 20ºC 75ºC
(lbs)
AWG
Al/Stl Al Aw Core Al Aw lbs ohms/1000ft amps
or MCM
Cable Total
Swan/AW 46/1 .0834 .0834 .0834 .250 39.0 15.6 54.6 1,780 .3917 .4770 145
Swanate/AW 47/1 .0772 .1029 .1029 .257 39.0 23.8 62.7 2,280 .3814 .4642 148
Sparrow/AW 26/1 .1052 .1052 .1052 .316 62.0 24.8 86.9 2,760 .2462 .2997 194
Sparate/AW 27/1 .0974 .1299 .1299 .325 62.0 37.9 99.9 3,510 .2396 .2917 198
Robin/AW 16/1 .1181 .1181 .1181 .354 78.2 31.3 109.5 3,450 .1950 .2373 225
Raven/AW 1/06/1 .1327 .1327 .1327 .398 98.7 39.5 138.2 4,250 .1547 .1884 260
Quail/AW 2/0 6/1 .1489 .1489 .1489 .447 124.3 49.7 174.0 5,130 .1227 .1494 301
Pigeon/AW 3/0 6/1 .1672 .1672 .1672 .502 156.7 62.7 219.4 6,300 .09747 .1188 347
Penguin/AW 4/0 6/1 .1878 .1878 .1878 .563 197.7 79.1 276.8 7,690 .07726 .09422 402
Waxwing/AW 266.8 18/1 .1217 .1217 .1217 .609 250.3 33.2 283.5 6,820 0.6364 .07776 451
Partridge/AW 266.8 26/7 .1013 .0788 .2364 .642 251.7 97.9 349.6 10,800 .06169 .07541 465
Ostrich/AW 300.0 26/7 .1074 .0835 .2505 .680 282.9 110.0 392.9 12,100 0.5489 .06712 500
Merlin/AW 336.4 18/1 .1367 .1367 .1367 .684 315.8 41.9 357.7 8,540 .05044 .06175 522
Linnet/AW 336.4 26/7 .1137 .0884 .2652 .720 317.1 123.2 440.3 13,500 .04897 .05989 537
Oriole/AW 336.4 30/7 .1059 .1059 .3177 .741 318.2 177.0 495.2 16,700 .04795 .05861 547
Chickadee/AW 397.5 18/1 .1486 .1486 .1486 .743 373.1 49.5 422.6 9,780 .04268 .05230 580
Brant/AW 397.5 24/7 .1287 .0858 .2574 .772 375.0 116.1 491.1 14,100 .04185 .05124 592
Ibis/AW 397.5 26/7 .1236 .961 .2883 .783 374.7 145.6 520.3 15,800 .04144 .05072 597
Lark/AW 397.5 30/7 .1151 .1151 .3453 .806 375.8 209.1 585.0 19,600 .04059 .04965 608
Pelican/AW 477.0 18/1 .1628 .1628 .1682 .814 447.8 59.5 507.3 11,500 .03556 .04344 651
Flicker/AW 477.0 24/7 .1410 .0940 .2820 .846 450.1 139.4 589.5 16,700 .03487 .04273 663
Hawk/AW 477.0 26/7 .1354 .1053 .3159 .858 449.6 174.9 624.5 18,900 .03453 .04231 669
33
ACSR/AW
Diámetro Carga
Código C a l i b r e Formación AC @ C a p a c i d a d
Alambre Indiv. Aw Completo Peso por 1000 pies de Resistencia
75ºC de
Rotura
Corriente
Code Word Size Stranding Diameter (inches)
Rated Resistance AC @
Weight Per 1000 ft Current Rating
Indiv. Wires Aw Complete Strenght DC@ 20ºC 75ºC
AWG
Al/Stl Al Aw Core (lbs) lbs ohms/1000ft amps
or MCM
Cable Al Aw To t a l
Hen/AW 477.0 30/7 .1261 .3783 .883 .883 451.1 251.0 702.1 23,400 .03382 .04139 682
Osprey/AW 556.5 18/1 .1758 .1758 .1758 .879 522.2 69.4 591.6 13,200 .03050 .03749 715
Parakeet/AW 556.5 24/7 .1523 .1015 .3045 .914 525.1 162.5 687.6 19,300 .02989 .03667 731
Dove/AW 556.5 26/7 .1463 .1138 .3414 .927 525.0 204.2 729.2 21,900 .02958 .03627 737
Eagle/AW 556.5 30/7 .1362 .1362 .4086 .953 526.3 292.8 819.1 26,800 .02899 .03551 751
Peacock/AW 605.0 24/7 .1588 .1059 .3177 .953 570.9 176.9 747.8 21,000 .02749 .03377 770
Squab/AW 605.0 26/7 .1525 .1186 .3558 .966 570.4 221.8 792.2 23,600 .02588 .03341 777
Teal/AW 605.0 30/19 .1420 .0852 .4260 .994 572.0 311.4 883.4 28,500 .02672 .03274 791
Kingbird/AW 636.0 18/1 .1880 .1880 .1880 .940 597.2 79.3 676.5 15,000 .02667 .03286 778
Rook/AW 636.0 24/7 .1628 .1085 .3255 .977 600.0 185.7 785.7 22,000 .02616 .03216 794
Grosbeak/AW 636.0 26/7 .1564 .1216 .3648 .990 599.5 233.2 833.1 24,800 .02588 .03179 801
Egret/AW 636.0 30/19 .1456 .0874 .4370 1.019 601.4 327.6 929.0 29,900 .02541 .03118 815
Flamingo/AW 666.6 24/7 .1667 .1111 .3333 1.000 629.1 194.7 826.8 23,100 .02495 .03069 818
Gannet/AW 666.6 26/7 .1601 .1245 .3735 1.014 628.7 244.5 873.1 26,00 .02471 .03034 825
Starling/AW 715.5 26/7 .1659 .1290 .3870 .1051 675.0 262.4 937.5 27,500 .02300 .02830 863
Redwing/AW 715.5 30/19 .1544 .0926 .4630 1.081 676.3 367.8 1044 33,400 .02260 0.2777 878
Cuckoo/AW 795.0 24/7 .1820 .1213 .3639 1.092 749.9 232.0 982.0 27,500 .02093 .02582 913
Drake/AW 795.0 26/7 .1749 .1360 .4080 1.108 750.3 291.7 1042 30,500 .02070 .02549 922
Tem/AW 795.0 45/7 .1329 .0886 .2658 1.063 749.8 123.8 873.6 21,500 .02135 .02638 896
Condor/AW 795.0 54/7 .1213 .1213 .3639 1.092 749.5 231.8 981.3 27,800 .02091 .02578 913
Mallard/AW 795.0 30/19 .1628 .0977 .4885 1.140 751.9 409.4 1161 37,100 .02033 .02500 938
Ruddy/AW 900.0 45/7 .1414 .0943 .2829 1.131 848.7 140.2 989.0 24,000 0.1886 0.2330 970
Canary/AW 900.0 54/7 .1291 .1291 .3873 1.162 849.0 262.6 1112 31,000 .01849 .02286 986
Rail/AW 954.0 45/7 .1456 .0971 .2913 1.165 899.9 148.7 1049 25,400 .01779 .02210 1003
Cardinal/AW 954.0 54/7 .1329 .1329 .3987 1.196 899.7 278.3 1178 32,900 0.1744 .02161 1022
Ortolan/AW 1033.5 45/7 .1515 .1010 .3030 1.212 974.3 160.9 1135 27,200 0.1641 .02044 1054
Curlew/AW 1033.5 54/7 .1383 .1383 .4149 1.245 974.3 301.3 1276 35,200 0.1609 .01997 1074
Bluejay/AW 1113.0 45/7 .1573 .1049 .3147 1.259 1050 173.5 1224 29,300 0.1606 .01905 1103
Finch/AW 1113.0 54/19 .1436 .0862 .4310 1.293 1056 318.7 1374 37,500 0.1503 .01870 1121
Bunting/AW 1192.5 45/7 .1628 .1085 .3255 1.302 1125 185.7 1311 31,300 0.1423 0.1784 1150
Grackle/AW 1192.5 54/19 .1486 .0892 .4460 1.338 1130 341.3 1472 40,200 0.1403 .01751 1168
Bittern/AW 1272.0 45/7 .1681 .1121 .3363 1.345 1200 198.2 1398 33,400 0.1335 .01679 1196
Pheasant/AW 1272.0 54/19 .1535 .0921 .4605 1.382 1206 363.8 1570 42,400 0.1315 .01646 1216
34
ACSR/TW ACSR/TW
Los conductores ACSR/TW son un resultado de la tecnología ACSR/TW is an outgrowth of the technology developed in the
desarrollada del conductor Self Damping ACSR/SD. El conductor manufacture of self-damping conductor, ACSR/SD. The conductor
provee la misma sección del conductor pero con un diámetro provides the same conductor are with a reduced diameter,
reducido, en comparación con el diseño tradicional de compared with more traditional "round strand" ACSR designs.
conductores ACSR. The smaller diameter, depending on and wind loading, may
Por tener un diámetro más pequeño, la carga del viento es menor, reduce cost; ligther or fewer structures are needed for installation.
por esta razón, permite reducir costos y utilizar menor cantidad
de estructuras o que las mismas sean más livianas.
