Model RV-1 Pressure Relief Valve


2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar)
Pilot-Operated, Globe and Angle Body Styles
General
Description
The TYCO Model RV-1 Pressure Relief
Valves, 2 through 8 inch (DN50 through
DN200), are factory assembled and
fully trimmed valve arrangements for
relief of excess water pressure. These
valves are typically used to automatically
relieve excess pressure in a fire protec-
tion system that utilizes a fire pump.
Pilot-controlled, the Model RV-1 Valve
maintains a relatively constant system
pressure at the pump discharge as flow
demands change. Nominal Valve Size
Body
The Model RV-1 Pressure Relief Valve End Connection 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch
Style
may be field-set to a nominal relief “set (DN50) (DN80) (DN100) (DN150) (DN200)
pressure” of 30 to 250 psi (2,1 to 17,2 bar). Globe Flange x Flange • • • • •
Features are as follows: Thread x Thread • N/A N/A N/A N/A
Angle
• Globe or angle pattern Flange x Flange N/A • • • •
• Installation in any orientation
• One-piece, one-moving-part diaphragm
• Available N/A = Not Available

• Ceramic enamel-coated interior


• Standard nylon-coated exterior Technical End Connections
Threaded end connections are avail-
• Accurate pressure control Data able as NPT threaded or threaded per
ISO 7/1. Flanged end connections are
• In-line service
Approvals available as drilled per Table A.
• No need to bleed trapped air from the UL Listed; FM Approved
diaphragm chamber Construction (Figure 2)
• One pilot valve sub-assembly that Maximum Inlet Pressure • Body:
provides for any outlet “set pressure”; 250 psi (17,2 bar) Rilsan1 blue-coated ductile iron per
that is; 30 to 250 psi (2,1 to 17,2 bar) ASTM A536-77, Grade 65-4512
Temperature Range • Diaphragm Cover:
NOTICE 50°F to 175°F (10°C to 80°C) Rilsan blue-coated ductile iron per
The TYCO Model RV-1 Pressure Relief ASTM A53677, Grade 65-45-12
Field Relief “Set Pressure” Range
Valves described herein must be in- 30 to 250 psi (2,1 to 17,2 bar) • Diaphragm:
stalled and maintained in compliance Nylon fabric-reinforced, natural rub-
with this document and with the ap- NFPA 20 Recommended ber per ASTM D2000
plicable standards of the National Fire Maximum Flow
Protection Association, in addition to • Diaphragm Cover Fasteners:
• 2 Inch (DN50): 250 GPM (946 LPM) Galvanized carbon steel
the standards of any authorities having
jurisdiction. Failure to do so may impair • 3 Inch (DN80): 500 GPM (1893 LPM) • Pilot Valve:
the performance of these devices. • 4 Inch (DN100): 1000 GPM (3785 LPM) Cast bronze and stainless steel with
Owners are responsible for maintaining nylon fabric reinforced, natural rubber
• 6 Inch (DN150): 2500 GPM (9462 LPM) per ASTM D2000 diaphragm
their fire protection system and devices
in proper operating condition. The install- • 8 Inch (DN200): 5000 GPM (18925 LPM)
ing contractor or sprinkler manufacturer Refer also to Figure 4 for inlet pres- 1 The Rilsan coating is a polyamide (Nylon 11)
should be contacted with any questions. sure versus flow characteristics. coating. Rilsan is a registered trademark of
ATOFINA Chemicals, Inc.

Page 1 of 8 APRIL 2011 TFP1585


TFP1585
Page 2 of 8

• Pressure Gauges:
2-1/2 inch (65 mm) diameter, stain-
less steel case, 0 to 350 psi (25 bar).
• Strainer, Tube, Fittings, and Needle PRESSURE
Valve: RELIEF
Stainless steel MODEL RV-1
PRESSURE
WATER RELIEF VALVE
Operation TANK

