Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Instructions to Students:
01. You are allowed 10 minutes EXTRA reading time to familiarize, evaluate
and study the requirements being asked in all the problems before
starting to write your solutions.
02. Begin each answer on a fresh page, avoid too many erasures and use
both sides of the answer sheet.
03 Write your candidate number at the top of each attached answer sheet.
04. Write clearly the number(s) of the question(s) attempted on the top of
each sheet.
05. Insert all written foolscap, drawing paper, etc. in their correct sequence
and secure with string.
06. Candidates are warned not to open any Structural Design 2 lecture
notes. Any attempt to do so and was caught shall be outright
disqualification to sit in the Final Examination and the student shall be
subject to academic disciplinary action, THE PENALTY OF WHICH IS
SUSPENSION FOR ONE YEAR.
08. Use black or blue ball pen in answering, pencils are not allowed, except
for drawing figures.
1
QUESTION 1
(30 marks)
The second floor rectangular beams of an office building will carry the load of the
concrete floor slab as shown in the figure below.
x x
L
Beam to be
designed L
Y
L1 L1
D The beam to
be designed
Sectional view Y - Y
D = 400 mm ; b = 240mm
A B C
L1 =4,500mm L1 = 4,500mm
Sectional view x - x
2
240 mm
d=350 mm
50 mm
(i) Develop bending moment diagram and shear force diagram using the simplified
method of structural analysis;
(ii) Determine the value of (‐) M*(min) and (+)M*(min);
(iii) Design the negative bending reinforcement over the first interior support of the end
span only of the rectangular beam. Use D16 main reinforcement;
(iv) Determine the spacing of stirrups at the interior support;
3
QUESTION 2
(15 marks)
QUESTION 3
(10 marks)
A 310 UC 118 is used as a column to carry axial load N* . It has an unsupported length
of 4.60 meters. Using fy = 300 MPa, Es = 200,000 MPa. Determine the maximum axial
load it could carry for the following end support conditions.
a) Both ends are fixed (ke = 0.70)
b) Both ends are pinned (ke = 1.0)
c) One end fixed and other end pinned (ke = 0.85)
N*
L = 4.6 m
4
QUESTION 4
(10 marks)
A bolted connection shown in figure below is using a 32.22 mm diameter bolt. Thread Length
is 38 mm.
Grip L
12mm 25mm 12mm
L required
x 38 mm
Figure Q4
5
QUESTION 5
(20 marks)
MA
wkN/m
A
B C
6,000mm 6,000 mm
Figure Q5
6
QUESTION 6
(15 marks)
A 7.50 meters steel truss is shown in Figure Q6. By method of joint/method of section and by
Maxwell truss diagram, the maximum axial compressive force on the top chord of the truss was
found acting on member AB with a magnitude of 2300 kN. Assuming no bolt holes with fy=
300 MPa, Kf=1.00 (for pin connected members of a Steel Truss), determine a size of universal
column that will be structurally adequate to support the maximum axial compressive force in
the top chord of the truss.
a) Also, check the nominal section capacity of the designed section, and
b) Design the web with regards to shear strength. Use Plasticity Slenderness
Parameter Limit λsp =9.0.
Rise = 1.70m
B
A
1.5 1.50 1.5 1.50 1.5
Figure Q6
N* =2300.0 kN
1.372 m
A
Member AB of Truss
N*= 2300.0 kN