Test Report issued under the responsibility of:

TEST REPORT
IEC 62040-1
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS

Report Reference No. .................... : 203983-AS3-1 CB / DE1-54209/M1


Date of issue .................................... : 2014-11-11
Total number of pages .................... : 81

CB Testing Laboratory .................. : VDE Prüf- und Zertifizierungsinstitut GmbH


VDE Testing and Certification Institute
Address ............................................ : Merianstrasse 28, D-63069 Offenbach, Germany
Applicant’s name ........................... : American Power Conversion (APC)
Address ............................................ : 85 Rangeway Road Bldg #2, N.Billerica, MA, 01862
Test specification:
Standard .......................................... : DIN EN 62040-1 (VDE 0558-510):2009-06
EN 62040-1:2008
st
IEC 62040-1 : 2008 (1 Edition)
Test procedure ................................. : VDE, CB
Non-standard test method…………..: N/A
Test Report Form No. .................... : IEC62040_1A
TRF Originator ................................. : TÜV Rheinland Japan Ltd.
Master TRF ...................................... : Dated 2009-11
Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copy-
right owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the
reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 2 of 81 VDE Report No. 203983-AS3-1

Test item description ..................... : Uninterruptible Power Supply (UPS)


Trade Mark ....................................... :

Manufacturer .................................... : American Power Conversion (APC)


85 Rangeway Road Bldg #2, N.Billerica, MA, 01862
Model/Type reference ...................... : SRT3000RMXLI-IEC, SRT2200RMXLI-IEC,
SRT3000XLW-IEC, SRT3000XLW-IEC, (see model matrix)
See below rating of UPS and battery tray.
Ratings ............................................. : See below 2 tables for UPS and External battery pack.
Ambient: 40 °C

Rating of UPS:
SRT3000RMXLI-IEC ,
SRT2200RMXLI-IEC
SRT3000XLW-IEC
SRT3000XLW-IEC
A B C D see Model Matrix (Appendix
Input 208-240Vac, 50/60Hz; Output 3000VA, 2700W

UPS: Rating difference:


SRT3000XLI, SRT3000RMXLI Input 220-240Vac, 50-60Hz; Output 3000VA, 2700W
SRT2200XLI, SRT2200RMXLI Input 220-240Vac, 50-60Hz; Output 2200VA, 1980W

Rating of external battery pack:


External battery pack: Rating:
SRT72BP, SRT72RMBP 72Vdc (for 2200VA models)
SRT96BP, SRT96RMBP: 96Vdc (for 3000VA models)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 4 of 81 VDE Report No. 203983-AS3-1

Summary of testing:

Tests performed (name of test and test clause): Testing location:

See appendix 3 American Power Conversion Holding Inc.


No further tests were considered to be necessary.
For additional information refer to main test report, 3F., No.205, Sec. 3, Beixin Rd., Xindian Dist., New
mentioned in project history below Taipei City 231, Taiwan (R.O.C.)
TMP (TDAP File no. 5003241-9501-0001)
Summary of compliance with National Differences:

Note: EN Group Differences together with National Differences and Special National Conditions, if any, are in
the Appendix to the main body of this TRF.
Summary of testing:
Clause 4.5 Components ........................................................................................: Pass N/A
Clause 4.6 Power interface ...................................................................................: Pass N/A
Clause 4.7 Markings and instructions....................................................................: Pass N/A
Clause 5.1 Protection from electric shock and energy hazards ............................: Pass N/A
Clause 5.2 Requirements for auxiliary circuits ....................................................... Pass N/A
Clause 5.2.2 Telephone network voltage circuits – TNV........................................... Pass N/A
Clause 5.2.3 Limited current circuits ......................................................................... Pass N/A
Clause 5.2.4 External signalling circuits Pass N/A
Clause 5.3 Provisions for earthing and bonding ..................................................... Pass N/A
Clause 5.4 AC and D.C. power isolation ................................................................ Pass N/A
Clause 5.5 Overcurrent and earth fault protection ................................................. Pass N/A
Clause 5.6 Protection of personnel – Safety interlocks .......................................... Pass N/A
Clause 2.9 Electrical insulation ..............................................................................: Pass N/A
Clause 5.7 Clearances, creepage distances and distances through insulation ..... Pass N/A
Clause 6.2 Connection to power ............................................................................ Pass N/A
Clause 6.3 Wiring terminals for external power conductors ................................... Pass N/A
Clause 3.3 Wiring terminals for connection of external conductors ....................... Pass N/A
Clause 7 Physical requirements Pass N/A
Clause 7.5 Resistance to fire Pass N/A
Clause 7.7 Temperature rise Pass N/A
Clause 8 Electrical requirements and simulated abnormal conditions Pass N/A
Clause 8.1 earth leakage Pass N/A
Clause 8.2 Electric strength Pass N/A
Clause 8.3 Abnormal operating and fault conditions Pass N/A
Annex A Tests for resistance to heat and fire Pass N/A
Annex B Motor Tests under abnormal conditions Pass N/A
Annex C Transformers Pass N/A
Annex G Alternative Method for determining minimum clearances Pass N/A
Annex M Ventilation of battery compartments Pass N/A
Annex U Insulated winding wires for use without interleaved insulation Pass N/A
Annex V AC Power Distribution Systems Pass N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 5 of 81 VDE Report No. 203983-AS3-1

Copy of marking plate:


The above label may show a draft of an artwork for making plate pending approval by National Certification
Bodies and it shall not be affixed to products prior to such an approval.

Refer to IEC 60950-1 test report – Copy of marking plate:

Test item particulars................................................. :


Equipment mobility................................................... : movable stationary for building-in
Rack mount
Connection to the mains .......................................... : pluggable equipment permanent connection
detachable power supply cord
non-detachable power supply cord
Operating condition .................................................. : continuous rated operating / resting time:
Access location ....................................................... : operator accessible
restricted access location
Over voltage category (OVC) ................................. : OVC I OVC II OVC III OVC IV
other:
Mains supply tolerance (%) or absolute mains supply -10 % / +6 %
values ...................................................................... :
Tested for IT power systems .................................. : Yes No
IT testing, phase-phase voltage (V) ........................ :
Class of equipment ................................................. : Class I Class II Not classified
Considered current rating (A) ................................. :
Pollution degree (PD) .............................................. : PD 1 PD 2 PD 3
IP protection class ................................................... : IP--
Altitude during operation (m) .................................. : ≤ 2000 m
Altitude of test laboratory (m) .................................. : app. 40 m
Mass of equipment (kg) .......................................... : >18 kg
Possible test case verdicts:
– ......test case does not apply to the test object: N/A
– ......test object does meet the requirement : P (Pass)
– ......test object does not meet the requirement : F (Fail)
Testing
Date of receipt of test item .......................................... : 2014-11-10
Date (s) of performance of tests ................................. : 2014-11-10 - 2014-11-11
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma (point) is used as the decimal separator.
List of test equipment must be kept on file and available for review.
Standard IEC 62040-1:2008 is to be used in conjunction with IEC 60950-1:2005, which is referred to in this
TRF as "RD".
Note: EN Group Differences together with National Differences and Special National Conditions, if any,
are in the Appendix to the main body of this TRF.

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 6 of 81 VDE Report No. 203983-AS3-1

General product information:


Complete details of construction and testing as well as supporting documentation such as photographs and
schematics are done by previous Test Reports and partly included in the attachments.
The UPS provides reinforced insulation between primary and secondary circuits.

Conditions of Installation:
The units are suitable for a maximum manufacturer’s recommended ambient operating temperature (Tma)
of 40 °C.
Unit is designed and approved for use in installation category II.
Unit intended for continuous operation while charging.
UPS are Class 1 and designed for Pollution Degree 2.
Unit could be used as stand-alone (tower) or rack mounted version.
VDE approved appliance inlets and outlets are used.
– Alternative construction for AC power input and/or output power outlet to be terminal block struc-
ture. See installation manual for detail.
Secondary circuits are designed in 3 areas, (MB + DCLPS board and Communication Boards) other boards
are defined as Primary circuit area.

Model differences:
All models are identical except:
 UPS, Main differences:
1. Electric Ratings
2. Transformers: Charger transformer, DC/DC transformer, and Logic Power Supply transformer
3. Chokes: Input choke (for EMI), PFC choke L1203, Inverter choke L1207
4. TRIAC (for improving relay transfer time), Hall Sensor (for current sense)
5. Size of PCB (2.2KVA is 2 inch shorter than 3KVA). Layout in the area of PFC choke, Inverter
choke.

 External Battery Pack: (for example: SRT96BP/72BP)


1. Electric rating;
2. Quantity of batteries inside
3. Metal chassis is same as 2.2KVA of UPS.

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 7 of 81 VDE Report No. 203983-AS3-1

Factory (for information only)


Name ........... : American Power Conversion Corporation (A.P.C.) B.V.
Address ...... : LOT 3 BLK 14, PHASE III, PEZA, 4106 ROSARIO, CAVITE, PHILIPPINES

Name ........... : American Power Conversion Corporation (A.P.C.) B.V.


Address ...... : LOT 10, BLK 16, PHASE IV, PEZA, 4106 ROSARIO, CAVITE, PHILIPPINES

Name ........... : American Power Conversion Corporation (A.P.C.) B.V.


Address ...... : 2ND ST, PEZA, Cavite Economic Zone, 4106 ROSARIO, CAVITE, PHILIPPINES

This test report includes the following Appendices:

Appendix No. Description Page(s)

Appendix 1 Pictures 50 - 54

Appendix 2 Test Results 55 – 77

Appendix 3 Model Matrix 78

Appendix 4 List of test equipment used 79

Appendix 5 BACKFEED PROTECTION TEST and Schematic IEC Version. 80 - 81

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 8 of 81 VDE Report No. 203983-AS3-1

Appendix to test report reference No. : 1924400-3335-0067/203983

VDE Test- and Certification Institute DIN EN 62040-1 (VDE 0558-510):2009-06


GmbH Merianstrasse 28 EN 62040-1:2008
st
IEC 62040-1 : 2008 (1 Edition)
D - 63069 Offenbach
TYPE OF APPLIANCE : Uninterruptible Power Supply (UPS)
Made by : Schneider Electric IT Corporation
Trade mark : Schneider Electric IT Corporation
Model/type ref. : Structure of type name:
SRT3000RMXLI-IEC, SRT2200RMXLI-IEC,
SRT3000XLW-IEC, SRT3000XLW-IEC, (see model matrix)
A B C D
(see matrix on next page for further details)

Commission received from Ken Hsieh Date: 2014-11-10

Modification on the appliance:

1. Add the following model Numbers:

SRT3000RMXLI-IEC, SRT2200RMXLI-IEC, SRT3000XLW-IEC, SRT3000XLW-IEC


A B C D
(see matrix on next page for further details)
same as approved versions with approved IEC plugs. ( With alternate Critical Components)

Test Report History:


This report may consist of more than one report and is valid only with additional or previous issued reports:
(Licence No. 40040308
Date: CB-Ref. No.: Test Report Number Modifications:
Additional test report (this report)
2014-11-10 CB / DE1-54209/M1 1924400-3335-0067/203983 Addition of alternate model SRT 3000 RM
XLI-IEC with alternate components
Main test report approved to
DIN EN 62040-1 (VDE
0558-510):2009-06
2013-10-31 CB / DE1-54209 1924400-3335-0067/203209 EN 62040-1:2008
st
IEC 62040-1 : 2008 (1 Edi-
tion)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 9 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4 GENERAL CONDITIONS FOR TESTS P


4.5 Components P
Comply with IEC 62040-1 or relevant component (see appended table 4.5) P
standard
1.5.2/RD Evaluation and testing of components Certified components are P
used in accordance with their
ratings and certifications, and
they comply with applicable
parts of this standard. Com-
ponents not certified are used
in accordance with their rat-
ings and they comply with ap-
plicable parts of IEC 60950-1
and the relevant component
standard. Components, for
which no relevant IEC-
Standard exists, have been
tested under the conditions
occurring in the equipment,
using applicable parts of IEC
60950-1
1.5.3/RD Thermal controls no thermal controls N/A
1.5.4/RD Transformers see annex C for details P
1.5.5/RD Interconnecting cables Interconnecting cables are not N/A
used in this application
nd
1.5.6/RD Capacitors bridging insulation Certified to IEC60384-14 2 P
Edition. See Components List
for details.
Y2 capacitors used between
Lines and Ground and one Y1
between SELV and Primary
circuits
X2 capacitors used between
Line and Neutral.
See clause 2.4 for details of
requirements and compliance
of limited current circuits.
1.5.7/RD Resistors bridging insulation Bridging resistor between Line P
and ground
1.5.7.1/RD Resistors bridging functional, basic or supplemen- functional insulation only N/A
tary insulation
1.5.7.2/RD Resistors bridging double or reinforced insulation N/A
between a.c. mains and other circuits
1.5.7.3/RD Resistors bridging double or reinforced insulation N/A
between a.c. mains and antenna or coaxial cable
1.5.8/RD Components in equipment for IT power systems N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 10 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.6 Power interface P


1.6.1/RD AC power distribution systems TN-System P
1.6.2/RD Input current (see appended table 4.6) P
4.6 Neutral conductor Neutral is insulated from earth P
1.6.4/RD with basic insulation. Compo-
nents connected between
phases and earth are rated
and certified for a minimum
working voltage of 250 V. See
Components List

4.7 Marking and instructions P


4.7.1 General P
4.7.2 Power rating Refer to copy of rating label P
Input rated voltage/range (V)....................................: see page 2 P
Input rated current/range (A) ....................................: see page 2 P
Input symbol for nature of supply (d.c.) ...................: AC Unit P
Input rated frequency/range (Hz) .............................: see page 2 P
1.7.1/RD Number of Input phases and neutral ........................: one phase P
Output rated voltage/range (V) ................................: see page 2 P
Output rated current/range (A) ................................: see page 2 P
Output rated power factor, (if less than unity, or ac- see page 2 P
tive power and apparent power or active power and
rated current) ...........................................................:
1.7.1/RD Number of output phases and neutral .....................: one phase P
Output rated active power (W) ................................: see page 2 P
Output rated apparent power (VA) ..........................: see page 2 P
Output symbol for nature of supply (d.c.) ................: N/A
Output rated frequency/range (Hz) ..........................: see page 2 P
Ambient operating temperature range (°C) .............: 40°C P
Manufacturer’s name or trademark or identification P
mark .........................................................................:

Type/model or type reference ..................................: see page 2 P


Symbol for Class II equipment only .........................: Class I equipment N/A
Other symbols .........................................................: P
Certification marks ...................................................: VDE GS P
Instructions for units with automatic bypass / see Safety Instructions P
maintenance bypass, additional input a.c. supply, or
external batteries, having text “See installation in-
structions before connecting to the supply” .............:

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 11 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.7.3 Safety instructions see Safety Instructions P


4.7.3.1 General see Safety Instructions P
4.7.3.2 Installation ................................................................: Unit is an auto-ranging type N/A
Location in a restricted access location only ...........: N/A
Permanent connector UPS.......................................: Refer to appendices P
Pluggable type A or Pluggable type B UPS ............: P
4.7.3.3 Operation ..................................................................: P
4.7.3.4 Maintenance .............................................................: P
4.7.3.5 Distribution related backfeed ....................................: P
4.7.4 Main voltage adjustment .........................................: Unit is an auto-ranging type N/A
1.7.4/RD
Methods and means of adjustment; reference to in- N/A
stallation instructions ...............................................:
4.7.5 Power outlets ............................................................: Power outlets are marked with P
1.7.5/RD max. output
4.7.6 Fuse identification (marking, special fusing charac- Refer to appendices P
1.7.6/RD teristics, cross-reference) ........................................:
4.7.7 Wiring terminals Fuses are marked with ratings P
1.7.7/RD or symbols like F1, fuses are
not customer replaceable.
1.7.7.1/RD Protective earthing and bonding terminals ..............: UPS, provided with appliance P
inlet – and outlets (VDE
approved), refer to critical
component list and installation
guide for further details)
1.7.7.2/RD Terminals for a.c. mains supply conductors UPS, provided with appliance P
inlet – and outlets (VDE
approved), refer to critical
component list for further
details)
1.7.7.3/RD Terminals for d.c. mains supply conductors Battery connectors are P
marked with “+” and “-“
4.7.8 Battery terminals .....................................................: P
4.7.9 Controls and indicators P
1.7.8/RD
1.7.8.1/RD Identification, location and marking .........................: P
1.7.8.2/RD Colours ...................................................................: No indicators with colours N/A
1.7.8.3/RD Symbols according to IEC 60417 .............................: P
1.7.8.4/RD Markings using figures ...........................................: P
4.7.10 Isolation of multiple power sources .........................: No multiple power sources P
1.7.9/RD
4.7.11 IT power systems No marking on removable N/A
1.7.2.4/RD parts
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 12 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.7.12 Protection in building installation P