The TYCO Model RV-1 Pressure Relief


Valve is normally installed on-line in a tee
configuration (Figure 1), after the fire pump
and before the system’s check valve.
When the Model RV-1 Pressure Relief
Valve opens to permit excess flow and
to relieve pressure to the atmosphere
within the water tank, the fire protection ISOLATION
VALVE ISOLATION
system is accurately maintained at the VALVE
desired preset pressure. In case the
demand of the fire system completely
stops, the Model RV-1 Pressure Relief FIRE
Valve remains fully open, relieving 100% PUMP
of the pump’s capacity.
The check valve then closes, isolating CHECK
the system from the pump. The pump VALVE
shuts off safely, avoiding the risk of
system surges. As the pump shuts, TO FIRE
the Model RV-1 Pressure Relief Valve PROTECTION
slowly closes. SYSYEM
The operation sequence (Figure 3) is
as follows: FIGURE 1
• When inlet pressure is below the re- TYPICAL APPLICATION
lief “set pressure”, the Model RV-1 (Showing pressure relief return to unpressurized tank)
Pressure Relief Valve Diaphragm Seat
is closed and the Pilot Valve Seat is
closed. With the Pilot Valve Seat closed,
pressure is trapped in the Diaphragm
Design • The Model RV-1 Pressure Relief Valve-
must be in an area that is easily ac-
Chamber to seat the Diaphragm, and
the Model RV-1 Pressure Relief Valve
Considerations cessible for maintenance purposes,
not subject to freezing temperatures,
remains closed. The following items must be consid­ered and not subject to physical damage.
and applied accordingly for an installa- • The Model RV-1 Pressure Relief Valve
• When inlet pressure is above the relief tion that will be using the TYCO Model
“set pressure”, the Pilot Valve Seat is designed for fresh water service.
RV-1 Pressure Relief Valve: When corrosive atmos­pheres and/or
opens to relieve pressure from the
Diaphragm Chamber faster than pres- • The Model RV-1 Pressure Relief Valve contaminated water supplies are pres-
sure can be re-established through the may be installed vertically or horizon- ent, responsibility lies with owners to
Needle Valve. Loss of pressure in the tally and in any orientation without af- verify com­patibility with the pressure
Diaphragm Chamber allows the Model fecting its operating effi­ciency. When relief valve, pilot valve, and trim.
RV-1 Pressure Relief Valve to open. planning the position­ing of the Model
RV-1 Valve, it is recommended that
• Subsequent to relieving excess pres-
consideration be given to the viewing
sure, when the inlet pressure starts to
of the pressure gauge. Con­sideration
fall below the relief “set pressure”, the
should also be given to positioning
Pilot Valve Seat closes to allow the
the Model RV-1 Valve so that the dia­
Diaphragm Chamber to re-pressurize
phragm cover is facing up. With the
automatically and close the Model RV-1
cover facing up, internal access is
Pressure Relief Valve. The restriction
more easily achieved.
orifice provided by the Needle Valve
controls the speed at which the Model • The installation of an isolation valve in
RV-1 Valve closes to provide a slow the inlet connection to the Model RV-1
re-closure. Pressure Relief Valve is recommended
to facilitate perform­ing preventative
maintenance on the Model RV-1 Valve.
Isolating valves installed per Figure
1 will meet this recommenda­tion in
addition to providing isolation means
for the fire pump, water tank, and fire
protection system.
TFP1585
Page 3 of 8