Merlin/Tw 336.4 0.2642 0.2788 6 14 1x0.1367 0.630 0.1367 365.0 315.5 49.5 8,560
Flicker/TW 477.0 0.3747 0.4233 13 18 7x0.0940 0.776 0.2820 612.8 448.4 164.4 17,200
Hawk/TW 477.0 0.3746 0.4356 16 18 7x0.1053 0.789 0.3159 655.0 448.7 206.3 19,400
Parakeet/TW 556.5 0.4371 0.4937 13 18 7x0.1015 0.835 0.3045 714.9 523.2 191.7 20,000
Dove/TW 556.5 0.4371 0.5083 16 20 7x0.1138 0.852 0.3414 764.5 523.5 241.0 22,600
Swift/TW 636.0 0.4995 0.5133 3 27 1x0.1329 0.850 0.1329 646.0 599.2 46.8 13,500
Rook/TW 636.0 0.4995 0.5643 13 19 7x0.1085 0.890 0.3255 816.0 597.9 219.1 22,900
Grosbeak/Tw 636.0 0.4995 0.5808 16 20 7x0.1216 0.908 0.3648 873.5 598.4 275.1 25,400
Tern/TW 795.0 0.6244 0.6675 7 17 7x0.0886 0.960 0.2658 892.0 745.9 146.1 21,000
Puffin/TW 795.0 0.6244 0.6919 10 18 7x0.1108 0.980 0.3324 975.3 746.9 228.4 25,900
Condor/TW 795.0 0.6244 0.7053 13 20 7x0.1203 0.993 0.3639 1021 747.2 273.8 28,200
Drake/TW 795.0 0.6244 0.7261 16 20 7x0.1360 1.010 0.4080 1092 747.8 344.2 13,800
Phoenix/TW 954.0 0.7493 0.7876 5 30 7x0.0837 1.044 0.2511 1032 901.6 130.4 23,700
Rail/TW 954.0 0.7493 0.8011 7 32 7x0.0971 1.061 0.2913 1075 900.0 175.0 25,900
Cardinal/TW 954.0 0.7493 0.8464 13 20 7x0.1329 1.084 0.3987 1226 897.3 328.7 33,500
Snowbird/TW 1033.5 0.8117 0.8564 5 30 7x0.0871 1.089 0.2613 1115 973.8 141.2 25,700
Ortolan/TW 1033.5 0.8117 0.8678 7 32 7x0.1010 1.102 0.3030 1165 975.2 189.8 28,100
Curlew/TW 1033.5 0.8117 0.9169 13 22 7x0.1383 1.129 0.4149 1327 971.1 355.9 36,300
Avocet/TW 1113.0 0.8742 0.9191 5 30 7x0.0904 1.129 0.2712 1201 1048.9 152.1 27,500
35
ACSR/TW
Bluejay/TW 1113.0 0.8742 0.9347 7 33 7x0.1049 1.143 0.3147 1257 1052.2 204.8 30,300
Finch/TW 1113.0 0.8742 0.9851 13 38 19x0.0862 1.185 0.4310 1429 1052.6 376.4 39,100
Oxbird/TW 1192.5 0.9366 0.9848 5 30 7x0.0936 1.167 0.2808 1286 1123 163 29,500
Bunting/TW 1192.5 0.9366 1.0013 7 33 7x0.1085 1.181 0.3255 1343 1124 219 32,400
Grackle/TW 1192.0 0.9366 1.0554 13 38 19x0.0892 1.225 0.4460 1530 1127 403 41,900
Scissortail/TW 1272.0 0.9991 1.0505 5 30 7x0.0967 1.203 0.2901 1372 1198 174 31,400
Bittern/TW 1272.0 0.9990 1.0681 7 35 7x0.1121 1.220 0.3363 1433 1199 234 34,600
Pheasant/TW 1272.0 0.9990 1.1256 13 39 19x0.9210 1.264 0.4605 1632 1202 430 44,100
Dipper/Tw 1351.5 1.0615 1.1348 7 35 7x0.1155 1.256 0.3465 1522 1274 248 36,700
Martin/TW 1351.5 1.0615 1.1959 13 39 19x0.0949 1.300 0.4745 1734 1278 456 46,800
Bobolink/TW 1431.0 1.1236 1.2017 7 36 7x0.1189 1.291 0.3567 1613 1350 263 38,900
Plover/TW 1431.0 1.1239 1.2664 13 37 19x0.0977 1.337 0.4885 1836 1353 483 49,600
Lapwing/TW 1590.0 1.2488 1.3351 7 36 7x0.1253 1.358 0.3759 1791 1499 292 42,200
Falcon/TW 1590.0 1.2488 1.4071 13 42 19x0.1030 1.408 0.5150 2040 1503 537 55,100
Chukar/TW 1780.0 1.3986 1.512 8 37 19x0.0874 1.445 0.4370 2063 1676 387 50,700
Bluebird/TW 2156.0 1.0934 1.8312 8 64 19x0.0961 1.608 0.4805 2515 2047 468 61,100
Merlin/Tw 336.4 6 14/1 2 0.2654 0.2715 0.2986 0.3258 0.0200 0.475 0.1079
Flicker/TW 477.0 13 18/7 2 0.1860 0.1904 0.2094 0..2284 0.0257 0.444 0.1017
Hawk/TW 477.0 16 18/7 2 0.1854 0.1878 0.2087 0.2277 0.0264 0.441 0.1013
Parakeet/TW 556.5 13 18/7 2 0.1593 0.1633 0.1796 0.1959 0.0277 0.435 0.0994
Dove/TW 556.5 16 20/7 2 0.1588 0.1628 0.1790 0.1953 0.0286 0.431 0.0991
Swift/TW 636.0 3 27/1 3 0.1416 0.1461 0.1605 0.1748 0.0273 0.437 0.0991
Rook/TW 636.0 13 18/7 2 0.1395 0.1432 0.1574 0.1717 0.0296 0.427 0.0978
Grosbeak/Tw 636.0 16 20/7 2 0.1390 0.1426 0.1568 0.1710 0.0305 0.423 0.0971
Tern/TW 795.0 7 17/7 2 0.1123 0.1160 0.1274 0.1388 0.0312 0.4209 0.0955
Puffin/TW 795.0 10 18/7 2 0.1118 0.1152 0.1266 0.1380 0.0323 0.4165 0.0949
Condor/TW 795.0 13 20/7 2 0.1113 0.1147 0.1260 0.1373 0.0331 0.4137 0.0945
Drake/TW 795.0 16 20/7 2 0.1111 0.1144 0.1257 0.1370 0.0339 0.4105 0.0940
Phoenix/TW 954.0 5 30/7 3 0.0942 0.0982 0.1077 0.1172 0.0343 0.4094 0.0928
Rail/TW 954.0 7 32/7 3 0.0940 0.0979 0.1073 0.1160 0.0349 0.407 0.0925
Cardinal/TW 954.0 13 20/7 2 0.0931 0.0962 0.1056 0.1151 0.0362 0.403 0.0919
Snowbird/TW 1033.5 5 30/7 3 0.0868 0.0908 0.0995 0.1083 0.0356 0.405 0.0917
Ortolan/TW 1033.5 7 32/7 3 0.0867 0.0906 0.0993 0.1081 0.0363 0.402 0.0914
