Sei sulla pagina 1di 10

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO.

8, AUGUST 2013 3185

Control Strategy for Power Flow Management in a


PV System Supplying DC Loads
Balasubramanian Indu Rani, Member, IEEE, Ganesan Saravana Ilango, and
Chilakapati Nagamani, Member, IEEE

Abstract—The growing concern for energy saving has increased nonlinear loads connected at the ac side. A fair amount of
the usage of LED-based street lights, electronic chokes, compact literature [3], [4], [25]–[29] has dealt with the operation of
fluorescent lamps, and inverter-fed drives. Hence, the load profile hybrid systems. In some hybrid systems [4], [23] battery is
seen by the electrical grid is undergoing a notable change as
these devices have to operate from a dc source. Photovoltaics (PV) used to compensate the mismatch between the generation and
being a major energy source, the aforementioned loads can be demand. In developing countries, the demand for power is
connected directly to the dc bus. A grid-connected PV system growing beyond the planner’s estimation, and the power grid
involves a power source (PV array), a power sink (load), and is weak, and scheduled power outages throughout the year
two power sources/sink (utility and battery), and hence, a power are common. In addition, there are also unscheduled short-
flow management system is required to balance the power flow
among these sources. One such system is developed for selecting term outages which are random and frequent. As a result, a
the operating mode of the bidirectional converter by sensing grid-connected PV system with a battery backup has many
the battery voltage. The viability of the scheme has been ascer- advantages such as peak shaving to generate power during peak
tained by performing experimental studies on a laboratory proto- load hours, and therefore, the grid-side inverter should operate
type. The control strategy is digitally implemented on an Altera in grid-tied mode and off-grid mode to supply uninterrupted
Cyclone II Field Programmable Gate Array (FPGA) board, and
the algorithm is verified for different modes of operation by power to the critical loads during power outages [9]. In some
varying the load. Experimental results are presented to bring out applications [15], [26], [29], a battery was connected directly
the usefulness of the control strategy. in parallel with the dc bus. The size of the battery can be
Index Terms—Bidirectional converter, dc bus, photovoltaic, reduced when a battery charger/discharger circuit is inserted
power flow management system (PMS). between the dc bus and the battery [25], [30]. Utilizing the
battery charger/discharger circuit for regulating dc link voltage
I. I NTRODUCTION decouples the dc link control from the ac current control and
achieves faster regulation of dc link voltage.

W ITH THE ever-increasing demand for low-cost energy


and growing concern about environmental issues, PV-
based systems are being increasingly employed in diverse
In the literature, much attention has not been paid to PV
systems supplying dc loads. The growing emphasis on energy
saving has increased the usage of LED-based street lights,
applications both at domestic and commercial levels [1]. Pho- electronic chokes, compact fluorescent lamps, and inverter-fed
tovoltaic systems can be broadly classified into stand-alone drives. PV being a major energy source enables the dc loads to
system and grid-connected system [2], [3]. The stand-alone be connected directly to the dc bus. In this paper, the control
system is widely used in remote places where access to elec- of a PV system feeding dc loads is considered for study. In
tricity is not viable. The stand-alone configuration can provide GCPVs, the variation in PV power will cause fluctuation in dc
a well-regulated load voltage, but the reliability of power supply link voltage, which is regulated by adjusting the ac line current
cannot be guaranteed [3]. Storage batteries are widely used amplitude [3], [12]–[18], and under grid failure, a separate
to improve the reliability of the stand-alone system [4]. The controller is required to regulate the dc bus voltage [3], [25]. For
integration of a PV system to the grid is rapidly increasing due systems with dc loads, in addition to the PV power variation, the
to the improvement in the power electronics technology [5], [6]. fluctuation in loads also affects the dc bus voltage. The variation
Various topologies and control strategies [1]–[4], [7]–[28] for in the dc link voltage causes a proportional change in the ac line
grid-connected inverters have been reported in the literature. In current. This causes the line current amplitude to vary often,
grid-connected PV systems (GCPVs) [13]–[24], the generated leading to poor power quality [22].
PV power is fed to the grid, or it supplies the linear and Moreover, when the solar radiation is less, the power quality
is degraded as the total harmonic distortion (THD) of the line
Manuscript received November 24, 2011; revised March 1, 2012 and current is inversely proportional to the power injected into the
April 20, 2012; accepted May 25, 2012. Date of publication June 8, 2012; date grid [25], [31]. Furthermore, the disturbance in dc link voltage
of current version April 11, 2013. This work was supported by the National is reflected in PV array power, and the PV operating point
Mission on Power Electronics Technology (an initiative by Department of
Information Technology, Government of India) toward laboratory infrastructure shifts from the maximum power point (MPP). Hence, a fast
development. regulation of dc link voltage is necessary to ensure constant
The authors are with the Department of Electrical and Electronics Engineer- dc voltage while simultaneously maintaining the THD of the
ing, National Institute of Technology, Tiruchirappalli 620015, India (e-mail:
indu_b04@yahoo.com; gsilango@nitt.edu; cnmani@nitt.edu). current injected into the grid within the standard limits. An
Digital Object Identifier 10.1109/TIE.2012.2203772 attempt was made in [16] to provide reliable power to the loads

