CLEVIS HANGERS & SHIELDS

Fig. 260 (Formerly Afcon Fig. 371)

Contents
Ring Clevis Hangers General Pictorial Table of
Adjustable Clevis Hanger

TOC
Size Range: 1⁄2" through 30"
Material: Carbon steel
Finish: P lain, 8" & Smaller: Zinc Plated (Hot-Dip Galvanized optional), 10" & Larger: Hot-Dip Galvanized

Notes
with Zinc Plated Bolts & Nuts, or Primed, also available in Plastic or Epoxy Coated.
Service: R  ecommended for the suspension of stationary pipe lines.

& Shields
Maximum Temperature: Plain 650° F, Galvanized and Epoxy 450° F
Approvals: C  omplies with Federal Specification A-A-1192A (Type 1), WW-H-171-E (Type 1),
ANSI/MSS SP-69 and MSS SP-58 (Type 1). FM Approved (Sizes 3⁄4" through 8"),

& Straps Clamps Clamps Hangers


UL and ULC Listed (Sizes 1/2" through 8")
Installation: Hanger load nut above clevis must be tightened securely to assure proper hanger performance.
Adjustment: Vertical adjustment without removing pipe may be made from 3⁄8" through 5 1⁄8",

Pipe
varying with the size of clevis. Tighten upper nut after adjustment.
Features:

Wall Ceiling Plates Beam AWWA CPVC U-Bolts Riser


• Design has yoke on outside of lower U-strap so yoke cannot slide toward center of bolt, thus
bending of bolt is minimized.
• Sizes 5" and up have rod and two nuts instead of bolt and nut; thread length on clevis rod is such that the thread locks the
nuts in place, and threads are not in shear plane.
Ordering: Specify pipe size, figure number, name and finish.
Notes: Punched forming holes may be present on certain sizes of this clevis hanger. These holes are solely for the purpose of manufac-
turing, and do not effect the structural integrity or load carrying capacities of these hangers. For insulated line options without shields,
see Figures 260 ISS and Figure 300. For insulated line options with shields, see Figures 167 and 168. For ductile iron pipe sizes, see Figure 590.

Accessories Attachments & Turnbuckles Eye Rods & Attachments Attachments Brackets & Flanges Clamps
Caution: When an oversize clevis is used, a pipe spacer or multispacer should be placed over clevis bolt to ensure that the lower
U-strap will not move in on the bolt.

A
FIG. 260: DIMENSIONS (IN) • LOADS (LBS) • WEIGHTS (LBS)
Pipe Max Span Rod Rod Take Adjust. H Width
Weight B C G
Size Load Ft. Size A Out E F Lower
G F ⁄2
1
0.34 23⁄16 11⁄2
B 610 211⁄16
⁄4
3
0.34 2 15⁄16

Welded
E
C 7* 5
⁄8
1 0.35 25⁄16 3 15⁄8
3
⁄8 1
⁄4
11⁄4 0.40 23⁄8 31⁄4 111⁄16
CL 730 1
11⁄2 9* 0.45 213⁄16 313⁄16 21⁄8 ⁄8
7

Rod Couplings Rod & Concrete Inserts


H 2 10* 0.50 35⁄16 41⁄2 25⁄8 11⁄8
21⁄2 11* 0.65 41⁄16 51⁄2 33⁄16 15⁄16
Pipe Size 1/2" to 3/4"
3 1,350 12* 0.85 1
⁄2 43⁄4 61⁄2 41⁄16 15⁄8 3
⁄8
31⁄2 13* 1.10 51⁄16 71⁄16 43⁄16 113⁄16
11/4
A 4 14* 1.51 59⁄16 713⁄16 41⁄2 111⁄16
1,430 5
⁄8 3
⁄8
5 16* 1.70 69⁄16 815⁄16 51⁄2 115⁄16 13/16
6 1,940 17* 3.10 615⁄16 101⁄4 53⁄4 111⁄16
3
⁄4 1
⁄2 17/16
8 2,000 19* 4.75 83⁄8 1211⁄16 73⁄16 2
F
G 10 3,600 22* 8.60 97⁄8 151⁄4 87⁄16 21⁄8 13/4
7
⁄8 5
⁄8
B 12 3,800 23* 11.20 119⁄16 1715⁄16 101⁄8 213⁄16
E
2
14 4,200 25* 12.50 129⁄16 199⁄16 1011⁄16 211⁄16 3
⁄4
C
16 4,600 27 19.85 1 14 22 12 23⁄4
Swivel

