SHEET INDEX
A PAGE SHEET ID REV DATE TITLE A
1 WM043 3 2019-03-06 COVER
DESCRIPTION:
B 4 WM601 3 2019-03-06
CONTROL ROOM B
COMMUNICATION BLOCK DIAGRAM
DRAFTED
HMI, PPC
5 WM602 2 2019-02-26
SOLAR ARRAY
6 WM612 2 2019-02-26 FIBER DETAIL - CONTROL ROOM
2019-01-25
2019-02-26
2019-03-06
DATE:
8 WM614 2 2019-02-26 FIBER DETAIL - INVERSTATION 3&4
DA BAC 1 - VN
PWH
PWH
PWH
BY:
D 10 WM615 2 2019-02-26 FIBER DETAIL - INVERSTATION 7&8 D
REV:
11 WM621 2 2019-02-26 SCHEDULES
SCADA
1
2
3
SINGLE LINE DIAGRAM - CONTROL
12 WM631 3 2019-03-06
ROOM
SINGLE LINE DIAGRAM -
E 13 WM632 2 2019-02-26
INVERSTATION 1 E
SINGLE LINE DIAGRAM -
14 WM633 2 2019-02-26
INVERSTATION 2
15 WM634 2 2019-02-26
SINGLE LINE DIAGRAM - VIETNAM
INVERSTATION 3
SINGLE LINE DIAGRAM -
F 16 WM635 2 2019-02-26
INVERSTATION 4
F
SINGLE LINE DIAGRAM - PROJECT OVERVIEW PROJECT DESCRIPTION
17 WM636 2 2019-02-26
EST118150
INVERSTATION 5
DA BAC 1
SINGLE LINE DIAGRAM -
18 WM637 2 2019-02-26
INVERSTATION 6
FIXED ARRAY
G SINGLE LINE DIAGRAM -
G
-
19 WM638 2 2019-02-26 SITE NAME DA BAC 1 - VN
INVERSTATION 7
SINGLE LINE DIAGRAM - SCOPE: SITE ADDRESS -, -, - -, VIETNAM
20 WM639 2 2019-02-26
INVERSTATION 8 SITE OWNER SOLAR SM JSC
PANEL LAYOUT - CONTROL ROOM
21 WM651 3 2019-03-06 DATA ACQUISITION AND CONTROL OF SOLAR PV SITE EPC NAME ZZZ - ANONYMOUS CUSTOMER
RACK
SEE SCOPE OF WORK DOCUMENT FOR FULL DETAILS
H 22 WM652 3 2019-03-06
PANEL LAYOUT - RACK MOUNTED
SHELF
SYSTEM SIZE - H
SITE SUMMARY: SYSTEM TYPE MONITORING/UTILITY/SCADA/RIG
23 WM653 2 2019-02-26 PANEL LAYOUT - INVERSTATION 1
24 WM654 2 2019-02-26 PANEL LAYOUT - INVERSTATION 2 TECH CONTACT NAME SOLAR SM JSC : TRAN VAN TON
25 WM655 2 2019-02-26 PANEL LAYOUT - INVERSTATION 3 MAIN CONTROL WITH: TECH CONTACT EMAIL INFOR@SILVERROCK.IN
26 WM656 2 2019-02-26 PANEL LAYOUT - INVERSTATION 4 SKYSERV RTSO TECH CONTACT PHONE +84 898 759-966
I 27 WM657 2 2019-02-26 PANEL LAYOUT - INVERSTATION 5 SKYSERV LOCAL I
ALSOENERGY SALES REP. SUSHAIN SHARMA
28 WM658 2 2019-02-26 PANEL LAYOUT - INVERSTATION 6 SKY-IPC SKYLOG (4)
SKY-IPC PPC ALSOENERGY ACCT. MGR. NICK GOODROAD
29 WM659 2 2019-02-26 PANEL LAYOUT - INVERSTATION 7
866-303-5668, USA
34 WM702 1 2019-01-25 DETAIL ADAM 6050 DIGITAL I/O
K DETAIL WEATHER TOWER
INVERTER PADS (8) AT DA BAC 1, EACH WITH: K
35 WM703 1 2019-01-25 SMA SC3000-EV INVERTERS (2) PROVIDED BY OTHERS
INSTALLATION 1
DETAIL WEATHER TOWER TRANSFORMER ALARMS VIA INVERTERS PROVIDED BY OTHERS
36 WM704 1 2019-01-25
INSTALLATION 2 RMU STATUS AND CONTROL CONTACTS PROVIDED BY OTHERS
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
DATE:
N N
COVER SHEET
O O
P WM043 P
1 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
ABBREVIATIONS GENERAL NOTES
A AMPS 1. THIS SYSTEM HAS BEEN DESIGNED TO ALSOENERGY SPECIFICATIONS. MODIFICATIONS MADE TO THE SYSTEM MAY CAUSE IMPROPER
OPERATION UNLESS YOU NOTIFY ALSOENERGY OF THE CHANGES.
AC ALTERNATING CURRENT
DESCRIPTION:
B B
ACD AC DISCONNECT 2. INTERNAL DEVICES (POWER SUPPLY, DATA LOGGER, METER AND RS-485 PORT CARD SURGE SUPPRESSORS) SUPPLIED PRE-WIRED WITH IP
C CELSIUS 3. THE RS-485 BUS USES DAISY-CHAINED CONFIGURATION FOR ALL DEVICES, I.E. NO MORE THEN TWO WIRES ON ANY TERMINAL.
C CB CIRCUIT BREAKER C
4. FOR RS-485 CONNECTIONS, ONLY CONNECT THE DRAIN WIRE OF THE SHIELDED CABLE AT ONE END. DO NOT GROUND THE DRAIN WIRE AT
1
DCD DC DISCONNECT 6. USE BELDEN 7919A CAT5e NETWORK CABLE OR EQUIVALENT FOR ALL HUB TO CABLE MODEM TO GATEWAY ETHERNET CONNECTIONS, 300FT
MAX.
DISC DISCONNECT
E E
F FAHRENHEIT 7. ALL WORK SHALL COMPLY WITH APPLICABLE CODE.
FO FIBER OPTIC 8. SINGLE MODE FIBER CABLE WILL BE OS2 WITH LC CONNECTORS UNLESS OTHERWISE SPECIFIED.
GHI GLOBAL HORIZONTAL IRRADIANCE
F GND GROUND
9. ALL FIBER CONNECTIONS INDICATE A STRAND FOR BOTH TX AND RX UNLESS OTHERWISE SPECIFIED. F
EST118150
HV HIGH VOLTAGE
DA BAC 1
ID INSIDE DIAMETER 10. SENSOR CABLES MAY BE CALIBRATED AND LENGTH SHOULD NOT BE MODIFIED WITHOUT APPROVAL FROM ALSOENERGY OR SENSOR
MANUFACTURER.
G INV INVERTER G
-
JB JUNCTION BOX 11. RADIO CONNECTIONS MUST BE LINE OF SIGHT.