VALVE PARTS 8
NO. DESCRIPTION QTY. KIT
1 Valve Body . . . . . . . . . . . 1 NR
7
2 Diaphragm . . . . . . . . . . . 1 (a)
3 Diaphragm Cover . . . . . . 1 NR
4 Flat Washer,
2 Inch Valve, M12 . . . . . . 4 CH 4, 5, 6 DIAPHRAGM
3 & 4 Inch Valves, M16 . . 4 CH
6 & 8 Inch Valves, M16 . . 8 CH CHAMBER
5 Hex Bolt,
2 Inch Valve, M12 x 35 . . 4 CH
3 & 4 Inch Valves, 3
1
M16 x 55 . . . . . . . . . . . . . 4 CH
6 Inch Valve, M16 x 45 . . 8 CH
8 Inch Valve, M16 x 55 . . 8 CH
6 Hex Nut, M16, 2
4 Inch Valve Only . . . . . . . 4 CH 10
7 Pilot Valve . . . . . . . . . . . . 1 (b)
8 Water Pressure Gauge . . 1 (c)
9 Strainer . . . . . . . . . . . . . . 1 (d) INLET
10 Tubing and Fittings . . . . . 1 (e) OUTLET
CAVITY
CAVITY
REPLACEMENT PART KITS
KIT DESCRIPTION P/N
(a) Diaphragm, 9
Fits Either Body Style,
Includes Item 2 only: STRAINER
2 Inch Valves . . . . . . . . . . . . . 92-570-2-011 (SEE DETAIL)
3 Inch Valves . . . . . . . . . . . . . 92-570-2-012
4 Inch Valves . . . . . . . . . . . . . 92-570-2-013 GLOBE BODY STYLE
6 Inch Valves . . . . . . . . . . . . . 92-570-2-014
8 Inch Valves . . . . . . . . . . . . . 92-570-2-015
(b) Pilot Valve . . . . . . . . . . . . . . . 92-572-2-200
(c) Water Pressure Gauge . . . . . 92-570-2-211
INTERIOR 9 1 10
(d) Strainer: OF INLET
2, 3, & 4 Inch Valves . . . . . . . 92-570-2-202 CAVITY
6 & 8 Inch Valves . . . . . . . . . . 92-570-2-209 8
(e) Tubing and Fitting Kit,
Excludes Items 7, 8, 9, and 10
Globe Style Valve: STRAINER
2 Inch Valve . . . . . . . . . . . . . . 92-572-3-001 7 DETAIL
3 Inch Valve . . . . . . . . . . . . . . 92-572-3-002
4 Inch Valve . . . . . . . . . . . . . . 92-572-3-003
6 Inch Valve . . . . . . . . . . . . . . 92-572-3-004
8 Inch Valve . . . . . . . . . . . . . . 92-572-3-005 DIAPHRAGM
Angle Style Valve: CHAMBER
2 Inch Valve . . . . . . . . . . . . . . 92-573-3-001 4, 5, 6
3 Inch Valve . . . . . . . . . . . . . . 92-573-3-002
4 Inch Valve . . . . . . . . . . . . . . 92-573-3-003
6 Inch Valve . . . . . . . . . . . . . . 92-573-3-004
8 Inch Valve . . . . . . . . . . . . . . 92-573-3-005 1
3
NOTES:
1. NR - Not Replaceable
10
2. CH - Common Hardware 2

OUTLET
OUTLET 9
CAVITY

ORIENT GLOBE
DIAPHRAGM TAB INLET
PERPENDICULAR CAVITY
TO OUTLET

OUTLET
STRAINER
(SEE DETAIL)
ANGLE ANGLE BODY STYLE

FIGURE 2
MODEL RV-1 PRESSURE RELIEF VALVE
— ASSEMBLY —
TFP1585
Page 4 of 8

INTERIOR VALVE
PILOT VALVE OF INLET BODY
PRESSURE PILOT DIAPHRAGM CAVITY
GAUGE PILOT
VALVE CHAMBER PRRESSURE
VALVE
SEAT RELIEF LINE
ADJUSTING REGULATING
DIAPHRAGM
SCREW SPRING STRAINER
CHAMBER
LOCKNUT SUPPLY LINE
NEEDLE
VALVE STRAINER
DETAIL

DIAPHRAGM
CHAMBER
TAMPER
CAP PILOT VALVE PILOT
RV-1
DIAPHRAGM VALVE BY-PASS
DIAPHRAGM
SEAL LINE
SEAT
DIAPHRAGM
CHAMBER RV-1
SUPPLY LINE DIAPHRAGM

INLET OUTLET
CAVITY CAVITY

FROM FIRE PUMP PRESSURE


OVERPRESSURE RELIEF

PILOT
LINE COMPONENTS SHOWN IN
STRAINER ALTERED POSITIONS AND
(SEE DETAIL) ORIENTATIONS TO CLARIFY
FUNCTION
FIGURE 3
MODEL RV-1 PRESSURE RELIEF VALVE
— OPERATION —

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3.785 LPM)
0 4000 8000 12000 16000 20000
250
16
225
IN POUNDS PER SQUARE INCH (PSI)

NOMINAL INLET PRESSURE IN BAR

200 14
NOMINAL INLET PRESSURE

)
2 INCH (DN50)

100

0)
0)
(DN80

(1 PSI = 0.06895 BAR)

175 12
20
15
(DN

DN
(DN

150 10
H(
3 INCH

CH

H
NC

NC

125
4 IN

6I

8I

8
100
6
75
4
50

25 2

0 0
0 1000 2000 3000 4000 5000
FLOW RATE IN GALLONS PER MINUTE (GPM)