Curlew/TW 1033.5 13 21/7 2 0.0859 0.0389 0.0976 0.1063 0.0377 0.398 0.0906
Avocet/TW 1113.0 5 30/7 3 0.0807 0.0847 0.0928 0.1009 0.0369 0.400 0.0906
36
ACSR/TW
Bluejay/TW 1113.0 7 33/7 3 0.0805 0.0845 0.0925 0.1005 0.0376 0.398 0.0903
Finch/TW 1113.0 13 38/19 3 0.0802 0.0837 0.0917 0.0998 0.0399 0.391 0.0891
Oxbird/TW 1192.5 5 30/7 3 0.0753 0.0794 0.0869 0.0945 0.0382 0.396 0.0896
Bunting/TW 1192.5 7 33/7 3 0.0752 0.0791 0.0866 0.0941 0.0390 0.394 0.0893
Grackle/TW 1192.5 13 38/19 3 0.0749 0.0783 0.0859 0.0934 0.0412 0.387 0.0883
Scissortail/TW 1272.0 5 30/7 3 0.0706 0.0747 0.0817 0.0889 0.0394 0.392 0.0888
Bittern/TW 1272.0 7 35/7 3 0.0705 0.0745 0.0815 0.0885 0.0403 0.390 0.0884
Pheasant/TW 1272.0 13 39/19 3 0.0701 0.0736 0.0806 0.0876 0.0426 0.383 0.0874
Dipper/Tw 1351.5 7 25/7 3 0.0664 0.0704 0.0769 0.0836 0.0415 0.386 0.0874
Martin/TW 1351.5 13 39/19 3 0.0659 0.0694 0.0760 0.0826 0.0438 0.377 0.0865
Bobolink/TW 1431.0 7 36/7 3 0.0627 0.0668 0.0730 0.0792 0.0427 0.383 0.0867
Plover/TW 1431.0 13 39/19 3 0.0624 0.0659 0.0721 0.0784 0.0451 0.376 0.0860
Lapwing/TW 1590.0 7 36/7 3 0.0564 0.0606 0.0661 0.0717 0.0449 0.377 0.0851
Falcon/TW 1590.0 13 42/19 3 0.0561 0.0598 0.0653 0.0709 0.0476 0.370 0.0841
Chukar/TW 1780.0 8 37/19 3 0.0503 0.0545 0.0594 0.0644 0.0482 0.368 0.0832
Bluebird/TW 2156.0 8 64/19 4 0.0415 0.0465 0.0504 0.0544 0.0538 0.355 0.0801
Tipo Cableado Diámetro Exterior Peso por 1000 pies Carga de Tamaño y
Código Calibre
No Stranding Outsider Diameter Weight per 1000 ft. Rotura Cableado
Area en Pulg. de ACSR con igual
Code Word kcmil Cuadradas Diámetro Size & dStranding
i á m e t rofo ACSR
Type Aluminio Acero Total del Núcleo Total Aluminio lb Acero lb Rated with equal diameter
Area Square Inches
No Aluminum Steel
Complete de Acero Total Aluminum lb Steel lb Strenght lb
Aluminio Total Conductor in.
Steel Core in.
kcmil Cableado
Aluminum Total
Monogahela/TW 405.1 0.3181 0.3362 6 14 1x.1520 0.680 0.1520 441.0 379.8 61.2 10,200 336.4 18/1
Mohawk/TW 571.7 0.4490 0.5074 13 18 7x.1030 0.846 0.3090 734.7 537.3 197.4 20,700 477.0 24/7
Calumet/TW 565.3 0.4439 0.5165 16 18 7x.1147 0.858 0.3438 714.8 523.1 191.7 22,900 477.0 26/7
Mystic/TW 666.6 0.5236 0.5914 13 20 7x.1111 0.913 0.3330 856.3 626.6 229.7 24,00 556.5 24/7
Oswego/TW 664.8 0.5221 0.6072 16 20 7x.1244 0.927 0.3732 913.4 625.4 288.0 26,600 556.5 26/7
Nechako/TW 768.9 0.6039 0.6220 3 27 1x.1520 0.980 0.1520 781.9 720.7 61.2 16,400 636.0 36/1
Maumee/TW 768.2 0.6034 0.6819 13 20 7x.1195 0.977 0.3585 987.8 722.1 265.7 27,700 636.0 24/7
Wabash/TW 762.8 0.5992 0.6966 16 20 7x.1331 0.990 0.3343 1047 717 330 30,500 636.0 26/7
Kettle/TW 957.2 0.7518 0.8038 7 32 7x.0973 1.060 0.2919 1079 902.8 176.2 26,000 795.0 45/7
Fraser/TW 946.7 0.7436 0.8168 10 35 7x.1154 1.077 0.3462 1142 894 248 29,600 795.0 22/7
Columbia/TW 966.2 0.7589 0.8573 13 21 7x.1338 1.092 0.4014 1241 908 333 34,000 795.0 54/7
Suwannee/TW 959.6 0.7537 0.8762 16 22 7x.1493 1.108 0.4479 1318 903 415 37,000 795.0 26/7
Cheyenne/TW 1168.1 0.9175 0.9646 5 30 7x.0926 1.155 0.2778 1260 1100.4 159.6 28,900 954.0 42/7
Genesse/TW 1158.0 0.9095 0.9733 7 33 7x.1078 1.165 0.3234 1308 1092 216 31,600 954.0 45/7
Hudson/TW 1158.4 0.9098 1.0281 13 26 7x.1467 1.196 0.4401 1489 1089 400 39,600 954.0 54/7
Catawba/TW 1272.0 0.9991 1.0505 5 30 7x.0967 1.203 0.2901 1372 1198 174 31,400 1033.5 42/7
Nelson/TW 1257.1 0.9874 1.0557 7 35 7x.115 1.213 0.3345 1417 1185.7 231.3 34,200 1033.5 45/7
Yukon/TW 1233.6 0.9689 1.0925 13 38 19x.0910 1.245 0.455 1586 1166.5 419.5 42,900 1033.5 54/7
Truckee/TW 1372.5 1.078 1.1334 5 30 7x.1004 1.248 0.3012 1481 1293.4 187.6 33,400 1113.0 42/7
37
ACSR/TW
Tipo Cableado Diámetro Exterior Peso por 1000 pies Carga de Tamaño y
Código Calibre
No Stranding Outsider Diameter Weight per 1000 ft. Rotura Cableado
Area en Pulg. de ACSR con igual
Code Word kcmil Cuadradas Diámetro Size & dStranding
i á m e t rofo ACSR
Type Aluminio Acero Total del Núcleo Total Aluminio lb Acero lb Rated with equal diameter
Area Square Inches
No Aluminum Steel
Complete de Acero Total Aluminum lb Steel lb Strenght lb
Aluminio Total Conductor in.
kcmil Cableado
Steel Core in.