KV KILOVOLT 12. WARRANTY IS VOID IF HOLES ARE MADE TOO CLOSE TO EDGES OR ANYWHERE OTHER THAN BOTTOM OF ENCLOSURE.
KW KILOWATT
H H
KWH KILOWATT-HOUR
LV LOW VOLTAGE
MAX MAXIMUM
I MCE MAIN COMMUNICATION ENCLOSURE I
MIN MINIMUM
866-303-5668, USA
OD OUTSIDE DIAMETER
K K
POA PLANE OF ARRAY # REFERENCE NOTE NUMBER # SAME PAGE PYRANOMETER - GLOBAL HORIZONTAL
IRRADIANCE
PB PANELBOARD
PCC/POCC POINT OF COMMON COUPLING # REFERENCE PAGE WM-XXX FIGURE # PYRANOMETER - PLANE OF ARRAY
WM-XXX
L POS POSITIVE L
PWH
-
PV PHOTOVOLTAIC TAG DEVICE OR LOCATION TAG
REFERENCE CELL - PLANE OF ARRAY
SCADA SUPERVISORY CONTROL AND DATA
CHECKED BY:
ACQUISITION
M CIRCUIT BREAKER M
DRAWN BY:
SCH SCHEDULE
TYP TYPICAL
DATE:
FUSE PRECIPITATION SENSOR
UL UNDERWRITERS LABORATORIES
N V VOLTS N
ANTENNA
VAC VOLTS AC RELATIVE HUMIDITY SENSOR
%
GENERAL NOTES
VAR VOLT-AMPERE REACTIVE
T
O VDC VOLTS DC MOD MODULE TEMPERATURE ANALOG SENSOR O
W WATTS BAROMETRIC PRESSURE SENSOR
WS WEATHER STATION
TAMB
XF TRANSFORMER AMBIENT TEMPERATURE ANALOG SENSOR
P WM044 P
2 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
- RTAC
C - SKYCONTROL PPC C
- SKYSERV RTSO
1
2
E E
INVERSTATION 1-1 INVERSTATION 1-7
EST118150
DA BAC 1
G G
-
INVERSTATION 1-2 INVERSTATION 1-7
866-303-5668, USA
K INVERSTATION 1-5 K
- (2) SMA 3MW INVERTERS
- (1) TRANSFORMER
- (1) RMU
- (1) WEATHER TOWER WITH POA
L INVERSTATION 1-4 PYRANOMETER AND L
PWH
-
INTEGRATED WEATHER
- (2) SMA 3MW INVERTERS STATION,
- (1) TRANSFORMER - (2) MODULE TEMPERATURE
- (1) RMU SENSORS
CHECKED BY:
M M
DRAWN BY:
DATE:
N N
WIRE LEGEND
COMMUNICATION
FIBER MULTI MODE
FIBER SINGLE MODE
O CAT5E O
OVERVIEW
SERIAL / RS485
24VDC POWER
12VDC POWER
ANALOG / PULSE / DRY CONTACT
AC AC POWER
P CT
VT
CURRENT TRANSFORMER
WM045 P
VOLTAGE TAP/TRANSFORMER
3 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
CONTROL ROOM
A A
DA BAC 1
ALSOENERGY RACK
DESCRIPTION:
B B
DRAFTED
SKY-IPC †
HMI, PPC
SKYLOG
C C
2019-01-25
2019-02-26
2019-03-06
SKY-IPC †
DATE:
SKYLOG
PWH
PWH
PWH
BY:
SKY-IPC †
D D
REV:
SKYLOG
1
2
3
SEL-2407 †
E E
GPS CLOCK
SEL-3505 †
RTAC
F F
EST118150
UPS †
DA BAC 1
G G
-
SKYSERV † SEL-2730M †
H SKYSERV † H
LOCAL
FIBER PATCH PANEL †
SINGLE MODE LC
HMI †
I I
SEL-3620 †
J J
RTU ‡
866-303-5668, USA
K K
OPERATIONS STATION 1
SITE INTERNET
DESKTOP HMI † PROVIDED BY OTHERS
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
PROVIDED BY ALSOENERGY
DATE:
†
‡ PROVIDED BY OTHERS
N ALL CABLE AND CONDUIT PROVIDED BY OTHERS N
UNLESS OTHERWISE SPECIFIED FIBER RING DA BAC 1 WM602 1
WIRE LEGEND INVERSTATIONS
COMMUNICATION
BLOCK DIAGRAM
CONTROL ROOM
FIBER MULTI MODE 1-1 THROUGH 1-8 WM602 2
FIBER SINGLE MODE
O CAT5E O
SERIAL / RS485 DA BAC 1
24VDC POWER SOLAR ARRAY
12VDC POWER
ANALOG / PULSE / DRY CONTACT
AC AC POWER
P CT
VT
CURRENT TRANSFORMER
WM601 P
VOLTAGE TAP/TRANSFORMER
4 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A ARRAY 1-8
INVERTER ‡ A
1-8.1
DESCRIPTION:
B WM601 2
ALSOENERGY
NETWORK ENCLOSURE
†
XFMR ‡ B
1-8
C MET STATION ‡ C
1-8
1
2
‡
ALSOENERGY 1-7.2
†
WM601 1 XFMR ‡
NETWORK ENCLOSURE ALSOENERGY †
1-1 XFMR ‡
E CONTROL ROOM INVERSTATION 1-1 NETWORK ENCLOSURE
1-7 E
INVERSTATION 1-7
RMU ‡
1-1 RMU ‡
1-7
MET STATION ‡
1-1
F F
EST118150
ARRAY 1-6
DA BAC 1
ARRAY 1-2 INVERTER ‡
INVERTER ‡
1-6.1
1-2.1
G G
-
INVERTER ‡
INVERTER ‡
1-6.2
1-2.2
ALSOENERGY †
ALSOENERGY † XFMR ‡
XFMR ‡ NETWORK ENCLOSURE
NETWORK ENCLOSURE 1-6
1-2 INVERSTATION 1-6
INVERSTATION 1-2
H RMU ‡
RMU ‡ H
1-6
1-2
I ARRAY 1-3
ARRAY 1-5
INVERTER ‡
I
INVERTER ‡
1-5.1
1-3.1
866-303-5668, USA
RMU ‡
1-5
1-3
K K
ARRAY 1-4
INVERTER ‡
L 1-4.1
L
PWH
-
INVERTER ‡
1-4.2
ALSOENERGY †
XFMR ‡
NETWORK ENCLOSURE
CHECKED BY:
1-4
M INVERSTATION 1-4 M
DRAWN BY:
RMU ‡
1-4
DATE:
† PROVIDED BY ALSOENERGY
‡ PROVIDED BY OTHERS
N ALL CABLE AND CONDUIT PROVIDED BY OTHERS
N
COMMUNICATION
BLOCK DIAGRAM
NETWORK PADS
FIBER MULTI MODE
FIBER SINGLE MODE
O CAT5E O
SERIAL / RS485
24VDC POWER
12VDC POWER
ANALOG / PULSE / DRY CONTACT
AC AC POWER
P CT CURRENT TRANSFORMER
WM602 P
VT VOLTAGE TAP/TRANSFORMER
5 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
ALL CABLE, TERMINATIONS, AND CONDUIT WILL BE
PROVIDED AND TESTED BY OTHERS UNLESS
A OTHERWISE SPECIFIED. A
DESCRIPTION:
B B
C4
PWR
C C
5 6 9 10 11 12 13 14 15 16
1
2
Rx Tx
Tx ORANGE Rx ORANGE
E GREEN GREEN E
BROWN BROWN
SLATE SLATE
WHITE WHITE
F F
RED RED
EST118150
DA BAC 1
BLACK BLACK
YELLOW YELLOW
G G
-
VIOLET VIOLET
ROSE ROSE
AQUA AQUA
H BLUE/BK BLUE/BK H
ORANGE/BK ORANGE/BK
GREEN/BK GREEN/BK
BROWN/BK BROWN/BK
I I
SLATE/BK SLATE/BK
WHITE/BK WHITE/BK
866-303-5668, USA
VIOLET/BK VIOLET/BK
K ROSE/BK ROSE/BK K
1 AQUA/BK AQUA/BK
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
DATE:
N N
NOTES:
CONTROL ROOM