1 21/2
CL 18 4,800 28 22.25 1515⁄16 2415⁄16 1315⁄16 313⁄16
20 4,800 30 40.33 179⁄16 279⁄16 153⁄16 11⁄4
37⁄8
24 4,800 32 49.83 1 ⁄4
1
1913⁄16 3113⁄16 175⁄16 7
⁄8* 3
Hardware &

H 30** 6,000 33 70.18 243⁄16 393⁄16 219⁄16 51⁄8 11⁄4


“Span” represents the maximum recommended distance between hangers on a continuous and straight run of horizontal
Pipe Sizes 1" and Larger standard weight steel pipe filled with water. In all cases, verify that chosen location of hangers does not subject hangers to a
load greater than the maximum recommended load shown above. *Indicates that span represents the maximum span for water
filled pipe as given in Table 1 of page 268.
* The 24" pipe size assembly includes a 11/4" SCH 40 pipe spacer over the 7/8" threaded rod.
** 30" pipe size: When assembled, the U-strap sits outside of the yoke.
www.anvilintl.com 25
PH-1.18
CLEVIS HANGERS & SHIELDS

Fig. 260SS Adjustable Clevis Hanger

Size Range: 1⁄2" through 12"


Material: 304 stainless steel
Service: R ecommended for the suspension of stationary pipe lines.
Maximum Temperature: 650° F
Approvals: C  omplies with Federal Specification A-A-1192A (Type 1), WW-H-171-E (Type 1),
ANSI/MSS SP-69 and MSS SP-58 (Type 1).
Installation: Hanger load nut above clevis must be tightened securely to assure proper
hanger performance.
Adjustment: Vertical adjustment without removing pipe may be made from 3⁄8" through 5 1⁄8",
varying with the size of clevis. Tighten upper nut after adjustment.
Features:
• Design has yoke on outside of lower U-strap so yoke cannot slide toward center of bolt,
thus bending of bolt is minimized.
• Sizes 5" and up have rod and two nuts instead of bolt and nut; thread length on clevis
rod is such that the thread locks the nuts in place, and threads are not in shear plane.
Ordering: Specify pipe size, figure number and name.
Notes: P unched forming holes may be present on certain sizes of this clevis hanger. These holes are
solely for the purpose of manufacturing, and do not effect the structural integrity or load carrying capacities of these hangers.
For insulated line options without shields, see Figures 260 ISS and Figure 300. For ductile iron pipe sizes, see Figure 590SS.
Caution: When an oversize clevis is used, a pipe spacer or multispacer should be placed over clevis bolt to ensure that the lower
U-strap will not move in on the bolt.

A
FIG. 260SS: DIMENSIONS (IN) • LOADS (LBS) • WEIGHTS (LBS)
Pipe Max Load Rod Rod Take Adjust. H Width
Weight B C G
G F Size 450˚ F 650˚ F Size A Out E F Lower
B ⁄2
1
0.34 23⁄16 11⁄2
E
C 211⁄16
⁄4
3
0.34 2 15⁄16 5
⁄8
1 0.35 25⁄16 3 15⁄8
CL 520 470 ⁄8
3 1
⁄4
11⁄4 0.40 23⁄8 31⁄4 111⁄16
1
H 11⁄2 0.45 213⁄16 313⁄16 21⁄8 ⁄8
7