Aluminum Total
Mackenzie/TW 1359.7 1.0679 1.1418 7 36 7x.1159 1.259 0.3477 1530 1280 250.0 36,900 1113.0 45/7
Thames/TW 1334.6 1.348 1.1809 13 39 19x.0944 1.290 0.4720 1713 1261.6 451.4 46,300 1113.0 54/19
St. Croix/TW 1467.8 1.1529 1.2124 5 33 7x.1041 1.292 0.3123 1585 1383 202 35,800 1192.5 42/7
Miramichi/TW 1455.3 1.1430 1.2222 7 36 7x.1200 1.302 0.3600 1640 1372 268 39,200 1192.5 45/7
Merrimack/TW 1433.6 1.125 1.2677 13 39 19x.0978 1.340 0.489 1840 1356 434 49,700 1192.5 54/19
Platte/TW 1569.0 1.2323 1.2957 5 33 7x.1074 1.334 0.3222 1693 1478 215 38,200 1272.0 42/7
Potomac/TW 1557.4 1.2232 1.3079 7 36 7x.1241 1.345 0.3723 1755 1468 287 41,900 1272.0 45/7
Rio Grande/TW 1533.3 1.2043 1.3571 13 39 19x.1012 1.382 0.5060 1968 1449 519 53,200 1272.0 54/1
Schuylkill/TW 1657.4 1.3020 0.3920 7 36 7x.1280 1.386 0.3840 1868 1563 305 44,000 1351.5 45/7
Pecos/TW 1622.0 1.2739 1.4429 13 39 19x.1064 1.424 0.5320 2107 1533 574 57,500 1351.5 54/19
Pee Dee/TW 1758.6 1.3810 1.4770 7 37 7x.1319 1.427 0.3957 1982 1658 324 46,700 1431.0 45/7
James/TW 1730.6 1.359 1.5314 13 34 19x.1075 1.470 0.5375 2221 1636 585 59,400 1431.0 54/19
Athabacka/TW 1949.6 1.5312 1.6377 7 42 7x.1392 1.504 0.4176 2199 1838 361 51,900 1590.0 45/7
Cumberland/TW 1926.9 1.5134 1.7049 13 42 19x.1133 1.545 0.5665 2471 1821 650 65,300 1590.0 54/19
Powder/TW 2153.8 1.6912 1.8290 8 64 19x.0961 1.602 0.4805 2498 2030 468 61,100 1780.0 84/19
Santee/TW 2627.3 2.063 2.2268 8 64 19x.1062 1.762 0.5310 3048 2477 571 74,500 2156.0 84/19
Monogahela/TW 405.1 6 14/1 2 0.2205 0.2258 0.2483 0.2709 0.0218 0.464 0.1097
Mohawk/TW 571.7 13 18/7 2 0.1550 0.1590 0.1748 0.1907 0.0281 0.433 0.0991
Calumet/TW 565.3 16 20/7 2 0.1564 0.1603 0.1763 0.1923 0.0288 0.430 0.0988
Mystic/TW 666.6 13 20/7 2 0.1331 0.1367 0.1503 0.1638 0.0304 0.424 0.0970
Oswego/TW 664.8 16 20/7 2 0.1329 0.1364 0.1500 0.1635 0.0310 0.421 0.0964
Nechako/TW 768.9 3 27/1 3 0.1171 0.1214 0.1332 0.1451 0.0300 0.425 0.0965
Maumee/TW 768.2 13 20/7 2 0.1155 0.1189 0.1306 0.1424 0.0325 0.416 0.0949
Wabash/TW 762.8 16 20/7 2 0.1159 0.1191 0.1309 0.1428 0.0330 0.413 0.0946
Kettle/TW 957.2 7 32/7 3 0.0938 0.0976 0.1071 0.1166 0.0350 0.407 0.0925
Fraser/TW 946.7 10 35/7 3 0.0945 0.0982 0.1077 0.1173 0.0358 0.404 0.0919
Columbia/TW 966.2 13 21/7 2 0.0918 0.0949 0.1042 0.1136 0.0364 0.402 0.0917
Suwannee/TW 959.6 16 22/7 2 0.0922 0.0951 0.1045 0.1138 0.0373 0.399 0.0913
Cheyenne/TW 1168.1 5 30/7 3 0.0769 0.0810 0.0886 0.0963 0.0378 0.397 0.0901
Genesse/TW 1158.0 7 33/7 3 0.0774 0.0813 0.0891 0.0968 0.0384 0.395 0.0897
Hudson/TW 1158.4 13 25/7 2 0.0764 0.0794 0.0871 0.0948 0.0400 0.391 0.0889
Catawba/TW 1272.0 5 30/7 3 0.0706 0.0747 0.0817 0.0888 0.0394 0.392 0.0889
Nelson/TW 1257.1 7 35/7 3 0.0713 0.0753 0.0824 0.0895 0.0400 0.390 0.0886
Yukon/TW 1233.6 13 38/19 3 0.0723 0.0758 0.0830 0.0903 0.0420 0.385 0.0877
Truckee/TW 1372.5 5 30/7 3 0.0654 0.0697 0.0761 0.0826 0.0409 0.388 0.0877
38
ACSR/TW
39
SECCION IV
CABLES DE ALUMINIO
REFORZADOS CON ALEACIÓN
DE ALUMINIO 6201 (ACAR)
Aluminum Conductor Alloy Reinforced (ACAR)
40
CABLES DE ALUMINIO REFORZADOS VENTAJAS QUE OFRECEN LOS CABLES AAC,
CON ALEACION DE ALUMINIO AAAC Y ACAR
ACAR A. Permite el empleo de postes de construcción más ligera.
B. Buena conductividad eléctrica.
El cable ACAR es un conductor de cableado concéntrico que se C. Elevadas sobrecargas.
compone de alambres 1350-H19, reforzados por un núcleo D. Bajas pérdidas de corona.
(alma) de alambres de aleación de aluminio 6201-T81. E. Alta resistencia térmica.
A continuación, una ilustración de las combinaciones de cableado F. Resistente a las influencias atmosféricas.
y formación de los cables ACAR. G. Buen comportamiento a las variaciones de temperaturas.
Los cables no se seleccionan como un rubro separado de una H. Cables homogéneos con accesorios sencillos.
línea aérea, se seleccionan por consideraciones económicas que I. No presentan problemas electromagnéticos.
implican el costo instalado de la línea, conjuntamente con los J. Los cables AAC, AAAC (6201) y ACAR pesan
requerimientos financieros relacionados con su operación, tales aproximadamente la mitad de un conductor de cobre de la
como las pérdidas de energía, intereses sobre capital, misma conductividad.
depreciación. DISEÑO DE LOS CONDUCTORES
Los cables de aleación de aluminio tratados térmicamente no Para calcular todos los parámetros de los cables, se debe de
son cosa nueva. En el año 1925 ya estos cables se usaban en disponer de la siguiente información:
Europa para los sistemas aéreos de transmisión y distribución. 1.- Diseño del cable mensajero (o cable portante) que sostiene
Las aleaciones de magnesio han sido usadas por mucho tiempo el peso de los cables aislados, este diseño abarca:
con éxito, en planchas y como refuerzo en forma de cinta o
a. El módulo de elasticidad.
alambre de cables aislados; también para refuerzos de cables
b. El coeficiente de dilatación lineal.
submarinos y cables armados con aleación 6201. Puede decirse
c. El peso por metro total (kg/m).
que la aleación de aluminio ya tiene años de haber probado sus
d.- El diámetro total.
características en aplicaciones eléctricas.
e.- La velocidad del viento en zona.
FABRICACION DE LOS HILOS (ALAMBRES) f.- Temperatura promedio diaria en la zona.
La aleación de aluminio se trefila a partir del alambrón o varilla, g.- Tipo de aleación.
estas varillas se someten a un tratamiento térmico en solución y h.- Calibre del cable mensajero o cable portante.
una vez trefilado el alambre se somete a un envejecimiento
artificial. El envejecimiento artificial y el tratamiento térmico son
esenciales para obtener óptimas propiedades mecánicas y
eléctricas. ALUMINUM CONDUCTOR
ALLOY REINFORCED
FABRICACION DEL CABLE
(ACAR)
Se usan las mismas cableadoras que fabrican los cables de
aluminio. Las especificaciones del paso y cambio de dirección This bare concentric-lay-stranded conductor is made from round
de las capas son aplicables a los cables de aleación de aluminio. aluminum 1350-H19 (extra hard) wires and round aluminum-
En las aleaciones se requiere una operación de conformación al alloy 6201-T81 core wires for use as overhead electrical
cablear los alambres para asegurar máxima estabilidad del conductors. It presents a higher mechanical resistance.
cable y buenas características de manejo. The following tables show different combinations of stranding
regarding this type of conductor (ACAR).