2. SEL-2730M MANAGED SWITCH PANEL AND ETHERNET CONNECTION KEY SHOWN BELOW. WM613 1 WM615 5
INVERSTATION 1-1 INVERSTATION 1-8
FIBER DETAIL
GREEN - RJ45 FOR CAT5E ETHERNET
O PORTS 5-8: 10/100/1000 O
PORTS 9-20:
9-24: 10/100
PURPLE - PORTS
LC CONNECTOR
21-24 LC CONNECTOR
FOR SINGLE MODE
FOR SINGLE
FIBER MODE FIBER
ALARM
SEL-2730M SEL-9330-C
7 8 17 18 19 20 21 22 23 24
POWER SUPPLY
7 8
ENABLED
IN 24V/48V
MAX 1.7A, 42W
ALARM +3 -2 GND
P WM612 P
1 OUT 12.5V
C1 C2 C3 17 18 19 20 21 22 23 24 MAX 2.9A, 36W
1 2 3 4 GND
5 6 9 10 11 12 13 14 15 16
C4
1 2 3 4 5 6 9 10 11 12 13 14 15 16
PWR
6 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
FIBER ETHERNET ALL CABLE, TERMINATIONS, AND CONDUIT WILL BE
SWITCH ET-MS-2LC8 PROVIDED AND TESTED BY OTHERS UNLESS
A PORT NUMBERS OTHERWISE SPECIFIED. A
DESCRIPTION:
B B
1
2
MANAGED SWITCH MANAGED SWITCH
E 9 10 9 10 E
Tx Rx Tx Rx Tx Rx Tx Rx
EST118150
GREEN GREEN GREEN GREEN
DA BAC 1
BROWN BROWN BROWN BROWN
G G
-
SLATE SLATE SLATE SLATE
866-303-5668, USA
WHITE/BK WHITE/BK WHITE/BK WHITE/BK
K K
RED/BK RED/BK RED/BK RED/BK
PWH
-
VIOLET/BK VIOLET/BK VIOLET/BK VIOLET/BK
CHECKED BY:
M M
DRAWN BY:
2 INVERSTATION 1-1 3 INVERSTATION 1-2
DATE:
N N
INVERSTATION 1 & 2
FIBER DETAIL
O O
P WM613 P
7 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
FIBER ETHERNET ALL CABLE, TERMINATIONS, AND CONDUIT WILL BE
SWITCH ET-MS-2LC8 PROVIDED AND TESTED BY OTHERS UNLESS
A PORT NUMBERS OTHERWISE SPECIFIED. A
DESCRIPTION:
B B
1
2
MANAGED SWITCH MANAGED SWITCH
E 9 10 9 10 E
Tx Rx Tx Rx Tx Rx Tx Rx
EST118150
GREEN GREEN GREEN GREEN
DA BAC 1
BROWN BROWN BROWN BROWN
G G
-
SLATE SLATE SLATE SLATE
866-303-5668, USA
WHITE/BK WHITE/BK WHITE/BK WHITE/BK
K K
RED/BK RED/BK RED/BK RED/BK
PWH
-
VIOLET/BK VIOLET/BK VIOLET/BK VIOLET/BK
CHECKED BY:
M M
DRAWN BY:
4 INVERSTATION 1-3 5 INVERSTATION 1-4
DATE:
N N
INVERSTATION 3 & 4
FIBER DETAIL
O O
P WM614 P
8 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
FIBER ETHERNET ALL CABLE, TERMINATIONS, AND CONDUIT WILL BE
SWITCH ET-MS-2LC8 PROVIDED AND TESTED BY OTHERS UNLESS
A PORT NUMBERS OTHERWISE SPECIFIED. A
DESCRIPTION:
B B
1
2
MANAGED SWITCH MANAGED SWITCH
E 9 10 9 10 E
Tx Rx Tx Rx Tx Rx Tx Rx
EST118150
GREEN GREEN GREEN GREEN
DA BAC 1
BROWN BROWN BROWN BROWN
G G
-
SLATE SLATE SLATE SLATE
866-303-5668, USA
WHITE/BK WHITE/BK WHITE/BK WHITE/BK
K K
RED/BK RED/BK RED/BK RED/BK
PWH
-
VIOLET/BK VIOLET/BK VIOLET/BK VIOLET/BK
CHECKED BY:
M M
DRAWN BY:
6 INVERSTATION 1-5 7 INVERSTATION 1-6
DATE:
N N
INVERSTATION 5 & 6
FIBER DETAIL
O O
P WM615 P
9 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
FIBER ETHERNET ALL CABLE, TERMINATIONS, AND CONDUIT WILL BE
SWITCH ET-MS-2LC8 PROVIDED AND TESTED BY OTHERS UNLESS
A PORT NUMBERS OTHERWISE SPECIFIED. A
DESCRIPTION:
B B
1
2
MANAGED SWITCH MANAGED SWITCH
E 9 10 9 10 E
Tx Rx Tx Rx Tx Rx Tx Rx
EST118150
GREEN GREEN GREEN GREEN
DA BAC 1
BROWN BROWN BROWN BROWN
G G
-
SLATE SLATE SLATE SLATE
866-303-5668, USA
WHITE/BK WHITE/BK WHITE/BK WHITE/BK
K K
RED/BK RED/BK RED/BK RED/BK
PWH
-
VIOLET/BK VIOLET/BK VIOLET/BK VIOLET/BK
CHECKED BY:
M M
DRAWN BY:
8 INVERSTATION 1-7 9 INVERSTATION 1-8
DATE:
N N
INVERSTATION 7 & 8
FIBER DETAIL
O O
P WM616 P
10 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
COMMUNICATIONS FIELD TERMINALS
DEVICE ID DESCRIPTION COMMUNICATION COMMUNICATION UNIT ID IP ADDRESS SUPPLIER
A PROTOCOL PORT / CHANNEL ID TB# SIGNAL A
LOGGER 1 GW0.1 SKY-IPC SKYLOG TCP/IP LAN1 - 172.24.0.111 ALSOENERGY CP1.1
LOGGER 2 GW0.2 SKY-IPC SKYLOG TCP/IP LAN1 - 172.24.0.112 ALSOENERGY CP2.1 1 INPUT POWER LINE 120-277VAC
DESCRIPTION:
LOGGER WEATHER STATION 1 GW2.1 POWERLOGGER 1000 TCP/IP LAN1 - 172.24.8.111 ALSOENERGY 4 INPUT POWER NEUTRAL
B LOGGER WEATHER STATION 2 GW5.1 POWERLOGGER 1000 TCP/IP LAN1 - 172.24.9.111 ALSOENERGY
CP5.1 B
CP5.2
1
2
8 DC POWER +24VDC
NETWORK SWITCH INVERSTATION 3 NET3.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.3.9 ALSOENERGY RP2.2
9 DC POWER COMMON
NETWORK SWITCH INVERSTATION 4 NET4.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.4.9 ALSOENERGY RP5.2
5 EGC
NETWORK SWITCH INVERSTATION 5 NET5.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.5.9 ALSOENERGY
E NETWORK SWITCH INVERSTATION 6 NET6.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.6.9 ALSOENERGY
10 RS485 COMMON E
RTU2.1 11 RS485 DATA+
NETWORK SWITCH INVERSTATION 7 NET7.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.7.9 ALSOENERGY RTU5.1 12 RS485 DATA-
NETWORK SWITCH INVERSTATION 8 NET8.1 MANAGED ETHERNET SWITCH - 8 COPPER RJ45 - 2 SFP WITH SM LC TCP/IP LAN1 - 172.24.8.9 ALSOENERGY 13 RS485 SHIELD
INVERTER 1.1 PV0 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.1.11 BY OTHERS
14 RS485 COMMON
INVERTER 1.2 PV1 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.1.12 BY OTHERS