0278-0046/$31.00 © 2012 IEEE


3186 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013

connected at the dc side, yet in this case, the PV power is not


utilized effectively. When the generated PV power is more than
the load demand, only the load power demand is met by the
PV, and the excess PV power is not fed to the grid. Moreover,
the impact of dc loads on the performance of the system is not
discussed.
The proposed PV system consists of three power sources
(grid, PV array, and battery), three power sinks (grid, battery,
and load), and a power flow management system (PMS) to
balance the power flow among these. This paper illustrates an
effective power flow management scheme for providing unin- Fig. 1. Grid-connected PV system with ac and dc loads.
terrupted power supply to the dc loads from a grid-connected
PV system while facilitating the evacuation of excess PV power
at high quality into the grid. Combining (6) and (7)
2T 2T T
2
Vdc 2
= Vdc(ref) − (pbo − pL ) + pb + Vm I m .
II. S YSTEM D ESCRIPTION Cdc Cdc Cdc η
(8)
In a grid-connected PV system with dc loads as shown in
From (8), it is clear that the fluctuations in PV power due to the
Fig. 1, the instantaneous power relationship is given by
change in solar radiation and the load power cause variations in
pbo (t) = pb (t) + pdc (t) + pL (t) + pinv (t) (1) the dc link voltage. The average current at the dc link can be
written as
where pbo is the output power of the boost converter, pb is the
power delivered by the charger/discharger circuit, pdc is the Ibo = IL + Iinv + Ib + Idc (9)
power to the dc link capacitor, pL is the power consumed by
where Ibo is the output current of the boost converter, IL is
the dc load, and pinv is the power extracted by the inverter. The
the load current, and Iinv is the current on the input side of
instantaneous ac power can be written as
the inverter. If Vpv and Ipv are the PV voltage and current,
pac = (Vm sin ωt)(Im sin ωt) (2) respectively, for the boost converter operating at a duty cycle D,
the following equations can be written:
Vm I m Vm I m
= − cos 2ωt (3)
2 2 (1 − D)Ipv = IL + Iinv + Ib + Idc (10)
where Vm is the amplitude of the phase voltage and Im is the Vpv
Vdc =   (11)
amplitude of grid current. The ac power includes a dc term and (1 − D) 1 + RL
R(1−D)2
a second-order ripple in the dc voltage. The average power on
the dc side can be written as where RL is the parasitic resistance of the inductor and R is the
equivalent resistance of the load. When there is a sudden change
Pinv = Vdc Iinv (4) in load, Vdc changes to (Vdc ± ΔVdc ). Since the perturbation
of MPP tracker (MPPT) is slow, D remaining the same, the PV
where Iinv is the average current on the dc side of the inverter.
voltage shifts from the optimal voltage
Equating the average power on the dc side to the dc term on the
ac side Vpv = Vmpp ± ΔVpv (12)
Vm I m Ipv = Impp ∓ ΔIpv (13)
= ηVdc Iinv (5)
2
Ppv = Vmpp Impp ± ΔVpv Impp ∓ ΔIpv Vmpp
where η is the efficiency of the inverter. If Vdc and Vdc(ref) are
the actual and reference values of dc link voltage, respectively, ∓ ΔIpv ΔVpv . (14)
the change in energy (ΔEdc ) stored in the dc link capacitor Cdc
It is clear from (11) and (14) that the disturbances in dc link
can be written as
voltage are reflected in the PV array power and shift the PV
Cdc  2 
power from the MPP until the dc voltage is restored. Hence,
ΔEdc = Vdc(ref) − Vdc2
. (6)
2 a fast regulation of dc link voltage is necessary to ensure a
constant dc link voltage. A charger/discharger controller is
To inject the PV power to the grid while maintaining a constant
designed based on (8) to regulate the dc link voltage. The
Vdc , the following energy balance should be satisfied:
control structure of the system is shown in Fig. 2 where Vdc
 
Vm I m is regulated by the charger/discharger circuit. The converter
ΔEdc = T pbo − pL − pb − (7) control to output transfer function Gdc [32] is expressed as (15),

shown at the bottom of the next page, where rs is the resistance
where T is the time period of ac supply. of the battery, C1 and C2 are the input and output capacitances,
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3187

modes of operation is used to regulate the dc link voltage. The


PV system focuses on providing an uninterrupted power supply
to the loads connected at the dc side, and the grid is used
as a backup means when there is insufficient PV power and
complements the grid when excess PV power is available. This
necessitates the bidirectional converter to have three operating
modes, namely, idle mode (grid is disconnected), inverter mode,
and rectifier mode. The battery is charged either from PV or
grid depending upon the availability of the PV power and load
Fig. 2. Control structure of the proposed system. demand. The voltage control loop of the charger/discharger
circuit determines the charging/discharging mode of the battery.
TABLE I
PARAMETERS OF THE C ONTROLLER
The PV system involves three energy sources PV, battery, and
grid, and a PMS balances the power flow among these sources.
The control algorithm for the PMS is implemented on an Altera
Cyclone II FPGA board, and the control strategy is dealt in the
next section.

