TECHNICAL BRIEF
SETTING THE GRID PROFILE - EN50438:2007 DEFAULT PROFILE
This guide shows you how to select and modify a grid profile using the Envoy interface. You can configure a
grid profile to meet local requirements.
Caution
Enphase provides this Grid Profile configuration only as a suggested guideline for
interoperation with the local electric utility grid. Check the voltage and frequency trip point
requirements of your local electrical utility before making adjustments to the Grid Profile
and confirm that the suggested parameters conform to local requirements.
Nuisance tripping, production losses, and product damage can occur when the Grid
Profile does not match local frequency and voltage requirements. The Enphase Limited
Warranty does not cover nuisance tripping, production losses, or damage resulting from
mismatch or from electric utility grid variance.
Only an authorised installer, with the permission and following the requirements of the
local electrical utility, should make Grid Profile adjustments.
Final responsibility of the grid setting is the installer’s and Enphase assumes no liability for
errors or non-compliance as a result of this process.
5. In the Profile name field of the Edit Profile page, enter a new name for the profile, such as EN50438: 2007
Country_Name. Where “Country_Name” is the country where the system is located.
6. Change the following parameters to the
values listed here:
Parameter Value
Voltage limits
Over voltage limit No Change
Over voltage trip time 0.2 s
Over voltage limit (slow) 264.5 V
Over voltage trip time (slow) 0.2 s
Under voltage limit No Change
Under voltage trip time 1.5 s
Remaining parameters No Change
Parameter Value
Frequency limits
Over frequency limit 51.0 Hz
Over frequency trip time 0.5 s
Over frequency limit (slow) 51.0 Hz
Over frequency trip time (slow) 0.5 s
Under frequency Limit 47.0 Hz
Under frequency trip time 0.5 s
Under frequency limit (slow) 47.0 Hz
Under frequency trip time (slow) 0.5 s
Remaining parameters No Change
Parameter Value
Reconnect
Short Term reconnect time 20.0 s
Long Term reconnect time 20.0 s
Reconnect AC frequency high No Change
Reconnect AC frequency low No Change
Reconnect on frequency trip Disable
Reconnect AC voltage high No Change
Reconnect AC voltage low No Change
Reconnect on voltage trip Disable
Reconnect time 20.0 s
Reconnect power ramp up rate No Change
Remaining parameters No Change
7. Click Make Copy. This creates your grid profile, EN50438: 2007
Country_Name.
8. Click Save Profile.
Continue with System Activation. For details, refer to the Enlighten Help Center in Enlighten or to the Envoy
Communications Gateway Installation & User Manual found on www.enphase.com/support.