RTU2.2 15 RS485 DATA+
F INVERTER 2.1
INVERTER 2.2
PV2
PV3
SMA SC3000-EV
SMA SC3000-EV
MODBUS TCP
MODBUS TCP
LAN1
LAN1
3
3
172.24.2.11
172.24.2.12
BY OTHERS
BY OTHERS
RTU5.2 16 RS485 DATA- F
17 RS485 SHIELD
INVERTER 3.1 PV4 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.3.11 BY OTHERS
EST118150
101 XMFR FEEDER CB NC
DA BAC 1
INVERTER 3.2 PV5 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.3.12 BY OTHERS
102 XMFR FEEDER CB NO
INVERTER 4.1 PV6 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.4.11 BY OTHERS
103 XMFR FEEDER DC NC
INVERTER 4.2 PV7 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.4.12 BY OTHERS DI1.1 104 XMFR FEEDER DC NO
G G
-
INVERTER 5.1 PV8 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.5.11 BY OTHERS DI2.1
105 XMFR FEEDER EW NC
INVERTER 5.2 PV9 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.5.12 BY OTHERS DI3.1
106 XMFR FEEDER EW NO
INVERTER 6.1 PV10 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.6.11 BY OTHERS DI4.1
107 XMFR FEEDER CAPDIS S2+ NC
INVERTER 6.2 PV11 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.6.12 BY OTHERS DI5.1
108 XMFR FEEDER CAPDIS S2+ NO
INVERTER 7.1 PV12 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.7.11 BY OTHERS DI6.1
109 CABLE FEEDER 1 DC NC
INVERTER 7.2 PV13 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.7.12 BY OTHERS DI7.1
H INVERTER 8.1 PV14 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.8.11 BY OTHERS DI8.1 110
111
CABLE FEEDER 1 DC NO
CABLE FEEDER 1 EW NC
H
INVERTER 8.2 PV15 SMA SC3000-EV MODBUS TCP LAN1 3 172.24.8.12 BY OTHERS
112 CABLE FEEDER 1 EW NO
DA1.1 172.24.1.102
RMU 01 ADAM 6050 DIGITAL I/O FOR RMU STATUS AND CONTROL MODBUS TCP LAN1 - ALSOENERGY 113 DIGITAL I/O COMMON
DA1.2 172.24.1.103
DA2.1 172.24.2.102 114 CABLE FEEDER 1 CAPDIS S2+ NC
RMU 02 ADAM 6050 DIGITAL I/O FOR RMU STATUS AND CONTROL MODBUS TCP LAN1 - ALSOENERGY 115 CABLE FEEDER 1 CAPDIS S2+ NO
DA2.2 172.24.2.103
I RMU 03
DA3.1
ADAM 6050 DIGITAL I/O FOR RMU STATUS AND CONTROL MODBUS TCP LAN1 -
172.24.3.102
ALSOENERGY DI1.2
116 CABLE FEEDER 2 DC NC I
DA3.2 172.24.3.103 117 CABLE FEEDER 2 DC NO
DA4.1 172.24.4.102 DI2.2
RMU 04 ADAM 6050 DIGITAL I/O FOR RMU STATUS AND CONTROL MODBUS TCP LAN1 - ALSOENERGY 118 CABLE FEEDER 2 EW NC
DA4.2 172.24.4.103 DI3.2
119 CABLE FEEDER 2 EW NO
866-303-5668, USA
DA8.2 172.24.8.103 126 DIGITAL I/O COMMON
TRANSFORMER 1.1 ALARMS DA1.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.1.11 ALSOENERGY DO1.1 131 CB OPEN 1
K TRANSFORMER 1.2 ALARMS DA1.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.1.12 ALSOENERGY DO2.1 132 CB OPEN 2 K
TRANSFORMER 2.1 ALARMS DA2.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.2.11 ALSOENERGY DO3.1 133 CB CLOSE 1
TRANSFORMER 2.2 ALARMS DA2.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.2.12 ALSOENERGY DO4.1
134 CB CLOSE 2
TRANSFORMER 3.1 ALARMS DA3.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.3.11 ALSOENERGY DO5.1
DO6.1 135 LOCAL/REMOTE SWITCH NC
TRANSFORMER 3.2 ALARMS DA3.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.3.12 ALSOENERGY
TRANSFORMER 4.1 ALARMS DA4.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.4.11 ALSOENERGY DO7.1 136 LOCAL/REMOTE SWITCH NO
L DA4.5 DO8.1 137 DIGITAL I/O COMMON L
PWH
TRANSFORMER 4.2 ALARMS SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.4.12 ALSOENERGY
-
TRANSFORMER 5.1 ALARMS DA5.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.5.11 ALSOENERGY DO1.2 138 SPRING CHARGE NC
TRANSFORMER 5.2 ALARMS DA5.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.5.12 ALSOENERGY DO2.2
139 SPRING CHARGE NO
TRANSFORMER 6.1 ALARMS DA6.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.6.11 ALSOENERGY DO3.2
DO4.2 140 RS485 DATA+
TRANSFORMER 6.2 ALARMS DA6.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.6.12 ALSOENERGY
CHECKED BY:
DO5.2 141 RS485 DATA-
M TRANSFORMER 7.1 ALARMS DA7.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.7.11 ALSOENERGY
M
DRAWN BY:
DO6.2
TRANSFORMER 7.2 ALARMS DA7.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.7.12 ALSOENERGY 142 RS485 SHIELD
DO7.2
TRANSFORMER 8.1 ALARMS DA8.4 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.8.11 ALSOENERGY 143 DIGITAL I/O COMMON
DO8.2
TRANSFORMER 8.2 ALARMS DA8.5 SMA INVERTER INTEGRATED TRANSFORMER STATUS MODBUS TCP LAN1 - 172.24.8.12 ALSOENERGY
DATE:
WEATHER STATION ARRAY 2 WS2.1 LUFFT WS601-UMB MODBUS RTU RTU2.2 41 172.24.2.111 (503) ALSOENERGY
POA PYRANOMETER ARRAY 2 WS2.2 HUKSEFLUX SR-30 MODBUS RTU RTU2.2 42 172.24.2.111 (503) ALSOENERGY
N MODULE TEMPERATURE 1 ARRAY 2 WS2.3 IMT RS485 MODULE TEMPERATURE MODBUS RTU RTU2.1 43 172.24.2.111 (502) ALSOENERGY
LAN1 N