A. Control Strategy for PMS


respectively, L is the leakage inductance of the transformer, fsw
is the switching frequency, and d is the phase shift between the The PMS monitors the battery voltage and generates a
two bridges. The source to input transfer function [32] is given mode selection signal for the bidirectional converter, and it
by (16), shown at the bottom of the page. The transfer function also generates the reference current for the hysteresis current
of the load is represented by GL controller. The converter mode selection is carried out using
predetermined double bands of battery voltages. The outer
vdc (s) 1
GL (s) = =− (17) band corresponds to two voltage limits, i.e., the outer upper
IL (s) Cdc (s + 1/RCdc ) threshold voltage (VOUT ) and the outer lower threshold voltage
where R is the equivalent resistance of the load, and the relation (VOLT ). These limits correspond to the extreme voltages of
between PV current and the dc link voltage is expressed as the battery, i.e., the float value and the deep discharge level,
respectively. Similarly, the inner band voltage limits, i.e., the
vdc (s) inner upper threshold voltage (VIUT ) and inner lower threshold
Gpv (s) = = R(1 − D). (18)
Ipv (s) voltage (VILT ) correspond to interior voltage levels for the
purpose of control. For instance, for a battery with a nominal
Ginv denotes the transfer function of the grid-connected voltage of 36 V, the outer limits are VOUT = 40 V and VOLT =
inverter 32 V, and the inner limits are VIUT = 38 V and VILT = 34 V.
k vdc (s) Furthermore, the information of prevailing battery voltage (Vb )
Ginv (s) = = (19) and the present mode of converter are utilized in deciding
(1 + sτ ) Vg (s)
the next mode of the converter such that the converter does
where k is the amplitude gain and τ is the sampling delay. The not repeatedly shuttle between two different modes when the
parameters used in the controller are shown in Table I. system is operating near a threshold. The idea is to ensure that
The PV system consists of a PV array, a boost converter, the converter does not oscillate between rectifier and inverter
a battery storage unit with its charger/discharger circuit, and modes of operation.
a bidirectional converter to interface with the grid, and the The converter-mode-selection strategy is illustrated using
schematic of the PV system is shown in Fig. 3. A boost Table II and Fig. 4. The main feature of the strategy is that
converter is used to track the maximum power from the PV the transition from idle mode to conducting (rectifier/inverter)
array, and a dual H-bridge bidirectional converter (battery mode is based on the outer band limits, whereas a changeover
charger/discharger) capable of operating in both buck and boost from conducting mode to idle mode is based on the inner

vdc (s) (s + 2/rs C1 ) [(2d − 1)2V1 (3C2 − C1 )] /(fsw LC1 C2 )


Gdc (s) = = (15)
d(s) s + (2/rs C1 + 2/rs C1 )s + 4/Rrs C1 C2 + (2d2 − 2d)2 /fsw
2 2 L2 C C
1 2

vdc (s) (−2d2 + 2d)2/(f Lrs C1 C2 )


Gvb (s) = = (16)
Vb (s) s2 + (2/rs C1 + 2/rs C1 )s + 4/Rrs C1 C2 + (2d2 − 2d)2 /f 2 L2 C1 C2
3188 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013

Fig. 3. Schematic of the bidirectional converter with PMS.

TABLE II
C ONTROL S TRATEGY FOR PMS

Fig. 4. State diagram showing the power flow under various modes of
operation of the converter.
band limits. The control circuit for the implementation of
PMS is shown in Fig. 5(a), and the variation of Vb and the
reference current under each case is shown in Fig. 5(b). Based mode (idle or rectifier). However, the reference current for the
on the voltage threshold limits, two selection signals (S1 , S0 ) hysteresis controller is dictated by the previous mode. In case 1,
for the multiplexer determine the mode (M) of operation of the reference current is the a predefined constant current Ic ,
the converter. The inputs for the multiplexer 0, 1, and −1 whereas in case 8, it is (Ic + δI) (Table II). Next, if the battery
denote the idle, rectifier, and inverter modes of operation, voltage increases such that VOLT ≤ Vb , the converter continues
respectively. The operation of the PMS is explained for the to be in rectifier mode with the same reference current until
conduction when Vb < VOLT . In this situation, the converter Vb ≤ VIUT and is indicated in case 7. Similarly, when the
has to switch to rectifier mode irrespective of the previous battery voltage is higher than VOUT , then, the converter will
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3189

Fig. 5. (a) Control circuit of the PMS. (b) Reference current under different
cases shown in Table II.
Fig. 6. Power flow under various modes of operation of the bidirectional
converter. (a) Idle mode. (b) Inverter mode. (c) Rectifier mode.
move to the inverter mode irrespective of the previous mode
(cases 3 and 5). However, the current reference is dictated by drawn from the grid. However, if the battery is discharged to
the previous mode. Thus, it is ensured that the converter does less than VOLT , the reference current is incremented by δI so
not oscillate between rectifier and inverter modes under any that Vb > VOLT . As seen from Table II (case 8), the change
situation. in reference current is δI, and the PV and the grid charge the
Initially, assuming the converter to be in idle mode, the PV battery to VIUT . At this condition, the converter enters into idle
supplies the load connected at the dc side and also charges mode (case 9), and the direction of power flow for this mode is
the battery when Ppv > PL (case 2). This increases the battery shown in Fig. 6(c).
voltage, and once Vb ≥ VOUT , the converter enters into inverter
mode. If Ppv < PL , then both battery and PV contribute to
supply the load. However, this decreases Vb , and when Vb ≤ B. Hysteresis Controller
VOLT , the converter enters into rectifier mode. The power flow
A hysteresis current controller which is well proven and
diagram for this mode is shown in Fig. 6(a).
adopted to many industrial applications [33] is employed for
When the converter is in inverter mode, the PV power is
the current control of an inverter. The reference signal for the
injected into the grid, and the power flow diagram for this mode
hysteresis current controller is generated as a function of the
is shown in Fig. 6(b). Here, there is a possibility of Vb to in-
phase of the grid voltage using Phase Locked Loop (PLL).
crease or decrease depending on whether the battery is charging
The injected current is in phase with the grid voltage, and
or discharging. If VILT ≤ Vb ≤ VOUT , (case 4) the reference
thus, unity power factor is achieved. For an average switching
current is injected into the grid. However, when Vb ≥ VOUT , the
frequency fsavg , the value of inductance [33] is calculated as
reference current is incremented by a small amount δI (case 5)
18 mH using
such that Vb ≤ VOUT . Once Vb is less than the outer upper

threshold, there will be no change in the reference current, and Vdc a2
the converter operates in inverter mode until Vb > VILT after L1 = 1− (20)
4Δifsavg 2
which it stops injecting power and becomes idle (case 6).
When the converter is in rectifier mode, the battery may where Vdc is the dc link voltage, “a” is the modulation index,
charge or discharge depending on the availability of PV power and Δi is the ripple in the inverter current. The specifications
and load demand. If VOLT ≤ Vb ≤ VIUT , the current Ic is of the hysteresis current controller are shown in Table III.
3190 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013

TABLE III
S PECIFICATIONS OF THE H YSTERESIS C ONTROLLER

TABLE IV
S PECIFICATIONS OF THE E XPERIMENTAL S ETUP

III. R ESULTS AND D ISCUSSION


To evaluate the performance of the developed control strat-
egy, the time-domain simulation studies in MATLAB/Simulink
environment are presented, and the experimental tests are car-
ried out on a prototype unit built in the laboratory. The details of
the experimental setup are shown in Table IV. The system con-
sists of a PV array, a boost converter, a single-phase full-bridge
converter, and a charger/discharger circuit for the battery. The Fig. 7. Steady-state response. (a) Rectifier mode. (b) Inverter mode.
array configuration includes five parallel strings with each hav-
ing two panels (rated 80 W · p) in series to get 36 V at the MPP. indicating that the converter is operating in rectifier mode and
A boost converter raises the PV voltage to 110 V. A bidirec- supplies 230 W at 0.99 power factor. The THD of the line
tional dual H-bridge circuit which can operate in either buck or current is found to be 3.7%. Fig. 7(b) shows the steady-state
boost mode acts as the charger/discharger circuit of the battery. performance of the system in the inverter mode, and a 192-W
The well-known phase shift modulation strategy [34] is used to power is fed to the grid from the PV. The THD of the line
control the charger/discharger circuit. The voltage control loop current in this mode is found to be 4.1%. It can be observed that
of the charger/discharger circuit maintains the dc link voltage. a near unity power factor is achieved in both the rectifier and
The single-phase bidirectional converter is built using power inverter modes of operation. In both the modes of operation, the
Insulated Gate Bipolar Transistor ( IGBT) SKM100GB063D minimum current is set as 1 A by the PMS. Under any operating
and is connected to the grid through an 80/230-V line frequency mode, the injected current is more than the minimum value, and
transformer. The gate pulses to the converter are fed through therefore, the THD will always be less than the standard limit
SKHI22A driver circuits. The grid voltage and the battery volt- of 5%.
age are sensed using isolated voltage transducers LV25P, and
the actual current is measured using current transducer LA55P.
The control algorithm including MPP tracking, dc link voltage B. Dynamic Response
control, hysteresis current control, and the power management To validate the effectiveness of the system in employing the
system are digitally implemented in an Altera Cyclone II FPGA charger/discharger circuit to regulate the dc link voltage, the
board. The performance of the converter under steady state and dynamic performance of the system for two different cases,
transient conditions such as step change in load and step change namely, a step change in dc load and a step change in insolation,
in insolation is analyzed and compared with the performance of is obtained and compared with the results obtained for a typical
the ac line current control technique [22]. The control strategy ac line current control.
of the PMS is verified for different modes of operation by In a typical ac line current control, the mismatch between
varying the load. input PV power and the load power dictates the mode of
operation of the converter, and the dc link voltage is regulated
by varying the ac line current magnitude. On the other hand, in
A. Steady-State Response
the proposed control, the battery voltage is used to determine
The steady-state response of the single-phase converter op- the mode of operation of the converter, and the dc link voltage
erating in rectifier mode is shown in Fig. 7. It can be observed is regulated by the battery charger/discharger circuit. For a step
from Fig. 7(a) that the grid voltage and line current are in phase, change in load, two different cases are considered.
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3191