2 0.50 35⁄16 41⁄2 25⁄8 1 ⁄8


1
Pipe Size 1/2" to 3/4"
21⁄2 0.65 41⁄16 51⁄2 33⁄16 15⁄16
960 865 ⁄2
1 3
⁄8
3 0.85 43⁄4 61⁄2 41⁄16 15⁄8
A 4 1.51 59⁄16 713⁄16 41⁄2 111⁄16
1,215 1,095 ⁄8
5 3
⁄8
5 1.70 69⁄16 815⁄16 51⁄2 115⁄16 13/16
6 1,650 1,485 3.10 615⁄16 101⁄4 53⁄4 111⁄16
⁄4
3 1
⁄2 17/16
8 1,700 1,530 4.75 83⁄8 1211⁄16 73⁄16 2
F
G 10 1,750 1,575 8.60 97⁄8 151⁄4 87⁄16 21⁄8 13/4
⁄8
7 5
⁄8
B 12 1,850 1,665 11.20 119⁄16 1715⁄16 101⁄8 213⁄16 2
E
C “Span” represents the maximum recommended distance between hangers on a continuous and straight run of horizontal
standard weight steel pipe filled with water. In all cases, verify that chosen location of hangers does not subject hangers to a
load greater than the maximum recommended load shown above. *Indicates that span represents the maximum span for water
CL
filled pipe as given in Table 1 of page 268.

Pipe Sizes 1" and Larger

26
www.anvilintl.com
PH-1.15
CLEVIS HANGERS & SHIELDS

Fig. 260 ISS

Contents
Ring Clevis Hangers General Pictorial Table of
Clevis Hanger with Insulation Saddle System

TOC
Size Range: 1/2" through 12" pipe and accommodates up to 2" of insulation.
Material: Carbon steel with high impact glass reinforced polypropylene saddle and
carbon steel pipe spacer.

Notes
Finish: Plain, 8" & Smaller: Zinc Plated (Hot-Dip Galvanized optional), 10" & Larger: Hot-Dip
Galvanized with Zinc Plated Bolts & Nuts, or Primed, also available in Plastic or Epoxy Coated.

& Shields
Service: R ecommended for the suspension of stationary insulated chilled or hot
water pipe lines.
Maximum Temperature: 40° F to 200˚ F
Approvals: D  ual Fire Ratings, UL E94 V, and ASTM E84 Class 1 25/60.

& Straps Clamps Clamps Hangers


Installation: Hanger load nut above clevis must be tightened securely to assure
proper performance. Position the pipe on the saddle. Notch insulation to fit around
the saddle. Square cut adjoining insulation and butt the insulation ends to each

Pipe
other. Insulation joint is coated, caulked and taped following standard insulation
practice used on flanges and valves.

Wall Ceiling Plates Beam AWWA CPVC U-Bolts Riser


Adjustment: V  ertical adjustment without removing the hanger may be made 7/8"
through 23/8" varying with the size of the
clevis. Tighten all nuts after adjustment. FIG. 260 ISS SIZING TABLE FIG. 260 ISS SIZING TABLE
Features: V-Block design cradles pipe Insulation Thickness Copper Insulation Thickness
Pipe
through out the entire erection process. Tube
Size 1
/2" 3
/4" 1" 11/2" 2" 1
/2" 3
/4" 1" 11/2" 2"
Clevis bolt spacer included as standard Size
keeps the clevis lower strap from collapsing. (Size Number) (Size Number)

Eliminates:
1
/2 2 2 3 — — 3
/8 2 2 3 — —
3
/4 2 3 3 — — 1
/2 2 2 3 — —

Accessories Attachments & Turnbuckles Eye Rods & Attachments Attachments Brackets & Flanges Clamps
• Wood blocks and standard shields
1 2 3 3 — — 5
/8 2 2 3 — —
• Costly calcium silicate inserts
11/2 3 4 4 — — 3
/4 2 2 3 — —
• Re-leveling of piping at each 2 4 4 5 — — 1 2 3 3 — —
individual hanger after insulation 21/2 5 5 5 6 8 11/4 3 3 3 — —
is completed. 3 5 5 5 6 8 11/2 3 3 4 — —
Ordering: S pecify size number, pipe size, 31/2 5 6 6 8 8 2 4 4 4 — —
insulation thickness, figure number name 4 6 6 8 8 8 21/2 4 5 5 6 —
and finish. 5 8 8 8 10 10 3 5 5 5 6 8
6 10 10 10 10 10 31/2 5 5 6 8 8
8 12 12 12 12 12 4 6 6 8 8 8

Welded
10 14 14 14 14 16 5 8 8 8 8 10
12 16 16 16 16 — 6 8 10 10 10 10
8 10 10 12 12 12