41
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
42
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
43
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
44
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
45
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
46
Cables de Aluminio Reforzado
con Aleación de Aluminio ACAR
Aluminum Conductors Alloy Reinforced (ACAR)
47
SECCION V
INFORMACION TECNICA
Information Technical
48
Información Técnica
49
Información Técnica
50
Información Técnica
51
Información Técnica
(uno en cada extremo) son suficientes. La sacudida y el salto por hielo no dañan a los
Vanos mayores de 365 m. pueden requerir dos conductores materialmente, ni ninguna otra parte de la
amortiguadores en cada extremo, vanos mayores de línea, excepto que ha ya peligro de que los conductores
670m. pueden requerir hasta tres amortiguadores en cada se toquen produciendo cortocicuitos y dañando y hasta
extremo. En casos excepcionales donde no es suficiente
posiblemente quemando los conductores. Al igual que
usar tres amortiguadores, se colocarán a lo largo del vano
con la sacudida, no se ha perfeccionado ningún método
amortiguadores adicionales.
satisfactorio par eliminar el salto, el mismo tipo de
2 ) La Sacudida
dispositivo que elimina la sacudida también será efectivo
Otro tipo de vibración en los conductores es la
para eliminar el salto.
comúnmente llamada Sacudida, y es una oscilación
3 ) Rotación Ciclónica
de baja frecuencia y larga amplitud, en la cual los puntos
de soporte se mueven longitudinalmente el uno con Otra forma de trastorno violento en las líneas de
transmisión se debe a condiciones localizadas donde el
respecto al otro. Aunque este tipo de oscilación no ocurre
aire está rarificado o donde se ha producido el vacío
con frecuencia, sin embargo se ha observado y registrado. parcial por efectos de vientos de altas velocidades y de
Generalmente comienza por efecto del viento sobre carácter ciclónico, cerca de los conductores.
secciones irregulares de hielo y nieve en los conductores. Esta acción del viento tiende a levantar los conductores y
El temblor producido por el viento sobre dichas secciones habiendo neutralizado el efecto de gravedad, los
es amplificado por la acción de los aisladores de cadena conductores quedan libres para mecerse al azar en
y por los postes y torres de soporte. En algunas ocasiones cualquier dirección obedeciendo los impulsos del viento.
las oscilaciones verticales en los tramos de cientos de El resultado es una rotación violenta en los conductores
metros de largo, suelen medir 4.5 a 6 metros. En esos con peligro de que se toquen y se dañen por el arco
voltáico. Cualquier remedio, para que sea efectivo,
casos la velocidad del viento generalmente es bastante
requiere estudio cuidadoso de las condiciones locales para
alta aproximadamente 40 a 48 Km/hr. cada caso.
Todavía no hay ningún remedio práctico para eliminar la Las breves observaciones anteriores no abarcan todo el
sacudida, es probable que se pueda desarrollar algún ramo de las vibraciones en los conductores de las líneas
dispositivo para evitar ese tipo de oscilación pero no se de transmisión pero el objeto es indicar los diferentes tipos
sabe con seguridad si el costo de la instalación de dicho de vibraciones que se sabe ocurren en los conductores
dispositivo puede justificarse en vista de que este fenómeno como resultado de la acción del viento. La vibración
más común de todas es naturalmente, la vibración
no ocurre con frecuencia. Pero hay algunos casos sin
resonante mencionada primeramente, y el objeto principal
duda, como en los cruces de ríos, los cuales requieren
de este artículo es presentar la manera adecuada de evitar
tratamiento especial. Aún no se sabe exactamente qué fatiga de los conductores en los soportes debido a esta
tipo de dispositivo se requiere para esos lugares. causa.
Una sacudida especial se desarrolla cuando una carga
de hielo o nieve muy pesada se desprende del tramo. En
tales casos el conductor salta hacia arriba debido a su
propia elasticidad. Si los extremos del tramo son
terminales, la violencia del salto del conductor no es muy
fuerte y el trastorno se amortigua rápidamente. Pero si los
extremos del tramo están suspendidos con cadenas de
aisladores, los tramos contiguos reciben el movimiento y
lo transmiten a las torres. Como resultado, este tipo de
salto frecuentemente produce trastornos e inicia violentas
oscilaciones en muy largas distancias en las líneas.
52
Módulos de Elasticidad Finales
y Coeficientes de Dilatación Lineal
Final Elasticity Modulus and Expansion Lineal Coefficient
k g f / m m2
Nota: Los Módulos de Elasticidad indicados son el promedio de los valores obte-
nidos en ensayos de esfuerzo - deformación
53
Información Técnica
CREEP - DEFORMACION NO ELASTICA de 2.54 mm. Los hilos de diámetro más pequeño sufren
Un aspecto del comportamiento de los cables que no mayor pérdida de sus propiedades debido a la corrosión.
54
Requerimientos para Calcular la
Capacidad de Corriente de las
Líneas de Transmisión
Ejemplo:
Frecuencia 60
Coeficiente de temperatura (1/ C)= o
ALF 0,004
Resistencia en dc a 20 oC (Ohm/Km)= RDC 0,0509
Diámetro exterior (mm)= D 31,98
Altitud respecto nivel del mar (m)= h 50
Altitud del cable (m) HB 10
Emisividad= E 0,5
Temperatura ambiente ( C)= o
TA 25
Velocidad del viento (m/s)= V 0,6
Radiación del sol (W/m2)= 1,2
Coeficiente de absorción solar= A 0,5
Temperatura de trabajo ( c)=
o
TC 75
Radiación solar (W/m2) WS 15,40
Energía disipada por radiación (W/m2)= WR 19,32
Energía disipada por convección WC 69,74
Resistencia (Ohms)= R 0,062098
Efecto pelicular= K 1,038407
55
PARTE III
CONDUCTORES DE
ALUMINIO AISLADOS
Insulated Aluminum Conductors
56
SECCION V
INFORMACION TECNICA
Technical Information
57
CABLES DE LINEA Y MULTIPLEX tramo, el número de conductores aislados por fase, la carga
del diseño mecánico y las condiciones atmosféricas.
Los cables aéreos aislados con XLPE, sin suspensión propia El XLPE tiene una resistencia dieléctrica muy alta, buena
(cables de línea), tienen su principal aplicación en distribución resistencia mecánica y alta resistencia al ataque del sol, por
y
aérea secundaria, líneas urbanas y en ambientes muy lo tanto, es el mejor material para revestir los conductores
contaminados. Están formados por un conductor (1350 ó para instalaciones aéreas.
AA6201) recubierto con aislamiento de XLPE
. Poseen un Los cables Multiplex se utilizan para acometidas de servicio,
rango de voltaje definido y el espesor de aislamiento depende líneas alimentadoras de bajo voltaje (600 V o menos) y para
tanto del rango de voltaje como del tamaño del conductor
. distribución secundaria; también se usan extensamente en
Los cables aéreos aislados con XLPE y suspensión propia los sistemas de alumbrado de calles.
(cables Multiplex), consisten de un (Duplex), dosriplex)
(T o Las ventajas de estos cables consisten en que se reduce el
tres (Cuadruplex) conductores de fase aislados (Aluminio con número de conductores que han de tenderse, ajustarse a la
XLPE, cableados alrededor de un mensajero o neutro flecha y atarse a los terminales. Este detalle ahorra
(Aluminio, AA6201 ó ACSR) desnudo, cual soporta al cable, considerable material y tiempo para la erección.
a la vez que actúa de neutro; se asume que todo el esfuerzo Debido a la estrecha separación, se reduce la reactancia y la
de tracción del cable es soportado por el mensajero. caída de voltaje. Además, lo que es de mucha importancia
La elección del mensajero depende del tamaño del cable, el en las localidades, mejora la apariencia de las líneas tendidas
en alto.