MODULE TEMPERATURE 2 ARRAY 2 WS2.4 IMT RS485 MODULE TEMPERATURE MODBUS RTU RTU2.1 44 172.24.2.111 (502) ALSOENERGY
GATEWAY 172.24.0.254
UPS WEATHER STATION 1 DA2.3 ALSOENERGY SMART UPS MODBUS TCP LAN1 192 172.24.2.241 ALSOENERGY
SUBNET MASK 255.255.0.0
WEATHER STATION ARRAY 5 WS5.1 LUFFT WS601-UMB MODBUS RTU RTU5.2 45 172.24.5.111 (503) ALSOENERGY
DHCP START 172.24.254.1
POA PYRANOMETER ARRAY 5 WS5.2 HUKSEFLUX SR-30 MODBUS RTU RTU5.2 46 172.24.5.111 (503) ALSOENERGY
DHCP END 172.24.254.254
MODULE TEMPERATURE 1 ARRAY 5 WS5.3 IMT RS485 MODULE TEMPERATURE MODBUS RTU RTU5.1 47 172.24.5.111 (502) ALSOENERGY
O O
SCHEDULES
MODULE TEMPERATURE 2 ARRAY 5 WS5.4 IMT RS485 MODULE TEMPERATURE MODBUS RTU RTU5.1 48 172.24.5.111 (502) ALSOENERGY
UPS WEATHER STATION 2 DA5.3 ALSOENERGY SMART UPS MODBUS RTU LAN1 192 172.24.5.241 ALSOENERGY
P WM621 P
11 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
EN0
A PRIMARY SCADA RACK LOCATED IN CONTROL HOUSE - DA BAC 1 - SA-RK-01 A
DESCRIPTION:
B B
PS0.1 DA0.1 GW0.1 GW0.2 GW0.3 GW0.4
DRAFTED
HMI, PPC
POWER SUPPLY SEL 3505 SKY-IPC SKY-IPC SKY-IPC SKY-IPC
INPUT 120-277VAC RTAC SKYLOG SKYLOG SKYLOG SKYLOG
OUTPUT 24VDC
C PS-277-52 SA-3505 C
2019-01-25
2019-02-26
2019-03-06
DATE:
IRIG-B
AC IN
ETH1
RJ45
RJ45
RJ45
RJ45
PWH
PWH
PWH
BY:
D AC AC D
IRIG-B
REV:
AC AC AC AC AC AC AC AC AC AC AC AC AC AC AC
1
2
3
AC AC AC AC AC AC AC AC AC AC AC AC AC
CB1
AC AC AC AC AC AC AC AC AC AC AC
AC
E E
AC
CP1
AC
AC
AC AC AC AC AC AC AC AC
AC
IRIG-B
AC AC AC AC AC AC AC
AC AC AC
AC
AC
220VAC
220VAC
220VAC
220VAC
220VAC
220VAC
220VAC
220VAC
220VAC
220VAC
AC
AC
F F
AC
AC
PS0.5
EST118150
IRIG-B
DA BAC 1
120-240VAC 85-264VAC 100-240VAC 100-240VAC 100-240VAC 100-240VAC 120-240VAC
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
G NET0.1 NET0.2 GW0.6 GW0.5 NET0.6 NET0.4 G
-
1 2 3 4 5 6 7 8
MANAGED ETHERNET SWITCH SEL 2407 SKYSERV LOCAL SKYSERV RTSO HMI SEL 3620
220VAC
16 - 10/100 RJ45 4 - 10/100/1000 RJ45 GPS CLOCK FIREWALL
IRIG-B
220VAC
4 SFP WITH SM LC
DA0.3 ET-2730 SA-HM-01 ET-3620
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
H H
INPUT 1
INPUT 2
UPS 220VAC
SM LC
SM LC
SM LC
SM LC
IRIG-B
ETH1
ETH2
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
VGA
VGA
USB
USB
ANT
SA-UPS-1.6KWHR
I I
220VAC
BATT
RJ45
VGA
USB
AC AC
SM LC
J PS0.2 PS0.3 PS0.4
J
AC
866-303-5668, USA
UP-BAT-120 UP-BAT-120 UP-BAT-120
48 STRAND
K K
SM LC
SM LC
AC
TO SUBSTATION NETWORK
L 1 CONFIGURED AND PROVIDED 1 L
PWH
-
1 BY OTHERS
220VAC WM639 9
ANT1
LTE5
EU4-16P
CHECKED BY:
NET0.7
M SUBSTATION M
DATE:
STATION 1 WM631
WM632 1 INVERSTATION INVERSTATION
N INVERSTATION 1 1-1 1-8 N
NOTES: WM632 WM639
CONTROL ROOM
2. SEL-2730M MANAGED SWITCH PANEL AND ETHERNET CONNECTION KEY SHOWN BELOW. WIRE LEGEND 1-2 1-7
GREEN - RJ45 FOR CAT5E ETHERNET FIBER MULTI MODE WM633 WM638
O PORTS 5-8: 10/100/1000 FIBER SINGLE MODE O
PORTS 9-20: 10/100 CAT5E INVERSTATION INVERSTATION
DA BAC 1
PURPLE - PORTS 21-24 LC CONNECTOR FOR SINGLE MODE FIBER SERIAL / RS485 1-3 1-6
24VDC POWER WM634 WM637
ALARM
12VDC POWER
SEL-2730M SEL-9330-C
ANALOG / PULSE / DRY CONTACT
7 8 17 18 19 20 21 22 23 24
INVERSTATION INVERSTATION
POWER SUPPLY
7 8
ENABLED
IN 24V/48V
MAX 1.7A, 42W
ALARM +3 -2 GND
P AC
WM631 P
1 OUT 12.5V
1 2
C1 C2
3
C3
4
17 18 19 20 21 22 23 24 MAX 2.9A, 36W
GND
AC POWER 1-4 1-5
5 6 9 10 11 12 13 14 15 16
C4
1 2 3 4 5 6 9 10 11 12 13 14 15 16
PWR
A A
EN1.1
NETWORK INVERSTATION 1 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO1.1
DO1.2
DI1.1
DI1.2
RP1.1
CP1.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-1
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM632 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 13 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN2.1
NETWORK INVERSTATION 2 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
24VDC IN 24VDC IN 24VDC IN
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
NET2.4 GW2.1 NET2.5
1
2
ETHERNET SWITCH POWERLOGGER RTU/TCP
COPPER/FIBER 1000 CONVERTER
AC
RJ45 LAN1
RJ45 LAN1
PORT1
PORT2
PORT1
PORT2
RJ45
RJ45
RJ45
RJ45
RJ45
DA2.3
AC
F UNINTERRUPTED F
FRP
POWER SUPPLY
UP-277-38
EST118150
RP2.3
DA BAC 1
INPUT 120-277VAC
OUTPUT 24VDC
AC
G IN NEMA 4 G
-
ENCLOSURE
16"X32"X16"
FUPS
CP2.2 CB1
FRP
CB1
CB1
H H
RTU2.1
RTU2.2
DO2.1
DO2.2
RP2.3
RP2.3
DI2.1
DI2.2
RP2.2
RP2.1
CP2.1
RP2.2
RJ45
I 120-277VAC 1ɸ 50-60HZ
I
AC
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
-
RS485 RS485 RS485 RS485
24VDC 24VDC 24VDC 24VDC
CHECKED BY:
M WS2.3 WS2.4 WS2.2 WS2.1 M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING TMOD TMOD %
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A
TAMB N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-2
INVERSTATION INVERSTATION SENSORS MOUNTED IN FIELD.
