FIRE FIGHTING SYSTEM DESIGN,FABRICATION & OPERATION


 Fire Fighting System connection with the existing firefighting network. (Refer attached
Layout for Fire Fighting System-Annexure-I). Water Tapping to be done from existing 8”
Fire Hydrant (U/G Line) tapping (E=2343.605M, N=939.874M) shall be available from
weigh bridge area of rolling plant.).Further distribution shall be in bidder’s scope of supply.

 Fire Detection, Protection alarm & Fire Extinguishers as required.

 Each Substation/ switchgear rooms shall be provided with CO 2 fire extinguisher(min 2)(Refer
enclosed Page No.60 of 780-Annexure-II)

Note: Design, fabrication & operation of the plant shall be based on Cl. No.4.01.12 (Annexure-III enclosed)
a) Fire protection manual of fire sectional committee, Insurance association of India
b) NFPA code of practice.
c) Codes and standrad’s to be followed as per Cl. No.4.01.12 (enclosed)

2. INTRODUCTION
Fire Fighting System is mainly designed for the fire department use to provide quick and convenient
means for obtaining effective fire protection. It fights fires of serious proportions in all classes of risks
and continues to be in full operation even if parts of affected buildings or structures have collapsed. It
also keeps cool all adjoining properties, thereby minimizing the exposure hazard.

3. AREAS TO BE COVERED
a) Unloading Wagon Shed.(68mx18m,1 No. Floor)
b) Along Pipe Conveyor Tunnel & Gallery PC-100(Approx. length=350m)
c) Pent-House. (6m x 6m, 1 No. Floor)
d) Transfer Tower TP-01.(12.250mx10.200m,4 Nos. of Floor)
e) Along Pipe Conveyor Gallery PC-200(Approx. length=665m)
f) Transfer Tower TP-02. (11mx10.200m,3 Nos. of Floor)
g) Along Pipe Conveyor Gallery PC-300(Approx. length=485m)
h) Transfer Tower TP-03 with Lift. (11mx10.200m,3 Nos. of Floor)
i) MCC Room(22mx 12.2m,Floors-G+2Nos)
j) Blower & PLC Room. (10mx10m, Floors-G+1No.)
k) Watch Tower with Operating Cabin (5mx5m, 1 No. Floor)

4. SYSTEM DESCRIPTION
A fire water piping network is planned with provision of internal, yard hydrants at regular intervals,
fire detection and protection system. The pipelines shall be laid inside the plant to cover all areas.
Internal hydrant shall be provided inside the premises, floors of the buildings, junction houses, office
building, conveyor galleries, storages, entry and exit of the electrical premises etc.

Hydrant piping shall be laid underground with proper rapping & coating. However, piping for internal
hydrants shall be laid as per requirement. Yard hydrant will be provided with a hose box nearby to
contain two nos. of 15 m long hose (yard hydrant)/two nos. of 15m long hose (internal hydrants)
along with 1 no branch pipe with nozzle.
5. SPECIFICATION
Hydrant System
FIRE FIGHTING SYSTEM
Rev.: 0

a) Category of Hazard : Ordinary (as per TAC)


b) Yard Hydrants : @ 45 m interval.
c) Internal Hydrants : @ 30 m interval.

6. SPECIFICATION OF FIRE HYDRANTS AND ACCESSORIES


Sl No. IS No Description
A Internal Hydrants
1. IS:5290 Type-A Fire hydrant (landing valves) single outlet oblique type of 75mm flanged inlet, 63mm
(1993) outlet with hand wheel, Instantaneous stainless steel male & female coupling at outlet
and blank cap.
(Stainless steel)

3. Hose cabinet shall be fabricated out of fiber reinforced plastic (thickness 2.5 mm) with glass front (for
indoor installation, One number Hose box for each landing valve to keep 15m long hoses (2 Nos.) branch
pipe, nozzle and spanner) consisting of the following:
a) IS:636 Type-2 Reinforced rubberized fabric lined flexible canvas hose of 15 m length having 63mm
(1988) & dia, each fitted (as per IS:1648:1961) with instantaneous male Coupling at one end
IS:903 (1984 R.A.- and female Coupling at the other end.
1990)
B Yard Hydrants
1. IS:5290 Fire hydrant (landing valves) single outlet oblique type of 75mm flanged inlet,
Type-A 63mm outlet with hand wheel, Instantaneous stainless steel male & female coupling
(1993) at outlet and blank cap.
( Stainless Steel )
3. Hose cabinet shall be fabricated out of fiber reinforced plastic (thickness 2.5 mm) with glass front (for
indoor installation, One number Hose box for each landing valve to keep 15m long hoses (2 Nos.) branch
pipe, nozzle and spanner) consisting of the following:

a) IS:636 Type-2 Reinforced rubberised fabric lined flexible canvas hose of 15m length having 63mm
(1988) & IS:903 dia, each fitted (as per IS:1648 -1961) with instantaneous male Coupling at one end
(1984 R.A.- and female Coupling at the other end including intermediate coupling for joining
1990) 1x15m long hose

7. FOLLOWING SHALL BE CONSIDERED IN SCOPE OF SUPPLY:


a) Ring Main
b) Fire Hydrant Valve.
c) Hose Reel with Hose Reeling Drum.
d) M.S Double door Hose Box.
e) Water Monitor.
f) Fire Fighting Piping along with Fittings.
g) Landing Valves and Manual Isolation Valves where ever required.
h) Additional accessories in order to complete the System.
i) Civil work if any.

8. Exclusions:
a) Firefighting water up to the battery limits.

9. Reference Drawing/Document
a) Layout of Fire Fighting System.(Annexure-I)