4.7.13 High leakage current (mA) ......................................: Statement in the instructions P
5.1/RD that the unit is connected to a
separate ground connector in
the back of the unit near the
appliance inlet , screw is
marked with the ground
symbol
4.7.14 Thermostats and other regulating devices No adjustable thermal devices N/A
1.7.10/RD employed
4.7.15 Language(s) ............................................................: ⎯
1.7.2.1/RD
and
1.7.8.1/RD
4.7.16 Durability of markings P
1.7.11/RD
4.7.17 Removable parts No marking on removable P
1.7.12/RD parts
4.7.18 Replaceable batteries Replaceable Lead Acid P
1.7.13/RD Batteries
Language(s) ............................................................: ⎯
4.7.19 Operator access with a tool ......................................: Cannot access hazardous P
1.7.2.5/RD part.
4.7.20 Battery See component list P
Clearly legible information .......................................: P
Battery type .............................................................: Sealed Lead Acid P
Nominal voltage of total battery (V) .........................: P
Nominal capacity of total battery (optional) .............: P
Warning label ..........................................................: P
Instructions ..............................................................: P
2.1.1.5/RD Protection against energy hazards Battery terminals are protect- N/A
ed
4.7.21 Installation instructions See instruction N/A
1.7.2.4/RD

5 FUNDAMENTAL DESIGN REQUIREMENTS P


5.1 Protection against electric shock and energy hazards P
5.1.1 Protection for UPS intended to be used in operator No operator access to haz- P
2.1.1/RD access areas ardous parts.
All user accessible outputs ful-
fil SELV Requirements.
2.1.1.1/RD Access to energized parts see clause 2.1.1 P
Test by inspection ...................................................: all wires in the front and back P
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 13 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

of the unit which are accessi-


ble with the test pin are double
insulated or have an thickness
of insulation > 0.4 mm
Test with test finger (Figure 2A) ..............................: P
Test with test pin (Figure 2B) ..................................: P
Test with test probe (Figure 2C) ..............................: P
2.1.1.2/RD Battery compartments P
2.1.1.3/RD Access to ELV wiring No ELV circuits N/A
Working voltage (Vpeak or Vrms); minimum dis- (See appended table 2.10.5) ⎯
tance through insulation (mm)
2.1.1.4/RD Access to hazardous voltage circuit wiring No access to hazardous volt- N/A
age circuit wiring
2.1.1.5/RD Energy hazards .......................................................: Battery terminal are provided P
2.1.1.6/RD Manual controls See table 2.10 P
2.1.1.7/RD Discharge of capacitors in equipment P
Measured voltage (V); time-constant (s) ..................: ⎯
2.1.1.8/RD Energy hazards – d.c. mains supply AC unit N/A
a) Capacitor connected to the d.c. mains supply ..: N/A
b) Internal battery connected to the d.c. mains N/A
supply ................................................................:
2.1.1.9/RD Audio amplifiers .......................................................: No audio Amplifiers N/A
5.1.2 Protection for UPS intended to be used in service P
2.1.1.5 c) access areas
/RD
Hazardous energy level N/A
5.1.3 Protection for UPS intended to be used in restricted N/A
2.1.1.5 c) access areas
/RD
Hazardous energy level N/A
5.1.4 Backfeed protection (see appended table 5.7) ⎯
Shock hazard after de-energization of a.c. input for Output is not grounded, P
UPS Relays with 1.4 mm gap are
provided.
The measured voltage in
previous Test Reports is
voltage from the filter
capacitors (leakage current is
very low) refer to test results.
Measured voltage (V); time-constant (s) ..................: ⎯
Description of the construction ................................: Considered. P
5.1.5 Emergency switching device N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 14 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

5.2 Requirements for auxiliary circuits P


5.2.1 Safety extra low voltage circuit – SELV 2.2.3.1 – 2.2.3.3/RD P
2.2/RD
2.2.1/RD General requirements Data Circuits fulfil SELV re- P
quirements.
SELV circuits considered as
safe touchable under normal
operating condition and after a
single fault.
2.2.2/RD Voltages under normal conditions (V) .....................: Less than or equal to 42.4Vpk P
or 60Vdc
2.2.3/RD Voltages under fault conditions (V) .........................: Less than or equal to 42.4Vpk P
or Vdc
Maximum voltage under fault
condition less than 71Vpk or
12Vdc for not longer than 0.2
sec.
There are no single faults
which can cause voltage levels
on the outputs to exceed the
SELV limits.
2.2.4/RD Connection of SELV circuits to other circuits ..........: SELV circuit are considered to P
be connected only to SELV or
earth.
5.2.2 Telephone network voltage circuits – TNV N/A
2.3/RD
2.3.1/RD Limits N/A
Type of TNV circuits .................................................: No TNV circuits ⎯
2.3.2/RD Separation from other circuits and from accessible N/A
parts
2.3.2.1/RD General requirements N/A
2.3.2.2/RD Protection by basic insulation N/A
2.3.2.3/RD Protection by earthing N/A
2.3.2.4/RD Protection by other constructions ............................: N/A
2.3.3/RD Separation from hazardous voltages N/A
Insulation employed .................................................: ⎯
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed .................................................: ⎯
2.3.5/RD Test for operating voltages generated externally N/A
Test with test probe (Figure 2C) ..............................: N/A
5.2.3 Limited current circuits N/A
2.4/RD
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 15 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

2.4.1/RD General requirements N/A


2.4.2/RD Limit values (See appended table 5.2.3) ⎯
Frequency (Hz) .........................................................: ⎯
Measured current (mA) ............................................: ⎯
Measured voltage (V) ...............................................: ⎯
Measured circuit capacitance (nF or µF)..................: ⎯
2.4.3/RD Connection of limited current circuits to other cir- N/A
cuits
5.2.4 External signalling circuits N/A
3.5/RD
3.5.1/RD General requirements Interconnection of P/S outputs P
(SELV) with other circuits is to
be evaluated in end-use prod-
uct
3.5.2/RD Types of interconnection circuits .............................: SELV circuits P
3.5.3/RD ELV circuits as interconnection circuits No ELV interconnection N/A
3.5.4/RD Data ports for additional equipment P
5.2.5 Limited power source See Test result for details. P
2.5/RD
a) Inherently limited output N/A
b) Impedance limited output P
c) Regulating network limited output under normal P
operating and single fault condition
d) Overcurrent protective device limited output P
Max. output voltage (V), max. output current (A), ⎯
max. apparent power (VA) .......................................:
Current rating of overcurrent protective device (A) ⎯

5.3 Protective earthing and bonding P


5.3.1 General P
2.6/RD Provisions for earthing and bonding P
2.6.1/RD Protective earthing Accessible metal parts are reli- P
ably earthed, refer to installa-
tion instructions
2.6.2/RD Functional earthing Functional earthing not pro- N/A
vided
2.6.3/RD Protective earthing and protective bonding conduc- VDE approved appliance inlet P
tors
2.6.3.1/RD General P
2.6.3.2/RD Size of protective earthing conductors Construction is designed for P

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 16 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

the expected current.


Rated current (A), cross-sectional area (mm2), ⎯
AWG .........................................................................:
2.6.3.3/RD Size of protective bonding conductors see 2.6.3.2 P
Rated current (A), cross-sectional area (mm2), ⎯
AWG .........................................................................:
Protective current rating (A), cross-sectional area ⎯
(mm2), AWG.............................................................:
2.6.3.4/RD Resistance of earthing conductors and their termi- Considered. P
nations; resistance (Ω), voltage drop (V), test cur-
rent (A), duration (min) .............................................:
2.6.3.5/RD Colour of insulation ...................................................: Green/Yellow used only for P
protective earthing
2.6.4/RD Terminals Unit is provided with two ap- N/A
pliance inlet’s for input
2.6.4.1/RD General N/A
2.6.4.2/RD Protective earthing and bonding terminals Unit is provided with two ap- N/A
pliance inlet’s for input
Rated current (A), type, nominal thread diameter ⎯
(mm) .........................................................................:
2.6.4.3/RD Separation of the protective earthing conductor N/A
from protective bonding conductors
2.6.5/RD Integrity of protective earthing P
2.6.5.1/RD Interconnection of equipment N/A
2.6.5.2/RD Components in protective earthing conductors and none N/A
protective bonding conductors
2.6.5.3/RD Disconnection of protective earth P
2.6.5.4/RD Parts that can be removed by an operator N/A
2.6.5.5/RD Parts removed during servicing N/A
2.6.5.6/RD Corrosion resistance P
2.6.5.7/RD Screws for protective bonding P
2.6.5.8/RD Reliance on telecommunication network or cable N/A
distribution system
5.3.2 Protective earthing Accessible metal parts are re- P
2.6.1/RD liable earthed.
Unit is provided with appliance
inlet’s for input
2.10/RD Clearances, creepage distances and distances Installation Category II is P
through insulation assumed for this unit.
4.2/RD Mechanical strength P
5.2/RD Electric strength P
5.3.3 Protective bonding P

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 17 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

5.4 AC and d.c. power isolation P


5.4.1 General P
3.4/RD Disconnection from the mains supply P
3.4.1/RD General requirement P
3.4.2/RD Disconnect devices Unit is provided with Appli- P
ance Inlet for input
3.4.3/RD Permanently connected equipment see 3.4.1 P
3.4.4/RD Parts which remain energized P
3.4.5/RD Switches in flexible cords N/A
3.4.6/RD Number of poles – single-phase and d.c. equipment see 3.4.1 P
3.4.7/RD Number of poles – three-phase equipment see 3.4.1 P
3.4.8/RD Switches as disconnect devices N/A
3.4.9/RD Plugs as disconnect devices N/A
3.4.10/RD Interconnected equipment N/A
3.4.11/RD Multiple power sources N/A
5.4.2 Disconnect devices P

5.5 Overcurrent and earth fault protection P


5.5.1 General P
2.7.3/RD Short-circuit backup protection Protective devices have P
adequate breaking (rupturing)
capacity to interrupt the max.
fault current (including short
circuit), see 2.7.1
2.7.4/RD Number and location of protective devices .............: see schematics and compo- P
nent list for details
2.7.5/RD Protection by several devices N/A
2.7.6/RD Warning to service personnel ..................................: N/A
5.5.2 Basic requirements P
5.5.3 Battery circuit protection P
5.5.3.1 Overcurrent and earth fault protection P
5.5.3.2 Location of protective device P
5.5.3.3 Rating of protective device P
5.3.1/RD Protection against overload and abnormal operation (see appended table 8.3) P

5.6 Protection of personnel – Safety interlocks P


5.6.1 Operator protection N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 18 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

2.8/RD Safety interlocks N/A


2.8.1/RD General principles N/A
2.8.2/RD Protection requirements N/A
2.8.3/RD Inadvertent reactivation N/A
2.8.4/RD Fail-safe operation N/A
2.8.5/RD Moving parts N/A
2.8.6/RD Overriding N/A
2.8.7/RD Switches and relays N/A
2.8.7.1/RD Contact gaps (mm) ..................................................: N/A
2.8.7.2/RD Overload test N/A
2.8.7.3/RD Endurance test N/A
2.8.7.4/RD Electric strength test N/A
2.8.8/RD Mechanical actuators N/A
5.6.2 Service person protection P
5.6.2.1 Introduction P
5.6.2.2 Covers P
5.6.2.3 Location and guarding of parts P
5.6.2.4 Parts on doors N/A
5.6.2.5 Component access P
2.8.3/RD Inadvertent reactivation N/A
5.6.2.6 Moving parts P
5.6.2.7 Capacitor banks N/A
5.6.2.8 Internal batteries P

5.7 Clearances, creepage distances and distances through insulation P


2.10/RD
2.10.1/RD General Installation Category II is as- P
sumed for this unit.
2.10.1.1/RD Frequency ................................................................: Considered P
2.10.1.2/RD Pollution degrees .....................................................: PD2 considered. P
2.10.1.3/RD Reduced values for functional insulation Functional insulation provided, P
unit meets criteria for
functional insulation as per
5.3.4 a) or c).
2.10.1.4/RD Intervening unconnected conductive parts Considered P
2.10.1.5/RD Insulation with varying dimensions Considered P
2.10.1.6/RD Special separation requirements Considered P
2.10.1.7/RD Insulation in circuits generating starting pulses No starting pulses N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 19 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

2.10.2/RD Determination of working voltage P


2.10.2.1/RD General P
2.10.2.2/RD RMS working voltage P
2.10.2.3/RD Peak working voltage P
2.10.3/RD Clearances P
2.10.3.1/RD General P
2.10.3.2/RD Mains transient voltages Overvoltage Category II P
a) AC mains supply ...............................................: Between the phases P
AC 250 V
2500 V transient
b) Earthed d.c. mains supplies ..............................: N/A
c) Unearthed d.c. mains supplies ..........................: N/A
d) Battery operation ...............................................: N/A
2.10.3.3/RD Clearances in primary circuits P
2.10.3.4/RD Clearances in secondary circuits P
2.10.3.5/RD Clearances in circuits having starting pulses N/A
2.10.3.6/RD Transients from a.c. mains supply ..........................: P
2.10.3.7/RD Transients from d.c. mains supply ..........................: N/A
2.10.3.8/RD Transients from telecommunication networks and N/A
cable distribution systems .......................................:
2.10.3.9/RD Measurement of transient voltage levels Transient levels not measured N/A
a) Transients from a mains supply N/A
For an a.c. mains supply ...................................: N/A
For a d.c. mains supply .....................................: N/A
b) Transients from a telecommunication network .: N/A
2.10.4/RD Creepage distances P
2.10.4.1/RD General P
2.10.4.2/RD Material group and comparative tracking index P
CTI tests ...................................................................: Material group IIIb is assumed ⎯
to be used
2.10.4.3/RD Minimum creepage distances (See Test result for details.; P
2.10.3 and 2.10.4)
2.10.5 /RD Solid insulation P
2.10.5.1/RD General P
2.10.5.2/RD Distances through insulation See Test result for details. P
2.10.5.3/RD Insulating compound as solid insulation see clause 2.10.5.4 P
2.10.5.4/RD Semiconductor devices all Opto-isolators have either a P
distance through insulation of
0.4 mm, which has been
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 20 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

tested for AC 5000 V Electric


Strength and for compliance of
clause 2.10.5.5, or an internal
creepage distance of > 4 mm
and a Thermal Cycling Test to
clause 2.10.10 has been
performed to fulfil the
requirements for Pollution
Degree 1. All opto-isolators are
also certified to VDE 0884
and/or IEC 60747-5-5
see critical component list for
details on opto-isolators
2.10.5.5/RD Cemented joints see 2.10.5.4 and 2.10.6.3 P
2.10.5.6/RD Thin sheet material – General Used in Transformer N/A
2.10.5.7/RD Separable thin sheet material 3 layers, see annex C N/A
Number of layers (pcs) ............................................: ⎯
2.10.5.8/RD Non-separable thin sheet material not used N/A
2.10.5.9/RD Thin sheet material – standard test procedure see 2.10.5.10 N/A
Electric strength test ⎯
2.10.5.10 Thin sheet material – alternative test procedure Alternative test procedure N/A
/RD used
Electric strength test (see appended table 8.2) ⎯
2.10.5.11 Insulation in wound components N/A
/RD
2.10.5.12 Wire in wound components P
/RD
Working voltage .......................................................: ⎯
a) Basic insulation not under stress ......................: N/A
b) Basic, supplementary, reinforced insulation .....: N/A
c) Compliance with Annex U .................................: See 2.10.5.11 N/A
Two wires in contact inside wound component; an- N/A
gle between 45° and 90° .........................................:
2.10.5.13 Wire with solvent-based enamel in wound compo- Not used N/A
/RD nents
Electric strength test ⎯
Routine test N/A
2.10.5.14 Additional insulation in wound components N/A
/RD
Working voltage .......................................................: ⎯
– Basic insulation not under stress ......................: N/A
– Supplementary, reinforced insulation ...............: N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 21 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