58
Cables de Línea
Conductor de Aluminio AAC
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
59
Cables de Línea Compactados
Conductor de Aluminio AAC
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
AWG mm mm mm kg/km
60
Cables de Línea 600V
Conductor de Aluminio AAC
Código Calibre del Calibre y Cableado C a b l e a d o Diámetro Espesor Diámetro Peso Total
Cable de de los ACSR del del de To t a l (aproximado)
aleación mismo diámetro Conductor Aislamiento (aproximado)
6201 que los cables de
Code Stranding Diameter Insulation Total Diameter Total Weight
aleación
Thickness
MCM AWG Al/Acero mm mm mm kg/km
61
Cables Aéreos Duplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Basset 1/0 7 9,36 1,6 12,56 1/0 7 9,36 1/0 7 21,92 362
Malemute 1/0 19 9,46 1,6 12,66 1/0 7 9,36 1/0 19 22,02 359
62
Cables Aéreos Duplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Bloodhound 1/0 7 9,36 1,6 12,56 1/0 6/1 10,11 22,66 430
Bull 1/0 19 9,46 1,6 12,66 1/0 6/1 10,11 22,78 427
63
Cables Aéreos Duplex Compactado
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
64
Cables Aéreos Triplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
65
Cables Aéreos Triplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Homarus 6 Sólido 4,11 1,2 6,51 30,58 Sólido 4,44 - - 14,08 153
Minex 6 Sólido 4,11 1,2 6,51 30,58 7 5,04 6 6/1 14,08 154
Cabera 6 7 4,66 1,2 7,06 30,58 Sólido 4,44 - - 15,27 164
Hippa 6 7 4,66 1,2 7,06 30,58 7 5,04 6 6/1 15,27 165
Artemia 4 Sólido 5,19 1,2 7,59 30,58 7 5,04 6 6/1 16,39 205
Maira 4 7 5,88 1,2 8,28 30,58 Sólido 4,44 - - 17,88 221
Crab 4 7 5,88 1,2 8,28 30,58 7 5,04 6 6/1 17,88 221
Luidia 4 Sólido 5,19 1,2 7,59 48,69 Sólido 5,60 - - 16,39 229
Prawn 4 Sólido 5,19 1,2 7,59 48,69 7 6,36 4 6/1 16,39 230
Metalia 4 7 5,88 1,2 8,28 48,69 Sólido 5,60 - - 17,88 245
Barnacles 4 7 5,88 1,2 8,28 48,69 7 6,36 4 6/1 17,88 247
Solaster 2 7 7,42 1,2 9,82 48,69 7 6,36 4 6/1 21,21 333
Sandcrab 1/0 7 9,36 1,6 12,56 77,47 7 8,02 2 6/1 27,11 537
Echinus 1/0 19 9,46 1,6 12,66 77,47 7 8,02 2 6/1 27,37 531
Gammarus 1/0 7 9,36 1,6 12,56 123,30 7 10,11 1/0 6/1 27,11 601
66
Cables Aéreos Triplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Leda 1/0 19 9,46 1,6 12,66 123,30 7 10,11 1/0 6/1 27,37 594
Crayfish 2/0 7 10,51 1,6 13,71 97,63 7 9,00 1 6/1 29,64 661
Sipho 2/0 19 10,63 1,6 13,83 97,63 7 9,00 1 6/1 29,89 653
Dungenese 2/0 7 10,51 1,6 13,71 155,40 7 11,35 2/0 6/1 29,64 741
Cyclops 2/0 19 10,63 1,6 13,83 155,40 7 11,35 2/0 6/1 29,89 733
Slug 3/0 7 11,80 1,6 15,00 123,30 7 10,11 1/0 6/1 32,38 816
Fulgur 3/0 19 11,94 1,6 15,14 123,30 7 10,11 1/0 6/1 32,70 806
Balanus 3/0 19 11,94 1,9 15,74 123,30 7 10,11 1/0 6/1 34,00 834
Stonecrab 3/0 7 11,80 1,6 15,00 195,70 7 12,74 3/0 6/1 32,38 918
Flustra 3/0 19 11,94 1,6 15,14 195,70 7 12,74 3/0 6/1 32,70 907
Crisia 3/0 19 11,94 1,9 15,74 195,70 7 12,74 3/0 6/1 34,00 935
Squid 4/0 7 13,25 1,6 16,45 155,40 7 11,35 2/0 6/1 35,55 1.010
Arca 4/0 19 13,40 1,6 16,60 155,40 7 11,35 2/0 6/1 35,88 996
Bugula 4/0 19 13,40 1,9 17,20 155,40 7 11,35 2/0 6/1 37,17 1.026
Kingcrab 4/0 7 13,25 1,6 16,45 246,90 7 14,31 4/0 6/1 35,55 1.138
Lepas 4/0 19 13,40 1,6 16,60 246,90 7 14,31 4/0 6/1 35,88 1.124
Cassis 4/0 19 13,40 1,9 17,20 246,90 7 14,31 4/0 6/1 37,17 1.154
67
Cables Aéreos Triplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
68
Cables Aéreos Triplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Sanddollar 3/0 7 11,80 1,6 15,00 1/0 6/1 10,11 32,38 860
Aega 3/0 19 11,94 1,6 15,14 1/0 6/1 10,11 32,70 850
Pisa 3/0 19 11,94 1,9 15,74 1/0 6/1 10,11 34,00 878
Cherrystone 3/0 7 11,80 1,6 15,00 3/0 6/1 12,75 32,38 988
Mursia 3/0 19 11,94 1,6 15,14 3/0 6/1 12,75 32,70 978
Mysis 3/0 19 11,94 1,6 15/74 3/0 6/1 12,75 34,00 1.005
Cuttlefish 4/0 7 13,25 1,6 16,45 2/0 6/1 11,35 35,55 1.065
Cerapus 4/0 19 13,40 1,6 16,60 2/0 6/1 11,35 35,88 1.052
Nepatus 4/0 19 13,40 1,9 17,20 2/0 6/1 11,35 37,17 1.082
Razor 4/0 7 13,25 1,6 16,45 4/0 6/1 14,30 35,55 1.226
Zuzara 4/0 19 13,40 1,6 16,60 4/0 6/1 14,30 35,88 1.213
Alima 4/0 19 13,40 1,9 17,20 4/0 6/1 14,30 37,17 1.243
Callista 266,8 19 15,05 1,9 18,85 3/0 6/1 12,75 40,74 1.337
Dosinia 266,8 19 15,05 1,9 18,85 266,8 18/1 15,47 40,74 1.424
Cowry 336,4 19 16,90 1,9 20,70 4/0 6/1 14,30 44,76 1.657
Limpet 336,4 19 16,90 1,9 20,70 336,4 18/1 17,37 44,76 1.767
69
Cables Aéreos Triplex Compactado
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
70
Cables Aéreos Cuadruplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
71
Cables Aéreos Cuadruplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Bay 6 Sólido 4,11 1,2 6,51 30,58 7 5,04 6 6/1 15,71 209
French-Coach 6 7 4,66 1,2 7,06 30,58 7 5,04 6 6/1 17,04 226
German-Coach 4 Sólido 5,19 1,2 7,59 48,69 7 6,36 4 6/1 18,29 311
Arabian 4 7 5,88 1,2 8,28 48,69 7 6,36 4 6/1 19,95 336
Dapple-grey 2/0 7 10,51 1,6 13,71 155,40 7 11,35 2/0 6/1 33,07 1.004
Thoroughbred 2/0 19 10,63 1,6 13,83 155,40 7 11,35 2/0 6/1 33,35 992
Dobbin 3/0 7 11,80 1,6 15,00 195,70 7 12,74 3/0 6/1 36,13 1.240
Trotter 3/0 19 11,94 1,6 15,14 195,70 7 12,74 3/0 6/1 36,49 1.224
Pony 4/0 7 13,25 1,6 16,45 246,90 7 14,31 4/0 6/1 39,67 1.534
Walking 4/0 19 13,40 1,6 16,60 246,90 7 14,31 4/0 6/1 40,03 1.514
72
Cables Aéreos Cuadruplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
Chicoteagues 2/0 7 10,51 1,6 13,71 2/0 6/1 11,35 33,07 1.059
Grullo 2/0 19 10,63 1,6 13,83 2/0 6/1 11,35 33,35 1.047
Mare 3/0 7 11,80 1,6 15,00 3/0 6/1 12,75 36,13 1.310
Suffolk 3/0 19 11,94 1,6 15,14 3/0 6/1 12,75 36,49 1.295
Stallion 4/0 7 13,25 1,6 16,45 4/0 6/1 14,30 39,67 1.622
Appaloosa 4/0 19 13,40 1,6 16,60 4/0 6/1 14,30 40,03 1.602
73
Cables Aéreos Cuadruplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
COMPACTADO *
Conductor de Aluminio Compactado Mensajero (Neutro) Cable Completo
(Valores Aproximados)
Código Calibre Nº de Diámetro del Espesor de Diámetro Calibre Nº de Diámetro Diámetro Peso total
hilos Conductor aislamiento total hilos total del circulo (Kg/Km)
circunscrito
mm
Aluminum Conductor Neutral Messenger Complete Cable
Code Size Nº of Diameter Insulation Total Size Nº of Diameter Outside Total
Strands Thickness Diameter Strands Diameter Weight
74
Cables Aéreos Cuadruplex
AISLAMIENTO DE XLPE
CARACTERISTICAS FISICAS Y MECANICAS
75
Cables de Línea y Multiplex
CURRENT RATING
Size Size
6 100 3x4 83
4 125 3x2 108
2 175 3x1 124
1 192 3x1/0 147
180 240 3x2/0 170
2/0 270 3x3/0 197
3/0 325 3x4/0 227
4/0 375
Calibres en mm2
Hipótesis de Cálculo:
1.- Cables aislados con XLPE para 90o
mm2
2.- Temperatura ambiente 30o
3x16 72
3.- Velocidad del viento 0,6 m/seg 3x25 91
4.- Se tomó en cuenta el efecto del Sol 3x35 116
Nota: Para una temperatura ambiente 3x50 142
diferente a 30o, consultar con CONAL 3x70 174
3x95 210
3x120 240
200
Nota: Para una temperatura ambiente
150
diferente a 30o, consultar con CONAL
100
50
0 50 100 150
CALIBRES (mm2)
76
SECCION II
CABLES PREENSAMBLADOS
(AUTOPORTANTES)
Self Supporting
77
Cables Preensamblados
Self Supporting
DUPLEX
mm 2 mm mm mm mm kg mm kg/km ohms/km
TRIPLEX
mm 2 mm mm mm mm kg mm kg/km ohms/km
78
Cables Preensamblados
Self Supporting
CUADRUPLEX
ECOLOGICOS
PREENSAMBLADOS DE ALUMINIO (ALEACION 1350)
Sección Espesor Diámetro Peso Resistencia Resistencia Reactancia Corriente Caída de
Aislamiento envolvente AWG 20 grados 90 grados Tensión
Section Insulation Diameter Weight Resistance Resistance Reactance Current Voltage Drop
Thickness at 20ºC at 90ºC
79
80
SECCION III
81
CABLE MONOPOLAR DE MEDIA TENSION
5KV - 35 KV
82
Conductores Aislados
Insulated Aluminum Conductors
1.- LÍNEAS ECOLÓGICAS AISLADAS PARA ZONAS 1.- ECOLOGICAL INSULATED LINES FOR FOREST AREAS
BOSCOSAS In the distribution line, the conductor is the most important
En las líneas de distribución, el cable es el componente de component because its characteristics will determine the
mayor importancia, ya que sus características determinan la geometry and behavior of the line. On this behalf, the most
geometría y el comportamiento de la línea. Por lo tanto, la important reason to assure better costs and optimize the
cuidadosa selección de los cables, basada en el characteristics of the operation is to carefully select the
conocimiento a fondo de sus propiedades, es de máxima conductor, based on a profound knowledge of its properties.
importancia para asegurar los mejores costos y óptimas The objective of the ecological lines (insulated distributions)
características de operación. is to minimize the interruptions of the electrical energy
Las líneas ecológicas (distribución aisladas) tienen como produced by the contact with trees or with branches. One
objetivo minimizar las interrupciones de energía eléctrica technique to reduce the interruptions is to insulate the primary
debido a contactos con árboles o caída de ramas en las lines with cross-link polyethylene XLPE.
líneas. Una técnica para reducir las fallas, es aislar las The secondary lines of low tension will be formed by one,
líneas primarias con polietileno reticulado XLPE e instalarlas two, three or four conductors (depending on the case), the
en separadores poliméricos en posición vertical horizontal, insulated conductors will be stranded around a bare
o formando un triángulo equilátero (esta es la instalación conductor that is the messenger.
mas recomendada). Los cables estarán suspendidos con
guayas de acero.
2.- ECOLOGICAL LINES WITH MULTIPLEX
Las líneas secundarias de baja tensión estarán formadas
CONDUCTORS -600V
por uno, dos, tres o cuatro cables (según el caso), los cables
aislados serán cableados sobre un cable desnudo que es el
mensajero (cable portante). A.- (One insulated conductor)
B.- Duplex Conductor (One insulated conductor and one
2.- LÍNEAS ECOLÓGICAS CON CABLES MULTIPLEX - bare)
600V C.- Triplex Conductor (Two insulated conductor and one
bare)
A.- Cables de LÍNEA (Un cable aislado) D.- Cuadruplex Conductor (Three insulated conductor and
one bare)
B.- Cables DUPLEX (Un cable aislado y uno desnudo)-600V
C.- Cables TRIPLEX (Dos cables aislados y uno desnudo)-
600V These conductors are for overhead and are suspended with
a messenger conductor or neutro that can be bare or
D.- Cables CUADRUPLEX (Tres cables aislados y uno
insulated.
desnudo)-600V
The conductors used in overhead are based on aluminum
Estos cables son aéreos y están auto suspendidos por un
conductors insulated with polyethylene cross-link XLPE
cable mensajero o neutro que puede ser desnudo o aislado.
Los cables utilizados en líneas aéreas están basados en
cables de aluminio aislados con polietileno reticulado XLPE. 3.- ECOLOGICAL LINES INSTALLED IN SPACER
3.- LÍNEAS ECOLÓGICAS INSTALADAS EN SPACER The objective of the conductors installed in ecological Spacer
is to minimize or finish with the interruptions of electrical
Los cables instalados en separadores (SPACER
energy in areas with a lot of trees. They are constructed with
ECOLÓGICOS) tienen como objetivo minimizar o terminar
aluminum conductors and insulated with XLPE and installed
con las interrupciones de energía eléctrica en zonas donde
in Spacer; this way eliminates the interruptions produced by
hay árboles. Estos cables están formados por un conductor
the contact with trees or with the branches.
de aluminio y aislados con XLPE e instalados en separadores
poliméricos (SPACER), con ello eliminan las fallas
83
Conductores Aislados
Insulated Aluminum Conductors
ocasionadas por contacto con árboles y ramas que puedan There is insulation for low tension and insulation for high
desprenderse. tension, these conductors are classified in conductors of
Hay aislados para baja tensión y cables aislados para alta medium tension and conductors of low tension.
tensión, estos cables se clasifican en: cables de media tensión
y cables de baja tensión.
4.- APPLICATIONS:
4.- APLICACIONES • National Parks
Parques Nacionales. • In places where there is a lot of trees with dried branches.
En lugares en donde abundan los árboles con ramas • Narrow streets.
secas.
• Electrical net with more than one circuit
Calles estrechas.
• Trunk lines
Redes eléctricas con más de un circuito.
Líneas troncales (alimentadores). • In areas where it is necessary to trim the trees frequently
Zonas en donde es necesario podar árboles con bastante • Places with high pollution
frecuencia. • Distribution lines close to the sea.
Lugares de alta contaminación.
Líneas de distribución cerca del mar.
5.- ADVANTAGE:
Advantage of the aluminum in overhead distribution lines.
5.- VENTAJAS
The high conductivity of the aluminum is as important as the
Ventajas del aluminio en líneas aéreas de distribución.
high mechanical resistance. The aluminum conductors have
La alta conductividad del aluminio es tan importante como
la alta resistencia mecánica del mismo. Los conductores de a better mechanical resistance than the equivalent in copper
aluminio son más resistentes mecánicamente que los conductors.
conductores de cobre equivalentes. De aquí resulta, por lo The most important characteristic is its low weight, this makes
tanto, que todos los tipos de conductores de aluminio son it easier and quicker to be installed.
mucho más resistentes que los de cobre.