Fig. 8. Dynamic response for step change in load: (a) AC line current control (iL —0.5 A/div; Vdc —55 V/div; Ppv —100 W/div; io —0.5 A/div). (b) AC
line current control (iL —1 A/div; Vdc —55 V/div; Ppv —100 W/div; io —0.5 A/div). (c) Proposed control (iL —1 A/div; Vdc —55 V/div; Ppv —100 W/div;
ib —1 A/div; io —1 A/div; Vb —5 V/div). Dynamic response for step change in insolation: (d) AC line current control (iL —0.5 A/div; Vdc —40 V/div; Ppv —100
W/div; io —1 A/div). (e) AC line current control (iL —0.5 A/div; Vdc —40 V/div; Ppv —100 W/div; io —1 A/div). (f) Proposed control (iL —0.5 A/div; Vdc —55
V/div; Ppv —200 W/div; ib —1 A/div; io —1 A/div; Vb —5 V/div). Time: 0.025 s/div.

1) When a step change in load closely matches the generated In the proposed system, for the same step increase in
PV power with the load power (Ppv ≈ PL ). load from 224 to 342 W (Ppv < PL ), the increase in load
In this case with ac line current control, the remaining current is compensated by the increase in current ib of the
less amount of power (Ppv − PL ) is fed to the grid. One charger/discharger circuit. The current injected into the grid
such situation is shown in Fig. 8(a). When the dc load remains constant as set by the PMS and is shown in Fig. 8(c). It
is increased from 164 to 202 W, with the PV power can also be observed that the change in battery voltage during
remaining the same, the current injected into the grid is this period is less (39.2 to 37.7 V), and hence, the converter
reduced to 0.1 A. This increases the THD of the injected does not change the mode of operation of the converter.
line current to a high value of 28.8%. The magnified Similarly, for step change in insolation, two cases are
view of ripple in the ac line current io is shown in the considered.
subplot in Fig. 8(a). However, in the proposed technique,
the minimum current reference is set as 1 A by the PMS 1) When a step change in insolation closely matches the
as shown in Fig. 7(b). generated PV power with the load power (Ppv ≈ PL ).
2) When a step change in load changes (Ppv > PL ) to In the ac line current control with the load power
(Ppv < PL ). remaining constant at 160 W, the PV power is decreased
In this case, the converter initially operating in in- to 348 W. The current injected into the grid is reduced to
verter mode changes to rectifier mode. Fig. 8(b) shows 0.7 A, and this increases the THD to 5.2%. The subplot
that, initially, the inverter supplies the surplus PV power in Fig. 8(d) is the magnified view of the current io . It can
(Ppv > PL ) to the grid, and as the load power is increased be observed that the THD of the current injected into the
to 342 W, the PV power (282 W) is insufficient to supply grid varies with the insolation. In the proposed technique,
the load demand, and the grid supplies the deficit power. It the charger/discharger complements the PV power, and
is clear from Fig. 8(b) that fluctuations in load conditions always, a minimum current is fed to the grid.
cause the converter to swing between inverter and rectifier 2) When a step change in insolation changes (Ppv > PL ) to
modes of operation. Moreover, it can be observed that (Ppv < PL ).
the disturbance in Vdc causes PV array power to decrease In the ac line current control, the PV power is reduced
from its maximum value. to 168 W (Ppv < PL ) with the load power remaining
3192 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013

Fig. 9. Grid failure under (a) inverting mode and (b) rectifier mode. y-axis: Iinv : 4 A/div; Vb : 80 V/div; Ib : 4 A/div; IL : 4 A/div. x-axis: time: 50 s/div.

