Sei sulla pagina 1di 10

Midos Type MVGC01

Static Voltage Regulating


Control Relay

Features
● Integral line drop compensation
● Inverse or definite time
characteristics
● Reverse reactance or circulating
current compensation
● Undervoltage, overvoltage and
overcurrent supervision
● Digital voltage setting
● Comprehensive led indications and
alarms
● Local or remote voltage reduction
for load shedding or voltage
targetting
● Single relay can be used on
110/125 or 220/250V ac
supplies and 1A and 5A CTs

Figure 1: Type MVGC relay withdrawn from case.

Application Description
To maintain a system voltage supply Housed in a standard size 8 case,
within finite limits, it is necessary to incorporating a terminal block for
regulate the system voltage. This is external connections, the voltage
achieved by the use of regulating regulating relay, type MVGC01 is a
transformers of various types, the most solid state device offering many
common being the on-load tap functions previously requiring a
changing transformer which maintains number of separate relays to provide
a stable secondary voltage by such features as line drop
selecting appropriate tappings on the compensation, supervision and alarm
secondary windings. functions.
The tap changer operation is
controlled automatically by the
voltage regulating relay, which
continuously monitors the system and
initiates the tap changer mechanism.

2
B B
25 S10 A S8 A RL6
A 1 2
CT B t
IC S7 1 A 1 3 MIN
26 Alarm
IC S9
24 Definite t B
X1 RL2
VC Inverse X10
Pilot X1 Range 2
23 Range X2 E E R
& 1
& Lower
RL5
2 80% RL1
VS & 1 2
IL &
IL Raise
27 + +

Figure 2: Block diagram – static voltage regulating relay.


VS + – 1 1
CT F (A B)
VR
28
& 1
1 SEC
VXL Reverse VS Volts
X1 High Low
Direct Test
Range X2 R
17 RL7 t
RL7–1 B 1 2 0-10 SEC Tap
Ref Volts Load shedding In
18 A
–3% –6% –9% RL3
COM +3% +1.5% –1.5% Out S6 2 RL6 6
RL7–2
22 VO Alarm
8 RL6 10
19 VO RL4 2 12 Alarm
20 RL4 Under
4 4 voltage RL2 RL4 5 Lower
21
volts
VU RL3 7 RL5 3
Common
13 Over
220V 9 RL1 RL3 1 Raise
VU voltage
Aux. 15 volts
Volts 110V
14 Power
0V supply Note: Both ranges of load shedding limits are shown.
circuits The relay will have limits of either
–3%, –6%, –9% or +3%, +1.5%, –1.5%
as specified with order

3
Phase to phase input voltage Phase to neutral input voltage
with single phase input current with phase to phase input current
A
A A
P1 P2 P1 P2
B B
S1 S2 S1 S2 P1 P2
C C
C B S1 S2
V1 V2 Phase rotation V1 v1

v1 110V v2 V2 v2

18 17 27 28
MVGC01

25 6
8
Alarm
26
24 10
23 12
Alarm
27
28 Lower volts
5
17 3 Common
18 1 Raise volts
22
0% 3%
19
6% 2
20 Undervoltage
See Note 2 9% 4
21 Note 1. Earth connections are typical only
220V 7
Aux. 110V
13 Overvoltage 2. Remote load shedding control when required
15 9
supply 0V 14

See Note 1

Figure 3: Application diagram – single transformer application

Operation Relay type MVGC01 incorporates line


drop compensation to simulate
On relay type MVGC01, the resistive and reactive components of
regulated voltage, Vs is set by means the voltage drop across a line
of a digital switch and the connected to the regulating
appropriate deadband setting, ∆V%, transformer. Compounding the
selected. When the regulated voltage simulated line drop voltage into the
moves outside the deadband setting, voltage regulating circuits allows a
the relay actuates the tap changer constant supply voltage to be
mechanism to regulate the power maintained at the user end of the line
system voltage. irrespective of the line load current.
In order to minimise unnecessary tap Where the relay is used to control two
changes due to transient voltage or more transformers in parallel, either
fluctuations, the relay incorporates a circulating current compensation, Vc,
continuously variable delay before the or reverse reactance compounding
reclosure of the relevant tap change can be used to maintain a minimum
initiating contact for 1 second. The circulating current between
initial time delay is selectable for transformers.
either a definite time or a time delay Under conditions of undervoltage,
which is inversely proportional to the overvoltage and overcurrent,
degree of voltage variations from the supervision circuits can be set to
Vs setting. prevent undesired tap change
Subsequent tap changes are initiated initiations. In the event of tap changer
after a definite inter-tap time delay. mechanism failure, an alarm is
For induction regulators, a non-pulsing initiated afler a 3 minutes delay. This
output is obtained by selecting the alarm is also operated by a
inter-tap time to less than zero. circulating current detector with or
without the 3 minutes delay.

