Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Abstract—The growing concern for energy saving has increased nonlinear loads connected at the ac side. A fair amount of
the usage of LED-based street lights, electronic chokes, compact literature [3], [4], [25]–[29] has dealt with the operation of
fluorescent lamps, and inverter-fed drives. Hence, the load profile hybrid systems. In some hybrid systems [4], [23] battery is
seen by the electrical grid is undergoing a notable change as
these devices have to operate from a dc source. Photovoltaics (PV) used to compensate the mismatch between the generation and
being a major energy source, the aforementioned loads can be demand. In developing countries, the demand for power is
connected directly to the dc bus. A grid-connected PV system growing beyond the planner’s estimation, and the power grid
involves a power source (PV array), a power sink (load), and is weak, and scheduled power outages throughout the year
two power sources/sink (utility and battery), and hence, a power are common. In addition, there are also unscheduled short-
flow management system is required to balance the power flow
among these sources. One such system is developed for selecting term outages which are random and frequent. As a result, a
the operating mode of the bidirectional converter by sensing grid-connected PV system with a battery backup has many
the battery voltage. The viability of the scheme has been ascer- advantages such as peak shaving to generate power during peak
tained by performing experimental studies on a laboratory proto- load hours, and therefore, the grid-side inverter should operate
type. The control strategy is digitally implemented on an Altera in grid-tied mode and off-grid mode to supply uninterrupted
Cyclone II Field Programmable Gate Array (FPGA) board, and
the algorithm is verified for different modes of operation by power to the critical loads during power outages [9]. In some
varying the load. Experimental results are presented to bring out applications [15], [26], [29], a battery was connected directly
the usefulness of the control strategy. in parallel with the dc bus. The size of the battery can be
Index Terms—Bidirectional converter, dc bus, photovoltaic, reduced when a battery charger/discharger circuit is inserted
power flow management system (PMS). between the dc bus and the battery [25], [30]. Utilizing the
battery charger/discharger circuit for regulating dc link voltage
I. I NTRODUCTION decouples the dc link control from the ac current control and
achieves faster regulation of dc link voltage.
TABLE II
C ONTROL S TRATEGY FOR PMS
Fig. 4. State diagram showing the power flow under various modes of
operation of the converter.
band limits. The control circuit for the implementation of
PMS is shown in Fig. 5(a), and the variation of Vb and the
reference current under each case is shown in Fig. 5(b). Based mode (idle or rectifier). However, the reference current for the
on the voltage threshold limits, two selection signals (S1 , S0 ) hysteresis controller is dictated by the previous mode. In case 1,
for the multiplexer determine the mode (M) of operation of the reference current is the a predefined constant current Ic ,
the converter. The inputs for the multiplexer 0, 1, and −1 whereas in case 8, it is (Ic + δI) (Table II). Next, if the battery
denote the idle, rectifier, and inverter modes of operation, voltage increases such that VOLT ≤ Vb , the converter continues
respectively. The operation of the PMS is explained for the to be in rectifier mode with the same reference current until
conduction when Vb < VOLT . In this situation, the converter Vb ≤ VIUT and is indicated in case 7. Similarly, when the
has to switch to rectifier mode irrespective of the previous battery voltage is higher than VOUT , then, the converter will
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3189
Fig. 5. (a) Control circuit of the PMS. (b) Reference current under different
cases shown in Table II.
Fig. 6. Power flow under various modes of operation of the bidirectional
converter. (a) Idle mode. (b) Inverter mode. (c) Rectifier mode.
move to the inverter mode irrespective of the previous mode
(cases 3 and 5). However, the current reference is dictated by drawn from the grid. However, if the battery is discharged to
the previous mode. Thus, it is ensured that the converter does less than VOLT , the reference current is incremented by δI so
not oscillate between rectifier and inverter modes under any that Vb > VOLT . As seen from Table II (case 8), the change
situation. in reference current is δI, and the PV and the grid charge the
Initially, assuming the converter to be in idle mode, the PV battery to VIUT . At this condition, the converter enters into idle
supplies the load connected at the dc side and also charges mode (case 9), and the direction of power flow for this mode is
the battery when Ppv > PL (case 2). This increases the battery shown in Fig. 6(c).
voltage, and once Vb ≥ VOUT , the converter enters into inverter
mode. If Ppv < PL , then both battery and PV contribute to
supply the load. However, this decreases Vb , and when Vb ≤ B. Hysteresis Controller
VOLT , the converter enters into rectifier mode. The power flow
A hysteresis current controller which is well proven and
diagram for this mode is shown in Fig. 6(a).
adopted to many industrial applications [33] is employed for
When the converter is in inverter mode, the PV power is
the current control of an inverter. The reference signal for the
injected into the grid, and the power flow diagram for this mode
hysteresis current controller is generated as a function of the
is shown in Fig. 6(b). Here, there is a possibility of Vb to in-
phase of the grid voltage using Phase Locked Loop (PLL).
crease or decrease depending on whether the battery is charging
The injected current is in phase with the grid voltage, and
or discharging. If VILT ≤ Vb ≤ VOUT , (case 4) the reference
thus, unity power factor is achieved. For an average switching
current is injected into the grid. However, when Vb ≥ VOUT , the
frequency fsavg , the value of inductance [33] is calculated as
reference current is incremented by a small amount δI (case 5)
18 mH using
such that Vb ≤ VOUT . Once Vb is less than the outer upper
threshold, there will be no change in the reference current, and Vdc a2
the converter operates in inverter mode until Vb > VILT after L1 = 1− (20)
4Δifsavg 2
which it stops injecting power and becomes idle (case 6).
When the converter is in rectifier mode, the battery may where Vdc is the dc link voltage, “a” is the modulation index,
charge or discharge depending on the availability of PV power and Δi is the ripple in the inverter current. The specifications
and load demand. If VOLT ≤ Vb ≤ VIUT , the current Ic is of the hysteresis current controller are shown in Table III.
3190 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013
TABLE III
S PECIFICATIONS OF THE H YSTERESIS C ONTROLLER
TABLE IV
S PECIFICATIONS OF THE E XPERIMENTAL S ETUP
Fig. 8. Dynamic response for step change in load: (a) AC line current control (iL —0.5 A/div; Vdc —55 V/div; Ppv —100 W/div; io —0.5 A/div). (b) AC
line current control (iL —1 A/div; Vdc —55 V/div; Ppv —100 W/div; io —0.5 A/div). (c) Proposed control (iL —1 A/div; Vdc —55 V/div; Ppv —100 W/div;
ib —1 A/div; io —1 A/div; Vb —5 V/div). Dynamic response for step change in insolation: (d) AC line current control (iL —0.5 A/div; Vdc —40 V/div; Ppv —100
W/div; io —1 A/div). (e) AC line current control (iL —0.5 A/div; Vdc —40 V/div; Ppv —100 W/div; io —1 A/div). (f) Proposed control (iL —0.5 A/div; Vdc —55
V/div; Ppv —200 W/div; ib —1 A/div; io —1 A/div; Vb —5 V/div). Time: 0.025 s/div.
1) When a step change in load closely matches the generated In the proposed system, for the same step increase in
PV power with the load power (Ppv ≈ PL ). load from 224 to 342 W (Ppv < PL ), the increase in load
In this case with ac line current control, the remaining current is compensated by the increase in current ib of the
less amount of power (Ppv − PL ) is fed to the grid. One charger/discharger circuit. The current injected into the grid
such situation is shown in Fig. 8(a). When the dc load remains constant as set by the PMS and is shown in Fig. 8(c). It
is increased from 164 to 202 W, with the PV power can also be observed that the change in battery voltage during
remaining the same, the current injected into the grid is this period is less (39.2 to 37.7 V), and hence, the converter
reduced to 0.1 A. This increases the THD of the injected does not change the mode of operation of the converter.
line current to a high value of 28.8%. The magnified Similarly, for step change in insolation, two cases are
view of ripple in the ac line current io is shown in the considered.
subplot in Fig. 8(a). However, in the proposed technique,
the minimum current reference is set as 1 A by the PMS 1) When a step change in insolation closely matches the
as shown in Fig. 7(b). generated PV power with the load power (Ppv ≈ PL ).
2) When a step change in load changes (Ppv > PL ) to In the ac line current control with the load power
(Ppv < PL ). remaining constant at 160 W, the PV power is decreased
In this case, the converter initially operating in in- to 348 W. The current injected into the grid is reduced to
verter mode changes to rectifier mode. Fig. 8(b) shows 0.7 A, and this increases the THD to 5.2%. The subplot
that, initially, the inverter supplies the surplus PV power in Fig. 8(d) is the magnified view of the current io . It can
(Ppv > PL ) to the grid, and as the load power is increased be observed that the THD of the current injected into the
to 342 W, the PV power (282 W) is insufficient to supply grid varies with the insolation. In the proposed technique,
the load demand, and the grid supplies the deficit power. It the charger/discharger complements the PV power, and
is clear from Fig. 8(b) that fluctuations in load conditions always, a minimum current is fed to the grid.
cause the converter to swing between inverter and rectifier 2) When a step change in insolation changes (Ppv > PL ) to
modes of operation. Moreover, it can be observed that (Ppv < PL ).
the disturbance in Vdc causes PV array power to decrease In the ac line current control, the PV power is reduced
from its maximum value. to 168 W (Ppv < PL ) with the load power remaining
3192 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013
Fig. 9. Grid failure under (a) inverting mode and (b) rectifier mode. y-axis: Iinv : 4 A/div; Vb : 80 V/div; Ib : 4 A/div; IL : 4 A/div. x-axis: time: 50 s/div.
constant at 202 W. As shown in Fig. 8(e), the converter A sudden removal of grid supply forces the converter to idle
changes from inverter to rectifier mode. With the pro- mode; as Ppv < PL , the battery supplies the deficit power;
posed system for the same step change in insolation, the when its voltage drops to 32 V, noncritical loads are removed to
deficit power is supplied by the charger/discharger circuit, avoid deep discharge of batteries; the other loads are supplied
and a minimum current set by the PMS is injected into by PV.
the grid as shown in Fig. 8(f). It can also be observed that
the change in battery voltage during this period is from
D. Automatic Power Flow Mode
38.6 to 37.1 V, and hence, the converter does not shuttle
between different modes. An increase in PV power or a decrease in load power leads to
It can also be observed from the aforementioned results inverter mode, whereas a decrease in PV power or an increase
that dc link voltage regulation using ac line current affects in load power leads to rectifier mode. Hence, to test the control
the THD of the injected grid current, and the converter often strategy of the PMS, four different cases are considered for
oscillates between the rectifier and inverter modes of operation study as follows:
for variation in load and PV power. Moreover, the disturbance Case 1) inverter to rectifier mode via idle mode;
in Vdc causes PV operation to shift from the MPP. Overall, Case 2) inverter to inverter mode via idle mode;
the proposed scheme is seen to be effective in preventing the Case 3) rectifier to inverter mode via idle mode;
undesirable shuttling of the PV operating point and maintains Case 4) rectifier to rectifier mode via idle mode.
the THD of the injected grid current within the allowable limit Since the mode of operation of the converter depends on
by setting a minimum current reference for injection. the battery voltage, to verify the control strategy, the variation
in battery voltage is obtained by changing the load across
the battery. The resistive loads are chosen such that a step
C. Grid Failure Mode
change in load causes the variation in battery voltage. The
When the grid power fails, irrespective of the present mode experimental waveforms are shown in Fig. 10. Traces 1 and 2
of operation of the converter (rectifier/inverter), the PMS forces show the battery voltage and battery current, respectively, and
the converter into idle mode. Both PV and battery supply the the converter current at the dc side is shown in trace 3.
load at the dc side. The worst case scenario under inverting Case I and Case II: When the PV power (352 W) is more
mode is grid failure when Vb is slightly less than VOUT and than the load power requirement of 242 W, the converter is in
Ppv > PL , and one such situation is shown in Fig. 9(a). With inverting mode and injecting 230 W of power into the grid.
233 W of PV power and 160 W of load power, the converter op- The contribution of the battery charger/discharger circuit is
erates in inverter mode and injects 230 W of power into the grid. 144 W. Now, an increase in dc load power (287 W) leads to
When Vb = 39.2 V, a sudden removal of grid supply forces the the reduction of battery voltage. This is obtained by applying
converter to idle mode, and now, the power balance is to be loads in steps at which the battery voltage falls below VILT
achieved among PV, load, and battery. As the excess PV power (33.8 V), and at this instant, the converter enters into idle mode,
charges the battery to VOUT , dump loads are switched on, and indicating a zero current. An increase in load power (320 W)
both PV and battery together supply the load. This is evident leads to the reduction in battery voltage to 31.8 V, and the
from the reversal of current direction in the charger/discharger converter enters into rectifier mode as shown in Fig. 10(a),
circuit. whereas a decrease in load power (222 W) makes the converter
The worst case scenario under rectifier mode occurs when to operate in inverter mode and inject 230 W of power to the
grid power fails when Vb is slightly more than VOLT and grid and is shown in Fig. 10(b).