constant at 202 W. As shown in Fig. 8(e), the converter A sudden removal of grid supply forces the converter to idle
changes from inverter to rectifier mode. With the pro- mode; as Ppv < PL , the battery supplies the deficit power;
posed system for the same step change in insolation, the when its voltage drops to 32 V, noncritical loads are removed to
deficit power is supplied by the charger/discharger circuit, avoid deep discharge of batteries; the other loads are supplied
and a minimum current set by the PMS is injected into by PV.
the grid as shown in Fig. 8(f). It can also be observed that
the change in battery voltage during this period is from
D. Automatic Power Flow Mode
38.6 to 37.1 V, and hence, the converter does not shuttle
between different modes. An increase in PV power or a decrease in load power leads to
It can also be observed from the aforementioned results inverter mode, whereas a decrease in PV power or an increase
that dc link voltage regulation using ac line current affects in load power leads to rectifier mode. Hence, to test the control
the THD of the injected grid current, and the converter often strategy of the PMS, four different cases are considered for
oscillates between the rectifier and inverter modes of operation study as follows:
for variation in load and PV power. Moreover, the disturbance Case 1) inverter to rectifier mode via idle mode;
in Vdc causes PV operation to shift from the MPP. Overall, Case 2) inverter to inverter mode via idle mode;
the proposed scheme is seen to be effective in preventing the Case 3) rectifier to inverter mode via idle mode;
undesirable shuttling of the PV operating point and maintains Case 4) rectifier to rectifier mode via idle mode.
the THD of the injected grid current within the allowable limit Since the mode of operation of the converter depends on
by setting a minimum current reference for injection. the battery voltage, to verify the control strategy, the variation
in battery voltage is obtained by changing the load across
the battery. The resistive loads are chosen such that a step
C. Grid Failure Mode
change in load causes the variation in battery voltage. The
When the grid power fails, irrespective of the present mode experimental waveforms are shown in Fig. 10. Traces 1 and 2
of operation of the converter (rectifier/inverter), the PMS forces show the battery voltage and battery current, respectively, and
the converter into idle mode. Both PV and battery supply the the converter current at the dc side is shown in trace 3.
load at the dc side. The worst case scenario under inverting Case I and Case II: When the PV power (352 W) is more
mode is grid failure when Vb is slightly less than VOUT and than the load power requirement of 242 W, the converter is in
Ppv > PL , and one such situation is shown in Fig. 9(a). With inverting mode and injecting 230 W of power into the grid.
233 W of PV power and 160 W of load power, the converter op- The contribution of the battery charger/discharger circuit is
erates in inverter mode and injects 230 W of power into the grid. 144 W. Now, an increase in dc load power (287 W) leads to
When Vb = 39.2 V, a sudden removal of grid supply forces the the reduction of battery voltage. This is obtained by applying
converter to idle mode, and now, the power balance is to be loads in steps at which the battery voltage falls below VILT
achieved among PV, load, and battery. As the excess PV power (33.8 V), and at this instant, the converter enters into idle mode,
charges the battery to VOUT , dump loads are switched on, and indicating a zero current. An increase in load power (320 W)
both PV and battery together supply the load. This is evident leads to the reduction in battery voltage to 31.8 V, and the
from the reversal of current direction in the charger/discharger converter enters into rectifier mode as shown in Fig. 10(a),
circuit. whereas a decrease in load power (222 W) makes the converter
The worst case scenario under rectifier mode occurs when to operate in inverter mode and inject 230 W of power to the
grid power fails when Vb is slightly more than VOLT and grid and is shown in Fig. 10(b).
Ppv < PL , and such a situation is shown in Fig. 9(b). With Case III and Case IV: To verify Cases III and IV, prior to
228 W of PV power, 242 W of load power, and Vb = 32.6 V, the experiment, the loads are applied, and the battery voltage
the converter operates in rectifier mode and charges the battery. is brought below 32 V, so that the power flow is from the grid
INDU RANI et al.: CONTROL STRATEGY FOR POWER FLOW MANAGEMENT IN PV SYSTEM SUPPLYING DC LOADS 3193

Fig. 10. Battery voltage, battery current, and dc current waveforms for different cases under automatic power flow control. (a) Case I. (b) Case II. (c) Case III.
(d) Case IV. y-axis: Vb : 10 V/div; Ibat : 2 A/div; Iinv : 4 A/div. x-axis: time: 20 s/div.

to the dc side. With 297 W of PV power and 221 W of power The significance of the proposed scheme has been demon-
from the grid, the battery charger/discharger circuit charges the strated by its effectiveness in preventing undesirable shuttling
battery. Now, the loads are released in steps, which rises the of the PV operating point and also in maintaining the THD
battery voltage above the VIUT (38.3 V), and the converter of the injected grid current within the allowable limit of 5%
enters into idle mode. The removal of load increases Vb above by setting a minimum current reference for injection. The
VOUT (40.2 V), and the converter changes into inverter mode, proposed configuration has been proved to be attractive from
and 230 W of power is fed to the grid. This can be observed the perspective of providing uninterruptible power to dc loads
from Fig. 10(c). However, an increase in load demand reduces while ensuring the evacuation of excess PV power of high
Vb . This situation is verified by applying loads in steps and is quality into the grid.
shown in Fig. 10(d). It is evident from the results that the system
exhibits a reasonably good response to the variation in load. R EFERENCES
[1] Yazdani and P. P. Dash, “A control methodology and characterization of
dynamics for a photovoltaic system interfaced with a distribution net-
work,” IEEE Trans. Power Del., vol. 24, no. 3, pp. 1538–1551, Jul. 2009.
IV. C ONCLUSION [2] X. Q. Guo and W. Y. Wu, “Improved current regulation of three-phase
grid-connected voltage-source inverters for distributed generation sys-
A versatile control strategy for power flow management in a tems,” IET Renew. Power Gener., vol. 4, no. 2, pp. 101–115, Mar. 2010.
grid-connected PV system feeding dc loads has been presented. [3] H. C. Chiang, T. T. Ma, Y. H. Cheng, J. M. Chang, and W. N. Chang,
The importance of the scheme has been brought out by per- “Design and implementation of a hybrid regenerative power system com-
bining grid-tie and uninterruptible power supply functions,” IET Renew.
forming experimental studies on a laboratory prototype. The Power Gener., vol. 4, no. 1, pp. 85–99, Jan. 2010.
steady-state performance of the converter for different modes [4] F. Giraud and Z. M. Salameh, “Steady-state performance of a grid-
of operation has been observed, and near unity power factor connected rooftop hybrid wind–photovoltaic power system with battery
storage,” IEEE Trans. Energy. Convers., vol. 16, no. 1, pp. 1–7, Mar. 2001.
has been achieved in both the rectifier and inverter modes. The [5] J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewicz, E. Galvàn,
transient performance of the system for step changes in load R. C. P. Guisado, M. A. M. Prats, J. I. León, and N. Moreno-Alfonso,
and insolation have been also illustrated. “Power electronic systems for the grid integration of renewable energy
sources: A survey,” IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1002–
The control strategy has been digitally implemented on an 1016, Aug. 2006.
Altera Cyclone II FPGA board, and the algorithm has been ver- [6] B. Kroposki, C. Pink, R. DeBlasio, H. Thomas, M. Simões, and P. K. Sen,
ified for different modes of operation by varying the load, and “Benefits of power electronic interfaces for distributed energy sources,”
IEEE Trans. Ind. Electron., vol. 25, no. 3, pp. 901–908, Sep. 2010.
a good correlation between the results of computer simulation [7] H. M. Kojabadi, B. Yu, I. A. Gadoura, L. Chang, and M. Ghribi, “A
and experiments has established the validity of the PMS. novel DSP-based current controlled PWM strategy for single phase grid
3194 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 60, NO. 8, AUGUST 2013