4
A A
P1 P2 P1 P2
B B
S1 S2 S1 S2
C C

V1 V2 A V1 V2

C B
v1 110V v2 v1 110V v2
Phase rotation

25 6
8
Alarm
26
24 10
23
Alarm
12
27
25 6
8
Alarm 28 5 Lower volts
26
24 10 17 3 Common
Alarm 18 1 Raise volts
23 12
See note 2 MVGC01
27 22
28 0% 3% 19
5 Lower volts
3 Common 6% 20 2
17
4
Undervoltage
18 1 Raise volts 9% 21
See Note 2 MVGC01
22 220V 7
Aux. 13 Overvoltage
0% 3% 19
110V
15 9
supply 0V
6% 2 14
20
4
Undervoltage
9% 21
220V 7 See note 1
13 Overvoltage
Aux. 110V
15 9
supply 0V
14
Note 1. Earth connections are typical only
2. Remote load shedding control when
See Note 1 required

Figure 4: Application diagram – parallel transformer operation (phase–phase voltage input and phase current)

Relay settings 80% undervoltage inhibit


To prevent tap change initiation for
Integrating timer undervoltage/fault conditions, the
The initial delay timer resets at a rate initial time delay is reset and inhibited
equal to the rate at which it times out. where the system voltage falls below
This ensures that a tap change 80% of the Vs setting.
sequence can only be initiated where
the mean system voltage remains Load shedding
outside the deadband for the set initial Load shedding or voltage target in
delay. For voltage swings through the stages of –3%, –6% or –9% can be
Vs setting, the initial delay timer is selected by connecting an
reset instantaneously and a new appropriate relay terminal to a
timing cycle is commenced. common terminal, 22, on the relay.
Local indication of selected load
Inter tap delay shedding is given by led indicators on
If more than one tap change is the relay and the selector switch can
necessary to bring the voltage within be local or remote through pilot wires.
deadband, the inter tap delay Alternatively, voltage targets of +3%,
determines the minimum permitted +1.5%, or –1.5% change in the
time between sequential tap changes. nominal Vs setting may be specified.
This delay is continuously adjustable
for 0 to 10 seconds and is normally
set to the operating time of the tap
changer mechanism. A setting of less
than zero gives a non-pulsing output.

5
(%)
110

Definite
100

90

Operating time delay (% of initial delay setting)


80

70

60

50

40
Inverse = Initial time delay setting
N
30

20

10

0 1 2 3 4 5 6 7 8 9 10
(N)
Vs V%
Voltage deviation from Vs in multiples of V%

Figure 5: Operating time characteristics.

Undervoltage, overvoltage detection Alarm relay


A malfunction of the tap changer An alarm output relay operates where
control system could drive the the regulating voltage continuously
transformer to upper or lower limits; to remains outside the deadband for a
prevent this, detectors are provided to period of 3 minutes, corresponding to
ensure that only tap changes which a tap changer mechanism failure.
would restore normal voltage are The time delay resets instantaneously
permitted. Undervoltage or when the voltage is restored to within
overvoltage conditions are indicated the deadband limits.
by front of panel leds and associated This feature may be removed by the
output contacts. internal switch S9.

Overcurrent detection By setting the internal S10 to B the


alarm output contact may be initiated
Separate overcurrent detectors are
by operation of the excessive
provided for excessive load current
circulating current detector to provide
and excessive circulating current
either an instantaneous or time delayed
between transformers in parallel.
alarm as set by the internal S8.
Indications of both fault conditions are
given by led indicators on the relay. Built in test facility
Operation of excessive load current
By connecting an ac voltmeter to the
detector, IL, operates an internal
‘VOLTAGE MONITOR’ terminals on
blocking relay preventing tap change the relay front panel, setting to ‘TEST’
initiation. The blocking relay can also position and turning the ‘TEST VOLTS
be operated by the excessive ADJUST’ potentiometer control, all the
circulating current detector as selected voltage settings and time delays can
by an internal setting switch. be checked by monitoring the
respective led indicators.