Ppv < PL , and such a situation is shown in Fig. 9(b). With Case III and Case IV: To verify Cases III and IV, prior to
228 W of PV power, 242 W of load power, and Vb = 32.6 V, the experiment, the loads are applied, and the battery voltage
the converter operates in rectifier mode and charges the battery. is brought below 32 V, so that the power flow is from the grid
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3193
Fig. 10. Battery voltage, battery current, and dc current waveforms for different cases under automatic power flow control. (a) Case I. (b) Case II. (c) Case III.
(d) Case IV. y-axis: Vb : 10 V/div; Ibat : 2 A/div; Iinv : 4 A/div. x-axis: time: 20 s/div.
to the dc side. With 297 W of PV power and 221 W of power The significance of the proposed scheme has been demon-
from the grid, the battery charger/discharger circuit charges the strated by its effectiveness in preventing undesirable shuttling
battery. Now, the loads are released in steps, which rises the of the PV operating point and also in maintaining the THD
battery voltage above the VIUT (38.3 V), and the converter of the injected grid current within the allowable limit of 5%
enters into idle mode. The removal of load increases Vb above by setting a minimum current reference for injection. The
VOUT (40.2 V), and the converter changes into inverter mode, proposed configuration has been proved to be attractive from
and 230 W of power is fed to the grid. This can be observed the perspective of providing uninterruptible power to dc loads
from Fig. 10(c). However, an increase in load demand reduces while ensuring the evacuation of excess PV power of high
Vb . This situation is verified by applying loads in steps and is quality into the grid.
shown in Fig. 10(d). It is evident from the results that the system
exhibits a reasonably good response to the variation in load. R EFERENCES
[1] Yazdani and P. P. Dash, “A control methodology and characterization of
dynamics for a photovoltaic system interfaced with a distribution net-
work,” IEEE Trans. Power Del., vol. 24, no. 3, pp. 1538–1551, Jul. 2009.
IV. C ONCLUSION [2] X. Q. Guo and W. Y. Wu, “Improved current regulation of three-phase
grid-connected voltage-source inverters for distributed generation sys-
A versatile control strategy for power flow management in a tems,” IET Renew. Power Gener., vol. 4, no. 2, pp. 101–115, Mar. 2010.
grid-connected PV system feeding dc loads has been presented. [3] H. C. Chiang, T. T. Ma, Y. H. Cheng, J. M. Chang, and W. N. Chang,
The importance of the scheme has been brought out by per- “Design and implementation of a hybrid regenerative power system com-
bining grid-tie and uninterruptible power supply functions,” IET Renew.
forming experimental studies on a laboratory prototype. The Power Gener., vol. 4, no. 1, pp. 85–99, Jan. 2010.
steady-state performance of the converter for different modes [4] F. Giraud and Z. M. Salameh, “Steady-state performance of a grid-
of operation has been observed, and near unity power factor connected rooftop hybrid wind–photovoltaic power system with battery
storage,” IEEE Trans. Energy. Convers., vol. 16, no. 1, pp. 1–7, Mar. 2001.
has been achieved in both the rectifier and inverter modes. The [5] J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewicz, E. Galvàn,
transient performance of the system for step changes in load R. C. P. Guisado, M. A. M. Prats, J. I. León, and N. Moreno-Alfonso,
and insolation have been also illustrated. “Power electronic systems for the grid integration of renewable energy
sources: A survey,” IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1002–
The control strategy has been digitally implemented on an 1016, Aug. 2006.
Altera Cyclone II FPGA board, and the algorithm has been ver- [6] B. Kroposki, C. Pink, R. DeBlasio, H. Thomas, M. Simões, and P. K. Sen,
ified for different modes of operation by varying the load, and “Benefits of power electronic interfaces for distributed energy sources,”
IEEE Trans. Ind. Electron., vol. 25, no. 3, pp. 901–908, Sep. 2010.
a good correlation between the results of computer simulation [7] H. M. Kojabadi, B. Yu, I. A. Gadoura, L. Chang, and M. Ghribi, “A
and experiments has established the validity of the PMS. novel DSP-based current controlled PWM strategy for single phase grid
3194 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013
connected inverters,” IEEE Trans. Ind. Electron., vol. 21, no. 4, pp. 985– [27] J. T. Bialasiewicz, “Renewable energy systems with photovoltaic power
993, Jul. 2006. generators: Operation and modeling,” IEEE Trans. Ind. Electron., vol. 55,
[8] J. C. Moreno, J. M. Espi Huerta, R. G. Gil, and S. A. Gonzalez, “A robust no. 7, pp. 2752–2758, Jul. 2008.
predictive current control for three-phase grid-connected inverters,” IEEE [28] T. Hirose and H. Matsuo, “Standalone hybrid wind–solar power gener-
Trans. Ind. Electron., vol. 56, no. 6, pp. 1993–2004, Jun. 2009. ation system applying dump power control without dump load,” IEEE
[9] Z. Yao, L. Xiao, and Y. Yan, “Seamless transfer of single phase grid Trans. Ind. Electron., vol. 59, no. 2, pp. 988–997, Feb. 2012.
interactive inverters between grid connected and standalone modes,” IEEE [29] W. Qi, J. Liu, X. Chen, and P. D. Christofides, “Supervisory predictive
Trans. Power Electron., vol. 25, no. 6, pp. 1597–1603, Jun. 2010. control of standalone wind/solar energy generation systems,” IEEE Trans.
[10] M. Singh, V. Khadkikar, A. Chandra, and R. K. Varma, “Grid intercon- Ind. Electron., vol. 19, no. 1, pp. 199–207, Jan. 2011.
nection of renewable energy sources at the distribution level with power- [30] K. Jin, X. Ruan, M. Yang, and M. Xu, “A hybrid fuel cell power system,”
quality improvement features,” IEEE Trans. Power Del., vol. 26, no. 1, IEEE Trans. Ind. Electron., vol. 56, no. 4, pp. 1212–1222, Apr. 2009.
pp. 307–315, Jan. 2011. [31] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-
[11] S. Yang, Q. Lei, F. Z. Peng, and Z. Qian, “A robust control scheme filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., vol. 41,
for grid-connected voltage-source inverters,” IEEE Trans. Ind. Electron., no. 5, pp. 1281–1291, Sep./Oct. 2005.
vol. 58, no. 1, pp. 202–212, Jan. 2011. [32] H. Bai, C. Mi, C. Wang, and S. Gargies, “The dynamic model and hybrid
[12] F.-S. Pai, J.-M. Lin, and S.-J. Huang, “Design of an inverter array for phase shift control of a dual active bridge converter,” in Proc. IECON,
distributed generations with flexible capacity operations,” IEEE Trans. 2008, pp. 2840–2845.
Ind. Electron., vol. 57, no. 12, pp. 3927–3934, Dec. 2010. [33] P. A. Dahono, “New hysteresis current controller for single-phase full-
[13] H. Patel and V. Agarwal, “Investigations into the performance of bridge inverters,” IET Power Electron., vol. 2, no. 5, pp. 585–594,
photovoltaics-based active filter configurations and their control schemes Sep. 2009.
under uniform and non-uniform radiation conditions,” IET Renew. Power [34] C. Mi, H. Bai, C. Wang, and S. Gargies, “Operation, design and control of
Gener., vol. 4, no. 1, pp. 12–22, Jan. 2010. dual H-bridge-based isolated bidirectional DC–DC converter,” IET Power
[14] Y.-C. Kuo, T.-J. Liang, and J.-F. Chen, “Novel maximum power point Electron., vol. 1, no. 4, pp. 507–517, Dec. 2008.
tracking controller for photovoltaic energy conversion system,” IEEE
Trans. Ind. Electron., vol. 48, no. 3, pp. 594–601, Jun. 2001.
[15] Y.-K. Lo, T.-P. Lee, and K.-H. Wu, “Grid-connected photovoltaic system
with power factor correction,” IEEE Trans. Ind. Electron, vol. 55, no. 5, Balasubramanian Indu Rani (M’10) received the
pp. 2224–2227, May 2008. B.E degree from Government College of Engineer-
[16] Y. K. Lo, H. J. Chiu, T. P. Lee, I. Purnama, and J. M. Wang, “Analysis ing, Tirunelveli, India, and the M.E degree from
and design of a photovoltaic system connected to the utility with a power Anna University, Chennai, India.
factor corrector,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4354– From 2004 to 2009, she was with the School of
4362, Nov. 2009. Electrical Sciences, VIT University, Vellore, India.
