EQUIPMENT TAGS:
SERVICE DESCRIPTION: CURRENT TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33014
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER
0 GENERAL
0 Manufacturer - VTS
0 Manufacturer location - VTS
0 Model No. - VTS
0 Serial No. - VTS
0 No. of years CT type in service (local/overseas) Years VTS
0 Year of manufacture - VTS
2.0 SITE CONDITIONS
2.1 Site conditions specification - XXXXX-XXXX-GXXXX
2.2 Pollution level -
2.3 Atmospheric conditions
2.4 Altitude above sea level m
2.5 Adverse ambient temperature conditions o
C
2.5 Design ambient temperature o
C
2.6 Seismic activity hazard factor (Z) -
2.7 Geographical location -
2.8 Project area
2.9 Hazardous area -
2.10 Environment -
2.11 Solar irradiance (maximum) W/m2
2.12 Design wind load m/s
2.13 Design life Years
3.0 SYSTEM PARAMETERS (not equipment rating)
3.1 System Nominal voltage kV 132
3.2 Supply frequency Hz 50, +/- 1Hz
3.3 Number of phases
3.4 System short circuit level kA/s
3.5 System earthing -
4.0 CURRENT TRANSFORMER SPECIFICATIONS
4.1 System Maximum voltage kV 145
4.2 Secondary cores 1 & 2
4.3 CT Ratio
4.4 Class
4.5 Specification
4.6 Secondary core 3
4.7 CT Ratio
4.8 Class
4.9 Specification
4.10 Secondary cores 4 & 5
4.11 CT Ratio
4.12 Class
4.13 Specification
4.14 Rated secondary current
4.15 Power frequency withstand voltage kV
4.16 Lightning impulse withstand voltage' kVp
4.17 Short time current withstand (rms) kA rms/s
4.18 Short time current withstand (peak) kA p
4.19 Service location Outdoor
5.0 CURRENT TRANSFORMER GENERAL
5.1 Type of insulation Oil / SF6 VTS
5.2 Type of oil VTS
5.3 Oil volume/ Weight L/kg VTS
5.4 Oil specification /standard VTS
5.5 SF6 Gas
5.6 Leakage Rate % per year VTS
5.7 Volume litres VTS
5.8 Pressure Atm VTS
5.9 Temperature rise at rated current:
5.10 Winding oC VTS
5.11 Core oC VTS
5.12 Oil oC VTS
5.13 Degree of Protection of secondary terminal box Specify IP rating
5.14 Secondary wiring Specify min. size
5.15 HV terminal type VTS
5.16 Main terminal material VTS
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779467.xlsx.xls


Page 2 of 17
0

0 DOC NO REV

0 0 0
0
EQUIPMENT TAGS:
SERVICE DESCRIPTION: CURRENT TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33014
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

5.0 CURRENT TRANSFORMER GENERAL


5.17 Terminal loads on each palm terminal Vertical/Transverse/Horizontal N VTS -
5.18 Bushings/Insulators:
5.19 Manufacturer /country VTS
5.20 Material VTS
5.21 Colour
5.22 Creepage distance for insulators/Interrupters mm/kV

5.23 Maximum guaranteed steady working cantilever strength of bushing (force applied
at terminal palm) N VTS
5.24 Partial discharge inception/ extinction voltage kV VTS
5.25 Max Partial discharge@ 1.50Um/ Ö3 pC VTS
5.25 Max DDF for Primary insulation in new condition mrad VTS
5.26 Class of insulation VTS
5.27 Hermetically sealed Yes/No VTS
5.28 Max pressure of inert gas @ max ambient temp Pa VTS
5.29 Max. oil quantity for sampling without refilling Litre VTS
5.30 Material of Primary winding/cross section area Specify material/ VTS
5.31 Material of Secondary winding/section area Specify material/ VTS
5.32 Tank and fittings:
5.33 Tank ferrous surface protection – hot dip galvanised VTS
5.34 Oil level indicator VTS
5.35 Bellow level indicator (top) VTS
5.36 Drain valve, filling/ sampling valve VTS
5.37 Lifting lugs VTS
5.38
5.39
5.40
5.41
5.42
6.0 STRUCTURAL DESIGN FOR DISCONNECTOR & SUPPORT STRUCTURE
6.1 Earthquake Loading:

6.2 AS 1170.4 -1993, Minimum Design


Loads on Structures, Part 4 -
Standard Earthquake Loads.
6.3 Structural Classification
6.4 Wind Loading:

AS 1170.2 -1989, Minimum design


6.5
Loads on Structures, Part 2 Wind
Standard loads.
6.6 Ultimate wind speed/region m/sec
6.7 Region / Terrain category
6.8 Importance factor
6.9 Cd - for insulators
7.0 TESTING AND INSPECTION
7.1 Type Test - Test Certificate as per IEC/AS
7.2 Routine Tests - As per AS
7.3 -
8.0 DIMENSIONS AND WEIGHT
8.1 Total Length mm VTS
8.2 Total Height mm VTS
8.3 Total Width mm VTS
8.4 Total Weight kg VTS
8.5
8.6
8.7
8.8

Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779467.xlsx.xls


Page 3 of 17
0

0 DOC NO REV

0 0 0
0
EQUIPMENT TAGS:
SERVICE DESCRIPTION: CURRENT TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33014
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

9.0 APPLICABLE SPECIFICATIONS & DRAWINGS


9.1
9.2
9.3
9.4
10.0 APPLICABLE STANDARDS
10.1 AS/ IEC 60044.1 Instrument Transformers - Current transformers

10.3 AS 1824.1 Insulation co-ordination - Definitions, principles and rules

Insulation co-ordination (phase-to-earth and phase-to-phase, above 1kV) -


10.4 AS 1824.2
application guide

10.5 AS 1931 High Voltage test techniques

Switchgear assemblies and ancillary equipment for alternating voltages above


10.6 AS 2067
1kV

10.7 AS 2650 Common specifications for high voltage switchgear and controlgear standards

10.8 AS/NZS 3000 SAA Wiring Rules

10.9 AS 4398 Insulators - ceramic and glass - station post for indoor and outdoor use

10.10 AS 4436 Guide for selection of insulators in respect of polluted conditions

10.11 AS 4680 Hot-Dip Galvanised (Zinc) Coatings on Fabricated Ferrous Articles

Hot-dip galvanized (zinc) coatings on ferrous hollow sections, applied by a


10.12 AS/NZS 4792
continuous or a specialized process

10.13 AS/NZS 60137 Insulated bushings for alternating voltages above 1000V

High voltage switchgear and controlgear - Dimensional standardisation of


10.14 AS/ IEC 62271.301
terminals

10.15 AS 1170 Series Structural Design Actions


11.0 LIST OF TERMS USED IN THIS DATA SHEET
11.1 CVT Capacitor Voltage Transformer
11.2 TBA To Be Advised
11.3 VTS Vendor To Specify

Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779467.xlsx.xls


Page 4 of 17
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

1.0 GENERAL
1.1 Manufacturer - STS
1.2 Manufacturer Location - STS
1.3 Model - STS
1.4 Design Standard - STS
1.5 Switchboard Technical Specification - 11442-0000-E0710
1.6 Wiring Identification Specification - 11442-0000-E0710
1.7 Single Line Diagram - Refer to Requisition
1.8
2.0 SITE CONDITIONS
2.1 Site Conditions Specification - 11442-0000-G0713
2.2 Altitude Above Sea Level m <1000
2.3 Design Ambient Temperature o
C 0-40
2.4 Seismic Condition - NA -
2.5 Location - Indoor
2.6 Environment - Indoor
2.7
3.0 SYSTEM PARAMETERS
3.1 System Voltage kV 11, +10% to -11%
3.2 Supply Frequency Hz 50, +/- 1Hz
3.3 No. of Phases - 3
3.4 System Prospective Short Circuit Current (Symmetrical RMS) kA/s 31.5kA / 3s
3.5 System Short Circuit Peak Current kA 60 70 - TBC P2
3.6 System Earthing - Resistance - TBA
3.7
4.0 SWITCHBOARD GENERAL
4.1 Rated Voltage kV 12
4.2 Rated Frequency Hz 50
4.3 Insulation Medium AIS / GIS AIS
4.4 Rated Short Circuit Withstand Current and Duration kA/s 31.5kA / 3s
4.5 Rated Peak Withstand Current kA 70
4.6 Rated Short Time Power Frequency Withstand kV 28
4.7 Rated Impulse Withstand Voltage kV 75
4.8 Type Test Certificate Number - STS
4.9 Type Testing Authority - STS
4.10 Arc Fault Containment Required Y/N Y
4.11 Duration of Arc Fault Test s STS
4.12 Name of Arc Testing Authority - STS
4.13 Total Switchboard Heat Loss at Full Load W STS
5.0 SWITCHBOARD BUSBARS
5.1 Busbar arrangement / Busbars per phase - STS
5.2 Busbar Material - Fully Insulated Cu
5.3 Main Busbar Size mm2 STS
5.4 Main Busbar Current Rating A 630A
5.5 Main Earth Busbar Size mm2 STS
5.6 Main Earth Busbar Current Rating A STS
5.7 Main Earth Bar Location - STS
5.8 Busbar Earth Switch (with Mechanical Interlock) Yes/No Yes
REV DATE BY CHK APPR AUTH DESCRIPTION
P1 7/28/2011 BR CJC CJC JR Issue for Client Review
P2 8/23/2011 BR CJC CJC JR Issue for Client Approval