6
Technical Data
Ratings
Rated current (In) 1A or 5A
Auxiliary supply Vx ac 110/120V and 220/250V
110/120V input may be regulated
voltage supply
Auxiliary supply range (V) 80–160 for 110/125 connection
160–320 for 220/250 connection
Rated frequency 50Hz or 60Hz
Frequency range –6% to +2% of rated frequency

Burdens
Auxiliary supply 20VA max at 120V
Line drop CT 0.4VA at rated current
Circulating current CT 0.8VA at rated current
Measuring input VT 2.0VA at 120V
Loading shedding or –3%, –6%, –9% Vs or
voltage targets +3%, +1.5%, –1.5% Vs
Settings
Regulated voltage setting Vs 100–139V in 1V steps ±0.5%
Deadband setting ∆V% ±0.5 to ±3.0% of Vs continuously
adjustable
Accuracy: ±0.2% of Vs setting
Initial delay setting 1.2–12s or 12–120s continuously
(refer to Figure 5) variable with range selected by 1 or
10 times multiplier
Initial delay setting accuracy
Definite time delay 1.2–12s range:
0.5s + setting,
Accuracy: –0 +0.8s or ±10%
whichever is greater
12–120s range: as setting, ±5%
Inverse time delay 1.2–12s range:
0.5s + (initial setting x 1/N)
Accuracy: –0 +0.8s or ±20%
whichever is greater
12–120s range:
Initial delay setting x 1/N
Accuracy: ±15%
where N is voltage deviation from Vs
setting in multiples of ∆V% setting
Inter-tap delay 0–10s continuously adjustable ±10%
Output pulse 1s ±0.2s continuous output obtainable
by setting inter-tap delay to less than
zero
Undervoltage inhibition 80% of Vs ±1%

7
Line drop compensation
Resistive setting VR 0–24V at rated current ±0.5V or ±5%
whichever is the greater
Reactive setting VXL 0–24V at rated current ±0.5V or ±5%
whichever is the greater
variable multiplier: 1 or 2 times
variable setting
Circulating current compensation VC 0–24V at rated current ±0.5V or ±5%
whichever is the greater
variable multiplier: 1 or 2 times
variable setting

Load shedding –3%, –6% or –9% or


+3%, +1.5% or –1.5% of Vs ±0.5%
External selection can be remote or
local
Supervision
Undervoltage setting VU 80–120V ±5%
Overvoltage setting VO 110–160V ±5%
Circulating current setting ΙC 50–500mA for I n = 1.0A ±5%
0.25–2.5A for I n = 5.0A ±5%
Load overcurrent setting ΙL 1.0–2.0A for I n = 1.0A ±5%
5.0–10.0A for I n = 5.0A ±5%
Alarm delay time 3 minutes 0 to 20%

Contacts
Make and carry for 0.2s ac 7500VA with maxima of 30A
and 300V
dc 7500VA with maxima of 30A
and 300V
Make and carry continuously 5A ac or dc
Break ac 1250VA with maxima of 5A
and 300V
dc 50W resistive
25W L/R = 0.04s with maxima
of 5A and 300V

Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

High voltage withstand


Dielectric withstand
IEC 255-5:1977 2kV rms for 1 minute between all
terminals and case earth.
2kV rms for 1 minute between
terminals of independent circuits
including contact circuits, with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.
High voltage impulse
IEC 255-5:1977 5kV peak, 1.2/50µs, 0.5J between
all terminals and case earth and
between adjacent terminals.

8
Electrical environment
High frequency disturbance
IEC 255-22-1:1988 Class III - 2.5kV peak between
independent circuits and case.
- 1.0kV peak across terminals of the
same circuit.
No additional tolerances are required
for the operating time or the unit’s
thresholds.
Electrostatic discharge
IEC 255-22-2:1989 Class II (4.0kV) - discharge in air with
cover in place.
IEC 801-2:1991 Level 2 (4.0kV) - point contact
discharge with cover removed.
No additional tolerances are required
for the operating time or the unit’s
thresholds.

Atmospheric environment
Temperature
IEC 255-6:1988 Storage and transit -25°C to +70°C
Operating -25°C to +55°C
IEC 68-2-1:1990 Cold
IEC 68-2-2:1974 Dry heat
Humidity
IEC 68-2-3:1969 56 days at 93% RH and 40°C
Enclosure protection
IEC 529:1989 IP50 (dust protected)

Mechanical environment
Vibration
IEC 255-21-1:1988 Response Class 1
Endurance Class 1

9
155.4
4 holes 4.4 24
200

168 159

Push button 203


projection 10 max
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

206 Flush mounting 11


All dimensions in mm

Figure 6: Case outline size 8.

Cases Information Required with


Order
Type MVGC relays are supplied in
size 8 cases. See Figure 6 Load shedding
limits: –3%, –6%, –9% Vs or
+3%, +1.5%, -1.5% Vs
Frequency

10

Potrebbero piacerti anche