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE DISTRIBUTE MODULE TEMPERATURE
O FIBER SINGLE MODE SENSORS THROUGHOUT ARRAY.
SENSORS MOUNTED ON TOWER.
O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485 DO NOT MOUNT MODULE TEMPERATURE
WM634 WM637 24VDC POWER PROBE NEAR EDGE OF ARRAY.
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM633 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 14 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN3.1
NETWORK INVERSTATION 3 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO3.1
DO3.2
DI3.1
DI3.2
RP3.1
CP3.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-3
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM634 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 15 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN4.1
NETWORK INVERSTATION 4 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO4.1
DO4.2
DI4.1
DI4.2
RP4.1
CP4.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-4
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM635 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 16 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN5.1
NETWORK INVERSTATION 5 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
24VDC IN 24VDC IN 24VDC IN
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
NET5.4 GW5.1 NET5.5
1
2
ETHERNET SWITCH POWERLOGGER RTU/TCP
COPPER/FIBER 1000 CONVERTER
AC
RJ45 LAN1
RJ45 LAN1
PORT1
PORT2
PORT1
PORT2
RJ45
RJ45
RJ45
RJ45
RJ45
DA5.3
AC
F UNINTERRUPTED F
FRP
POWER SUPPLY
UP-277-38
EST118150
RP5.3
DA BAC 1
INPUT 120-277VAC
OUTPUT 24VDC
AC
G IN NEMA 4 G
-
ENCLOSURE
16"X32"X16"
FUPS
CP5.2 CB1
FRP
CB1
CB1
H H
RTU5.1
RTU5.2
DO5.1
DO5.2
RP5.3
RP5.3
DI5.1
DI5.2
RP5.2
RP5.1
CP5.1
RP5.2
RJ45
I 120-277VAC 1ɸ 50-60HZ
I
AC
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
-
RS485 RS485 RS485 RS485
24VDC 24VDC 24VDC 24VDC
CHECKED BY:
M WS5.3 WS5.4 WS5.2 WS5.1 M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING TMOD TMOD %
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A
TAMB N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-5
INVERSTATION INVERSTATION SENSORS MOUNTED IN FIELD.
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE DISTRIBUTE MODULE TEMPERATURE
O FIBER SINGLE MODE SENSORS THROUGHOUT ARRAY.
SENSORS MOUNTED ON TOWER.
O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485 DO NOT MOUNT MODULE TEMPERATURE
WM634 WM637 24VDC POWER PROBE NEAR EDGE OF ARRAY.
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM636 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 17 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN6.1
NETWORK INVERSTATION 6 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO6.1
DO6.2
DI6.1
DI6.2
RP6.1
CP6.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-6
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM637 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 18 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN7.1
NETWORK INVERSTATION 7 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO7.1
DO7.2
DI7.1
DI7.2
RP7.1
CP7.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-7
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM638 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 19 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
EN8.1
NETWORK INVERSTATION 8 - E4-XL-NL
D D
FIBER OUT
FIBER OUT
RJ45 LAN1
RJ45 LAN1
LC FIBER
LC FIBER
FIBER IN
FIBER IN
AC IN
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
DO
DO
DI
DI
1
2
E AC
AC E
F F
EST118150
DA BAC 1
AC
G G
-
FRP
CB1
H H
DO8.1
DO8.2
DI8.1
DI8.2
RP8.1
CP8.1
I 120-277VAC 1ɸ 50-60HZ
I
MAX LOAD 0.5A @220VAC
CONTROL STATUS RJ45 RJ45
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DATE:
WM631 FUSE / BREAKER TABLE
ID TYPE RATING
INVERSTATION INVERSTATION
N 1-1 1-8 FRP 5X20mm FAST FUSE 4A N
WM632 WM639
SINGLE POLE CIRCUIT
CB1 6A
BREAKER - DC RATED
INVERSTATION 1-8
INVERSTATION INVERSTATION
1-2 1-7 WIRE LEGEND
WM633 WM638 FIBER MULTI MODE
O FIBER SINGLE MODE O
INVERSTATION INVERSTATION CAT5E
1-3 1-6 SERIAL / RS485
WM634 WM637 24VDC POWER
12VDC POWER
INVERSTATION INVERSTATION ANALOG / PULSE / DRY CONTACT
P 1-4 1-5 AC
CT
AC POWER
WM639 P
WM635 WM636 CURRENT TRANSFORMER
VT VOLTAGE TAP/TRANSFORMER 20 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
DESCRIPTION:
DA0.3 SA-UPS-SMX-3000 SMART UPS 220VAC 50HZ INPUT ALSOENERGY
B MANAGED ETHERNET SWITCH - 20 COPPER
B
NET0.1 ET-2730 ALSOENERGY
DRAFTED
HMI, PPC
RJ45 - 4 SM LC FIBER
NET0.2 - SEL-2407 GPS CLOCK ALSOENERGY
U42 NET0.4 NET0.4 ET-3620 SEL-3620 FIREWALL ALSOENERGY
NET0.5 ET-FPP-48-S 48-STRAND SM LC FIBER PATCH PANEL ALSOENERGY
C NET0.2
C
2019-01-25
2019-02-26
2019-03-06
NET0.6 SA-HM-01 1U RACK MOUNTED HMI ALSOENERGY
U40
ALARM
SEL-2730M SEL-9330-C
POWER SUPPLY
7 8
ENABLED
IN 24V/48V
NET0.1
MAX 1.7A, 42W
ALARM +3 -2 GND
DATE:
C1 C2 C3 17 18 19 20 21 22 23 24 MAX 2.9A, 36W
1 2 3 4 GND
C4
PWR
5 6 9 10 11 12 13 14 15 16
PWH
PWH
PWH
DC POWER SUPPLY - INPUT 120-277VAC -
BY:
PS0.1 PS-277-52 ALSOENERGY
D OUTPUT 24VDC 52W MAX D
REV:
DA0.1 SA-3505 SEL-3505 RTAC ALSOENERGY
NET0.5 U36
GW0.1 - SKY-IPC SKYLOG ALSOENERGY
1
2
3
GW0.2 - SKY-IPC SKYLOG ALSOENERGY
GW0.3 - SKY-IPC SKYLOG ALSOENERGY
U34
E GW0.4 - SKY-IPC SKYLOG ALSOENERGY E
ALL OTHER INTERNAL COMPONENTS INCLUDING CABLES, CONDUCTORS, TERMINAL BLOCKS, DIN
RAIL AND PROTECTIVE DEVICES TO BE SUPPLIED BY ALSOENERGY
U32 2U RACK SHELF
4U REQUIRED FOR
DA0.1 PS0.1 DEVICE CLEARANCE.