Para el montador de líneas el poco peso es su característica
más resaltante, esto hace posible facilitar y acelerar el ALUMINUM INSULATED CONDUCTORS
manejo de los conductores. The operational costs of the insulated lines for high and
CONDUCTORES DE ALUMINIO AISLADO low tension are 20 times lower than the bare lines, this means
Los costos operacionales de las líneas aisladas tanto de less interruptions, less maintenance, less trim of trees, reduced
alta como de baja tensión, son 20 veces menores que las space for installation of the line and a reduction in costs.
líneas desnudas, significa menos fallas, menos
mantenimiento, menos poda de árboles, espacio más
pequeño para la instalación de la línea y se reduce el costo. COPPER CONDUCTORS
CONDUCTORES DE COBRE When these lines are installed with copper conductors,
Cuando se instalan estas líneas con conductor de cobre, the cost increases because of the weight of the copper, this
el costo se incrementa debido al peso del cobre, este costo cost is reflected on the price of the tower which has to be
se nota en el precio de los postes y las estructuras, que tiene
more resistant and higher to support the tense and sags of
que ser más resistentes y de mayor altura para soportar las
the copper conductors.
tensiones y las flechas del cable de cobre.
84
Conductores Aislados
Insulated Aluminum Conductors
85
Conductores Ecológicos Protegidos
Ecological Conductors
ACSR
86
Conductores Ecológicos Protegidos
Ecological Conductors
87
Cables Ecológicos - Protegidos
88
LABORATORIO
Laboratory
SEPARADOR
LABORATORIO
89
Laboratorio
Laboratory
90
Laboratorio
Laboratory
La Unidad Técnica de Aluminio (U.T.A.) es un centro de The Aluminum Technical Unit is a service center located in
servicio ubicado en Planta CONAL, Valencia - Venezuela CONAL Plant, Valencia - Venezuela with the purpose of
con la finalidad de asistir a las compañías asociadas a PHELPS assist the companies associated to PHELPS DODGE
DODGE Wire and Cable Group, a los clientes y Wire and Cable Group, customers and suppliers in the
proveedores en la realización de cálculos y pruebas realization of calculus and special testing considering
especiales considerando equipos sofisticados de la más alta sophisticated equipments of the highest technology.;
tecnología, con primordial importancia en los siguientes with main importance in the following aspects:
aspectos:
Mechanical and Electric tests to a complete cable as:
Pruebas Mecánicas y Eléctricas al conductor completo tales
- Stress - Strain
como:
- Tensile
- Esfuerzo - Deformación
- Creep
- Rotura
- Fatigue
- Creep
- Electric Resistance in C.C .at 20ºC
- Fatiga
A Metallography Laboratory to investigate ferrous and
- Resistencia Eléctrica en corriente contínua a 20ºC
non-ferrous metals up to ½ in diameter. The samples
Laboratorio Metalográfico completo para investigar metales
are processing using a fully automatic preparation
ferrosos y no-ferrosos hasta de ½ de diámetro. Las muestras
system with metallurgic through on-line computarized
se procesan utilizando un sistema de preparación comple-
image analyzer system generating color
tamente automático con interpretación metalúrgica a través de
fotomicrographics of the samples.
un sistema de analizador de imágenes computarizado; gene-
rando fotomicrografías a color de las muestras. Annealing and artificial aging of Aluminum Rod and Wires.
Recocido y envejecimiento artificial de Alambrón y Alambres Quality Systems, training and audits.
91
Laboratorio
Laboratory
El sistema de prueba dinámico de materiales, Marca Instron, Instron Model 8500-Plus Dynamic Materials Testing System consists
Módelo 8500 Plus consiste en una cónsola tipo torre con tablero of a Tower Console, front Panel, a hidraulic power supply and a
delantero, una fuente de energía hidráulica y una celda de carga load cell as a load measurement device with an automatic control
como dispositivo de medición de carga, además cuenta con un system of increasing load controlled automatically and software
sistema de control automático de incremento de carga controlado incorporated that graphically represent by means of stadistic system
automáticamente y programa incorporado que representa the diagram regarding to the following tests:
gráficamente mediante un sistema estadístico los diagramas Stress - Strain.
relacionados con las siguientes pruebas: Modulus of Elasticity Initial and Final.
Esfuerzo - Deformación. Tensile.
Módulo de Elasticidad. Creep.
Rotura. Fatigue.
Creep.
Fatiga.
Longitud Máxima de la Muestra (m) / Maximun Sample of Load (in) 12,7 / 500
92
Laboratorio
Laboratory
Los puentes kelvin de Applications Electroniques S.A. / Aesa Applications Electroniques S.A./ Aesa Cortaillod Kelvin Bridge,
Cortaillod miden la resistencia y sección transversal sobre measures the resistance and cross-section on copper or aluminum
conductores completos de Cobre ó Aluminio, directamente en la complete cable, directly on the production machine or on pre-cut
máquina de producción ó en muestra de laboratorio pre- laboratories sample.
determinadas. A temperature probe automatically measures the temperature of
Un sensor de temperatura mide automáticamente la temperatura the conductor so that the system can correct the measured and
del conductor de manera que el sistema pueda corregir la output a value that corresponds to a referente temperature (20 ºC).
resistencia medida y el valor obtenido corresponde a una Reading are output on a digital display on the control unit.
temperatura de referencia (20º C). Las lecturas son mostradas
en el panel de la unidad de control.
93
Laboratorio
Laboratory
La máquina Instron, Modelo 4486, está diseñada para ensayos Instron Machine, Model 4486, is designed for tension,
de tensión, comprensión, y flexión, incluyendo un panel operador compression, shear, and flexion testing, including an operator
que permite cambios o ajustes de ensayo instantáneos con panel that allows instantaneous test set-ups or changes with
autorango para una simple operación y una resolución de data autoranging for simple operation and optimum data resolution.
óptima. El sistema de control servo digital con un traductor The servo digital control system with a high resolution optical
óptico de alta resolución mantiene velocidades y encoder maintains precise speeds and displacements, assuring
desplazamientos precisos, asegurando resultados de ensayo repeatable test results.
repetitivos.
94
Laboratorio
Laboratory
Completamente automático significa que las muestras pueden ser Fully automatic means that samples can be prepared from start
preparadas desde el inicio al final de forma continua sin la intervención to finish without continuous operator involvement. Just load up
del operador. Solo se preparan hasta seis muestras a la vez, se to six samples at a time, select the preparation method, and in a
selecciona y se programa el método de preparación y en un period of 15 to 20 minutes your samples will be finished, cleaned,
período de 15 a 20 minutos las muestras están limpias, secas y listas dried, and ready for analysis.
para el análisis.
Sistema Automático para Preparación de Muestras Ferrosas y no Ferrosas hasta un Diámetro de 1/2"
Fully Automatic Sample Preparation System for Ferrous and Non-Ferrous Samples Up to 1/2" Diameter.
El analizador de imagen es usada para evaluar The image analyzer is used to evaluate quantitative data from
cuantitativamente la data de una imagen o alguna propiedad an image, or some property of an specimen, represented in an
de una muestra, representada en forma de imagen. Este sistema image way. This system permits an analysis for higher quality in
permite un análisis de más alta calidad en corto tiempo. a short times.
95
96
TABLA DE CONVERSION
Conversion Table
97
Tabla de Conversión
Conversion Table
AREA FUERZA
VOLUMEN PRESION
MASA POTENCIA
98
RECOMENDACIONES PARA
EL MANEJO Y ALMACENAMIENTO
DE LOS CABLES
Handling and shipping recomendation for Aluminum Cables
99
Manejo y Almacenamiento de Cables
RECOMENDACIÓN PARA EL MANEJO Y tomar la precaución de que las alas de los carretes vecinos
ALMACENAMIENTO DE LOS CABLES no golpeen la capa externa del cable.
4.- Los dos extremos del cable deben estar sellados para
evitar la penetración de la humedad.
100
Manejo y Almacenamiento de Cables
CARRETES:
USO Y CUIDADO
101
Manejo y Almacenamiento de Cables
Figura 7
Figura 8
Figura 9
102