[17] E. Romero-Cadaval, M. I. Milanés-Montero, E. González-Romera, and She is currently a Full-time Research Scholar with
F. Barrero-González, “Power injection system for grid-connected pho- the National Institute of Technology, Tiruchirappalli,
tovoltaic generation systems based on two collaborative voltage source India. Her areas of interest include renewable energy
inverters,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4389–4398, systems and power electronics.
Nov. 2009.
[18] J. He, Y. Li, and M. S. Munir, “A flexible harmonic control approach
through voltage-controlled DG-grid interfacing converters,” IEEE Trans.
Ind. Electron., vol. 59, no. 1, pp. 444–455, Jan. 2012. Ganesan Saravana Ilango received the B.E. degree
[19] R. A. Mastromauro, M. Liserre, T. Kerekes, and A. Dell’ Aquila, “A from the University of Madras, Chennai, India, in
single-phase voltage-controlled grid-connected photovoltaic system with 2000, the M.E. degree from Bharathidasan Univer-
power quality conditioner functionality,” IEEE Trans. Ind. Electron, sity, Tiruchirappalli, India, in 2001, and the Ph.D.
vol. 56, no. 11, pp. 4436–4444, Nov. 2009. degree from the National Institute of Technology,
[20] J. M. Espí, J. Castelló, R. García-Gil, G. Garcerá, and E. Figueres, “An Tiruchirappalli.
adaptive robust predictive current control for three-phase grid-connected From 2001 to 2004, he was a Lecturer with Noorul
inverters,” IEEE Trans. Ind. Electron., vol. 58, no. 8, pp. 3537–3546, Islam College of Engineering, Kumaracoil, India.
Aug. 2011. Since 2006, he has been an Assistant Professor with
[21] J.-M. Kwon, B.-H. Kwon, and K.-H. Nam, “Grid-connected photovoltaic the National Institute of Technology. His preferred
multistring PCS with PV current variation reduction control,” IEEE Trans. working areas are Flexible AC Transmission Sys-
Ind. Electron., vol. 56, no. 11, pp. 4381–4388, Nov. 2009. tems controllers, digital controllers, renewable energy systems, and power
[22] Y.-M. Chen, H.-C. Wu, Y.-C. Chen, K.-Y. Lee, and S.-S. Shyu, “The AC quality.
line current regulation strategy for the grid connected PV system,” IEEE
Trans. Power Electron, vol. 25, no. 1, pp. 209–218, Jan. 2010.
[23] S. V. Araújo, P. Zacharias, and R. Mallwitz, “Highly efficient single phase
transformerless inverter for grid connected photovoltaic systems,” IEEE Chilakapati Nagamani (M’10) received the B.Tech.
Trans. Ind. Electron, vol. 57, no. 9, pp. 3118–3128, Sep. 2010. degree from the Sri Venkateswara University College
[24] R. Kadri, J.-P. Gaubert, and G. Champenois, “An improved maximum of Engineering, Tiruapati, India, the M.Tech. degree
power point tracking for photovoltaic grid-connected inverter based on from the Indian Institute of Technology, Kanpur,
voltage-oriented control,” IEEE Trans. Ind. Electron., vol. 58, no. 1, India, and the Ph.D. degree from the University of
pp. 66–75, Jan. 2011. Technology, Sydney, Australia.
[25] S.-K. Kim, J.-H. Jeon, C.-H. Cho, J.-B. Ahn, and S.-H. Kwon, “Dynamic From 1985 to 1991, she was with the Central
modeling and control of a grid-connected hybrid generation system with Power Research Institute, Bangalore, India. Sub-
versatile power transfer,” IEEE Trans. Ind. Electron., vol. 55, no. 4, sequently, she joined the Department of Electrical
pp. 1677–1688, Apr. 2008. and Electronics Engineering, National Institute of
[26] E. Serban and H. Serban, “A control strategy for a distributed power Technology (then known as Regional Engineering
generation micro grid application with voltage and current controlled College), Tiruchirappalli, India, as a Lecturer, where she is currently a Pro-
source converter,” IEEE Trans. Power Electron, vol. 25, no. 12, pp. 2981– fessor. Her areas of interest include power electronics and drives, renewable
2992, Dec. 2010. energy systems, and FACTS controllers.