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 5 of 17


473779467.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

6.0 AUXILIARY VOLTAGE


6.1 Auxiliary Voltage - Protection & Tripping Internal / External External
6.2 -Auxiliary Voltage Supply Rating (Switchboard Demand) W STS
6.3 -Voltage / Tolerance V/% 48V dc / 10%
6.4 -Peak Demand A STS
6.5 -Load per Circuit Breaker Trip Coil A STS
6.6 Auxiliary Voltage - Closing, Motor and spring charging Internal / External External
6.7 -Voltage / Tolerance V/% 48V dc / 10%
6.8 -Peak Demand A STS
6.9 -Load per Circuit Breaker Close Coil A STS
6.10 -Load per Circuit Breaker Charging A STS
6.11 Auxiliary Voltage - Heaters Internal / External External
6.12 Auxiliary Voltage Supply - Tolerance V/% 230V ac
6.13 -Peak Demand W STS
6.14 -Motor Heater Voltage V 230V ac
7.0 SWITCHBOARD - CONSTRUCTION
7.1 Future Extension - Both ends
7.2 Total Number of Tiers - 6
7.3 Incomer Sections - 1
7.4 Bus Tie Sections - None
7.5 Feeder Sections - 1
7.6 Motor Feeder Sections - 1
7.7 Switchboard Type - Partition Metallic
7.8 Enclosure IP Rating IP 42 41 P2
7.9 Enclosure Material - Steel 2mm
7.10 Module Type Withdrawable / Fixed Withdrawable
7.11 Power Cables - Cable Entry Top / Bottom Bottom
7.12 Control Cables - Cable Entry Top / Bottom Top
7.13 Gland Plate Material and Size - Al, 6mm
7.14 Surface Finish - Supplier standard
7.15 Colour Internal - Supplier standard
7.16 Colour External - RAL 7035
8.0 SWITCHBOARD - DIMENSIONS AND WEIGHTS
8.1 Overall Dimension (L x W x H) mm STS
8.2 Minimum Clearance Required at Front of Switchboard mm STS
8.3 Minimum Clearance Required at Rear of Switchboard mm <100mm typ
8.4 Minimum Clearance Required at Side of Switchboard mm <100mm typ
8.5 Minimum Clearance Required Above Switchboard mm <100mm typ
8.6 Lifting Arrangement - STS
8.7 Total Installed Weight kg STS
8.8 Total Shipping Weight kg STS
8.9 Shipping Section (L x W x H) and Qty mm / ea STS
8.10 Maximum Shipping Section Weight kg STS
9.0 ACCESSORIES AND OPTIONS
9.1 Circuit Breaker Trolley Y/N Y
9.2 CB Racking Handles Y/N Y
9.3 CB Charging Handles Y/N Y
9.4 Special Tools Y/N Y
9.5 Earth Switch Charging Handle Y/N Y
9.6 Remote Switchboard Control Panel Y/N Note 3
9.7 Remote PCS Control Y/N Y
9.8 Load Shedding Panel Y/N N -
9.9 Switchboard Monitoring and Control System Y/N Part of PCS -
9.10 Anticondensation Heaters Y/N Y
9.11 Fire Detection Y/N N -
9.12 Fire Suppression Y/N N -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 6 of 17


473779467.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

10.0 SWITCH BOARD AUXILIARY CONTROL EQUIPMENT MAKES AND MODELS


10.1 Miniature Circuit Breakers - -
10.2 Make / Type - STS
10.3 Rated Voltage kV STS
10.4 Control Voltage Transformer - -
10.5 Make / Type - STS
10.6 Voltage Ratio V/V STS
10.7 Rating VA STS
10.7 Load Capacity Calculation Basis - STS
10.8 DC Power Supply - External , By Others
10.9 Make / Type - NA
10.10 Vin / V Out V/V NA
10.11 Amps Continuous A NA
10.12 AC Control Relays - -
10.13 Make / Type - STS
10.13 Rated Voltage V ac 230V ac
10.14 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.15 Auxiliary Contact Rating V/A 230V ac, 10A
10.16 DC Control Relay - -
10.17 Make / Type - STS
10.18 Rated Voltage V dc 48
10.19 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.20 Auxiliary Contact Rating V/A 48V dc, 5A
10.21 Control Switches - Make / Type - STS
10.22 Control Switches - Voltage V STS
10.23 Pushbuttons - Make / Type - STS
10.24 Power Terminals Make / Type - STS
10.25 Control Terminals Make / Type - STS
11.0 SWITCHBOARD TIER - CURRENT TRANSFORMERS
11.1 Protection CT Manufacturer - STS
11.2 Protection CT Burden and Class - STS
11.3 Protection CT Ratio A/A As per Single Line Diagram
11.5 Differential Protection CT Manufacturer - STS
11.7 Differential Protection CT Burden and Class - STS
11.6 Differential Protection CT Ratio A/A As per Single Line Diagram
11.8 Earth Leakage Toroid Manufacturer - STS
11.9 Earth Leakage Toroid Ratio A/A As per Single Line Diagram
11.10 Earth Leakage Toroid Class - STS
11.11 Transformer Neutral CT Manufacturer - By Others -
11.12 Transformer Neutral CT Ratio A/A By Others -
11.13 Transformer Neutral CT Burden and Class - By Others -
12.0 SWITCHBOARD TIER - VOLTAGE TRANSFORMERS
12.1 Voltage Ratio V/V 11kV / 110V
12.2 Power / Class VA STS
12.3 Fixed / Withdrawable - STS
12.4 Primary Fuse Rating A STS
12.5 Secondary Fuse Rating A STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 7 of 17


473779467.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

13.0 SWITCHBOARD TIER


13.1 Service - Incomer
13.2 Device Type - Circuit Breaker
13.3 Device Model / Manufacturer - STS
13.4 Switching Device Insulation Type SF6 / Vacuum STS
13.5 Continuous Rating A 630A
13.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
13.7 Rated Short Circuit Breaking Current rms kA 31.5
13.8 Rated Short Circuit Making Current rms kA STS
13.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
13.10 Earth Switch Making Current Capacity kA STS
13.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
13.12 Spring Charging Manual Y/N Y
13.13 Spring Charging Motorized Y/N Y
13.14 Operation Duty - STS
13.15 Number of Operations per Annum - STS
13.16 Opening Time ms STS
13.17 Protection Scheme - Refer Single Line Diagram
13.18 Shunt Trip Coil Y/N Y
13.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min. 90%
13.20 No Voltage Coil Y/N N -
13.21 Amp Metering Switch & Ammeter Y/N N -
13.22 Volt Metering Switch & Voltmeter Y/N N -
13.23 Key Interlocking System Description - None
13.24 Surge Arrestor Y/N Y
13.25 Cable Type - Cu, XLPE/SWA/XLPE
13.26 Cable Entry - Bottom
13.27 Max Cable Size mm2 1 x 3C 95mm2
13.28 Live Cable Indication Y/N Y
13.29 Tier Section Dimensions (L x W x H) mm STS
14.0 SWITCHBOARD TIER
14.1 Service - Bus Tie
14.2 Device Type - Circuit Breaker
14.3 Device Model / Manufacturer - STS
14.4 Switching Device Insulation Type SF6 / Vacuum STS
14.5 Continuous Rating A 630A
14.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
14.7 Rated Short Circuit Breaking Current rms kA 31.5
14.8 Rated Short Circuit Making Current rms kA STS
14.9 Spring Charging Manual Y/N Y
14.10 Spring Charging Motorized Y/N Y
14.11 Operation Duty - STS
14.12 Number of Operations per Annum - STS
14.13 Opening Time (Full Load) ms STS
14.14 Protection Scheme - NA
14.15 Shunt Trip Coil Y/N N -
14.16 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
14.17 No Voltage Coil Y/N N -
14.18 Key Interlocking System Description - None
14.19 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 8 of 17


473779467.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

15.0 SWITCHBOARD TIER


15.1 Service - Typical Feeder
15.2 Device Type - Circuit Breaker
15.3 Device Model / Manufacturer - STS
15.4 Switching Device Insulation Type SF6 / Vacuum STS
15.5 Continuous Rating A 630A
15.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
15.7 Rated Short Circuit Breaking Current rms kA 31.5
15.8 Rated Short Circuit Making Current rms kA STS
15.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
15.10 Earth Switch Making Current Capacity kA STS
15.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
15.12 Spring Charging Manual Y/N Y
15.13 Spring Charging Motorized Y/N Y
15.14 Operation Duty - STS
15.15 Number of Operations per Annum - STS -
15.16 Opening Time ms STS -
15.17 Protection Scheme - Refer Single Line Diagram
15.18 Shunt Trip Coil Y/N Y
15.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min 90%
15.20 No Voltage Coil Y/N Motor Starter only
15.21 Amp Metering Switch & Ammeter Y/N N -
15.22 Volt Metering Switch & Voltmeter Y/N N -
15.23 Key Interlocking System Description - None
15.24 Surge Arrestor Y/N Y
15.25 Cable Type - Cu, XLPE/SWA/XLPE
15.26 Cable Entry - Bottom
15.27 Max Cable Size mm2 1 x 3C 95mm2
15.28 Live Cable Indication Y/N Y
15.29 Tier Section Dimensions (L x W x H) mm STS
16.0 SWITCHBOARD TIER
16.1 Service - Typical Motor Starter
16.2 Device Type - Circuit Breaker
16.3 Device Model / Manufacturer - STS
16.4 Switching Device Insulation Type SF6 / Vacuum STS
16.5 Continuous Rating A 630A
16.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
16.7 Rated Short Circuit Breaking Current rms kA 31.5
16.8 Rated Short Circuit Making Current rms kA STS
16.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
16.10 Earth Switch Making Current Capacity kA STS
16.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
16.12 Spring Charging Manual Y/N Y
16.13 Spring Charging Motorized Y/N Y
16.14 Operation Duty - STS
16.15 Number of Operations per Annum - STS -
16.16 Opening Time ms STS -
16.17 Protection Scheme - Refer Single Line Diagram
16.18 Shunt Trip Coil Y/N Y
16.19 Shunt Trip Coil - Minimum Voltage to Activate %V STS
16.20 No Voltage Coil Y/N Y
16.21 Amp Metering Switch & Ammeter Y/N N -
16.22 Volt Metering Switch & Voltmeter Y/N N -
16.23 Key Interlocking System Description - None
16.24 Surge Arrestor Y/N Y
16.25 Cable Type - Cu, XLPE/SWA/XLPE
16.26 Cable Entry - Bottom
16.27 Max Cable Size mm2 1 x 3C 95mm2
16.28 Live Cable Indication Y/N Y
16.29 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 9 of 17


473779467.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

17.0 SWITCHBOARD TIER - PROTECTION RELAYS


17.1 Protection Relay Model - Motors <1MW - STS
17.2 Protection Relay Model - Motors ≥1MW - STS
17.3 Protection Relay Model - Transformer - STS
17.4 Protection Relay Model - Incomer - STS
17.5 Protection Relay Model - Generators - STS
17.6 Protection device Open, Voltage Free Contact - 4 N/O
17.7 Protection device Closed, Voltage Free Contact - 4 N/O
17.8 Protection device Status, Voltage Free Contact - 2 N/O for each position
17.9 Protection device Spring Charged, Voltage Free Contact - 2 N/O
17.10 Protection Relay Trip, Voltage Free Contact - 2 N/O + 2 N/C
17.11 Protection Relay Alarm, Voltage Free Contact - 2 N/O + 2 N/C
17.12
18.0 SWITCHBOARD TIER - METERING
18.1 Metering Type Make / Type Part of protection relay
18.2 -Amp Meter Y/N Part of protection relay
18.3 -Volt Meter Y/N Part of protection relay
18.4 -kW, kVAr, kVA Meter Y/N Part of protection relay
18.5 -kW/hr, kVAr/hr, kVA/hr Meter Y/N Part of protection relay
18.6 -Power Factor Y/N Part of protection relay
18.7 -Hours Run Meter Y/N Part of protection relay
18.8 -Frequency Y/N Part of protection relay
18.9 -%THD Y/N Part of protection relay
18.10 -Communication Protocol - Profibus DP - TBC
18.11
19.0 NOTES & ABBREVIATIONS
19.1 1. Supplier to complete all empty fields or where noted as "STS" (Supplier to State)
19.2 2. Refer 11442-0000-E0710 Clause 8.24 and functionality shown in Single Line Diagram
19.3
19.4
19.5 Abbreviations
19.6 NA = Not Applicable
19.7 STS = Supplier to State
19.8 TBC = To be Confirmed
19.9
0

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 10 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

1.0 GENERAL
1.1 Manufacturer - STS
1.2 Manufacturer Location - STS
1.3 Model - STS
1.4 Design Standard - STS
1.5 Switchboard Technical Specification - 11442-0000-E0710
1.6 Wiring Identification Specification - 11442-0000-E0710
1.7 Single Line Diagram - Refer to Requisition
1.8
2.0 SITE CONDITIONS
2.1 Site Conditions Specification - 11442-0000-G0713
2.2 Altitude Above Sea Level m <1000
2.3 Design Ambient Temperature o
C 0-40
2.4 Seismic Condition - NA -
2.5 Location - Indoor
2.6 Environment - Indoor
2.7
3.0 SYSTEM PARAMETERS
3.1 System Voltage kV 11, +10% to -11%
3.2 Supply Frequency Hz 50, +/- 1Hz
3.3 No. of Phases - 3
3.4 System Prospective Short Circuit Current (Symmetrical RMS) kA/s 31.5kA / 3s
3.5 System Short Circuit Peak Current kA 70 - TBC
3.6 System Earthing - Resistance - TBA
3.7
4.0 SWITCHBOARD GENERAL
4.1 Rated Voltage kV 12
4.2 Rated Frequency Hz 50
4.3 Insulation Medium AIS / GIS AIS
4.4 Rated Short Circuit Withstand Current and Duration kA/s 31.5kA / 3s
4.5 Rated Peak Withstand Current kA 70
4.6 Rated Short Time Power Frequency Withstand kV 28
4.7 Rated Impulse Withstand Voltage kV 75
4.8 Type Test Certificate Number - STS
4.9 Type Testing Authority - STS
4.10 Arc Fault Containment Required Y/N Y
4.11 Duration of Arc Fault Test s STS
4.12 Name of Arc Testing Authority - STS
4.13 Total Switchboard Heat Loss at Full Load W STS
5.0 SWITCHBOARD BUSBARS
5.1 Busbar arrangement / Busbars per phase - STS
5.2 Busbar Material - Fully Insulated Cu
5.3 Main Busbar Size mm2 STS
5.4 Main Busbar Current Rating A Refer Single Line Diagram
5.5 Main Earth Busbar Size mm2 STS
5.6 Main Earth Busbar Current Rating A STS
5.7 Main Earth Bar Location - STS
5.8 Busbar Earth Switch (with Mechanical Interlock) Yes/No Yes
REV DATE BY CHK APPR AUTH DESCRIPTION
P1 6/10/2011 BR CJC CJC JR Preliminary review