connected inverters,” IEEE Trans. Ind. Electron., vol. 21, no. 4, pp. 985– [27] J. T. Bialasiewicz, “Renewable energy systems with photovoltaic power
993, Jul. 2006. generators: Operation and modeling,” IEEE Trans. Ind. Electron., vol. 55,
[8] J. C. Moreno, J. M. Espi Huerta, R. G. Gil, and S. A. Gonzalez, “A robust no. 7, pp. 2752–2758, Jul. 2008.
predictive current control for three-phase grid-connected inverters,” IEEE [28] T. Hirose and H. Matsuo, “Standalone hybrid wind–solar power gener-
Trans. Ind. Electron., vol. 56, no. 6, pp. 1993–2004, Jun. 2009. ation system applying dump power control without dump load,” IEEE
[9] Z. Yao, L. Xiao, and Y. Yan, “Seamless transfer of single phase grid Trans. Ind. Electron., vol. 59, no. 2, pp. 988–997, Feb. 2012.
interactive inverters between grid connected and standalone modes,” IEEE [29] W. Qi, J. Liu, X. Chen, and P. D. Christofides, “Supervisory predictive
Trans. Power Electron., vol. 25, no. 6, pp. 1597–1603, Jun. 2010. control of standalone wind/solar energy generation systems,” IEEE Trans.
[10] M. Singh, V. Khadkikar, A. Chandra, and R. K. Varma, “Grid intercon- Ind. Electron., vol. 19, no. 1, pp. 199–207, Jan. 2011.
nection of renewable energy sources at the distribution level with power- [30] K. Jin, X. Ruan, M. Yang, and M. Xu, “A hybrid fuel cell power system,”
quality improvement features,” IEEE Trans. Power Del., vol. 26, no. 1, IEEE Trans. Ind. Electron., vol. 56, no. 4, pp. 1212–1222, Apr. 2009.
pp. 307–315, Jan. 2011. [31] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-
[11] S. Yang, Q. Lei, F. Z. Peng, and Z. Qian, “A robust control scheme filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., vol. 41,
for grid-connected voltage-source inverters,” IEEE Trans. Ind. Electron., no. 5, pp. 1281–1291, Sep./Oct. 2005.
vol. 58, no. 1, pp. 202–212, Jan. 2011. [32] H. Bai, C. Mi, C. Wang, and S. Gargies, “The dynamic model and hybrid
[12] F.-S. Pai, J.-M. Lin, and S.-J. Huang, “Design of an inverter array for phase shift control of a dual active bridge converter,” in Proc. IECON,
distributed generations with flexible capacity operations,” IEEE Trans. 2008, pp. 2840–2845.
Ind. Electron., vol. 57, no. 12, pp. 3927–3934, Dec. 2010. [33] P. A. Dahono, “New hysteresis current controller for single-phase full-
[13] H. Patel and V. Agarwal, “Investigations into the performance of bridge inverters,” IET Power Electron., vol. 2, no. 5, pp. 585–594,
photovoltaics-based active filter configurations and their control schemes Sep. 2009.
under uniform and non-uniform radiation conditions,” IET Renew. Power [34] C. Mi, H. Bai, C. Wang, and S. Gargies, “Operation, design and control of
Gener., vol. 4, no. 1, pp. 12–22, Jan. 2010. dual H-bridge-based isolated bidirectional DC–DC converter,” IET Power
[14] Y.-C. Kuo, T.-J. Liang, and J.-F. Chen, “Novel maximum power point Electron., vol. 1, no. 4, pp. 507–517, Dec. 2008.
tracking controller for photovoltaic energy conversion system,” IEEE
Trans. Ind. Electron., vol. 48, no. 3, pp. 594–601, Jun. 2001.
[15] Y.-K. Lo, T.-P. Lee, and K.-H. Wu, “Grid-connected photovoltaic system
with power factor correction,” IEEE Trans. Ind. Electron, vol. 55, no. 5, Balasubramanian Indu Rani (M’10) received the
pp. 2224–2227, May 2008. B.E degree from Government College of Engineer-
[16] Y. K. Lo, H. J. Chiu, T. P. Lee, I. Purnama, and J. M. Wang, “Analysis ing, Tirunelveli, India, and the M.E degree from
and design of a photovoltaic system connected to the utility with a power Anna University, Chennai, India.
factor corrector,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4354– From 2004 to 2009, she was with the School of
4362, Nov. 2009. Electrical Sciences, VIT University, Vellore, India.
[17] E. Romero-Cadaval, M. I. Milanés-Montero, E. González-Romera, and She is currently a Full-time Research Scholar with