F U30 GW0.1 GW0.2 GW0.3 GW0.4 SEE WM652 FOR F
DETAIL
EST118150
DA BAC 1
U28
GW0.5
G G
-
U26
GW0.6
U24 NET0.6
H H
FRONT
U22 40"
866-303-5668, USA
U14
K K
48" U12
PS0.2
41"
U10
L L
PWH
-
U8
PS0.3
CHECKED BY:
M M
DRAWN BY:
U6
DATE:
U4
PS0.4
N N
U2
CONTROL ROOM
PANEL LAYOUT
O O
DA BAC 1
41"
A A
DRAFTED
HMI, PPC
RACK SHELF DETAIL
C C
2019-01-25
2019-02-26
2019-03-06
DATE:
PWH
PWH
PWH
BY:
D D
REV:
1
2
3
PS0.1
E E
DA0.1
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
-
OUTPUT 24VDC 52W MAX
DA0.1 SA-3505 SEL-3505 RTAC ALSOENERGY
GW0.1 - SKY-IPC SKYLOG ALSOENERGY
GW0.2 - SKY-IPC SKYLOG ALSOENERGY
H GW0.3 - SKY-IPC SKYLOG ALSOENERGY
H
GW0.4 - SKY-IPC SKYLOG ALSOENERGY
ALL OTHER INTERNAL COMPONENTS INCLUDING CABLES, CONDUCTORS, TERMINAL BLOCKS, DIN
RAIL AND PROTECTIVE DEVICES TO BE SUPPLIED BY ALSOENERGY
I I
GW0.1 GW0.2 GW0.3 GW0.4
866-303-5668, USA
K K
L L
PWH
-
FRONT
CHECKED BY:
M M
DRAWN BY:
DATE:
N N
PANEL LAYOUT
RACK SHELF
O O
DETAIL
P WM652 P
22 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET1.1 G
-
DA1.1 DA1.2
EN1.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-1
PANEL LAYOUT
O O
P WM653 P
23 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET2.1 G
-
DA2.1 DA2.2
EN2.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-2
PANEL LAYOUT
O O
P WM654 P
24 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET3.1 G
-
DA3.1 DA3.2
EN3.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-3
PANEL LAYOUT
O O
P WM655 P
25 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET4.1 G
-
DA4.1 DA4.2
EN4.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-4
PANEL LAYOUT
O O
P WM656 P
26 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET5.1 G
-
DA5.1 DA5.2
EN5.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-5
PANEL LAYOUT
O O
P WM657 P
27 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET6.1 G
-
DA6.1 DA6.2
EN6.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-6
PANEL LAYOUT
O O
P WM658 P
28 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET7.1 G
-
DA7.1 DA7.2
EN7.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-7
PANEL LAYOUT
O O
P WM659 P
29 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
C C
1
2
E E
F F
EST118150
DA BAC 1
ID PART NUMBER DESCRIPTION SUPPLIED BY
G NET8.1 G
-
DA8.1 DA8.2
EN8.1 E4-XL-NL NEMA 4 ENCLOSURE 31.5"X31.5"X12" ALSOENERGY
GND
GND
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
Rev. 1.4
DATE:
N N
INVERSTATION 1-8
PANEL LAYOUT
O O
P WM660 P
30 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
DESCRIPTION:
B B
1
2
E E
F F
EST118150
DA BAC 1
EN2.2
WEATHER STATION 1 - E4-ST-NL
G G
-
15.7"x15.7"x7.9" [400x400x200 mm]
NET2.4
GW2.1
NET2.5
H H
G
LAN G RX TX
V+ ZK
RS232
VDC
I I
G + - G + -
P1 10 11 12 TR 13 14 15 16 TR 17 P2
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
ID PART NUMBER DESCRIPTION SUPPLIED BY
DATE:
GW2.1 CH-E0-1000 INDUSTRIAL DATA LOGGER ALSOENERGY
INDUSTRIAL ETHERNET SWITCH - 5 COPPER
NET2.4 ET-UW-05 ALSOENERGY
N RJ45 N
NET2.5 ET-CV-02 MODBUS RTU/TCP CONVERTER ALSOENERGY
WEATHER STATION 1
38Ah UPS - INPUT 120-277VAC - OUTPUT
DA2.3 UP-277-38 ALSOENERGY
24VDC 52W MAX
PANEL LAYOUT
ALL OTHER INTERNAL COMPONENTS INCLUDING CABLES, CONDUCTORS, TERMINAL BLOCKS, DIN
RAIL AND PROTECTIVE DEVICES TO BE SUPPLIED BY ALSOENERGY
O O
P WM661 P
31 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
DESCRIPTION:
B B
1
2
E E
F F
EST118150
DA BAC 1
EN5.2
WEATHER STATION 2 - E4-ST-NL
G G
-
15.7"x15.7"x7.9" [400x400x200 mm]
NET5.4
GW5.1
NET5.5
H H
G
LAN G RX TX
V+ ZK
RS232
VDC
I I
G + - G + -
P1 10 11 12 TR 13 14 15 16 TR 17 P2
866-303-5668, USA
K K
L L
PWH
CHECKED BY: -
M M
DRAWN BY:
ID PART NUMBER DESCRIPTION SUPPLIED BY
DATE:
GW5.1 CH-E0-1000 INDUSTRIAL DATA LOGGER ALSOENERGY
INDUSTRIAL ETHERNET SWITCH - 5 COPPER
NET5.4 ET-UW-05 ALSOENERGY
N RJ45 N
NET5.5 ET-CV-02 MODBUS RTU/TCP CONVERTER ALSOENERGY
WEATHER STATION 2
38Ah UPS - INPUT 120-277VAC - OUTPUT
DA5.3 UP-277-38 ALSOENERGY
24VDC 52W MAX
PANEL LAYOUT
ALL OTHER INTERNAL COMPONENTS INCLUDING CABLES, CONDUCTORS, TERMINAL BLOCKS, DIN
RAIL AND PROTECTIVE DEVICES TO BE SUPPLIED BY ALSOENERGY
O O
P WM662 P
32 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
BELDEN 7919A OR RS485 WIRING
EQUIVALENT
SHIELDED CAT 5E. · EACH RS485 BUS MAY SUPPORT A SINGLE DAISY CHAIN. DO NOT WIRE AS A STAR CONFIGURATION AND ENSURE
TO LOCAL AREA NETWORK AND INTERNET
DESCRIPTION:
B THAT ALL STUBS ARE LESS THAN 50 FEET. IRREGULAR COMMUNICATION AND DATA LOSS MAY RESULT IF
COMMUNICATION LINES ARE NOT WIRED IN A DAISY CHAIN TOPOLOGY.