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 11 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

6.0 AUXILIARY VOLTAGE


6.1 Auxiliary Voltage - Protection & Tripping Internal / External External
6.2 -Auxiliary Voltage Supply Rating (Switchboard Demand) W STS
6.3 -Voltage / Tolerance V/% 48V dc / 10%
6.4 -Peak Demand A STS
6.5 -Load per Circuit Breaker Trip Coil A STS
6.6 Auxiliary Voltage - Closing, Motor and spring charging Internal / External External
6.7 -Voltage / Tolerance V/% 48V dc / 10%
6.8 -Peak Demand A STS
6.9 -Load per Circuit Breaker Close Coil A STS
6.10 -Load per Circuit Breaker Charging A STS
6.11 Auxiliary Voltage - Heaters Internal / External External
6.12 Auxiliary Voltage Supply - Tolerance V/% 230V ac
6.13 -Peak Demand W STS
6.14 -Motor Heater Voltage V 230V ac
7.0 SWITCHBOARD - CONSTRUCTION
7.1 Future Extension - Both ends
7.2 Total Number of Tiers - As per Single line Diagram
7.3 Incomer Sections - As per Single line Diagram
7.4 Bus Tie Sections - As per Single line Diagram
7.5 Feeder Sections - As per Single line Diagram
7.6 Motor Feeder Sections - As per Single line Diagram
7.7 Switchboard Type - Partition Metallic
7.8 Enclosure IP Rating IP 41
7.9 Enclosure Material - Steel 2mm
7.10 Module Type Withdrawable / Fixed Withdrawable
7.11 Power Cables - Cable Entry Top / Bottom Bottom
7.12 Control Cables - Cable Entry Top / Bottom Top / Bottom
7.13 Gland Plate Material and Size - Al, 6mm
7.14 Surface Finish - Supplier standard
7.15 Colour Internal - Supplier standard
7.16 Colour External - RAL 7035
8.0 SWITCHBOARD - DIMENSIONS AND WEIGHTS
8.1 Overall Dimension (L x W x H) mm STS
8.2 Minimum Clearance Required at Front of Switchboard mm STS
8.3 Minimum Clearance Required at Rear of Switchboard mm <100mm typ
8.4 Minimum Clearance Required at Side of Switchboard mm <100mm typ
8.5 Minimum Clearance Required Above Switchboard mm <100mm typ
8.6 Lifting Arrangement - STS
8.7 Total Installed Weight kg STS
8.8 Total Shipping Weight kg STS
8.9 Shipping Section (L x W x H) and Qty mm / ea STS
8.10 Maximum Shipping Section Weight kg STS
9.0 ACCESSORIES AND OPTIONS
9.1 Circuit Breaker Trolley Y/N Y
9.2 CB Racking Handles Y/N Y
9.3 CB Charging Handles Y/N Y
9.4 Special Tools Y/N Y
9.5 Earth Switch Charging Handle Y/N Y
9.6 Remote Switchboard Control Panel Y/N Note 3
9.7 Remote PCS Control Y/N Y
9.8 Load Shedding Panel Y/N N -
9.9 Switchboard Monitoring and Control System Y/N Part of PCS -
9.10 Anticondensation Heaters Y/N Y
9.11 Fire Detection Y/N N -
9.12 Fire Suppression Y/N N -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 12 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

10.0 SWITCH BOARD AUXILIARY CONTROL EQUIPMENT MAKES AND MODELS


10.1 Miniature Circuit Breakers - -
10.2 Make / Type - STS
10.3 Rated Voltage kV STS
10.4 Control Voltage Transformer - -
10.5 Make / Type - STS
10.6 Voltage Ratio V/V STS
10.7 Rating VA STS
10.7 Load Capacity Calculation Basis - STS
10.8 DC Power Supply - External , By Others
10.9 Make / Type - NA
10.10 Vin / V Out V/V NA
10.11 Amps Continuous A NA
10.12 AC Control Relays - -
10.13 Make / Type - STS
10.13 Rated Voltage V ac 230V ac
10.14 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.15 Auxiliary Contact Rating V/A 230V ac, 10A
10.16 DC Control Relay - -
10.17 Make / Type - STS
10.18 Rated Voltage V dc 48
10.19 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.20 Auxiliary Contact Rating V/A 48V dc, 5A
10.21 Control Switches - Make / Type - STS
10.22 Control Switches - Voltage V STS
10.23 Pushbuttons - Make / Type - STS
10.24 Power Terminals Make / Type - STS
10.25 Control Terminals Make / Type - STS
11.0 SWITCHBOARD TIER - CURRENT TRANSFORMERS
11.1 Protection CT Manufacturer - STS
11.2 Protection CT Burden and Class - STS
11.3 Protection CT Ratio A/A As per Single Line Diagram
11.5 Differential Protection CT Manufacturer - STS
11.7 Differential Protection CT Burden and Class - STS
11.6 Differential Protection CT Ratio A/A As per Single Line Diagram
11.8 Earth Leakage Toroid Manufacturer - STS
11.9 Earth Leakage Toroid Ratio A/A As per Single Line Diagram
11.10 Earth Leakage Toroid Class - STS
11.11 Transformer Neutral CT Manufacturer - By Others -
11.12 Transformer Neutral CT Ratio A/A By Others -
11.13 Transformer Neutral CT Burden and Class - By Others -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 13 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