F. Barrero-González, “Power injection system for grid-connected pho- the National Institute of Technology, Tiruchirappalli,
tovoltaic generation systems based on two collaborative voltage source India. Her areas of interest include renewable energy
inverters,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4389–4398, systems and power electronics.
Nov. 2009.
[18] J. He, Y. Li, and M. S. Munir, “A flexible harmonic control approach
through voltage-controlled DG-grid interfacing converters,” IEEE Trans.
Ind. Electron., vol. 59, no. 1, pp. 444–455, Jan. 2012. Ganesan Saravana Ilango received the B.E. degree
[19] R. A. Mastromauro, M. Liserre, T. Kerekes, and A. Dell’ Aquila, “A from the University of Madras, Chennai, India, in
single-phase voltage-controlled grid-connected photovoltaic system with 2000, the M.E. degree from Bharathidasan Univer-
power quality conditioner functionality,” IEEE Trans. Ind. Electron, sity, Tiruchirappalli, India, in 2001, and the Ph.D.
vol. 56, no. 11, pp. 4436–4444, Nov. 2009. degree from the National Institute of Technology,
[20] J. M. Espí, J. Castelló, R. García-Gil, G. Garcerá, and E. Figueres, “An Tiruchirappalli.
adaptive robust predictive current control for three-phase grid-connected From 2001 to 2004, he was a Lecturer with Noorul
inverters,” IEEE Trans. Ind. Electron., vol. 58, no. 8, pp. 3537–3546, Islam College of Engineering, Kumaracoil, India.
Aug. 2011. Since 2006, he has been an Assistant Professor with
[21] J.-M. Kwon, B.-H. Kwon, and K.-H. Nam, “Grid-connected photovoltaic the National Institute of Technology. His preferred
multistring PCS with PV current variation reduction control,” IEEE Trans. working areas are Flexible AC Transmission Sys-
Ind. Electron., vol. 56, no. 11, pp. 4381–4388, Nov. 2009. tems controllers, digital controllers, renewable energy systems, and power
[22] Y.-M. Chen, H.-C. Wu, Y.-C. Chen, K.-Y. Lee, and S.-S. Shyu, “The AC quality.
line current regulation strategy for the grid connected PV system,” IEEE
Trans. Power Electron, vol. 25, no. 1, pp. 209–218, Jan. 2010.
[23] S. V. Araújo, P. Zacharias, and R. Mallwitz, “Highly efficient single phase
transformerless inverter for grid connected photovoltaic systems,” IEEE Chilakapati Nagamani (M’10) received the B.Tech.
Trans. Ind. Electron, vol. 57, no. 9, pp. 3118–3128, Sep. 2010. degree from the Sri Venkateswara University College
[24] R. Kadri, J.-P. Gaubert, and G. Champenois, “An improved maximum of Engineering, Tiruapati, India, the M.Tech. degree
power point tracking for photovoltaic grid-connected inverter based on from the Indian Institute of Technology, Kanpur,
voltage-oriented control,” IEEE Trans. Ind. Electron., vol. 58, no. 1, India, and the Ph.D. degree from the University of
pp. 66–75, Jan. 2011. Technology, Sydney, Australia.
[25] S.-K. Kim, J.-H. Jeon, C.-H. Cho, J.-B. Ahn, and S.-H. Kwon, “Dynamic From 1985 to 1991, she was with the Central
modeling and control of a grid-connected hybrid generation system with Power Research Institute, Bangalore, India. Sub-
versatile power transfer,” IEEE Trans. Ind. Electron., vol. 55, no. 4, sequently, she joined the Department of Electrical
pp. 1677–1688, Apr. 2008. and Electronics Engineering, National Institute of
[26] E. Serban and H. Serban, “A control strategy for a distributed power Technology (then known as Regional Engineering
generation micro grid application with voltage and current controlled College), Tiruchirappalli, India, as a Lecturer, where she is currently a Pro-
source converter,” IEEE Trans. Power Electron, vol. 25, no. 12, pp. 2981– fessor. Her areas of interest include power electronics and drives, renewable
2992, Dec. 2010. energy systems, and FACTS controllers.

Potrebbero piacerti anche