B
1
DATA COMMON 10 14 20 24
DATA + 11 15 21 25
E DATA - 12 16 22 26 E
SHIELD/DRAIN 13 17 23 27
G + - G + - NOTE: DATA +/- MAY BE LABELED AS DATA A/B ON SOME DEVICES, HOWEVER THE POLARITY OF A AND B IS NOT STANDARDIZED. ALWAYS
P1 10 11 12 TR 13 14 15 16 TR 17 P2
REFER TO MANUFACTURER DOCUMENTS TO DETERMINE PROPER POLARITY AND WIRE ACCORDING TO POSITIVE / NEGATIVE RATHER THAN A /
B. DEVICES WILL NOT COMMUNICATE IF POLARITY IS REVERSED.
F F
EST118150
FIRST DEVICE LAST DEVICE
DA BAC 1
RS485 RS485
DATA COMMON
DATA COMMON
DATA COMMON
G G
10
11
12
13
14
15
16
17
-
TERMINATION TERMINATION TERMINATION
RESISTOR RESISTOR RESISTOR
TERMINATION RESISTOR NOT
DATA +
DATA +
DATA +
DATA -
DATA -
DATA -
ON ON ON TYPICALLY USED FOR 9600 BAUD
COMMUNICATION. IF USED THEN
ENSURE THAT ONLY THE FINAL
OFF OFF OFF
H DEVICE IN A DAISY CHAIN USES THE H
TERMINATION RESISTOR, ALL OTHERS
MUST BE SET TO 'OFF.'
I I
LAND SHIELD/DRAIN AT ONE END USE BELDEN 3106A OR SPLICE SHIELD AT EACH TRIM AND INSULATE SHIELD/DRAIN AT
OF THE DAISY CHAIN ONLY. EQUIVALENT SHIELDED, JUNCTION. INSULATE FINAL DEVICE IN CHAIN, DO NOT LAND
866-303-5668, USA
K K
RTU
L SLAVE L
PWH
-
RTU RTU RTU
MASTER CORRECT MASTER INCORRECT MASTER INCORRECT
CHECKED BY:
M M
DRAWN BY:
RTU RTU
RTU RTU RTU RTU RTU RTU RTU RTU SLAVE SLAVE
DATE:
SLAVE SLAVE SLAVE SLAVE SLAVE SLAVE SLAVE SLAVE
N N
RTU
SLAVE RTU RTU RTU
SLAVE SLAVE SLAVE
RS485 WIRING
O O
DETAIL
P WM701 P
33 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
COPPER CONDUCTOR BELDEN 7919A OR
12-24 AWG. EQUIVALENT
A SHIELDED CAT 5E. A
DESCRIPTION:
B B
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
1
E ADAM 6050 E
F F
EST118150
DA BAC 1
Iso. GND
(B)GND
(R)+Vs
COPPER CONDUCTOR
DI10
DI11
DO0
DO1
DO2
DO3
DO4
DO5
DI8
DI9
12-24 AWG.
G G
-
TO 24VDC POWER SOURCE
H H
COPPER CONDUCTOR
12-24 AWG.
I I
866-303-5668, USA
K K
L L
PWH
-
LOAD
CHECKED BY:
M M
DRAWN BY:
DATE:
NORMALLY CLOSED NORMALLY OPEN
COMMON 10-30VDC
N CONTACT CONTACT N
DIGITAL I/O
DETAIL
P WM702 P
34 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A PROVIDED BY ALSOENERGY
A
DESCRIPTION:
WIRE COLOR SIGNAL
B 1. EXTEND SENSOR CABLES TO SOLAR FIELD B
USING SHIELDED CAT5E OR EQUIVALENT. BLUE NOT USED
1
5. MODULE TEMPERATURE PROBE MOUNTED
TO BACK OF PANEL.
6. TOWER HEIGHT: ADJUSTABLE 9-12' MOUNT SO THAT THE CABLE
E IS ON THE NORTH SIDE OF E
NOTE: APPROXIMATE WEIGHT INCLUDING THE PYRANOMETER
TOWER MAXIMUM SENSORS AND ENCLOSURES: 110lbs
RECOMMENDED WIND
LOAD 110mph.
F F
USE LEVELING SCREWS TO
EST118150
ENSURE THE PLANE OF
DA BAC 1
ARRAY PYRANOMETER IS
IN-PLANE WITH THE SOLAR
ARRAY IN ALL DIRECTIONS
G G
-
MET STATION
H ENCLOSURE H
REFERENCE
I MARK POINTED I
TRUE NORTH,
ADJUST FOR
MAGNETIC
866-303-5668, USA
BACK OF MODULE
ROD 2 NEAR CENTER OF ARRAY
K 1 2 K
MAST
4
CLAMP
LUFFT CABLE
5
CONNECTION
L L
PWH
-
LUFFT CABLE
WIRE COLOR SIGNAL PIN
NORTH WHITE SUPPLY POWER NEGATIVE 1
CHECKED BY:
M M
DRAWN BY:
3 BROWN SUPPLY POWER POSITIVE 2
GREEN RS485 DATA + 3
DATE:
YELLOW RS485 DATA - 4
MODULE TEMPERATURE PROBE GRAY NOT USED 5
TYPICAL OF 2 PER MET STATION
N PINK NOT USED 6 N
BLUE HEATER POWER NEGATIVE 7
RED HEATER POWER POSITIVE 8
WEATHER TOWER
INSTALLATION 1
O 24" 24" O
DETAIL
P WM703 P
35 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A A
WEATHER TOWER ENCLOSURE INSTALLATION
DESCRIPTION:
B B
C C
1
E E
F F
MET
STATION
EST118150
DA BAC 1
ENCLOSURE
AND UPS
G 31.25" G
-
H H
I I
866-303-5668, USA
TOWER BASE
K K
2"
18"
L L
PWH
-
ANCHOR
24" BOLT 24"
CHECKED BY:
M WEATHER M
DRAWN BY:
TOWER
BASE
DATE:
CONCRETE
PAD 10.25"
N 24" N
WEATHER TOWER
INSTALLATION 2
SIDE VIEW TOP VIEW
O O
DETAIL
P WM704 P
36 OF 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21