12.0 SWITCHBOARD TIER - VOLTAGE TRANSFORMERS


12.1 Voltage Ratio V/V 11kV / 110V
12.2 Power / Class VA STS
12.3 Fixed / Withdrawable - STS
12.4 Primary Fuse Rating A STS
12.5 Secondary Fuse Rating A STS
13.0 SWITCHBOARD TIER
13.1 Service - Incomer
13.2 Device Type - Circuit Breaker
13.3 Device Model / Manufacturer - STS
13.4 Switching Device Insulation Type SF6 / Vacuum STS
13.5 Continuous Rating A As per Single Line Diagram
13.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
13.7 Rated Short Circuit Breaking Current rms kA 31.5
13.8 Rated Short Circuit Making Current rms kA STS
13.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
13.10 Earth Switch Making Current Capacity kA STS
13.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
13.12 Spring Charging Manual Y/N Y
13.13 Spring Charging Motorized Y/N Y
13.14 Operation Duty - STS
13.15 Number of Operations per Annum - STS
13.16 Opening Time ms STS
13.17 Protection Scheme - Refer Single Line Diagram
13.18 Shunt Trip Coil Y/N Y
13.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min. 90%
13.20 No Voltage Coil Y/N N -
13.21 Amp Metering Switch & Ammeter Y/N N -
13.22 Volt Metering Switch & Voltmeter Y/N N -
13.23 Key Interlocking System Description - Note 4
13.24 Surge Arrestor Y/N Y
13.25 Cable Type - Cu, XLPE/SWA/XLPE
13.26 Cable Entry - Bottom
13.27 Max Cable Size mm2 STS
13.28 Live Cable Indication Y/N Y
13.29 Tier Section Dimensions (L x W x H) mm STS
14.0 SWITCHBOARD TIER
14.1 Service - Bus Tie
14.2 Device Type - Circuit Breaker
14.3 Device Model / Manufacturer - STS
14.4 Switching Device Insulation Type SF6 / Vacuum STS
14.5 Continuous Rating A As per Single Line Diagram
14.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
14.7 Rated Short Circuit Breaking Current rms kA 31.5
14.8 Rated Short Circuit Making Current rms kA STS
14.9 Spring Charging Manual Y/N Y
14.10 Spring Charging Motorized Y/N Y
14.11 Operation Duty - STS
14.12 Number of Operations per Annum - STS
14.13 Opening Time (Full Load) ms STS
14.14 Protection Scheme - NA
14.15 Shunt Trip Coil Y/N N -
14.16 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
14.17 No Voltage Coil Y/N N -
14.18 Key Interlocking System Description - Note 4
14.19 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 14 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