Rod Couplings Rod & Concrete Inserts


FIG. 260 ISS: DIMENSIONS (IN) • LOADS (LBS) • WEIGHTS (LBS)
260 ISS *Max Rod Size **Rod Take Adjust.
Weight C G X
Size Number Load A Out E F
2 0.73 3
/8 41/2 25/8 /8
7 1
/4 23/8
3 550 1.32 1
/2 61/2 41/16 1 /16
7
35/8
4 1.83 713/16 41/2 11/2 3
/8 41/2
5
/8
5 2.44 815/16 51/2 13/4 511/16
750
6 3.81 101/4 53/4 11/2 611/16
3
/4 1
/2
8 5.60 1211/16 73/16 13/4 813/16
1100
10 9.73 151/4 87/16 17/8 103/4
Swivel

7
/8 5
/8
12 13.80 1715/16 101/8 29/16 127/16
14 1700 15.60 199/16 1011/16 21/2 /4
3
147/16
1
Hardware &

16 26.81 22 12 23/8 1 165/16


* Max load exceeds dead weight load requirement of pipe at max span, except 14 and 16 where max load is based on
2" through 16" industry standard spacing of 14. Further information on typical pipe spans and piping weight per length can be found
Patent #7,281,689 on pages 268 and 270, respectively.
** Based on maximum insulation thickness, variations due to pipe size and insulation thickness may occur.

www.anvilintl.com 27
PH-3.16
CLEVIS HANGERS & SHIELDS

Fig. 260 ISS Clevis Hanger with Insulation Saddle System (cont.)

Application: Anvil's insulation saddle system clevises are fully tested


and rated for a temperature range from 40˚F to 200˚F. Ideal for the sus-
pension of stationary insulated chilled or hot water pipelines.
Chilled Water Testing: Extensive field-testing and inspection has
been performed to confirm that the integrity of the insulation vapor
barrier for chilled water systems are sustained with the 260 ISS.
To Assure Proper Vapor Barrier: Each insulation joint should be
properly coated, caulked and taped. Applying standard insulation
practice that is used on flanges and valves.
Features: The Anvil 260 (ISS) Insulation Saddle System reduces your
overall installation time and greatly simplifies the way you insulate
copper and steel pipe systems. Contractors can support insulated
pipe with less parts and labor.
The revolutionary design of the 260 ISS spreads the load evenly over
the lower strap of the clevis. The innovative V-Block design cradles
the pipe at the design elevation throughout the erection process. The wide base V-Block design accommodates multiple pipe
sizes, reducing the on-site inventory and the flexibility of pipe and insulation combinations with each size number.
ASTM & UL Fire Ratings: The 260 ISS has been independently
tested by ASTM and UL for:
• Flame Spread Index (FSI)
• Smoke Development (SD) and drip ratings
Approvals from both agencies with the highest ratings for the type
of product.
Low Thermal Conductivity: V-Block low thermal conductivity of
.77 BTU-In./Sq.FT-Hr˚F
Insulation R-Values: The Figure 260 ISS polymer V-Block
component has an R-value ranging from 5.0 to 8.7, depending on
the hanger size. Meets or exceeds most commercial insulation
R-values.

28
www.anvilintl.com
PH-11.11
CLEVIS HANGERS & SHIELDS

Fig. 260 ISS

Contents
Ring Clevis Hangers General Pictorial Table of
Clevis Hanger with Insulation Saddle System (cont.)

TOC
Easy Installation
Make sure the double hex nuts installed with the upper hanger load nut above the clevis are tightened securely. Position pipe on saddle.

Notes
STEP 1 STEP 2

& Straps Clamps Clamps Hangers & Shields


Notch

Wall Ceiling Plates Beam AWWA CPVC U-Bolts Riser Pipe


Cope or notch insulation to fit around saddle. The notch Slide the notched insulation section over saddle.
should be deep enough to extend 1/8" to 1/4" beyond the saddle.

STEP 3 STEP 4

Accessories Attachments & Turnbuckles Eye Rods & Attachments Attachments Brackets & Flanges Clamps
Square Cut

Welded
Square cut adjoining insulation and butt the insulation ends to Caulk joints and finish taping.