FIGURE 4
MODEL RV-1 PRESSURE RELIEF VALVE
— INLET PRESSURE VERSUS FLOW CHARACTERISTICS —
TFP1585
Page 5 of 8

Installation Pilot Valve Pressure Gauge. Make all


pilot adjustments slowly and in small
Valve by following the instructions in
the section Placing the Valve in Ser-
The TYCO Model RV-1 Pressure Relief increments. vice. If the desired pressure cannot be
Valve must be installed with the flow achieved, the Diaphragm and/or Pilot
5. Tighten the Locknut and shut off
arrow located on the Diaphragm Cover Valve should be replaced.
the pump.
pointing in the intended direction of flow. • During pump start-ups, check that
Installation dimensions are provided in Note: After any pressure adjustment,
the Model RV-1 Pressure Relief Valve
Figures 5 and 6 for both body styles. the following items are to be recorded
relieves pressure as nec­essary. If
on a tag attached to the valve:
Before installing the Model RV-1 Pressure necessary, re-adjust the Model RV-1
Relief Valve, flush pipe lines to remove • Valve installation location Pressure Relief Valve by following the
all chips, scale, and foreign matter. • Inlet static pressure instructions in the section Placing the
Exercise care to assure that the trim is Valve in Service. If the desired pressure
not damaged during installation. • Relief set pressure cannot be achieved, the Diaphragm
The tag is not to be removed until after and/or Pilot Valve should be replaced.
NOTICE the system has been accepted by the • Check that the Model RV-1 Pressure
Do not lift the valve by its trim. Otherwise, Authority Having Jurisdiction. It is rec- Relief Valve, Pilot Valve, Tube, Fittings,
the trim may be damaged and impair ommended that the tag not be removed Needle Valve, and Pressure Gauge are
system operation. even after acceptance by the Authority in good condition and do not exhibit
Having Jurisdiction unless another means signs of damage or leakage.
Make the inlet and outlet connections of record-keeping is maintained.
based on the direction of flow arrow pro- • Make sure that the Pilot Valve Locknut
is securely tightened.
vided on the Diaphragm Cover. The valve
cannot operate if connected backwards. Care and Diaphragm Replacement.
Do not alter the trim. Altering the trim will
render the valve ineffective and impair
Maintenance Prior to re­placing the Diaphragm, the
Model RV-1 Pressure Relief Valve must
system operation. Inspection, testing, and maintenance be taken out of service and completely
must be performed in accordance with drained.
Placing the the requirements of the NFPA. Any
impairment must be immediately cor- With reference to Figure 2, the Diaphragm
Tab is oriented perpendicular to the outlet
Valve in Service rected. Refer to Table B for information
on troubleshooting valve problems. flow. When reinstalling the Diaphragm
Cover, the Diaphragm Cover Fasteners
Perform Steps 1 through 5 when placing Responsibility lies with owners for the must be uniformly and securely tightened
the TYCO Model RV-1 Pres­sure Relief in­spection, testing, and maintenance of using a cross-draw sequence. After
Valve in service. their fire protection system and devices tightening, double check to make cer­tain
in compliance with this document, as that all Diaphragm Cover fasteners are
NOTICE well as with the applicable standards of securely tightened.
Pressure relief adjustment is only to be any authorities having jurisdiction. The
performed by experienced personnel installing contractor or product manu- Pilot Valve Replacement.
who understand the impact of adjust­ing facturer should be contacted relative to Prior to removing the Pilot Valve, the
the pressure relief setting and who take any questions. Model RV-1 Pressure Relief Valve must
full responsibility of the relief set­ting. Automatic sprinkler systems are recom- be taken out of service and completely
mended to be inspected, tested, and drained.
Prior to pressurizing the Model RV-1
Pressure Relief Valve, make sure the maintained by a qualified Inspection When installing the replacement Pilot
necessary pressure gauges to measure Service in accordance with local require- Valve, the trim components must be
pressure in the system are installed as ments and/or national codes. replaced exactly as they were. After
required by the system designer. Note: Before closing a fire protection reinstalling the Pilot Valve and before
system main control valve for mainte- returning the Model RV-1 Pressure Relief
Note: Venting any trapped air from the Valve into service, completely unscrew
Diaphragm Chamber is not necessary. nance work on the fire protection system
that it controls, obtain permission to the Adjusting Screw. Then, to place
1. Loosen the Pilot Valve Locknut, then shut down the affected fire protection the Model RV-1 Pressure Relief Valve
completely loosen the Adjust­ing systems from the proper authorities and in service, follow the instructions in the
Screw. Tighten the Adjusting Screw notify all personnel who may be affected section Placing the Valve in Service.
three turns beyond the point at which by this decision.
spring resistance is encoun­tered. NOTICE
The TYCO Model RV-1 Pressure Relief
2. Loosen the Needle Valve Locknut, Valve requires no lubrication, packing The Pilot Valve is not field repairable.
completely tighten the Nee­dle Valve or preventative maintenance. However, Attempting to repair the Pilot Valve may
Adjusting Screw, loosen the Needle re­placement of the diaphragm every five render the valve ineffective and impair
Valve Adjusting Screw one turn, and years is recommended. the system operation.
tighten the Needle Valve Locknut. Completely unscrewing the Adjusting
3. Start the pump. One hundred per- Inspections. Screw of the replacement Pilot Valve
cent of pump capacity will now flow • Inspect the Model RV-1 Pressure Re- will help to avoid an accidental over-
through the Model RV-1 Pressure lief Valve on a weekly basis. pressurization of the system piping
Relief Valve into the tank. • Check the valve under static condi­tions prior to achieving the desired relief “set
to assure that the Model RV-1 Pres- pressure”.
4. Slowly tighten the Pilot Valve Ad-
justing Screw until the desired re- sure Relief Valve is not unnecessarily
lief “set pressure” is achieved on the relieving pressure. If necessary, re-
adjust the Model RV-1 Pressure Relief
TFP1585
Page 6 of 8

Flange x Flange End Connections


E

Nominal Nominal Installation Dimensions in Inches and (mm) Weight


Valve
Sizes lbs.
A B C D E (kg)
2" 7.48 3.15 8.27 6.50 4.72 23.2 D
(DN50) (190) (80) (210) (165) (120) (10,5)
3" 11.22 3.94 8.66 7.48 5.91 46.7
(DN80) (285) (100) (220) (190) (150) (21,2)
4" 12.00 4.53 9.45 7.68 6.50 64.2
(DN100) (305) (115) (240) (195) (165) (29,1) C
6" 16.14 5.71 10.43 9.45 5.12 118.0
(DN150) (410) (145) (265) (240) (130) (53,5)
8" 18.50 6.10 11.42 11.02 6.69 166.0 B
(DN200) (470) (155) (290) (280) (170) (75,3)
A
FIGURE 5
MODEL RV-1 PRESSURE RELIEF VALVE
— GLOBE STYLE INSTALLATION DIMENSIONS —

Thread x Thread End Connections

Nominal Nominal Installation Dimensions in Inches and (mm) Weight


Valve F
Sizes lbs.
A B C D E F (kg)
2" 3.35 3.15 8.46 5.51 6.10 5.91 15.9
(DN50) (85) (80) (215) (140) (155) (150) (7,2)
E
Flange x Flange End Connections

Nominal Nominal Installation Dimensions in Inches and (mm) Weight


Valve
Sizes lbs. C
A B C D E F (kg)
3" 6.10 4.33 9.45 6.10 7.48 4.72 35.1
(DN80) (155) (110) (240) (155) (190) (120) (15,9)
10.63 B
4" 6.50 4.53 6.10 7.87 5.51 67.3
(DN100) (165) (115) (270) (155) (200) (140) (30,5)
6" 7.87 5.91 11.61 4.53 9.45 6.10 118.0
(DN150) (200) (150) (295) (115) (240) (155) (53,5)
D A
8" 8.66 6.69 12.20 5.91 11.22 8.46 168.0
(DN200) (220) (170) (310) (150) (285) (215) (76,2)

FIGURE 6
MODEL RV-1 PRESSURE RELIEF VALVE
— ANGLE STYLE INSTALLATION DIMENSIONS —
TFP1585
Page 7 of 8

Flange Drilling Specification


Nominal Nominal Dimensions in Inches and (mm)
Valve ANSI B16.1 1 ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129
Size (Class 125) (PN10) 2 (PN16) 3 (10K) (Table E) Dim. A
A B N A B N A B N A B N A B N Bolt Circle
2 Inch 4.75 0.75 4.92 0.75 4.72 0.59 4.49 0.71 Diameter
4 4 4 4
(DN50) (120,7) (19,0) (125,0) (19,0) (120,0) (15,0) (114,0) (18,0)
3 Inch 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71 Dim. B
4 USE 8 8 4
(DN80) (152,4) (19,0) (160,0) (19,0) (150,0) (15,0) (146,0) (18,0) Bolt Hole
ISO 7005-2
4 Inch 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71 Diameter
8 (PN16) 8 8 8
(DN100) (190,5) (19,0) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0)
Qty. N
6 Inch 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 Number of
8 8 8 8
(DN150) (241,3) (22,2) (240,0) (23,0) (240,0) (19,0) (235,0) (22,0) Bolt Holes
8 Inch 11.75 0.88 11.61 0.91 11.61 0.91 11.42 0.75 11.50 0.87
8 8 12 12 8
(DN200) (298,5) (22,2) (295,0) (23,0) (295,0) (23,0) (290,0) (19,0) (292,0) (22,0)

Notes:
1. Same drilling as for ANSI B16.5 (Class 150) and ANSI B16.42 (Class 150).
2. Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
3. Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).

TABLE A
DIMENSIONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING

PROBLEM CAUSE SOLUTION

Valve fails to open 1. Water connections are blocked. 1. Dismantle and clean downstream
tubing.*
2. Pilot adjustment is too high.
2. Reset pressure by turning pressure
3. Pilot diaphragm or seal is damaged. adjusting screw CCW.
3. Replace pilot valve.*

Valve fails to close 1. Water connections are blocked. 1. Dismantle and clean upstream
tubing.*
2. Blocked or stuck needle valve.
2. Dismantle and clean needle valve.*
3. Blocked finger filter.
3. Dismantle and clean finger filter.*
4. Foreign object stuck under valve
diaphragm. 4. Loosen cover bolts, remove cover
and diaphragm, and dispose of
5. Valve diaphragm is leaking. foreign object.*
6. Pilot seal is damaged. 5. Loosen cover bolts and replace
diaphragm.*
6. Replace pilot valve.*
*Prior to performing solution, the Model RV-1 must be taken out of service and completely drained.

TABLE B
TROUBLESHOOTING PROCEDURE
TFP1585
Page 8 of 8

Limited Ordering 8 Inch F x F


ISO (PN16) Flange . . . . P/N 52-572-8-126

Procedure
8 Inch F x F
Warranty JIS Flange . . . . . . . . . . . P/N 52-572-8-726
8 Inch F x F
Products manufactured by Tyco Fire Contact your local distributor for avail- AS Flange . . . . . . . . . . . P/N 52-572-8-526
Suppression & Building Products (TFSBP) ability. When placing an order, indicate
are warranted solely to the original Buyer P/Ns for ANGLE BODY STYLE
the full product name and Part Number 2 Inch T x T
for ten (10) years against defects in (P/N). Refer to the Price List for a com- NPT. . . . . . . . . . . . . . . . . . . P/N 52-573-8-060
material and workmanship when paid plete list of part numbers. 2 Inch T x T
for and properly installed and main- ISO . . . . . . . . . . . . . . . . . . . P/N 52-573-8-160
tained under normal use and service. Pressure Relief Valve
3 Inch F x F
ANSI Flange. . . . . . . . . . . . P/N 52-573-8-022
This warranty will expire ten (10) years
Specify the following information for 3 Inch F x F
from date of shipment by TFSBP. No
warranty is given for products or com- the TYCO Model RV-1 Valve: (Globe or ISO (PN16) Flange . . . . . . . P/N 52-573-8-112

ponents manufactured by companies Angle) Type, (size), Connection Type 3 Inch F x F


JIS Flange. . . . . . . . . . . . . . P/N 52-573-8-722
not affiliated by ownership with TFSBP (Threaded, including NPT or ISO, or
3 Inch F x F
or for products and components which Flanged, including flange drilling speci- AS Flange. . . . . . . . . . . . . . P/N 52-573-8-522
have been subject to misuse, improper fication from below), and P/N (below). 4 Inch F x F
installation, corrosion, or which have not ANSI Flange. . . . . . . . . . . . P/N 52-573-8-023
• Valve Type and Size
been installed, maintained, modified or 4 Inch F x F
repaired in accordance with applicable Globe: 2, 3, 4, 6, or 8 Inch ISO (PN16) Flange . . . . . . . P/N 52-573-8-113
4 Inch F x F
Standards of the National Fire Protection Angle: 2, 3, 4, 6, or 8 Inch JIS Flange. . . . . . . . . . . . . . P/N 52-573-8-723
Association, and/or the standards of any 4 Inch F x F
other Authorities Having Jurisdiction. • Connection Type: Threaded or Flanged AS Flange. . . . . . . . . . . . . . P/N 52-573-8-523
Materials found by TFSBP to be defec- For threaded, specify NPT or ISO. 6 Inch F x F
tive shall be either repaired or replaced, ANSI Flange. . . . . . . . . . . . P/N 52-573-8-025
at TFSBP’s sole option. TFSBP neither For flanged, identify flange drilling 6 Inch F x F
assumes, nor authorizes any person to specification as follows: ISO (PN16) Flange . . . . . . . P/N 52-573-8-115
6 Inch F x F
assume for it, any other obligation in ANSI B16-1 (Class 125) JIS Flange. . . . . . . . . . . . . . P/N 52-573-8-725
connection with the sale of products or 6 Inch F x F
parts of products. TFSBP shall not be ISO 7005-2 (PN16) AS Flange. . . . . . . . . . . . . . P/N 52-573-8-525
responsible for sprinkler system design ISO 7005-2 (PN10) for 8-inch valve only 8 Inch F x F
errors or inaccurate or incomplete in- ANSI Flange. . . . . . . . . . . . P/N 52-573-8-026
formation supplied by Buyer or Buyer’s JIS B2210 (10K) 8 Inch F x F
ISO (PN10) Flange . . . . . . . P/N 52-573-8-116
representatives. AS 2129 (Table E) 8 Inch F x F
In no event shall TFSBP be liable, in Table A describes the flange drill­ing di- ISO (PN16) Flange . . . . . . . P/N 52-573-8-126
contract, tort, strict liability or under mensional specifications listed above. 8 Inch F x F
any other legal theory, for incidental, JIS Flange. . . . . . . . . . . . . . P/N 52-573-8-726
indirect, special or consequential dam- 8 Inch F x F
P/Ns for GLOBE BODY STYLE AS Flange. . . . . . . . . . . . . . P/N 52-573-8-526
ages, including but not limited to labor 2 Inch F x F
charges, regardless of whether TFSBP ANSI Flange. . . . . . . . . . . . P/N 52-572-8-010 Replacement Valve Parts
was informed about the possibility of 2 Inch F x F Specify (part description from Figure 2)
such damages, and in no event shall ISO (PN16) Flange . . . . . . P/N 52-572-8-130
2 Inch F x F
for use with (size) Model RV-1 Pressure
TFSBP’s liability exceed an amount Relief Valve, P/N (from Figure 2).
JIS Flange . . . . . . . . . . . P/N 52-572-8-710
equal to the sales price.
2 Inch F x F
The foregoing warranty is made in lieu AS Flange . . . . . . . . . . . P/N 52-572-8-510
of any and all other warranties, express 3 Inch F x F
ANSI Flange . . . . . . . . . P/N 52-572-8-022
or implied, including warranties of mer-
3 Inch F x F
chantability and fitness for a particular ISO (PN16) Flange . . . . P/N 52-572-8-112
purpose. 3 Inch F x F
JIS Flange . . . . . . . . . . . P/N 52-572-8-722
This limited warranty sets forth the
exclusive remedy for claims based on 3 Inch F x F
AS Flange . . . . . . . . . . . P/N 52-572-8-522
failure of or defect in products, materi- 4 Inch F x F
als or components, whether the claim ANSI Flange . . . . . . . . . P/N 52-572-8-023
is made in contract, tort, strict liability 4 Inch F x F
or any other legal theory. ISO (PN16) Flange . . . . P/N 52-572-8-113
4 Inch F x F
This warranty will apply to the full extent JIS Flange . . . . . . . . . . . P/N 52-572-8-723
permitted by law. The invalidity, in whole 4 Inch F x F
or part, of any portion of this warranty AS Flange . . . . . . . . . . . P/N 52-572-8-523
will not affect the remainder. 6 Inch F x F
ANSI Flange . . . . . . . . . P/N 52-572-8-025
6 Inch F x F
ISO (PN16) Flange . . . . P/N 52-572-8-115
6 Inch F x F
JIS Flange . . . . . . . . . . . P/N 52-572-8-725
6 Inch F x F
AS Flange . . . . . . . . . . . P/N 52-572-8-525
8 Inch F x F
ANSI Flange . . . . . . . . . P/N 52-572-8-026
8 Inch F x F
ISO (PN10) Flange . . . . P/N 52-572-8-116

Copyright © 2010 - 2011 Tyco Fire Suppression & Building Products. All rights reserved.

Potrebbero piacerti anche