15.0 SWITCHBOARD TIER


15.1 Service - Feeder or Motor Starter
15.2 Device Type - Fuse Contactor
15.3 Device Model / Manufacturer - NA -
15.4 Switching Device Insulation Type SF6 / Vacuum NA -
15.5 Fuse Continuous Rating A NA -
15.6 Fuse Rated Short-Time Withstand Current and Duration kA/s NA -
15.7 Contactor Continuous Rating A NA -
15.8 Contactor Rated Short-Time Withstand Current and Duration kA/s NA -
15.9 Contactor Breaking Current Capacity A NA -
15.10 Contactor Making Current Capacity A NA -
15.11 Earth Switch Required and Location (with mechanical interlock) Y/N NA -
15.12 Earth Switch Making Current Capacity kA NA -
15.13 Interrupting time ms NA -
15.14 Protection and Metering Relay Y/N NA -
15.15 Protection Scheme - NA -
15.16 Shunt Trip Coil Y/N NA -
15.17 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
15.18 No Voltage Coil Y/N NA -
15.19 Amp Metering Switch & Ammeter Y/N NA -
15.20 Volt Metering Switch & Voltmeter Y/N NA -
15.21 Key Interlocking System Description - NA -
15.22 Surge Arrestor Y/N NA -
15.23 Cable Type - NA -
15.24 Cable Entry - NA -
15.25 Max Cable Size mm2 NA -
15.26 Live Cable Indication Y/N NA -
15.27 Tier Section Dimensions (L x W x H) mm NA -
16.0 SWITCHBOARD TIER
16.1 Service - Typical Feeder
16.2 Device Type - Circuit Breaker
16.3 Device Model / Manufacturer - STS
16.4 Switching Device Insulation Type SF6 / Vacuum STS
16.5 Continuous Rating A 630A
16.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
16.7 Rated Short Circuit Breaking Current rms kA 31.5
16.8 Rated Short Circuit Making Current rms kA STS
16.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
16.10 Earth Switch Making Current Capacity kA STS
16.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
16.12 Spring Charging Manual Y/N Y
16.13 Spring Charging Motorized Y/N Y
16.14 Operation Duty - STS
16.15 Number of Operations per Annum - STS -
16.16 Opening Time ms STS -
16.17 Protection Scheme - Refer Single Line Diagram
16.18 Shunt Trip Coil Y/N Y
16.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min 90%
16.20 No Voltage Coil Y/N Motor Starter only
16.21 Amp Metering Switch & Ammeter Y/N N -
16.22 Volt Metering Switch & Voltmeter Y/N N -
16.23 Key Interlocking System Description - None
16.24 Surge Arrestor Y/N Y
16.25 Cable Type - Cu, XLPE/SWA/XLPE
16.26 Cable Entry - Bottom
16.27 Max Cable Size mm2 STS
16.28 Live Cable Indication Y/N Y
16.29 Tier Section Dimensions (L x W x H) mm STS
17.0 SWITCHBOARD TIER
17.1 Service - Typical Motor Starter
17.2 Device Type - Circuit Breaker
17.3 Device Model / Manufacturer - STS
17.4 Switching Device Insulation Type SF6 / Vacuum STS
17.5 Continuous Rating A 630A

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 15 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

17.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s


17.7 Rated Short Circuit Breaking Current rms kA 31.5
17.8 Rated Short Circuit Making Current rms kA STS
17.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
17.10 Earth Switch Making Current Capacity kA STS
17.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
17.12 Spring Charging Manual Y/N Y
17.13 Spring Charging Motorized Y/N Y
17.14 Operation Duty - STS
17.15 Number of Operations per Annum - STS -
17.16 Opening Time ms STS -
17.17 Protection Scheme - Refer Single Line Diagram
17.18 Shunt Trip Coil Y/N Y
17.19 Shunt Trip Coil - Minimum Voltage to Activate %V STS
17.20 No Voltage Coil Y/N Y
17.21 Amp Metering Switch & Ammeter Y/N N -
17.22 Volt Metering Switch & Voltmeter Y/N N -
17.23 Key Interlocking System Description - SAG & Ball Mill required
17.24 Surge Arrestor Y/N Y
17.25 Cable Type - Cu, XLPE/SWA/XLPE
17.26 Cable Entry - Bottom
17.27 Max Cable Size mm2 STS
17.28 Live Cable Indication Y/N Y
17.29 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 16 of 17


473779467.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

18.0 SWITCHBOARD TIER - PROTECTION RELAYS


18.1 Protection Relay - Motors <1MW - STS
18.2 Protection Relay - Motors ≥1MW - STS
18.3 Protection Relay - Transformer - STS
18.4 Protection Relay - Incomer - STS
18.5 Protection Relay - Generators - STS
18.6 Protection device Open, Voltage Free Contact - 4 N/O
18.7 Protection device Closed, Voltage Free Contact - 4 N/O
18.8 Protection device Status, Voltage Free Contact - 2 N/O for each position
18.9 Protection device Spring Charged, Voltage Free Contact - 2 N/O
18.10 Protection Relay Trip, Voltage Free Contact - 2 N/O + 2 N/C
18.11 Protection Relay Alarm, Voltage Free Contact - 2 N/O + 2 N/C
18.12
19.0 SWITCHBOARD TIER - METERING
19.1 Metering Type Make / Type Part of protection relay
19.2 -Amp Meter Y/N Part of protection relay
19.3 -Volt Meter Y/N Part of protection relay
19.4 -kW, kVAr, kVA Meter Y/N Part of protection relay
19.5 -kW/hr, kVAr/hr, kVA/hr Meter Y/N Part of protection relay
19.6 -Power Factor Y/N Part of protection relay
19.7 -Hours Run Meter Y/N Part of protection relay
19.8 -Frequency Y/N Part of protection relay
19.9 -%THD Y/N Part of protection relay
19.10 -Communication Protocol - Profibus DP - TBC
19.11
20.0 NOTES & ABBREVIATIONS
20.1 1. Supplier to complete all empty fields or where noted as "STS" (Supplier to State)
20.2
20.3 3. Refer 11442-0000-E0710 Clause 8.24 and functionality shown in Single Line Diagram
20.4 4. Fortress key interlock , 2 out of 3 operation for switchboard
20.5
20.6
20.7
20.8
20.9 Abbreviations
20.10 NA = Not Applicable
20.11 STS = Supplier to State
20.12 TBC = To be Confirmed
20.13
20.14