Rod Couplings Rod & Concrete Inserts


each other. To assure proper vapor barrier: Each insulation joint should
be properly coated, caulked and taped. Applying standard
insulation practice that is used on flanges and valves.
Finish via standard taping method.

For chilled systems a mastic for thermal insulations or similar sealant is


typically used:

Systems (50˚F or greater) apply sealant to:


• The coped and flat edges of the mating insulation sections.
Swivel

• The V-Block saddle at the insulation interface.


Systems (Below 50˚F) apply sealant as per 50 Degrees with additional
Hardware &

sealant to: Mastic applied to V-Block Additional sealant applied to


• The V-Block saddle joint between the two saddle halves. saddle at insulation interface. V-Block saddle joint between
(50˚F or greater) the two saddle halves.
(Chilled water below 50˚F)

www.anvilintl.com 29
PH-11.11
CLEVIS HANGERS & SHIELDS

Fig. 300 Adjustable Clevis for Insulated Lines

Size Range: 3⁄4" through 12"


Material: Carbon steel
Finish: Plain, 8" & Smaller: Zinc Plated (Hot-Dip Galvanized optional), 10" & Larger: Hot-Dip
Galvanized with Zinc Plated Bolts & Nuts or Epoxy Coated
Service: R  ecommended for suspension of insulated stationary pipe lines.
Maximum Temperature: Plain 650° F, Galvanized and Epoxy 450° F
Approvals: Complies with Federal Specification A-A-1192A (Type 1), WW-H-171-E (Type 1),
ANSI/MSS SP-69 and MSS SP-58 (Type 1).
Installation: Hanger load nut above clevis must be tightened securely to assure proper
hanger performance.
Adjustment: Vertical adjustment is provided, varying with the size of the clevis. Tighten
upper nut after adjustment.
Features:
• Designed for 2" of insulation on 3⁄4" through 1 1⁄2" pipe and 4" of insulation on 2" and larger pipe.
• When properly installed, clevis bolt is outside the insulation.
Ordering: Specify pipe size, figure number, name and finish.

G F

E H B
C

CL

FIG. 300: DIMENSIONS (IN) • LOADS (LBS) • WEIGHT (LBS)


Pipe Max Rod Size Adjustment I
Weight B C E G H Width
Size Load A F Lower
3
⁄4 0.51 35⁄8 41⁄4 27⁄8 1
⁄2
1 0.58 4 411⁄16 31⁄4 5
⁄8
2
11⁄4 730 0.64 3
⁄8 47⁄16 51⁄4 35⁄8 7
⁄8 1
⁄4
11⁄2 0.72 43⁄4 53⁄4 41⁄16 11⁄16 1
2 0.85 77⁄16 811⁄16 61⁄2 15⁄8
21⁄2 1.90 87⁄16 915⁄16 71⁄2 2
1,350 1
⁄2
3 2.00 85⁄8 105⁄16 79⁄16 13⁄4 3
⁄8
4 2.50 93⁄8 115⁄8 83⁄16 115⁄16
1,430 5
⁄8 11/4
5 3.00 97⁄8 125⁄8 83⁄4 13⁄4 4
1
⁄2
6 1,940 3.40 105⁄8 14 93⁄8 17⁄8 11/2
3
⁄4
8 2,000 6.70 123⁄8 163⁄4 11 2 5
⁄8
13/4
10 3,600 11.0 133⁄4 193⁄16 121⁄4 21⁄8
⁄8
7 3
⁄4
12 3,800 13.8 151⁄8 219⁄16 135⁄8 27⁄16 2

30
www.anvilintl.com
PH-1.15
CLEVIS HANGERS & SHIELDS

Fig. 590

Contents
Ring Clevis Hangers General Pictorial Table of
Adjustable Clevis for Ductile or Cast Iron Pipe

TOC
Size Range: 3" through 24" ductile or cast iron pipe
Material: Carbon steel

Notes
Finish: Plain or Hot-Dip Galvanized with Zinc Plated Bolts & Nuts
Service: R  ecommended for the suspension of stationary ductile iron or cast iron pipe.
Maximum Temperature: Plain 650° F, Galvanized 450° F

& Shields
Approvals: C  omplies with Federal Specification A-A-1192A (Type 1)
WW-H-171-E (Type 1), ANSI/MSS SP-69 and MSS SP-58 (Type 1).
Installation: Hanger rod nut above clevis must be tightened securely to assure

& Straps Clamps Clamps Hangers


proper hanger performance.
Adjustment: Vertical adjustment without removing pipe may be made

Pipe
from 1 15⁄16" through 3 3⁄16", varying with the size of the clevis. Tighten upper
nut after adjustment.

Wall Ceiling Plates Beam AWWA CPVC U-Bolts Riser


Ordering: Specify pipe size, figure number, name and finish.
Note: F igure 590 sizes 12" and below typically feature a Figure 260 Top Component.
A

Accessories Attachments & Turnbuckles Eye Rods & Attachments Attachments Brackets & Flanges Clamps
B C
E

CL

Welded
G

Rod Couplings Rod & Concrete Inserts


FIG. 590: DIMENSIONS (IN) • LOADS (LBS) • WEIGHT (LBS)
D.I./C.I. Max D.I./C.I. Rod Size G Width
Weight B C E F
Pipe Size Load Pipe O.D. A Lower
3 1,350 1.10 3.96 1
⁄2 51⁄16 71⁄16 43⁄16 113⁄16
11/4
4 1,430 1.64 4.80 5
⁄8 53⁄4 83⁄16 43⁄4
115⁄16
6 1,940 4.26 6.90 71⁄8 109⁄16 515⁄16 11/2
3
⁄4
8 2,000 6.70 9.05 85⁄8 133⁄16 71⁄2 21⁄4
13/4
10 3,600 9.73 11.10 101⁄8 1511⁄16 83⁄4 25⁄16
7
⁄8
12 3,800 13.64 13.20 121⁄16 1811⁄16 1011⁄16 27⁄8
Swivel

2
14 4,200 16.04 15.30 13 ⁄4
1
20 ⁄8
7
11 ⁄16
5
29⁄16
16 4,600 24.52 17.40 1 141⁄4 2215⁄16 129⁄16 27⁄16
21/2
Hardware &

18 4,800 27.45 19.50 167⁄8 265⁄8 153⁄16


20 4,800 46.24 21.60 181⁄4 291⁄16 163⁄8 313⁄16
11⁄4 3
24 4,800 57.10 25.80 205⁄16 331⁄4 183⁄8

www.anvilintl.com 31
PH-3.16
CLEVIS HANGERS & SHIELDS

Fig. 590SS Adjustable Clevis for Ductile or Cast Iron Pipe

Size Range: 4" through 12" ductile or cast iron pipe


Material: 304 stainless steel
Service: R  ecommended for the suspension of stationary ductile iron or cast iron pipe.
Approvals: Complies with Federal Specification A-A-1192A (Type 1)
WW-H-171-E (Type 1), ANSI/MSS SP-69 and MSS SP-58 (Type 1).
Installation: Hanger rod nut above clevis must be tightened securely to assure
proper hanger performance.
Adjustment: Vertical adjustment without removing pipe may be made
from 1 15⁄16" through 3 3⁄16", varying with the size of the clevis. Tighten upper
nut after adjustment.
Ordering: Specify pipe size, figure number and name.
Note: F igure 590 typically feature a Figure 260SS Top Component.

B C
E

CL

FIG. 590SS: DIMENSIONS (IN) • LOADS (LBS) • WEIGHT (LBS)


D.I./C.I. Max Load D.I./C.I. Rod Size G Width
Weight B C E F
Pipe Size 450˚ F 650˚ F Pipe O.D. A Lower
4 1,215 1,095 1.64 4.80 5
⁄8 53⁄4 83⁄16 43⁄4 11/4
115⁄16
6 1,650 1,485 4.26 6.90 71⁄8 109⁄16 515⁄16 11/2
3
⁄4
8 1,700 1,530 6.70 9.05 85⁄8 133⁄16 71⁄2 21⁄4
13/4
10 1,750 1,575 9.73 11.10 101⁄8 1511⁄16 83⁄4 25⁄16
7
⁄8
12 1,850 1,665 13.64 13.20 121⁄16 1811⁄16 1011⁄16 27⁄8 2

32
www.anvilintl.com
PH-1.15