2.10.6/RD Construction of printed boards P


2.10.6.1/RD Uncoated printed boards See Test result for details. P
2.10.6.2/RD Coated printed boards (see appended table 2.10.3 N/A
and 2.10.4)
2.10.6.3/RD Insulation between conductors on the same inner Compliance with clause N/A
surface of a printed board 2.10.5.5 “c)”,
2.10.6.4/RD Insulation between conductors on different layers of N/A
a printed board
Distance through insulation N/A
Number of insulation layers (pcs) ............................: N/A
2.10.7/RD Component external terminations N/A
2.10.8/RD Tests on coated printed boards and coated compo- Coating not applied. N/A
nents
2.10.8.1/RD Sample preparation and preliminary inspection N/A
2.10.8.2/RD Thermal conditioning N/A
2.10.8.3/RD Electric strength test ⎯
2.10.8.4/RD Abrasion resistance test N/A
2.10.9/RD Thermal cycling See clause 2.10.5.4, 2.10.5.5, N/A
2.10.6.3
2.10.10/RD Test for Pollution Degree 1 environment and insu- See clause 2.10.5.4 N/A
lating compound
2.10.11/RD Tests for semiconductor devices and cemented See clause 2.10.5.4, 2.10.6.3 N/A
joints
2.10.12/RD Enclosed and sealed parts N/A

6 WIRING, CONNECTIONS AND SUPPLY P


6.1 General P
6.1.1 Introduction P
3.1/RD General P
3.1.1/RD Current rating and overcurrent protection Internal wiring is adequate for P
the current. Protection is ade-
quate for the application
3.1.2/RD Protection against mechanical damage Wires do not touch sharp P
edges and heat sinks that
could damage the insulation
and cause hazard.
3.1.3/RD Securing of internal wiring Wires are adequately fixed to P
prevent excessive strain or
damage of the conductors' in-
sulation.
3.1.4/RD Insulation of conductors The insulation of the individual P
conductors is suitable for the

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 22 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

application and the working


voltage.
(see appended table 5.2)
3.1.5/RD Beads and ceramic insulators Beads or ceramic insulators N/A
are not used
3.1.6/RD Screws for electrical contact pressure Electrical and earthing con- P
nections engage at least two
complete threads into metal.
No screws of insulating mate-
rial are used for electrical and
earthing connections.
3.1.7/RD Insulating materials in electrical connections Current carrying and protec- P
tive earthing connections are
metal to metal.
Screws with star/spring wash-
er are used for the connection
between ground trace (PWB)
and chassis
3.1.8/RD Self-tapping and spaced thread screws Thread cutting or space P
thread screw not used for cur-
rent carrying electrical connec-
tions.
3.1.9/RD Termination of conductors Conductors are suitable ter- P
minated, creepage and clear-
ances maintained, second se-
curing for soldered termina-
tions provided.
10 N pull test 10 N applied to relevant con- P
ductors.
3.1.10/RD Sleeving on wiring Sleeving if safety related reli- P
ably kept in position.
6.1.2 Dimensions and rating of busbars and insulated P
conductors

6.2 Connection to power P


6.2.1 General provisions for connection to power P
3.2.2/RD Multiple supply connections only one supply connection N/A
3.2.3/RD Permanently connected equipment UPS. N/A
Unit is provided with an appli-
ance inlet.
Number of conductors, diameter of cable and con- ⎯
duits (mm) ................................................................:
3.2.4/RD Appliance inlets see component list for details P
on appliance inlet
3.2.5/RD Power supply cords AC Power Cord was not part N/A
of this investigation

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 23 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

3.2.5.1/RD AC power supply cords see 3.2.5 N/A


Type .........................................................................: ⎯
Rated current (A), cross-sectional area (mm²), ⎯
AWG ........................................................................:
3.2.5.2/RD DC power supply cords Power cord for external batter- N/A
ies are not part of this investi-
gation
3.2.6/RD Cord anchorages and strain relief N/A
Mass of equipment (kg), pull (N) ............................: ⎯
Longitudinal displacement (mm) .............................: ⎯
3.2.7/RD Protection against mechanical damage P
3.2.8/RD Cord guards N/A
Diameter or minor dimension D (mm); test mass (g) ⎯
..................................................................................:
Radius of curvature of cord (mm) .............................: ⎯
6.2.2 Means of connection ...............................................: P
More than one supply connection ...........................: N/A

6.3 Wiring terminals for external power conductors P


3.3/RD Wiring terminals for connection of external conduc- P
tors
3.3.1/RD Wiring terminals N/A
3.3.2/RD Connection of non-detachable power supply cords N/A
3.3.3/RD Screw terminals N/A
3.3.4/RD Conductor sizes to be connected N/A
Rated current (A), cord/cable type, cross-sectional ⎯
area (mm2) ...............................................................:
3.3.5/RD Wiring terminal sizes N/A
Rated current (A), type, nominal thread diameter ⎯
(mm) ........................................................................:
3.3.6/RD Wiring terminal design N/A
3.3.7/RD Grouping of wiring terminals N/A
3.3.8/RD Stranded wire N/A

7 PHYSICAL REQUIREMENTS P
7.1 Enclosure P

7.2 Stability P
4.1/RD

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 24 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

Angle of 10° P
Test force (N) ..........................................................: P

7.3 Mechanical strength P


4.2/RD
4.2.1/RD General P
4.2.2/RD Steady force test, 10 N Applied to relevant parts. ⎯
no hazard
4.2.3/RD Steady force test, 30 N Applied to relevant parts. P
no hazard
4.2.4/RD Steady force test, 250 N Applied to relevant parts. P
no hazard
4.2.5/RD Impact test Test performed on the top, P
bottom and on the side of the
unit. No hazard.
Fall test P
Swing test P
4.2.6/RD Drop test; height (mm) .............................................: N/A
4.2.7/RD Stress relief test ⎯
4.2.8/RD Cathode ray tubes No CRT’s N/A
Picture tube separately certified ..............................: ⎯
4.2.9/RD High pressure lamps No High Pressure Lamps N/A
4.2.10/RD Wall or ceiling mounted equipment; force (N) .........: Unit is not intended for wall or N/A
ceiling mounting

7.4 Construction details P


7.4.1 Introduction P
4.3.1/RD Edges and corners All edges and corners were P
judged to be sufficiently well
rounded as to not constitute a
hazard
4.3.2/RD Handles and manual controls; force (N)...................: No handles and manual con- N/A
trols
4.3.3/RD Adjustable controls No adjustable controls N/A
4.3.4/RD Securing of parts No loosening of parts impairing P
creepage distances or
clearances is likely to occur
4.3.5/RD Connection by plugs and sockets P
4.3.7/RD Heating elements in earthed equipment Not heating elements N/A
4.3.11/RD Containers for liquids or gases No such a container N/A
4.4/RD Protection against hazardous moving parts P
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 25 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.4.1/RD General Unit is provided with a DC fan P


4.4.2/RD Protection in operator access areas ........................: UPS. Fan guards provided P
4.4.3/RD Protection in restricted access locations .................: N/A
4.4.4/RD Protection in service access areas P
4.5/RD Thermal requirements P
4.5.1/RD General P
4.5.2/RD Temperature tests Insulation is not exposed to N/A
oil, grease, etc.
Normal load condition per Annex L .........................: Equipment does not produce N/A
dust
4.5.3/RD Temperature limits for materials No such a container N/A
4.5.4/RD Touch temperature limits P
4.5.5/RD Resistance to abnormal heat ...................................: (see appended table 7.4) P
7.4.2 Openings P
7.4.3 Gas Concentration P
7.4.4 Equipment movement P

7.5 Resistance to fire P


4.7/RD
4.7.1/RD Reducing the risk of ignition and spread of flame Risk of ignition due to high P
temperatures minimized by
design and components Mate-
rials with the required flamma-
bility classes are used.
Safety relevant components
used within their specified rat-
ing.
Electrical parts are not likely to
ignite nearby materials.
Temperatures see 4.5.1
Method 1, selection and application of components (see appended table 7.5) P
wiring and materials
Method 2, application of all of simulated fault condi- (see appended table 7.5) N/A
tion tests
4.7.2/RD Conditions for a fire enclosure enclosure is entirely made of P
metal
4.7.2.1/RD Parts requiring a fire enclosure P
4.7.2.2/RD Parts not requiring a fire enclosure P
4.7.3/RD Materials P
4.7.3.1/RD General P
4.7.3.2/RD Materials for fire enclosures P

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 26 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.7.3.3/RD Materials for components and other parts outside Front Bezel rated HB P
fire enclosures (for decorative only); Bezel for
Display (UI interface) is rated
HB (LPS circuits are complied.)
4.7.3.4/RD Materials for components and other parts inside fire All internal materials are rated P
enclosures V-2 or better, or are mounted
on printed wiring boards rated
V-1 or better
4.7.3.5/RD Materials for air filter assemblies No air filter assemblies N/A
4.7.3.6/RD Materials used in high-voltage components No high-voltage components N/A

7.6 Battery location P


7.6.1 Battery location and installation See manual, additional batter- P
ies data available on request
7.6.2 Accessibility and maintainability P
7.6.3 Distance P
7.6.4 Case insulation P
7.6.5 Wiring P
7.6.6 Electrolyte spillage P
7.6.7 Ventilation N/A
7.6.8 Charging voltage P

7.7 Temperature rise P


4.5/RD Thermal requirements P
4.5.1/RD General P
4.5.2/RD Temperature tests P
Normal load condition per Annex L .........................: ⎯
4.5.3/RD Temperature limits for materials (see appended table 7.7) P
4.5.4/RD Touch temperature limits (see appended table 7.7) P
4.5.5/RD Resistance to abnormal heat ...................................: (see appended table 4.5.5) P
Based on the physical
characteristic of the
thermoplastic materials
employed in the power supply,
this test was not considered
necessary

8 ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS P


8.1 General provisions for earth leakage P
5.1.1/RD General P
5.1.7/RD Equipment with touch current exceeding 3,5 mA N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 27 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

8.2 Electric strength P


5.2/RD
5.2.1/RD General (see appended table 8.2) P
5.2.2/RD Test procedure (see appended table 8.2) P

8.3 Abnormal operating and fault conditions P


8.3.1 General P
5.3.1/RD Protection against overload and abnormal operation (see appended table 8.3) P
5.3.2/RD Motors (see appended Annex B) P
5.3.3/RD Transformers (see appended Annex C) P
5.3.4/RD Functional insulation .................................................: P
5.3.5/RD Electromechanical components N/A
5.3.9/RD Compliance criteria for abnormal operating and P
fault conditions
8.3.2 Simulation of faults P
8.3.3 Conditions for tests P

9 CONNECTION TO TELECOMMUNICATION NETWORKS N/A


6/RD
6.1/RD Protection of telecommunication network service persons, and users of other N/A
equipment connected to the network, from hazards in the equipment
6.1.1/RD Protection from hazardous voltages N/A
6.1.2/RD Separation of the telecommunication network from N/A
earth
6.1.2.1/RD Requirements N/A
Supply voltage (V) ...................................................: ⎯
Current in the test circuit (mA) ...............................: ⎯
6.1.2.2/RD Exclusions ...............................................................: N/A
6.2/RD Protection of equipment users from overvoltages on telecommunication networks N/A
6.2.1/RD Separation requirements N/A
6.2.2/RD Electric strength test procedure N/A
6.2.2.1/RD Impulse test N/A
6.2.2.2/RD Steady-state test N/A
6.2.2.3/RD Compliance criteria N/A
6.3/RD Protection of the telecommunication wiring system from overheating N/A
Max. output current (A) ............................................: ⎯
3.5/RD Interconnection of equipment N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 28 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

3.5.1/RD General requirements N/A


3.5.2/RD Types of interconnection circuits .............................: N/A

3.5.3/RD ELV circuits as interconnection circuits N/A


3.5.4/RD Data ports for additional equipment N/A
2.1.3/RD Protection in restricted access locations N/A
2.3.1/RD Limits N/A
Type of TNV circuits .................................................: ⎯
2.3.2/RD Separation from other circuits and from accessible N/A
parts
2.3.2.1/RD General requirements N/A
2.3.2.2/RD Protection by basic insulation N/A
2.3.2.3/RD Protection by earthing N/A
2.3.2.4/RD Protection by other constructions ............................: N/A
2.3.3/RD Separation from hazardous voltages N/A
Insulation employed .................................................: ⎯
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed .................................................: ⎯
2.3.5/RD Test for operating voltages generated externally N/A
2.6.5.8/RD Reliance on telecommunication network or cable N/A
distribution system
2.10.3.3/RD Clearances in primary circuits N/A
2.10.3.4/RD Clearances in secondary circuits N/A
2.10.4/RD Creepage distances N/A
2.10.4.1/RD General N/A
2.10.4.2/RD Material group and comparative tracking index N/A
CTI tests ...................................................................: ⎯
2.10.4.3/RD Minimum creepage distances N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 29 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

M/RD ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD) N/A
M.1/RD Introduction N/A
M.2 /RD Method A N/A
M.3/RD Method B N/A
M.3.1/RD Ringing signal N/A
M.3.1.1/RD Frequency (Hz) ........................................................: ⎯
M.3.1.2/RD Voltage (V) ...............................................................: ⎯
M.3.1.3/RD Cadence; time (s), voltage (V) .................................: ⎯
M.3.1.4/RD Single fault current (mA) ..........................................: ⎯
M.3.2/RD Tripping device and monitoring voltage ..................: N/A
M.3.2.1/RD Conditions for use of a tripping device or a monitor- ⎯
ing voltage
M.3.2.2/RD Tripping device N/A
M.3.2.3/RD Monitoring voltage (V) .............................................: N/A

A/RD ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE N/A


A.1/RD Flammability test for fire enclosures of movable N/A
equipment having a total mass exceeding 18 kg,
and of stationary equipment (see 4.7.3.2/RD)
A.1.1/RD Samples....................................................................: ⎯
Wall thickness (mm) .................................................: ⎯
A.1.2/RD Conditioning of samples; temperature (°C) .............: N/A
A.1.3/RD Mounting of samples ...............................................: N/A
A.1.4/RD Test flame (see IEC 60695-11-3) N/A
Flame A, B, C or D ..................................................: ⎯
A.1.5/RD Test procedure N/A
A.1.6/RD Compliance criteria N/A
Sample 1 burning time (s) ........................................: ⎯
Sample 2 burning time (s) ........................................: ⎯
Sample 3 burning time (s) ........................................: ⎯
A.2/RD Flammability test for fire enclosures of movable N/A
equipment having a total mass not exceeding 18
kg, and for material and components located inside
fire enclosures (see 4.7.3.2/RD and 4.7.3.4/RD)
A.2.1/RD Samples, material .....................................................: ⎯
Wall thickness (mm) .................................................: ⎯
A.2.2/RD Conditioning of samples; temperature (°C) .............: N/A
A.2.3/RD Mounting of samples ...............................................: N/A
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 30 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

A.2.4/RD Test flame (see IEC 60695-11-4) N/A


Flame A, B or C .......................................................: ⎯
A.2.5/RD Test procedure N/A
A.2.6/RD Compliance criteria N/A
Sample 1 burning time (s) ........................................: ⎯
Sample 2 burning time (s) ........................................: ⎯
Sample 3 burning time (s) ........................................: ⎯
A.2.7/RD Alternative test acc. to IEC 60695-11-5, cl. 5 and 9 N/A
Sample 1 burning time (s) ........................................: ⎯
Sample 2 burning time (s) ........................................: ⎯
Sample 3 burning time (s) ........................................: ⎯
A.3/RD Hot flaming oil test (see 4.6.2/RD) N/A
A.3.1/RD Mounting of samples N/A
A.3.2/RD Test procedure N/A
A.3.3/RD Compliance criterion N/A

B/RD ANNEX B, P
MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2/RD and 5.3.2/RD)
B.1/RD General requirements DC fans used P
Position ....................................................................: See Components List ⎯
Manufacturer ...........................................................: See Components List ⎯
Type .........................................................................: See Components List ⎯
Rated values ..........................................................: See Components List ⎯
B.2/RD Test conditions P
B.3/RD Maximum temperatures See Test result for details. P
B.4/RD Running overload test N/A
B.5/RD Locked-rotor overload test N/A
Test duration (days) ................................................: ⎯
Electric strength test: test voltage (V) .....................: ⎯
B.6/RD Running overload test for d.c. motors in secondary Fans are VDE or TUV certi- P
circuits fied to IEC/EN60950-1
B.6.1/RD General See B.6 P
B.6.2/RD Test procedure See B.6 P
B.6.3/RD Alternative test procedure See B.6 P
B.6.4/RD Electric strength test; test voltage (V) .....................: See B.6 P
B.7/RD Locked-rotor overload test for d.c. motors in sec- Fans are VDE certified to P

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 31 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

ondary circuits IEC/EN60950-1


See Test result for details.
B.7.1/RD General See B.7 P
B.7.2/RD Test procedure See B.7 P
B.7.3/RD Alternative test procedure See B.7 P
B.7.4/RD Electric strength test; test voltage (V) .....................: See B.7 N/A
B.8/RD Test for motors with capacitors N/A
B.9/RD Test for three-phase motors N/A
B.10/RD Test for series motors N/A
Operating voltage (V) ..............................................: ⎯

C/RD ANNEX C, TRANSFORMERS (see 1.5.4/RD and 5.3.3/RD) P


Position ....................................................................: See IEC 60950 -1 Test Report ⎯
Manufacturer ...........................................................: ⎯
Type .........................................................................: ⎯
Rated values ..........................................................: ⎯
Method of protection .................................................: ⎯
C.1/RD Overload test P
C.2/RD Insulation P
Protection from displacement of windings................: P

D/RD ANNEX D P
MEASURING INSTRUMENTS FOR TOUCH CURRENT TESTS (see 5.1.4/RD)
D.1/RD Measuring instrument N/A
D.2/RD Alternative measuring instrument P

E/RD ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13/RD) N/A

F/RD Annex F, Measurements of clearances and creep- P


age distance (see 2.10/RD and Annex G/RD)

G/RD ANNEX G, N/A


ALTERNATIVE METHOD FOR DETERMINING MINIMUM CLEARANCES
G.1/RD Clearances Not used N/A
G.1.1/RD General N/A
G.1.2/RD Summary of the procedure for determining mini- N/A
mum clearances

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 32 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

G.2/RD Determination of mains transient voltage (V) N/A


G.2.1/RD AC mains supply .....................................................: N/A
G.2.2/RD Earthed d.c. mains supplies ....................................: N/A
G.2.3/RD Unearthed d.c. mains supplies ................................: N/A
G.2.4/RD Battery operation .....................................................: N/A
G.3/RD Determination of telecommunication network tran- N/A
sient voltage (V) ......................................................:
G.4/RD Determination of required withstand voltage (V) N/A
G.4.1/RD Mains transients and internal repetitive peaks ........: N/A
G.4.2/RD Transients from telecommunication networks .........: N/A
G.4.3/RD Combination of transients N/A
G.4.4/RD Transients from cable distribution systems N/A
G.5/RD Measurement of transient voltages (V) N/A
a) Transients from a mains supply N/A
For an a.c. mains supply N/A
For a d.c. mains supply N/A
b) Transients from a telecommunication network N/A
G.6/RD Determination of minimum clearances ....................: N/A

H ANNEX H, N/A
GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER AND
FOREIGN OBJECTS (see IEC 60529)

I ANNEX I, BACKFEED PROTECTION TEST P


I.1 General See Appendix 8 for detail. P
I.2 Test for pluggable UPS P
I.3 Test for permanently connected UPS N/A
I.4 Load-induced change of reference potential Refer to appendices. P
I.5 Solid-state backfeed protection P
(see clause 7.1-7.5 of IEC 62040-2 and clause 7.1-
7.2 of IEC 62040-3)

J/RD ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6/RD) N/A


Metal(s) used ...........................................................: ⎯

K/RD ANNEX K, THERMAL CONTROLS (see 1.5.3/RD and 5.3.8/RD) N/A


K.1/RD Making and breaking capacity N/A
K.2 /RD Thermostat reliability; operating voltage (V) ............: N/A

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 33 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

K.3/RD Thermostat endurance test; operating voltage (V) ..: N/A


K.4/RD Temperature limiter endurance; operating voltage N/A
(V) ............................................................................:
K.5/RD Thermal cut-out reliability N/A
K.6/RD Stability of operation N/A

L ANNEX L, REFERENCE LOADS P


L.1 General P
L.2 Reference resistive load P
L.3 Reference inductive-resistive load ⎯
L.4 Reference capacitive-resistive loads N/A
L.5 Reference non-linear load N/A
L.5.1 Test method N/A
L.5.2 Connection of the non-linear reference load ⎯

M ANNEX M, VENTILATION OF BATTERY COMPARTMENTS P


M.1 General Refer to test data, none venti- P
lation batteries
M.2 Normal conditions P
M.3 Blocked conditions P
M.4 Overcharge conditions P

N ANNEX N, MINIMUM AND MAXIMUM CROSS-SECTIONS OF COPPER N/A


CONDUCTORS SUITABLE FOR CONNECTION (see 6.3)

U/RD ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED P


INSULATION (see 2.10.5.4/RD)

V/RD ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1/RD) P


V.1/RD Introduction P
V.2/RD TN power distribution systems P

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 34 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

4.5 TABLE: List of critical components


Object/part no. Manufacturer/ Type/model Technical data Standard Mark(s) of con-
1.
trademark formity
Printed Circuit Board Various Various V-0 UL 796 UL
UPS
Fan (490-1059) Kaimei JF0825B2SRAR 24Vdc, 0.17A, max. IEC/EN 60950-1 50029788 (TUV)
48.53 CFM
Appliance Inlet Rong Feng SS-3B 16A, 250Vac IEC/EN 60320-1 40013645 (VDE)
(770-0339)
ELCOM EMI-18 16A, 250Vac 40014433 (VDE)
Alternate – Input WECO Electri- 327-HDS 3P 600V 1924400-3335- UL, CSA,
Terminal Block (740- cal Connectors 0065 / 180170 40039779 (VDE)
0076A) Inc.
AC Output Socket ELCOM EMO-14 10A, 250Vac IEC/EN 60320-1 40005067 (VDE)
(770-0006-Z-001)
Alternate -Output MOLEX 39910-0103 3P 600V, 65A 1924400-3335- UL
Terminal Block 0065 / 180170
(740-0067-Z)
Internal Battery Con- Anderson SBS50 50A UL1977 E26226 (UL)
nector
Connector for exter- Anderson SBS75X 75A UL1977 E26226 (UL)
nal battery
Case of display -- -- HB min. UL746C UL
module
Main Board (640-3700x for 3KVA, 640-3699x for 2.2KVA)
Choke (L1200) for APC 420- Class B IEC 60950-1 Tested within
model SRT3000XLI, 2213XXXXXXXX equipment
SRT3000RMXLI XX
(420-2213-Z)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1200) for APC 420- Class B IEC 60950-1 Tested within
model SRT2200XLI, 2209XXXXXXXX equipment
SRT2200RMXLI XX
(420-2209-Z)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1206) (420- APC 420- Class B IEC 60950-1 Tested within
0006-Z) 0006XXXXXXXX equipment
XX
(X can be any al-
phanumeric, +, *,
#, _, - or blank)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 35 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

Choke (L1203) APC 420- Class B IEC 60950-1 Tested within


2214XXXXXXXX equipment
for model
XX
SRT3000XLI,
SRT3000RMXLI (X can be any al-
(420-2214-Z) phanumeric, +, *,
#, _, - or blank)
Choke (L1203) APC 420- Class B IEC 60950-1 Tested within
2210XXXXXXXX equipment
for model
XX
SRT2200XLI,
SRT2200RMXLI (X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1207) APC 420- Class B IEC 60950-1 Tested within
2215XXXXXXXX equipment
for model
XX
SRT3000XLI,
SRT3000RMXLI (X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1207) APC 420- Class B IEC 60950-1 Tested within
2211XXXXXXXX equipment
for model
XX
SRT2200XLI,
SRT2200RMXLI (X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1208) APC 420- Class B IEC 60950-1 Tested within
2202XXXXXXXX equipment
(420-2202-Z)
XX
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Choke (L1201, APC 422- Class B IEC 60950-1 Tested within
L1202) 0016XXXXXXXX equipment
XX
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Charger Transformer APC 433- Class B IEC 60950-1 Tested within
(T1204) 0136XXXXXXXX equipment
XX
for model
SRT3000XLI, (X can be any al-
SRT3000RMXLI phanumeric, +, *,
#, _, - or blank)
Charger Transformer APC 433- Class B IEC 60950-1 Tested within
(T1204) 0132XXXXXXXX equipment
XX
for model
SRT2200XLI, (X can be any al-
SRT2200RMXLI I phanumeric, +, *,
#, _, - or blank)
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 36 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

AUX Charger Trans- APC 433- Class B IEC 60950-1 Tested within
former (T1201) 0133XXXXXXXX equipment
SRT3000XLI, XX
SRT3000RMXLI
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
AUX Charger Trans- APC 433- Class B IEC 60950-1 Tested within
former (T1201) 0123XXXXXXXX equipment
SRT2200XLI, XX
SRT2200RMXL
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
DC to DC transform- APC 433- Class B IEC 60950-1 Tested within
er (T1203) 0135XXXXXXXX equipment
XX
SRT3000XLI,
SRT3000RMXLI (X can be any al-
phanumeric, +, *,
#, _, - or blank)
DC to DC transform- APC 433- Class B IEC 60950-1 Tested within
er (T1203) 0130XXXXXXXX equipment
XX
SRT2200XLI,
SRT2200RMXL (X can be any al-
phanumeric, +, *,
#, _, - or blank)
Current Sense APC 460-1003 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1200)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Current Sense APC 460-1032 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1201)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Current Sense APC 460-1006 Class B IEC 60950-1 Tested within
Transformer XXXXXXXXXX equipment
(CT1202)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Transformer (T1200) APC 430-7205 Class B IEC 60950-1 Tested within
XXXXXXXXXX equipment
(430-7205-Z)
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Backfeed Relay Song Chuan 832A-1A-F-C-H- 20A, 250Vac EN 61810-1 6615 (VDE)
(RY1205) 24VDC Coil 24 Vdc UL60947-1 E88991 (UL)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 37 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

(450-3005-Z) Omron G8P-1A4P-BG 20A, 250Vac EN 61810-1 400004714 (VDE


Coil 24 Vdc )
Backfeed Relay HASCO HAT901CSDC24- 30A, 240Vac EN 61810-1 R 50194653
(RY1206) 1-4K Coil 24 Vdc (TUV)
(450-0029-Z)
Relay (RY1204) SongChuan 894H-2AH1-F-S 8A, 240Vac EN 61810-1 40007827 (VDE)
(450-2151A-Z) Coil 24 Vdc
Relay (RY1202, SongChuan 832A-1A-F-C U29 30A, 250Vac UL60947-1 E88991 (UL)
RY1203) Coil 24 Vdc
(450-3006-Z)
OMRON G8P-1A4P-A04 30A, 250Vac UL60947-1 E41643 (UL)
Coil 24 Vdc
Relay (RY1200) HASCO HATF905ASDC2 50A, 28Vdc UL60947-1 E75887 (UL)
(450-3004-Z) 4 Coil 24 Vdc
Capacitor X2 CAMEL Tech- MPX series 250Vac min., 2.2uF IEC/EN 60384-14 136014 (VDE)
(C1226, C1227, nology
C1228)
(232-1225-Z-001) EPCOS Elec- B3292 Series 40005524,
tronic 40005536,
40010694,
40019254,
40021331
(VDE)
ARCOTRONIC R.46 V4413 (ENEC03)
S
Capacitor Y2 Murata KH 250Vac, 4700pF IEC/EN 60384-14 40002796 (VDE)
(C1239, C1240,
C1241, C1242, Apex NU 40023096
C1243, C1244, (VDE)
C1245, C1246)
(221-1502-Z)
MOV (MV1200) Panasonic V14681U 680V, 190J max. IEC/EN 61051 5912 (VDE)
(380-4200-Z)
Epcos S14K420 420V, 90J IEC/EN 61051 40027582 (VDE)
Thinking TVR14681 680V, 130J IEC/EN 61051 5944 (VDE)
MOV (MV1204A, MAIDA D65ZOV511RA19 510Vac, 470J IEC/EN 61051 40031393
MV1205A) 0 (VDE)
(380-0511-Z)
Fuse COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
(F1202, F1203) BUSSMANN
(512-0030-Z)
Fuse LITTELFUSE TE5 808 250Vac, 3A UL 248-14 E67006 (UL)
(F1204, F1205)
(513-0020-Z) COOPER PCB-3-R 250Vac, 3A UL 248-14 E19180 (UL)
BUSSMANN
Fuse (F1200) (513- BEL FUSE MRT 4 250Vac, 4A EN 60127-3 139937 (VDE)
0022-Z)
Schurter AG MST 250 250Vac, 4A EN 60127-3 40013529 (VDE)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 38 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

LITTELFUSE 372 250Vac, 4A EN 60127-3 097187 (VDE)

Fuse (F1201) COOPER GBH-V030A6F 500V , 30A UL 248-1 E19180 (UL)


(515-1030A-Z) BUSSMANN

LITTELFUSE 505030 500V , 30A UL 248-1 E10480 (UL)

DC LPS board (640-3708x)


Isolated Transformer APC 433- Class B IEC 60950-1 Tested within
(T701) 0129XXXXXXXX equipment
See attached
XX
(433-0129-Z) datasheet
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Diode (D709) -- -- 3A, 200V -- --
(330-3100-Z)
Diode (D710) -- -- 1A, 200V -- --
(339-0030-Z)
Inverter Driver Board
Transformer (T801, APC 4300516XXXXXX Class B IEC 60950-1 Tested within
T802, T803) XXXX equipment
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
SOG Board
Output Relay SongChuan 832A-1A-F-C 30A, 250Vac UL60947-1 UL (E88991)
(RY881, RY882) Coil 24 Vdc
(450-3006-Z) OMRON G8P-1A4P 30A, 250Vac UL60947-1 UL (E41643)
Coil 24 Vdc
PFC Driver Board (640-3711x)
Transformer (T831) APC 430- Class B IEC 60950-1 Tested within
5016XXXXXXXX equipment
(430-5016-Z)
XX
(X can be any al-
phanumeric, +, *,
#, _, - or blank)
Communication Board (640-6009x)
Optical Isolator Liteon LTV-817 Dti > 0.8 mm UL1577 40015248
(IC1715, IC1710, 5000V min. isolati- (VDE)
IEC/EN 60747-5-
IC1718) on E113898(UL)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 39 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

(349-0100-Z) FAIRCHILD FOD817B Dti > 1 mm 5 40026857


5000V min. isolati- (VDE)
on E90700 (UL)
ISOCOM ISP817X Dti > 0.6 mm 40028086
5000V min. isolati- (VDE)
on E91231(UL)
VISHAY SFH6156 Dti > 0.5 mm 91888(VDE)
5000V min. E52744(UL)
Isolation
EVERLIGHT EL816 Dti > 0.4 mm 132249(VDE)
5000V min. isolati- E214129(UL)
on
AVAGO Tech- HCPL-817 Dti > 0.4 mm 5000V 40016429 (VDE)
nologies min. isolation E55361(UL)

Optical Isolator ( AVAGO Tech- 6N137-360E (for Single channel, IEC/EN 60747-5- 40009430 (VDE)
IC1707, IC1708, nologies Tube) 1000V 5
IC1711, IC1712)
6N137-560E (for /us, 630V
(349-0137-Z-001) Tape and Reel)
Battery Pack
Fuse (F1, F2) COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
BUSSMANN
(512-0030-Z)
Battery CSB HR1221W 12V, 21W UL 1989 MH14533(UL)
(910-6003-001) B&B BP5-12 12V, 5Ah MH19884(UL)
Case LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)
(876-1046)
(876-1047)

Optional Battery Pack SRT72BP, SRT72RMBP, SRT96BP, SRT96RMBP


Front Bezel -- -- HB min. UL746C --
Shunt Board (640-9926x)
Fuse (F1, F2) COOPER MDA-V-R 125Vdc, 30A UL 248-14 E19180 (UL)
BUSSMANN
Fuse (F3) Conquer MET Series 250V, 2A UL 248-14 40017155 (VDE)
(513-0002-Z) COOPER SR-5-2A-AP 40020046 (VDE)
BUSSMANN
LITTELFUSE 372 097187 (VDE)
Transformer (T1) APC 430- Class B IEC 60950-1 Tested within
10056XXXXXXX equipment
(430-10056-Z) XXX
(X can be any al-
phanumeric, +, *,
#, _, - or blank)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 40 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

Battery Pack
Fuse (F1, F2) COOPER MDA-V-R 250Vac, 30A UL 248-14 E19180 (UL)
(512-0030-Z) BUSSMANN
Battery KUNG LONG WP5-12 12V, 5Ah UL 1989 MH16982 (UL)
(910-6003-001)
B&B BP5-12 12V, 5Ah MH19884(UL)
6 or 8 used *)
Case LG AF312A 5V, 2.1mm min. UL746C E67171 (UL)
(876-1046)
(876-1047)
1
) an asterisk indicates a mark which assures the agreed level of surveillance
*) Number of batteries: 6 for battery pack SRT72BP, SRT72RMBP or 8 for SRT96BP, SRT96RMBP

1
) an asterisk indicates a mark which assures the agreed level of surveillance

4.6, TABLE: Electrical data (in normal conditions) P


1.6.2/RD
U (V) I (A) Irated (A) P (W) Fuse # Ifuse (A) Condition/status

Refer to IEC 60950-1 Test Report (Appendix 3)

Supplementary information:

5.1.1 and TABLE: discharge of capacitors in the primary circuit P


2.1.1.7/RD
Condition τ calculated τ measured t u→ 0V Comments
(s) (s) (s)

Refer to IEC 60950-1 Test Report (Appendix 3)

Note(s):

5.2.1 and TABLE: SELV measurement (under normal conditions) P


2.2.2/RD
Transformer Location Voltage (max.) (V) Voltage Limitation Com-
ponent
V peak V d.c.

Refer to IEC 60950-1 Test Report (Appendix 3)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 41 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

Supplementary information:

5.2.1 and TABLE: SELV measurement (under fault conditions) P


2.2.3/RD
Location Voltage (max.) (V) Comments

Refer to IEC 60950-1 Test Report (Appendix 3)

Supplementary information:

5.2.3 and TABLE: Limited current circuit measurement N/A


2.4.2/RD
Location Voltage Current Freq. Limit Comments
(V) (mA) (kHz) (mA)

Refer to IEC 60950-1 Test Report (Appendix 3)

Supplementary information:

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 42 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

5.2.5 and TABLE: Limited power source measurement N/A


2.5/RD
Limits Measured Verdict
According to Table 2B/2C (normal condition)
current (in A)
apparent power (in VA)
According to Table 2B/2C (single fault condition)
current (in A)
apparent power (in VA)
Supplementary information:

5.3.1 and TABLE: Resistance of earthing measurement P


2.6.3.4/RD
Location Resistance measured (mΩ) Comments

refer to IEC 60950-1 Test Report

Supplementary information:

5.5 and TABLE: Abnormal operating and fault conditions P


8.3
Ambient temperature (°C) ....................................: ⎯
Power source for EUT: Manufacturer, model/type, ⎯
output rating ..........................................................:
Component Fault Supply Test Fuse # Fuse Observation
No. voltage time current
(V) (A)

refer to IEC 60950-1 Test Report

Supplementary information:

5.7 and TABLE: Working voltage measurement P


2.10.2/RD
Location RMS voltage (V) Peak voltage (V) Comments

refer to IEC 60950-1 Test Report

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 43 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

Supplementary information:

5.7 and TABLE: Clearance and creepage distance measurements P


2.10.4/RD
Clearance (cl) and creepage U peak U r.m.s. Required cl cl Required cr
distance (cr) at/of/between: (V) (V) (mm) (mm) cr (mm) (mm)
Functional:

Basic / supplementary:

Reinforced:

Supplementary information: refer to IEC 60950-1 Test Report


5.8, TABLE: Distance through insulation measurements P
2.1.1.3/RD
and
2.10.5.1/RD
Distance through insulation (DTI) at/of: U peak U r.m.s. Test volt- Required DTI
(V) (V) age DTI (mm)
(V) (mm)

refer to IEC 60950-1 Test Report

Supplementary information:

6, 8.2 and TABLE: Electric strength tests, impulse tests and voltage surge tests P
9
Test voltage applied between: Voltage shape Test voltage Breakdown
(AC, DC, im- (V) Yes / No
pulse, surge)
Functional:

Basic / supplementary:

Reinforced:

Supplementary information: refer to IEC 60950-1 Test Report

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 44 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

7.4, TABLE: Ball pressure test of thermoplastic parts P


4.5.5/RD
Allowed impression diameter (mm) .................. : ≤ 2 mm ⎯
Part Test temperature Impression diameter
(°C) (mm)

refer to IEC 60950-1 Test Report

Supplementary information:

7.4.2, TABLE: Enclosure opening measurements P


Location Size (mm) Comments

refer to IEC 60950-1 Test Report

Supplementary information:

7.5 TABLE: Resistance to fire P


Part Manufacturer of ma- Type of material Thickness Flammability Evidence
terial (mm) class

refer to IEC 60950-1 Test Report

Supplementary information:

7.7 TABLE: Temperature test P


Supply voltage (V) .......................... : ⎯
Ambient Tmin (°C) ............................ : ⎯
Ambient Tmax (°C) ............................ : ⎯
Maximum measured temperature T of part/at:: T (°C) Allowed
Tmax (°C)

Supplementary information: refer to IEC 60950-1 Test Report (Appendix 3)


Temperature T of winding: t1 (°C) R1 (Ω) t2 (°C) R2 (Ω) T (°C) Allowed Insulatio
Tmax (°C) n class

Supplementary information: refer to IEC 60950-1 Test Report (Appendix 3)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 45 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

8.1 TABLE: Earth leakage current P


Condition L→ terminal A N → terminal A Limit Comments
(mA) (mA) (mA)
SRT3000RMXLI
“e” opened, normal 2.8 1.8 3.5 --
“e” opened, 1.8 2.8 3.5 --
reverse
Secondary
Condition P2 (+) P2 (-) Limit Comments
→ terminal A → terminal A (mA)
(mA) (mA)
USB, “e” closed, 0.01 0.01 3.5 --
normal
USB, “e” closed, 0.01 0.01 3.5 --
reverse
J1706, “e” closed, 2.2 2.2 3.5 --
normal
J1706, “e” closed, 2.2 2.2 3.5 --
reverse
J1711, “e” closed, 0.01 0.01 0.25 --
normal
J1711, “e” closed, 0.01 0.01 0.25 --
reverse
SRT2200RMXLI
“e” opened, normal 2.2 1.3 3.5 --
“e” opened, 1.3 2.2 3.5 --
reverse
Secondary
Condition P2 (+) P2 (-) Limit Comments
→ terminal A → terminal A (mA)
(mA) (mA)
USB, “e” closed, 0.01 0.01 3.5 --
normal
USB, “e” closed, 0.01 0.01 3.5 --
reverse
J1706, “e” closed, 1.8 1.8 3.5 --
normal
J1706, “e” closed, 1.8 1.8 3.5 --
reverse
J1711, “e” closed, 0.01 0.01 0.25 --
normal

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 46 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

J1711, “e” closed, 0.01 0.01 0.25 --


reverse
Supplementary information:

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 47 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

C.2/RD TABLE: Safety isolation transformer P


Construction details: Isolation Transformer
Transformer part name:
Manufacturer: See appended table 4.3
Type: See appended table 4.3
Recurring peak voltage
Required clearance for reinforced
insulation (from table 2H and 2J)
Effective voltage rms
Required creepage distance for reinforced
insulation (from table 2L)
Measured min. creepage distance
Location inside (mm) outside (mm)

Measured min. clearances


Location inside (mm) outside (mm)

Construction:
Pin numbers
Prim.
Sec.
Bobbin
Material
Thickness
Electric strength test
With AC 3000V after humidity treatment
Result Pass
Supplementary information: Refer to IEC 60950-1 Test Report (Appendix 3)

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 48 of 81 VDE Report No. 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

M TABLE: Ventilation of battery compartments N/A


The required dimension for the ventilation openings will be calculated with the
following formula:
A > K1 * Q
with Q = (0.054 m³/Ah) * n * I * C
where:
K1 : constant factor of 28 h * cm²/m³
Q : airflow in m³/h
n : number of battery cells
I : constant factor (0,2A/100Ah for valve regulated lead acid batteries)
C : nominal capacity of the battery
With the specific data for the UPS the following dimension for the ventilation
openings is required:
n :?
C :?
A > 28 h * cm²/m³ * (0.054 m³/Ah) * n * 0.2 A/100 Ah * C
A > ? cm²
Verdict
The size of ventilation openings in battery cabinet exceeds the required airflow by
far (as well as the UPS).

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 49 of 81 VDE Report No.: 203983-AS3-1

IEC 62040
Clause Requirement – Test Result – Remark Verdict

TABLE: List of test equipment used P


Clause Measurement / Testing / measuring equipment / Range used Calibration
testing material used date

refer to IEC 60950-1 Test Report / Liste of test equipment used (Appendix 7)

Supplementary information:

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 50 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 1

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 51 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 52 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Battery Pack

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 53 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

PCB in Battery Pack

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 54 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 1

Battery pack - SRC72BP

Battery pack - SRC96BP

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 55 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

INPUT TEST: 1.6.2.101

METHOD A

A sample of each model indicated below was operated in the normal mode, and the input was
measured using suitable meters.

METHOD B

Same as Method A except the unit was operated in the recharge mode.

METHOD C

Same as Method A except the unit was operated in the Stored Energy Mode.

METHOD D

Same as Method A except the unit was operated in the bypass mode.

Engineer: Use the following for single-phase units.

RESULTS

INPUT

Rated Measured
AC 50 Hz
Remote
Model Method
Battery V (A) (kVA) (W) (P.F.)
V (A) W PF
V A
A 208 16 - - - - 208.2 14.3 2957/2924 0.99
B 208 16 - - - - 208.2 15.6 3240/3210 0.99
C - - - - 96 31.1 - - - -
SRT3000(
RM)XLW- - AC 60 Hz - - - - - -
IEC
A 208 16 - - - - 208.1 14.3 2950/2920 0.99
B 208 16 - - - - 208.1 15.5 3225/3210 0.99
C - - - - 96 30.9 - - - -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 56 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Rated Measured
AC 50 Hz Remote
Model Method
Battery V (A) (kVA) (W) (P.F.)
V (A) W PF
V A
A 240 20 - - - - 240.2 12.3 2945/2920 0.99
B 240 20 - - - - 240.4 13.5 3220/3180 0.99
C - - - - 96 31.0 - - - -
SRT3000(
RM)XLW- - AC 60 Hz - - - - - -
IEC
A 240 20 - - 106 2 240.2 12.2 2940/2900 0.99
B 240 20 - - 106 2 240.3 13.4 3226/3184 0.99
C - - - - 96 31.0 - - - -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 57 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

INPUT TEST (CONT’D): 1.6.2.101

OUTPUT
Rated (50Hz) Measured, AC
Model Method
V (A) (kVA) (W) (P.F.) V (A) (kVA) (W) (P.F.)

SRT3000(RM)XLW- A 208 14.4 3000/2700 0.9 206.8 14.6 3019/2717 0.9


IEC
B 208 14.4 3000/2700 0.9 206.9 14.5 3000/2700 0.9
C 208 14.4 3000/2700 0.9 206.7 14.7 3038/2735 0.9
- Rated (60Hz) - - - -
A 208 14.4 3000/2700 0.9 206.9 14.6 3020/2718 0.9
B 208 14.4 3000/2700 0.9 206.9 14.5 3000/2700 0.9
C 208 14.4 3000/2700 0.9 206.7 14.7 3038/2734 0.9

Rated (50Hz) Measured, AC


Model Method
V (A) (kVA) (W) (P.F.) V (A) (kVA) (W) (P.F.)

SRT3000(RM)XLW- A 240 12.5 3000/2700 0.9 238.6 12.7 3030/2729 0.9


IEC
B 240 12.5 3000/2700 0.9 238.8 12.6 3000/2700 0.9
C 240 12.5 3000/2700 0.9 238.9 12.6 3010/2710 0.9
- Rated (60Hz) - - - -
A 240 12.5 3000/2700 0.9 238.7 12.7 3030/2729 0.9
B 240 12.5 3000/2700 0.9 238.8 12.7 3032/2729 0.9
C 240 12.5 3000/2700 0.9 238.9 12.6 3010/2709 0.9

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 58 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

INPUT TEST (CONT’D): 1.6.2.101

The input current [was] [was not] more than 110 percent of rated value.

NOTES:

1. - Applicable only for remote battery supplies; V is the nominal voltage rating of battery supply; A is
the measured value of battery current during Stored Energy Mode when the battery voltage was
equal to the nominal voltage rating.

2. - Applicable only to units intended for connection to a 3-phase, 4-wire supply. A true rms amme-
ter was used.

p= phase;
p-p = phase-to-phase;
p-n = phase-to-neutral.

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 59 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

HEATING TEST: RD 4.5.1, 1.4.12, 1.4.13

The sample was connected as noted below and operated until temperatures became stable. Temper-
atures were measured using the thermocouple method.

[ ] Rise in temperature of windings of motors and transformers were additionally determined by the
change-of-resistance method.

[X] Before starting the Heating Test, each special non-detachable power supply cord connection was
pulled with a force of 5 N (1.12 lbs) for one minute. During the Heating Test, the temperature of its
connections were recorded. (Maximum 60°C rise per 3.3.2.)

The sample operated as follows:

Method Comments
A sample of each model indicated below was operated in the normal mode under the con-
A ditions described under OPERATING MODES AND CONDITIONS. Each unit was oper-
ated continuously under these conditions until temperatures stabilized.
Same as Method A except each unit was operated in the recharge mode until tempera-
B
tures peaked.
C Same as Method A except each unit was operated in the Stored Energy Mode.
D Same as Method A except each unit was operated in the bypass mode.

[ ] The concentration of hydrogen gas in the battery compartment was measured during the test - see
Battery Compartment Ventilation Test on following pages for method and results.
Tmra was __40___ °C.

Test Conditions:
Model Method Input V Input Hz or DC
SRT3000(RM)XLW-IEC A 187, 208,240,254.4 60
B 187, 208,240,254.4 60
C 96 DC
D 187, 208,240,254.4 60

Note: (#) - All the measured data has been normalized to ambient 40ºC.
Note: (@) - If 60 Hz in “Input Test” is the most severe operating condition, then please replace fre-
quency in 60 Hz for “Heating Test”.

HEATING TEST (CONT'D): RD 4.5.1, 1.4.12, 1.4.13

RESULTS

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 60 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2
Model SRT3000RMXLW-IEC, I/P: 187 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 41.2 53.6 41.2 55.8 39.2 52.2 -
2. C1226 49.1 61.5 50.4 65.0 42.1 55.1 85
3. C1211 41.1 53.5 41.2 55.8 39.6 52.6 85
4. C1227 57.0 69.4 59.8 74.4 58.3 71.3 85
5. L1200 coil 54.5 66.9 57.2 71.8 42.3 55.3 90
6. L1206 coil 63.7 76.1 67.6 82.2 52.9 65.9 90
7. PCB near Q1211 42.6 55.0 42.2 56.8 39.6 52.6 90
8. T1201 coil 46.2 58.6 44.4 59.0 40.7 53.7 90
9. T1201 core 44.9 57.3 44.4 59.0 41.1 54.1 90
10. CT1200 coil 60.3 72.7 62.6 77.2 56.0 69.0 90
11. CT1200 core 60.4 72.8 62.8 77.4 56.5 69.5 90
12. C1200 49.8 62.2 52.3 66.9 52.0 65.0 90
13. L1208 coil 61.6 74.0 63.8 78.4 59.1 72.1 90
14. RY1200 coil 49.8 62.2 49.4 64.0 64.7 77.7 90
15. PCB near IC1202 60.2 72.6 62.5 77.1 55.7 68.7 90
16. PCB near IC1203 55.4 67.8 57.9 72.5 44.7 57.7 90
17. T802 coil 33.0 45.4 34.7 49.3 36.1 49.1 90
18. Q1218 Heat-sink 66.4 78.8 68.8 83.4 67.8 80.8 90
19. L1203 coil 67.2 79.6 71.5 86.1 46.2 59.2 90
20. T701 coil 56.9 69.3 57.5 72.1 51.6 64.6 90
21. T701 core 57.0 69.4 57.6 72.2 51.4 64.4 90
22. L1207 coil 83.8 96.2 85.6 100.2 77.1 90.1 110
23. PCB near Q1223 51.0 63.4 52.8 67.4 43.1 56.1 90
24. PCB near Q1220 52.8 65.2 55.0 69.6 41.5 54.5 90
25. RY1202 coil 55.2 67.6 57.3 71.9 47.2 60.2 90
26. RY1203 coil 85.0 97.4 86.8 101.4 79.9 92.9 110
27. RY1204 coil 47.6 60.0 48.5 63.1 41.8 54.8 90
28. RY1205 coil 80.4 92.8 82.9 97.5 43.3 56.3 110
29. RY1206 coil 72.3 84.7 74.3 88.9 41.4 54.4 90
30. C1268 32.5 44.9 34.2 48.8 43.8 56.8 85
31. C1269 37.2 49.6 37.7 52.3 44.9 57.9 85
32. L1202 coil 32.8 45.2 34.5 49.1 50.8 63.8 90
33. L1201 coil 30.1 42.5 32.2 46.8 45.8 58.8 90
34. T1200 coil 31.0 43.4 34.3 48.9 28.8 41.8 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 61 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

35. D1229 Heat-sink 29.9 42.3 31.8 46.4 53.2 66.2 90


36. T1203 coil 29.9 42.3 43.8 58.4 63.3 76.3 90
37. T1203 core 31.6 44.0 48.1 62.7 73.0 86.0 90
38. T1204 coil 44.5 56.9 84.2 98.8 28.9 41.9 110
39. T1204 core 39.8 52.2 69.2 83.8 28.8 41.8 90
40. CT1201 coil 31.6 44.0 31.1 45.7 46.0 59.0 85
41. CT1201 core 32.4 44.8 32.0 46.6 46.8 59.8 85
42. C1208 30.0 42.4 29.4 44.0 38.3 51.3 85
43. Output wire (J239) 54.1 66.5 56.7 71.3 54.9 67.9 90
44. Battery wire (+) 45.9 58.3 48.3 62.9 49.4 62.4 105
45. Input wire (Line) 45.7 58.1 48.5 63.1 47.2 60.2 105
46. RY881 coil 86.0 98.4 88.1 102.7 87.1 100.1 110
47. RY882 coil 86.2 98.6 88.1 102.7 86.2 99.2 110
48. RY883 coil 90.9 103.3 93.2 107.8 89.4 102.4 110
49. Outlet wire (IEC C19) 47.8 60.2 49.8 64.4 48.5 61.5 90
50. Battery body 27.6 40.0 32.7 47.3 29.3 42.3 -
51. Enclosure outside near L1207 (UPS) 32.0 44.4 31.5 46.1 35.3 48.3 70
52. PCB near J7 (Battery Pack) 28.5 40.9 29.1 43.7 27.6 40.6 90
53. PCB near J9 (Battery Pack) 29.4 41.8 30.2 44.8 27.5 40.5 90
54. PCB near J11 (Battery Pack) 28.5 40.9 29.3 43.9 27.6 40.6 90
55. T1 coil (Battery Pack) 45.6 58.0 46.3 60.9 27.2 40.2 90
56. T1 core (Battery Pack) 44.8 57.2 45.4 60.0 27.2 40.2 90
57. Battery body (Battery Pack) 26.0 38.4 33.4 48.0 27.3 40.3 -
58. Enclosure outside near PCB (Battery
27.5 39.9 27.5 42.1 27.3 40.3 70
Pack)
59. Battery wire (+) (Battery Pack) 29.0 41.4 28.8 43.4 28.0 41.0 105
60. Ambient 27.6 40.0 25.4 40.0 27.0 40.0 -
Test duration, h: min: sec 3:23:00 13:35:00 03:03:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 62 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000RMXLW-IEC, I/P: 208 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 40.6 52.2 41.9 53.3 37.5 49.6 -
2. C1226 47.5 59.1 49.9 61.3 41.1 53.2 85
3. C1211 40.4 52.0 41.7 53.1 37.9 50.0 85
4. C1227 57.2 68.8 61.7 73.1 56.7 68.8 85
5. L1200 coil 51.8 63.4 55.4 66.8 42.2 54.3 90
6. L1206 coil 61.9 73.5 66.7 78.1 51.1 63.2 90
7. PCB near Q1211 41.6 53.2 42.9 54.3 37.9 50.0 90
8. T1201 coil 43.5 55.1 45.0 56.4 38.9 51.0 90
9. T1201 core 43.2 54.8 44.7 56.1 39.2 51.3 90
10. CT1200 coil 59.5 71.1 63.2 74.6 54.2 66.3 90
11. CT1200 core 59.7 71.3 63.5 74.9 54.7 66.8 90
12. C1200 50.0 61.6 54.0 65.4 50.4 62.5 90
13. L1208 coil 61.0 72.6 64.6 76.0 57.2 69.3 90
14. RY1200 coil 50.4 62.0 50.9 62.3 62.2 74.3 90
15. PCB near IC1202 59.3 70.9 62.9 74.3 54.0 66.1 90
16. PCB near IC1203 53.2 64.8 56.5 67.9 44.3 56.4 90
17. T802 coil 33.6 45.2 36.6 48.0 34.8 46.9 90
18. Q1218 Heat-sink 66.5 78.1 70.9 82.3 66.5 78.6 90
19. L1203 coil 63.2 74.8 68.2 79.6 50.1 62.2 90
20. T701 coil 55.8 67.4 57.7 69.1 49.6 61.7 90
21. T701 core 55.8 67.4 57.6 69.0 49.7 61.8 90
22. L1207 coil 83.4 95.0 86.9 98.3 77.3 89.4 110
23. PCB near Q1223 48.7 60.3 51.5 62.9 40.6 52.7 90
24. PCB near Q1220 49.8 61.4 53.3 64.7 39.3 51.4 90
25. RY1202 coil 53.5 65.1 56.9 68.3 47.9 60.0 90
26. RY1203 coil 83.9 95.5 87.1 98.5 78.2 90.3 110
27. RY1204 coil 46.3 57.9 48.3 59.7 41.7 53.8 90
28. RY1205 coil 78.0 89.6 81.3 92.7 47.5 59.6 110
29. RY1206 coil 70.2 81.8 72.8 84.2 43.6 55.7 90
30. C1268 32.8 44.4 34.4 45.8 41.5 53.6 85
31. C1269 36.8 48.4 38.0 49.4 42.7 54.8 85
32. L1202 coil 33.3 44.9 36.3 47.7 47.2 59.3 90
33. L1201 coil 30.7 42.3 34.0 45.4 42.7 54.8 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 63 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 31.8 43.4 36.9 48.3 27.8 39.9 90


35. D1229 Heat-sink 30.5 42.1 33.5 44.9 49.2 61.3 90
36. T1203 coil 30.2 41.8 36.1 47.5 60.2 72.3 90
37. T1203 core 31.6 43.2 39.4 50.8 69.4 81.5 90
38. T1204 coil 48.5 60.1 86.4 97.8 31.8 43.9 110
39. T1204 core 42.1 53.7 72.1 83.5 31.5 43.6 90
40. CT1201 coil 31.9 43.5 32.4 43.8 42.3 54.4 85
41. CT1201 core 32.6 44.2 33.3 44.7 43.7 55.8 85
42. C1208 30.5 42.1 30.9 42.3 36.3 48.4 85
43. Output wire (J239) 54.1 65.7 58.1 69.5 53.2 65.3 90
44. Battery wire (+) 46.2 57.8 50.6 62.0 48.2 60.3 105
45. Input wire (Line) 47.1 58.7 51.0 62.4 48.5 60.6 105
46. RY881 coil 85.7 97.3 89.2 100.6 86.0 98.1 110
47. RY882 coil 86.0 97.6 89.6 101.0 85.1 97.2 110
48. RY883 coil 90.9 102.5 94.4 105.8 88.4 100.5 110
49. Outlet wire (IEC C19) 48.9 60.5 51.5 62.9 46.5 58.6 90
50. Battery body 28.2 39.8 35.2 46.6 28.6 40.7 -
51. Enclosure outside near L1207 (UPS) 32.4 44.0 34.0 45.4 34.3 46.4 70
52. PCB near J7 (Battery Pack) 29.6 41.2 31.5 42.9 29.0 41.1 90
53. PCB near J9 (Battery Pack) 30.6 42.2 32.6 44.0 29.9 42.0 90
54. PCB near J11 (Battery Pack) 29.6 41.2 31.7 43.1 29.0 41.1 90
55. T1 coil (Battery Pack) 46.9 58.5 49.6 61.0 39.1 51.2 90
56. T1 core (Battery Pack) 46.1 57.7 48.6 60.0 39.1 51.2 90
57. Battery body (Battery Pack) 27.9 39.5 36.9 48.3 27.9 40.0 -
58. Enclosure outside near PCB (Battery
28.6 40.2 29.6 41.0 28.1 40.2 70
Pack)
59. Battery wire (+) (Battery Pack) 29.7 41.3 30.9 42.3 28.9 41.0 105
60. Ambient 28.4 40.0 28.6 40.0 27.9 40.0 -
Test duration, h: min: sec 04:18:00 15:03:00 03:45:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 64 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000RMXLW-IEC, Input: 240 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 38.9 51.4 38.0 51.5 38.3 50.8 -
2. C1226 44.2 56.7 44.2 57.7 40.9 53.4 85
3. C1211 38.4 50.9 37.5 51.0 38.7 51.2 85
4. C1227 51.4 63.9 53.6 67.1 52.3 64.8 85
5. L1200 coil 47.2 59.7 48.2 61.7 41.5 54.0 90
6. L1206 coil 54.4 66.9 57.0 70.5 48.7 61.2 90
7. PCB near Q1211 40.6 53.1 39.7 53.2 38.7 51.2 90
8. T1201 coil 45.3 57.8 44.4 57.9 39.8 52.3 90
9. T1201 core 42.3 54.8 41.6 55.1 40.1 52.6 90
10. CT1200 coil 53.2 65.7 54.7 68.2 51.2 63.7 90
11. CT1200 core 53.3 65.8 54.9 68.4 51.5 64.0 90
12. C1200 45.6 58.1 47.6 61.1 47.7 60.2 90
13. L1208 coil 54.3 66.8 55.9 69.4 53.3 65.8 90
14. RY1200 coil 49.2 61.7 48.0 61.5 64.1 76.6 90
15. PCB near IC1202 52.6 65.1 53.9 67.4 50.7 63.2 90
16. PCB near IC1203 48.1 60.6 48.9 62.4 42.8 55.3 90
17. T802 coil 32.3 44.8 33.4 46.9 34.9 47.4 90
18. Q1218 Heat-sink 58.2 70.7 60.1 73.6 59.2 71.7 90
19. L1203 coil 55.3 67.8 57.1 70.6 47.4 59.9 90
20. T701 coil 52.6 65.1 52.1 65.6 50.6 63.1 90
21. T701 core 52.5 65.0 52.2 65.7 50.6 63.1 90
22. L1207 coil 70.0 82.5 71.1 84.6 66.8 79.3 110
23. PCB near Q1223 44.2 56.7 44.2 57.7 42.1 54.6 90
24. PCB near Q1220 45.3 57.8 45.4 58.9 40.4 52.9 90
25. RY1202 coil 48.6 61.1 49.6 63.1 45.6 58.1 90
26. RY1203 coil 78.2 90.7 79.3 92.8 76.2 88.7 110
27. RY1204 coil 43.1 55.6 42.8 56.3 40.7 53.2 90
28. RY1205 coil 73.8 86.3 74.6 88.1 48.2 60.7 110
29. RY1206 coil 66.5 79.0 67.0 80.5 44.4 56.9 90
30. C1268 30.9 43.4 33.3 46.8 42.7 55.2 85
31. C1269 34.2 46.7 34.8 48.3 43.7 56.2 85
32. L1202 coil 31.7 44.2 33.0 46.5 49.1 61.6 90
33. L1201 coil 29.6 42.1 31.2 44.7 44.5 57.0 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 65 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 30.9 43.4 34.2 47.7 28.3 40.8 90


35. D1229 Heat-sink 29.3 41.8 32.2 45.7 51.9 64.4 90
36. T1203 coil 29.1 41.6 38.7 52.2 62.3 74.8 90
37. T1203 core 30.3 42.8 39.3 52.8 71.9 84.4 90
38. T1204 coil 44.7 57.2 83.4 96.9 33.5 46.0 110
39. T1204 core 40.2 52.7 69.2 82.7 33.0 45.5 90
40. CT1201 coil 30.4 42.9 30.8 44.3 44.9 57.4 85
41. CT1201 core 30.9 43.4 31.1 44.6 45.7 58.2 85
42. C1208 29.2 41.7 28.3 41.8 37.6 50.1 85
43. Output wire (J239) 48.8 61.3 50.6 64.1 49.7 62.2 90
44. Battery wire (+) 41.8 54.3 44.0 57.5 44.5 57.0 105
45. Input wire (Line) 41.6 54.1 43.9 57.4 44.1 56.6 105
46. RY881 coil 82.2 94.7 83.4 96.9 83.3 95.8 110
47. RY882 coil 83.8 96.3 84.8 98.3 83.7 96.2 110
48. RY883 coil 87.2 99.7 88.6 102.1 86.1 98.6 110
49. Outlet wire (IEC C19) 44.0 56.5 45.4 58.9 44.4 56.9 90
50. Battery body 28.6 41.1 32.1 45.6 28.8 41.3 -
51. Enclosure outside near L1207 (UPS) 30.7 43.2 29.8 43.3 34.3 46.8 70
52. PCB near J7 (Battery Pack) 29.0 41.5 28.5 42.0 28.7 41.2 90
53. PCB near J9 (Battery Pack) 30.1 42.6 29.7 43.2 29.7 42.2 90
54. PCB near J11 (Battery Pack) 29.0 41.5 28.7 42.2 28.6 41.1 90
55. T1 coil (Battery Pack) 46.4 58.9 46.0 59.5 41.7 54.2 90
56. T1 core (Battery Pack) 45.6 58.1 45.2 58.7 41.6 54.1 90
57. Battery body (Battery Pack) 27.5 40.0 32.8 46.3 27.6 40.1 -
58. Enclosure outside near PCB (Battery
27.8 40.3 26.5 40.0 28.6 41.1 70
Pack)
59. Battery wire (+) (Battery Pack) 28.7 41.2 27.3 40.8 28.1 40.6 105
60. Ambient 27.5 40.0 26.5 40.0 27.5 40.0 -
Test duration, h: min: sec 03:45:00 14:16:00 03:56:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 66 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000RMXLW-IEC, Input: 254.4 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 39.0 51.1 41.4 52.9 39.3 51.1 -
2. C1226 43.5 55.6 46.8 58.3 42.0 53.8 85
3. C1211 38.3 50.4 40.6 52.1 39.8 51.6 85
4. C1227 51.0 63.1 56.3 67.8 53.4 65.2 85
5. L1200 coil 46.2 58.3 50.3 61.8 43.8 55.6 90
6. L1206 coil 53.4 65.5 58.9 70.4 49.8 61.6 90
7. PCB near Q1211 42.3 54.4 44.8 56.3 41.6 53.4 90
8. T1201 coil 50.4 62.5 53.8 65.3 49.4 61.2 90
9. T1201 core 44.1 56.2 47.1 58.6 42.6 54.4 90
10. CT1200 coil 52.6 64.7 57.2 68.7 52.3 64.1 90
11. CT1200 core 52.8 64.9 57.5 69.0 52.6 64.4 90
12. C1200 45.4 57.5 50.4 61.9 48.8 60.6 90
13. L1208 coil 53.7 65.8 58.4 69.9 54.5 66.3 90
14. RY1200 coil 49.1 61.2 50.5 62.0 65.2 77.0 90
15. PCB near IC1202 51.8 63.9 56.3 67.8 51.8 63.6 90
16. PCB near IC1203 47.0 59.1 50.8 62.3 44.2 56.0 90
17. T802 coil 32.2 44.3 36.2 47.7 35.9 47.7 90
18. Q1218 Heat-sink 57.8 69.9 63.0 74.5 60.4 72.2 90
19. L1203 coil 53.3 65.4 58.3 69.8 49.2 61.0 90
20. T701 coil 51.7 63.8 54.3 65.8 51.6 63.4 90
21. T701 core 51.8 63.9 54.4 65.9 51.5 63.3 90
22. L1207 coil 69.4 81.5 74.3 85.8 68.1 79.9 110
23. PCB near Q1223 43.0 55.1 46.4 57.9 43.1 54.9 90
24. PCB near Q1220 44.0 56.1 48.0 59.5 41.5 53.3 90
25. RY1202 coil 47.8 59.9 51.9 63.4 46.3 58.1 90
26. RY1203 coil 77.6 89.7 81.6 93.1 77.0 88.8 110
27. RY1204 coil 42.4 54.5 45.4 56.9 41.7 53.5 90
28. RY1205 coil 72.9 85.0 76.7 88.2 69.0 80.8 110
29. RY1206 coil 65.9 78.0 69.0 80.5 61.8 73.6 90
30. C1268 30.7 42.8 33.4 44.9 43.8 55.6 85
31. C1269 33.6 45.7 35.9 47.4 44.8 56.6 85
32. L1202 coil 31.6 43.7 35.8 47.3 50.0 61.8 90
33. L1201 coil 29.6 41.7 34.1 45.6 45.4 57.2 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 67 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 30.9 43.0 36.9 48.4 30.8 42.6 90


35. D1229 Heat-sink 29.3 41.4 33.5 45.0 53.1 64.9 90
36. T1203 coil 28.8 40.9 38.8 50.3 62.9 74.7 90
37. T1203 core 29.9 42.0 40.2 51.7 72.7 84.5 90
38. T1204 coil 44.5 56.6 86.1 97.6 49.4 61.2 110
39. T1204 core 40.1 52.2 71.6 83.1 42.3 54.1 90
40. CT1201 coil 30.2 42.3 31.8 43.3 46.0 57.8 85
41. CT1201 core 30.8 42.9 32.4 43.9 46.9 58.7 85
42. C1208 29.1 41.2 30.5 42.0 38.9 50.7 85
43. Output wire (J239) 48.5 60.6 53.5 65.0 50.9 62.7 90
44. Battery wire (+) 41.7 53.8 47.1 58.6 45.8 57.6 105
45. Input wire (Line) 41.2 53.3 46.6 58.1 44.7 56.5 105
46. RY881 coil 82.1 94.2 86.0 97.5 84.1 95.9 110
47. RY882 coil 83.6 95.7 87.3 98.8 84.5 96.3 110
48. RY883 coil 87.3 99.4 91.1 102.6 87.0 98.8 110
49. Outlet wire (IEC C19) 44.0 56.1 48.2 59.7 45.5 57.3 90
50. Battery body 27.9 40.0 33.8 45.3 29.0 40.8 90
51. Enclosure outside near L1207 (UPS) 30.7 42.8 33.2 44.7 35.8 47.6 70
52. PCB near J7 (Battery Pack) 28.4 40.5 31.7 43.2 28.2 40.0 90
53. PCB near J9 (Battery Pack) 29.4 41.5 32.8 44.3 29.6 41.4 90
54. PCB near J11 (Battery Pack) 28.4 40.5 31.8 43.3 28.5 40.3 90
55. T1 coil (Battery Pack) 45.7 57.8 48.8 60.3 45.4 57.2 90
56. T1 core (Battery Pack) 44.9 57.0 48.0 59.5 44.6 56.4 90
57. Battery body (Battery Pack) 26.7 38.8 35.4 46.9 27.4 39.2 60
58. Enclosure outside near PCB (Battery
27.4 39.5 29.7 41.2 28.0 39.8 70
Pack)
59. Battery wire (+) (Battery Pack) 28.2 40.3 30.7 42.2 28.6 40.4 105
60. Ambient 27.9 40.0 28.5 40.0 28.2 40.0 -
Test duration, h: min: sec 04:25:00 15:16:00 03:14:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 68 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000XLW-IEC, Input: 187.2 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 38.9 53.6 40.8 55.6 39.2 53.7 -
2. C1226 47.8 62.5 51.4 66.2 47.6 62.1 85
3. C1211 39.0 53.7 41.0 55.8 39.0 53.5 85
4. C1227 56.6 71.3 61.1 75.9 57.7 72.2 85
5. L1200 coil 52.8 67.5 58.0 72.8 51.1 65.6 90
6. L1206 coil 62.8 77.5 68.9 83.7 60.1 74.6 90
7. PCB near Q1211 40.1 54.8 42.1 56.9 40.4 54.9 90
8. T1201 coil 42.0 56.7 44.4 59.2 42.1 56.6 90
9. T1201 core 42.0 56.7 44.4 59.2 41.6 56.1 90
10. CT1200 coil 58.8 73.5 63.4 78.2 57.5 72.0 90
11. CT1200 core 58.9 73.6 63.6 78.4 57.6 72.1 90
12. C1200 48.3 63.0 52.8 67.6 50.5 65.0 90
13. L1208 coil 60.5 75.2 65.1 79.9 59.4 73.9 90
14. RY1200 coil 48.2 62.9 48.9 63.7 62.5 77.0 90
15. PCB near IC1202 58.4 73.1 63.2 78.0 57.1 71.6 90
16. PCB near IC1203 53.4 68.1 58.2 73.0 52.1 66.6 90
17. T802 coil 31.6 46.3 35.1 49.9 34.4 48.9 90
18. Q1218 Heat-sink 65.1 79.8 69.9 84.7 66.3 80.8 90
19. L1203 coil 65.5 80.2 72.3 87.1 63.1 77.6 90
20. T701 coil 55.1 69.8 57.7 72.5 54.9 69.4 90
21. T701 core 55.2 69.9 57.8 72.6 54.9 69.4 90
22. L1207 coil 82.3 97.0 86.7 101.5 76.5 91.0 110
23. PCB near Q1223 48.9 63.6 52.9 67.7 45.2 59.7 90
24. PCB near Q1220 50.8 65.5 55.4 70.2 46.5 61.0 90
25. RY1202 coil 53.2 67.9 57.5 72.3 53.1 67.6 90
26. RY1203 coil 83.3 98.0 87.3 102.1 83.2 97.7 110
27. RY1204 coil 45.7 60.4 48.8 63.6 45.7 60.2 90
28. RY1205 coil 79.0 93.7 83.5 98.3 79.0 93.5 110
29. RY1206 coil 70.7 85.4 74.7 89.5 70.3 84.8 90
30. C1268 30.9 45.6 35.2 50.0 41.1 55.6 85
31. C1269 35.6 50.3 37.3 52.1 42.5 57.0 85
32. L1202 coil 31.5 46.2 35.6 50.4 49.6 64.1 90
33. L1201 coil 28.8 43.5 33.1 47.9 45.1 59.6 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 69 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 30.2 44.9 37.0 51.8 30.6 45.1 90


35. D1229 Heat-sink 28.4 43.1 33.0 47.8 50.6 65.1 90
36. T1203 coil 28.2 42.9 40.6 55.4 59.7 74.2 90
37. T1203 core 30.1 44.8 41.5 56.3 70.0 84.5 90
38. T1204 coil 44.0 58.7 86.7 101.5 44.1 58.6 110
39. T1204 core 39.1 53.8 71.8 86.6 39.4 53.9 90
40. CT1201 coil 29.7 44.4 33.8 48.6 43.9 58.4 85
41. CT1201 core 30.6 45.3 33.9 48.7 45.0 59.5 85
42. C1208 28.2 42.9 32.0 46.8 36.3 50.8 85
43. Output wire (J239) 52.4 67.1 57.1 71.9 52.9 67.4 90
44. Battery wire (+) 41.5 56.2 45.4 60.2 44.9 59.4 105
45. Input wire (Line) 48.0 62.7 53.4 68.2 49.7 64.2 105
46. RY881 coil 84.8 99.5 88.3 103.1 84.7 99.2 110
47. RY882 coil 82.4 97.1 85.6 100.4 82.5 97.0 110
48. RY883 coil 89.2 103.9 92.5 107.3 88.6 103.1 110
49. Outlet wire (IEC C19) 46.1 60.8 49.8 64.6 45.8 60.3 90
50. Battery body 27.1 41.8 32.4 47.2 27.9 42.4 90
51. Enclosure outside near L1207 (UPS) 30.0 44.7 31.6 46.4 33.6 48.1 70
52. PCB near J7 (Battery Pack) 32.9 47.6 35.5 50.3 33.1 47.6 90
53. PCB near J9 (Battery Pack) 34.1 48.8 36.8 51.6 34.7 49.2 90
54. PCB near J11 (Battery Pack) 33.2 47.9 36.1 50.9 33.9 48.4 90
55. T1 coil (Battery Pack) 49.1 63.8 51.3 66.1 49.1 63.6 90
56. T1 core (Battery Pack) 48.5 63.2 50.5 65.3 48.5 63.0 90
57. Battery body (Battery Pack) 27.3 42.0 34.9 49.7 28.8 43.3 60
58. Enclosure outside near PCB (Battery
28.1 42.8 29.6 44.4 28.2 42.7 70
Pack)
59. Battery wire (+) (Battery Pack) 30.5 45.2 32.2 47.0 31.6 46.1 105
60. Ambient 25.3 40.0 25.2 40.0 25.5 40.0 -
Test duration, h: min: sec 05:52:00 17:57:00 03:04:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 70 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000XLW-IEC, Input: 208 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 39.1 51.6 42.9 52.3 38.3 50.9 -
2. C1226 47.0 59.5 51.4 60.8 45.9 58.5 85
3. C1211 39.0 51.5 42.8 52.2 38.3 50.9 85
4. C1227 56.6 69.1 62.2 71.6 58.1 70.7 85
5. L1200 coil 51.1 63.6 56.7 66.1 48.1 60.7 90
6. L1206 coil 61.4 73.9 68.1 77.5 56.8 69.4 90
7. PCB near Q1211 40.1 52.6 43.9 53.3 39.4 52.0 90
8. T1201 coil 41.9 54.4 45.7 55.1 40.9 53.5 90
9. T1201 core 41.6 54.1 45.5 54.9 40.4 53.0 90
10. CT1200 coil 58.6 71.1 64.1 73.5 57.4 70.0 90
11. CT1200 core 58.8 71.3 64.4 73.8 57.6 70.2 90
12. C1200 48.7 61.2 54.3 63.7 51.0 63.6 90
13. L1208 coil 60.6 73.1 66.1 75.5 59.3 71.9 90
14. RY1200 coil 48.8 61.3 52.0 61.4 63.4 76.0 90
15. PCB near IC1202 58.1 70.6 63.5 72.9 56.6 69.2 90
16. PCB near IC1203 51.8 64.3 57.2 66.6 49.8 62.4 90
17. T802 coil 32.6 45.1 37.3 46.7 35.1 47.7 90
18. Q1218 Heat-sink 65.6 78.1 71.3 80.7 66.9 79.5 90
19. L1203 coil 62.3 74.8 68.9 78.3 58.5 71.1 90
20. T701 coil 54.2 66.7 58.2 67.6 53.2 65.8 90
21. T701 core 54.3 66.8 58.2 67.6 53.2 65.8 90
22. L1207 coil 82.6 95.1 87.6 97.0 78.4 91.0 110
23. PCB near Q1223 47.3 59.8 52.2 61.6 41.6 54.2 90
24. PCB near Q1220 49.1 61.6 54.5 63.9 42.6 55.2 90
25. RY1202 coil 52.1 64.6 57.5 66.9 51.5 64.1 90
26. RY1203 coil 82.6 95.1 87.5 96.9 81.8 94.4 110
27. RY1204 coil 44.8 57.3 49.2 58.6 44.3 56.9 90
28. RY1205 coil 77.0 89.5 82.3 91.7 68.6 81.2 110
29. RY1206 coil 69.1 81.6 74.0 83.4 61.6 74.2 90
30. C1268 31.2 43.7 34.7 44.1 41.6 54.2 85
31. C1269 35.2 47.7 38.8 48.2 43.1 55.7 85
32. L1202 coil 32.3 44.8 37.8 47.2 50.2 62.8 90
33. L1201 coil 29.7 42.2 35.7 45.1 45.7 58.3 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 71 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 31.7 44.2 39.1 48.5 28.9 41.5 90


35. D1229 Heat-sink 29.1 41.6 34.7 44.1 51.3 63.9 90
36. T1203 coil 28.8 41.3 35.8 45.2 60.6 73.2 90
37. T1203 core 30.5 43.0 36.3 45.7 70.9 83.5 90
38. T1204 coil 45.3 57.8 88.3 97.7 40.5 53.1 110
39. T1204 core 40.8 53.3 73.9 83.3 37.3 49.9 90
40. CT1201 coil 30.3 42.8 33.9 43.3 45.1 57.7 85
41. CT1201 core 31.2 43.7 34.9 44.3 46.1 58.7 85
42. C1208 28.9 41.4 32.4 41.8 37.3 49.9 85
43. Output wire (J239) 52.7 65.2 58.5 67.9 53.7 66.3 90
44. Battery wire (+) 41.7 54.2 47.5 56.9 45.3 57.9 105
45. Input wire (Line) 48.3 60.8 55.5 64.9 50.9 63.5 105
46. RY881 coil 85.5 98.0 90.3 99.7 85.3 97.9 110
47. RY882 coil 83.3 95.8 87.2 96.6 83.0 95.6 110
48. RY883 coil 90.2 102.7 93.9 103.3 89.4 102.0 110
49. Outlet wire (IEC C19) 47.2 59.7 52.0 61.4 46.7 59.3 90
50. Battery body 30.0 42.5 33.8 43.2 29.1 41.7 90
51. Enclosure outside near L1207 (UPS) 30.7 43.2 34.5 43.9 34.7 47.3 70
52. PCB near J7 (Battery Pack) 34.0 46.5 37.4 46.8 33.7 46.3 90
53. PCB near J9 (Battery Pack) 35.3 47.8 38.7 48.1 35.5 48.1 90
54. PCB near J11 (Battery Pack) 34.4 46.9 37.8 47.2 34.6 47.2 90
55. T1 coil (Battery Pack) 50.5 63.0 53.5 62.9 49.9 62.5 90
56. T1 core (Battery Pack) 49.8 62.3 52.9 62.3 49.3 61.9 90
57. Battery body (Battery Pack) 30.3 42.8 35.7 45.1 30.3 42.9 60
58. Enclosure outside near PCB (Battery
29.6 42.1 32.5 41.9 28.8 41.4 70
Pack)
59. Battery wire (+) (Battery Pack) 31.0 43.5 34.3 43.7 31.7 44.3 105
60. Ambient 27.5 40.0 30.6 40.0 27.4 40.0 -
Test duration, h: min: sec 04:03:00 14:32:00 03:31:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 72 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000XLW-IEC, Input: 240 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 41.2 52.7 39.9 52.9 38.3 50.6 -
2. C1226 48.2 59.7 46.7 59.7 41.1 53.4 85
3. C1211 40.6 52.1 39.5 52.5 38.9 51.2 85
4. C1227 56.6 68.1 55.9 68.9 53.5 65.8 85
5. L1200 coil 50.7 62.2 50.5 63.5 41.1 53.4 90
6. L1206 coil 59.4 70.9 59.6 72.6 49.9 62.2 90
7. PCB near Q1211 42.1 53.6 41.9 54.9 38.8 51.1 90
8. T1201 coil 46.1 57.6 47.1 60.1 39.9 52.2 90
9. T1201 core 43.0 54.5 43.9 56.9 40.3 52.6 90
10. CT1200 coil 58.9 70.4 57.1 70.1 52.0 64.3 90
11. CT1200 core 58.9 70.4 57.3 70.3 52.3 64.6 90
12. C1200 50.4 61.9 49.8 62.8 48.5 60.8 90
13. L1208 coil 61.1 72.6 58.6 71.6 54.4 66.7 90
14. RY1200 coil 50.3 61.8 49.3 62.3 63.8 76.1 90
15. PCB near IC1202 58.6 70.1 56.1 69.1 51.2 63.5 90
16. PCB near IC1203 52.3 63.8 50.8 63.8 42.9 55.2 90
17. T802 coil 34.9 46.4 35.5 48.5 35.4 47.7 90
18. Q1218 Heat-sink 64.1 75.6 62.6 75.6 59.8 72.1 90
19. L1203 coil 61.0 72.5 59.2 72.2 45.2 57.5 90
20. T701 coil 55.3 66.8 53.7 66.7 50.7 63.0 90
21. T701 core 55.2 66.7 53.8 66.8 50.6 62.9 90
22. L1207 coil 76.6 88.1 73.8 86.8 67.9 80.2 110
23. PCB near Q1223 44.8 56.3 46.3 59.3 42.1 54.4 90
24. PCB near Q1220 46.5 58.0 48.2 61.2 40.7 53.0 90
25. RY1202 coil 53.7 65.2 51.4 64.4 44.9 57.2 90
26. RY1203 coil 84.3 95.8 81.0 94.0 76.1 88.4 110
27. RY1204 coil 46.4 57.9 44.9 57.9 40.8 53.1 90
28. RY1205 coil 76.8 88.3 76.5 89.5 47.0 59.3 110
29. RY1206 coil 68.2 79.7 69.2 82.2 43.4 55.7 90
30. C1268 32.7 44.2 35.8 48.8 42.1 54.4 85
31. C1269 36.7 48.2 37.4 50.4 43.5 55.8 85
32. L1202 coil 34.1 45.6 35.6 48.6 50.4 62.7 90
33. L1201 coil 31.3 42.8 33.8 46.8 46.3 58.6 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 73 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 32.9 44.4 38.1 51.1 28.8 41.1 90


35. D1229 Heat-sink 30.8 42.3 34.0 47.0 51.9 64.2 90
36. T1203 coil 30.7 42.2 41.0 54.0 61.2 73.5 90
37. T1203 core 32.3 43.8 41.9 54.9 71.7 84.0 90
38. T1204 coil 46.3 57.8 87.3 100.3 34.1 46.4 110
39. T1204 core 41.7 53.2 72.6 85.6 33.4 45.7 90
40. CT1201 coil 32.2 43.7 34.7 47.7 45.6 57.9 85
41. CT1201 core 32.9 44.4 34.8 47.8 46.7 59.0 85
42. C1208 29.8 41.3 32.9 45.9 37.8 50.1 85
43. Output wire (J239) 52.2 63.7 52.7 65.7 50.2 62.5 90
44. Battery wire (+) 42.5 54.0 43.1 56.1 42.9 55.2 105
45. Input wire (Line) 45.2 56.7 49.8 62.8 47.9 60.2 105
46. RY881 coil 85.1 96.6 85.1 98.1 82.9 95.2 110
47. RY882 coil 83.8 95.3 84.1 97.1 81.1 93.4 110
48. RY883 coil 88.9 100.4 89.6 102.6 85.3 97.6 110
49. Outlet wire (IEC C19) 47.2 58.7 47.6 60.6 44.7 57.0 90
50. Battery body 31.9 43.4 33.7 46.7 29.9 42.2 -
51. Enclosure outside near L1207 (UPS) 31.5 43.0 31.7 44.7 34.6 46.9 70
52. PCB near J7 (Battery Pack) 36.3 47.8 35.5 48.5 34.3 46.6 90
53. PCB near J9 (Battery Pack) 37.6 49.1 37.0 50.0 35.5 47.8 90
54. PCB near J11 (Battery Pack) 36.7 48.2 36.1 49.1 34.7 47.0 90
55. T1 coil (Battery Pack) 52.4 63.9 51.7 64.7 45.1 57.4 90
56. T1 core (Battery Pack) 51.7 63.2 51.0 64.0 44.9 57.2 90
57. Battery body (Battery Pack) 32.8 44.3 36.0 49.0 31.1 43.4 -
58. Enclosure outside near PCB (Battery
31.0 42.5 30.1 43.1 29.8 42.1 70
Pack)
59. Battery wire (+) (Battery Pack) 32.7 44.2 32.0 45.0 31.7 44.0 105
60. Ambient 28.5 40.0 27.0 40.0 27.7 40.0 -
Test duration, h: min: sec 04:45:00 15:12:00 03:18:00 -

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 74 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

Model SRT3000XLW-IEC, Input: 254.4 V ac, 50 Hz, O/P: 3000 VA, 2700 W
Maximum Measured Temperature, °C
Thermocouple Location Method / Mode
A A# B B# C C# Limit
1. D1238 39.8 51.9 40.7 52.8 39.5 51.0 -
2. C1226 44.8 56.9 46.5 58.6 44.3 55.8 85
3. C1211 39.2 51.3 40.1 52.2 39.9 51.4 85
4. C1227 52.1 64.2 56.0 68.1 54.1 65.6 85
5. L1200 coil 47.4 59.5 49.9 62.0 45.6 57.1 90
6. L1206 coil 54.9 67.0 58.9 71.0 51.5 63.0 90
7. PCB near Q1211 43.3 55.4 43.9 56.0 42.8 54.3 90
8. T1201 coil 51.8 63.9 52.6 64.7 49.3 60.8 90
9. T1201 core 45.2 57.3 46.1 58.2 44.6 56.1 90
10. CT1200 coil 53.7 65.8 56.9 69.0 52.7 64.2 90
11. CT1200 core 53.9 66.0 57.1 69.2 53.0 64.5 90
12. C1200 46.4 58.5 49.9 62.0 49.1 60.6 90
13. L1208 coil 55.1 67.2 58.5 70.6 55.1 66.6 90
14. RY1200 coil 49.4 61.5 50.0 62.1 64.6 76.1 90
15. PCB near IC1202 52.6 64.7 55.7 67.8 51.8 63.3 90
16. PCB near IC1203 47.7 59.8 50.1 62.2 46.4 57.9 90
17. T802 coil 33.1 45.2 35.9 48.0 36.1 47.6 90
18. Q1218 Heat-sink 58.9 71.0 62.6 74.7 60.4 71.9 90
19. L1203 coil 54.1 66.2 57.5 69.6 51.6 63.1 90
20. T701 coil 52.5 64.6 53.7 65.8 51.9 63.4 90
21. T701 core 52.5 64.6 53.8 65.9 52.1 63.6 90
22. L1207 coil 70.4 82.5 73.5 85.6 68.6 80.1 110
23. PCB near Q1223 43.8 55.9 45.9 58.0 43.0 54.5 90
24. PCB near Q1220 45.3 57.4 47.7 59.8 41.7 53.2 90
25. RY1202 coil 48.6 60.7 51.1 63.2 48.4 59.9 90
26. RY1203 coil 78.2 90.3 80.7 92.8 77.5 89.0 110
27. RY1204 coil 43.3 55.4 44.8 56.9 43.2 54.7 90
28. RY1205 coil 73.8 85.9 76.0 88.1 66.7 78.2 110
29. RY1206 coil 67.0 79.1 69.0 81.1 60.6 72.1 90
30. C1268 31.3 43.4 32.5 44.6 43.0 54.5 85
31. C1269 34.3 46.4 35.1 47.2 44.4 55.9 85
32. L1202 coil 32.6 44.7 36.1 48.2 51.3 62.8 90
33. L1201 coil 30.6 42.7 34.6 46.7 47.1 58.6 90

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 75 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

34. T1200 coil 32.3 44.4 38.6 50.7 31.0 42.5 90


35. D1229 Heat-sink 30.1 42.2 33.7 45.8 53.0 64.5 90
36. T1203 coil 29.6 41.7 32.2 44.3 61.9 73.4 90
37. T1203 core 30.9 43.0 32.3 44.4 72.7 84.2 90
38. T1204 coil 45.9 58.0 88.0 100.1 43.0 54.5 110
39. T1204 core 40.9 53.0 73.2 85.3 39.4 50.9 90
40. CT1201 coil 30.9 43.0 31.4 43.5 46.6 58.1 85
41. CT1201 core 31.7 43.8 32.3 44.4 47.8 59.3 85
42. C1208 29.6 41.7 30.5 42.6 38.8 50.3 85
43. Output wire (J239) 49.3 61.4 52.8 64.9 50.9 62.4 90
44. Battery wire (+) 40.0 52.1 43.8 55.9 43.6 55.1 105
45. Input wire (Line) 45.2 57.3 49.0 61.1 47.5 59.0 105
46. RY881 coil 82.7 94.8 85.0 97.1 83.3 94.8 110
47. RY882 coil 82.0 94.1 83.9 96.0 82.0 93.5 110
48. RY883 coil 87.5 99.6 89.4 101.5 86.8 98.3 110
49. Outlet wire (IEC C19) 45.2 57.3 47.7 59.8 45.3 56.8 90
50. Battery body 29.5 41.6 32.5 44.6 29.9 41.4 -
51. Enclosure outside near L1207 (UPS) 31.1 43.2 32.9 45.0 35.7 47.2 70
52. PCB near J7 (Battery Pack) 34.5 46.6 35.2 47.3 34.7 46.2 90
53. PCB near J9 (Battery Pack) 35.8 47.9 36.5 48.6 36.3 47.8 90
54. PCB near J11 (Battery Pack) 34.8 46.9 35.6 47.7 35.3 46.8 90
55. T1 coil (Battery Pack) 50.8 62.9 51.5 63.6 50.8 62.3 90
56. T1 core (Battery Pack) 50.1 62.2 50.8 62.9 50.1 61.6 90
57. Battery body (Battery Pack) 29.8 41.9 33.9 46.0 31.1 42.6 -
58. Enclosure outside near PCB (Battery
30.3 42.4 30.4 42.5 30.4 41.9 70
Pack)
59. Battery wire (+) (Battery Pack) 31.9 44.0 32.1 44.2 32.9 44.4 105
60. Ambient 27.9 40.0 27.8 39.9 28.5 40.0 -
Test duration, h: min: sec 04:45:00 12:05:00 03:25:00

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 76 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

POWER SUPPLY/OVERLOAD TEST: RD 5.3.6

METHOD

A sample of each model UPS indicated below was operated in the normal mode delivering maximum
rated output AC power into an adjustable resistive load.
[Once the sample reached thermal stability, the unit was operated in the Stored Energy Mode.]

The output was connected to a variable resistor to draw the maximum available output current with all
other outputs loaded to maximum normal rating. If the unit employed foldback or overcurrent circuitry,
the output current was adjusted to a level that was just below the point at which the power supply cir-
cuitry limited the output current. The trip point of overcurrent protective devices was considered to be
110 percent of their current rating; such devices were removed for this test and replaced with an am-
meter. If the unit employed an overtemperature device, the output current was adjusted to a level that
was just below the point at which the overtemperature device operated.

If the initial point selected (below foldback) caused the power supply to foldback after several minutes,
a point (10-20 percent) below foldback was selected. Temperatures were allowed to stabilize and us-
ing a stepwise procedure, the load was increased while monitoring temperatures. After temperatures
stabilized, the load was increased to the next incremental point. The process was continued until fold-
back. The maximum temperature obtained before foldback was recorded. This same stepwise incre-
mental procedure was used for units employing overtemperature protective service.

The equipment was operated until ultimate results (e.g., component opens, fire, etc.) or thermal equi-
librium was obtained. If any test was terminated by opening of a component other than a reliable
component (e.g., Listed/Recognized fuse, Recognized fusing resistor), the test was retested an addi-
tional two times (three times total) using new components as necessary.

RESULTS

Input AC Electric
Unit Model Observations
Voltage, Hz Strength, Pass
1. Output was loaded with 12.2A till temp
stability.
2. Then load up to 18.9A till temp stabil-
ity.
3. Then load up to 20A till temp stability.
4. The load up to 22A, UUT shutdown in-
SRT3000(RM)XLW- stantly, no hazard.
240, 50Hz [Yes] [No]
IEC

Max temp.
1.T1201 coil 50.3°C
2.T1201 core 47.5°C
3.CT1200 coil 57.2°C
4.CT1200 core 57.4°C
TRF No. IEC62040_1ª
VDE Report No. 1924400-3335-0067/203983
Page 77 of 81 VDE Report No.: 203983-AS3-1
Test Results APPENDIX 2

5.T802 coil 34.5°C


6.T701 coil 52.7°C
7.T701 core 53.3°C
8.T1200 coil 42.1°C
9.T1203 coil 29°C
10.T1203 core 30.4°C
11.T1204 coil 90°C
12.T1204 core 75.7°C
13.CT1201 coil 31.4°C
14.CT1201 core 32.3°C
15.T1 coil(battery pack) 50.8°C
16.T1 core(battery pack) 50.9°C
17.Ambient 25.8°C
1. Output was loaded with 13.1 till temp
stability.
2. The load up to 14.4, UUT shutdown
instantly, no hazard.

Max temp.
1.T1201 coil 44.7°C
2.T1201 core 45.1°C
3.CT1200 coil 57.4°C
4.CT1200 core 57.4°C
5.T802 coil 44.4°C
Stored energy 6.T701 coil 54.9°C
[Yes] [No]
mode
7.T701 core 56°C
8.T1200 coil 33.5°C
9.T1203 coil 65.7°C
10.T1203 core 74.5°C
11.T1204 coil 42.8°C
12.T1204 core 49.9°C
13.CT1201 coil 50.5°C
14.CT1201 core 49.9°C
15.T1 coil(battery pack) 50.8°C
16.T1 core(battery pack) 50.8°C
17.Ambient 26.1°C

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 78 of 81 VDE Report No.: 203983-AS3-1
Model Matrix APPENDIX 3

Model Matrix

SRT3000RMXLI-IEC, SRT2200RMXLI-IEC, SRT3000XLW-IEC, SRT3000XLW-IEC


A B C D (see matrix on next page for further details)
Input 208-240Vac, 50/60Hz; Output 3000VA, 2700W
A: SRT, means series name
B: 3000, 2200, means maximum VA output
C: RM (means Rack Mounted ) or none (means Tower Stand).
D: XLI or XLW-IEC. XL = Extended Run;
I = International(220/230/240V), W-IEC= Worldwide(208/220/230/240V)

Model/Type reference and rating of UPS:

UPS: Rating: Certification Mark:


SRT3000XLI, SRT3000RMXLI Input 220-240Vac, max. 16A, 50/60Hz;
Output 220-240Vac , 3000VA, 2700W
SRT2200XLI, SRT2200RMXLI Input 220-240Vac, max. 13A, 50/60Hz;
Output 220-240Vac , 2200VA, 1980W

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 79 of 81 VDE Report No.: 203983-AS3-1
List of Test Equipment Used APPENDIX 4

TRF No. IEC62040_1ª


VDE Report No. 1924400-3335-0067/203983
Page 80 of 81 VDE Report No.: 203983-AS3-1
Backfeed Protection Test and Schematic IEC Version APPENDIX 5

BACKFEED PROTECTION TEST and Schematic

METHOD
A sample of each model of UPS indicated below was operated in the reserve mode. The backfeed
potentials at the input AC terminals or attachment plug blades were measured. A solid-state device such as
a Triac, SCR, or the like, if provided in the input AC circuit, was shorted at its load terminals during this test.
Voltage Type Maximum Acceptable Voltages
1. Sinusoidal AC, 100 Hz or less 30 V, RMS
2. Non-sinusoidal AC, 100 Hz or less 42.4 V peak
3. Pure DC 60 V

RESULTS

Load Condi- Maximum Voltage


Model
tion Line-Line V Line-Ground V Line-Neutral V Neutral-Ground V
SRT3000(R
A -- 60 1 74
M)XLI
B -- 60 1 74
SRT2200(R
A -- 54 1 72
M)XLI
B -- 54 1 72

Load Condi- Maximum Leakage Current No Fault


Model
tion Line-Line V Line-Ground mA Line-Neutral mA Neutral-Ground mA
SRT3000(R
A -- 0.2 0.01 0.2
M)XLI
B -- 0.2 0.01 0.2
SRT2200(R
A -- 0.2 0.01 0.2
M)XLI
B -- 0.2 0.01 0.2

Load Condi- Maximum Leakage Current Q1212 pin2 and pin3 Shorted
Model
tion Line-Line V Line-Ground mA Line-Neutral mA Neutral-Ground mA
SRT3000XLI A -- 0.2 0.01 0.2
B -- 0.2 0.01 0.2
SRT2200XLI A -- 0.2 0.01 0.2
B -- 0.2 0.01 0.2

Load conditions as follows:

A- ac output loaded to rated value.


B- ac output at no load

The maximum voltage available at the input terminals or attachment plug blades [did not exceed] [exceeded]
the indicated maximum acceptable values. For equipment that exceeded the voltage values, a touch current
test was conducted. The maximum measured touch current [did not exceed] [exceeded] 3.5 mA for both no
fault and single fault conditions.