FOUNDATION
test
design.
a) Minimum 1.0m diameter bored cast-in-situ vertical piles in soil/rock have been
b) Open foundation have been contemplated primarily for the Access/Entry structure in firm
soil/ rocky
c) For pile carrying capacity, the SLS check only will be considered.
d) The lateral load capacity of pile shall be evaluated either by using empirical formulae
given in IS:
2911 (Part-1/ section-2) or by soil structure interaction analysis using Winkler’s spring
model.
f) The calculation should be carried out for rock socketing as per latest IRC:78 (including all
amendments). The latest amendment specifically covers the details on socketted piles in rock.
g) Initial load tests (not on working pile) shall be conducted first for determination of safe
vertical and
lateral loads. The safe load shall be taken as least of (a) load arrived at from the initial load
test and
(b) the calculated safe load based on static formula. Initial test shall be conducted for a load
of 2.5
h) The working load on pile for vertical and horizontal loads shall be checked by conducting
routine
i) In case of multiple pile system, spacing between the piles shall not be less than 3 times the
diameter
of pile in soil and 2.5 times the diameter when founded on rock.
j) The top of pile cap shall be kept about min 500mm (approx. as per site condition) below
the existing
ground level and weight of the earth cover will be applied on top of pile cap when
unfavorable. The
earth cover on pile cap for any favorable effect (stability, soil horizontal capacity.) will be
neglected.
k) For the calculation of pile capacity, value of bearing capacity factor Nq should be carried
out as per
latest IS:2911(Part 1/Sec 1)-2014 (including all amendments) and the value of bearing
capacity factor
N ( for General Shear Failure) should be taken directly from Table -1 of IS6403:1981.
l) The following limiting values shall not be exceeded for computation of safe load: