KEY PLAN

4.48-m
UP

F.F.L

PART01
PART02
3.00 3.00 3.00
3.00 3.00
outlet attenuator 3m*3m* 2m depth outlet attenuator 3m*3m* 2m depth outlet attenuator 2.5m*2.5m* 2m depth outlet attenuator 2.5m*2.5m* 2m depth outlet attenuator 3m*3m* 2m depth
MCC-B1-01

20A/380V
FOR FUEL PUMP
A ELEC
SHAFT HVAC
A
SHAFT

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN


5STRING X 46

5STRING X 46

5STRING X 46

5STRING X 46

5STRING X 46

5STRING X 46
Main contractor :

230BLOCKS

230BLOCKS

230BLOCKS

230BLOCKS

230BLOCKS

230BLOCKS
STAIRS
B13

BURIED FUEL TANK B inlet attenuator B


4.25m * 2 m * 1.5m depth

500KVA 500KVA 500KVA


4250

B24 B24 B22 B22 B24 LOBBY

160KVA 15- MIN

160KVA 15- MIN


2STRING X 40

2STRING X 40
BATTERY ROOM

80BLOCKS

80BLOCKS
UPS ROOM B12
B14
B14 2no.

DC

DC

DC

DC

DC

DC

DC

DC
32A/380V

CRAH 13
CW
1.5'' return 1.5'' return 1.25'' return 1.25'' supply fuel 1.25'' return 1.25'' supply fuel 1.5'' return
FOR CRAH-11 4.18-m PASSENGER LIFT OPENING

CRAH 11

200KVA 15- MIN

2STRING X 44
20A/380V inlet attenuator inlet attenuator inlet attenuator inlet attenuator 500KVA 500KVA 500KVA
B11
4.18-m
inlet attenuator
F.F.L

88BLOCKS
3.95m * 2 m * 2m depth 3.95m * 2 m * 2m depth
FOR FUEL PUMP
1.5'' supply fuel
3.95m * 2.25 m * 2m depth
1.5'' supply
3.95m
fuel* 2.25 m * 2m depth 1.5'' supply
3.95m
fuel* 2.25 m * 2m depth
32A/380V
F.F.L

RECRECREC

RECRECREC
daily tank
daily tank daily tank daily tank daily tank 2no. 2no. FOR CRAH-13
2m3 2m3
2m3
daily tank 2m3 2m3 2m3
32A/380V 32A/380V
FOR CRAH-12 FOR CRAH-02
32A/380V

REC
CRAH 12
2no.
FOR CRAH-01

200KVA
160 KVA 160 KVA
2no. 32A/380V
CRAH 01 CRAH 02 CRAH 03 FOR CRAH-03
C 2no. 2no.
2no.
2no.
2no.
2no. 2no. C
4.48-m EMCC-B1-01 2no. 2no.
2no. 2no. 2no. 2no. Main consultant :
F.F.L HVAC
OPENING CORRIDOR 4.18-m
CRAH 04 CRAH 05 CRAH 06
32A/380V
B04 F.F.L FOR CRAH-08 32A/380V 32A/380V
FOR CRAH-10 FOR CRAH-03
32A/380V 32A/380V 32A/380V
FOR CRAH-9 FOR CRAH-01 FOR CRAH-02

2no.

REC REC REC


REC REC REC
Mearaj City, Cairo Ring Road, Bldg No: 2075 To 2078
160 KVA 160 KVA 200KVA Tel: (202) 2520 4500 (10 lines) Fax: (202) 2520 4505

CRAH 10
4.18-m WWW.shakergroup.com
2no.
FREIGHT LIFT F.F.L

200KVA 15- MIN


88BLOCKS
2STRING X 44
TRANSFORMER ROOM TRANSFORMER ROOM
B03 4.18-m 4.18-m
B08 B09 2no.
F.F.L F.F.L UPS ROOM BATTERY ROOM ARCHITECURE & LANDSCAPE CONSULTANT:

CRAH 8
4.18-m 2no.
500KVA B10
500KVA 500KVA B12
F.F.L

DC

DC

DC

DC

DC

DC

DC

DC
2no.

160KVA 15- MIN

160KVA 15- MIN


80BLOCKS

80BLOCKS
2STRING X 40

2STRING X 40
D LOBBY 2no.
D

CRAH 9
M.V. ROOM
B02 4.18-m
B06 PANELS ROOM
500KVA 500KVA 500KVA
F.F.L
4.18-m
B07
F.F.L
E UP E
MCC-B1-02
FREIGHT LIFT 4.18-m

F.F.L

500KVA 15- MIN

500KVA 15- MIN


230BLOCKS

230BLOCKS
5STRING X 46

5STRING X 46
STAIRS

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN

500KVA 15- MIN


230BLOCKS

230BLOCKS

230BLOCKS

230BLOCKS
5STRING X 46

5STRING X 46

5STRING X 46

5STRING X 46
PANELS ROOM
B 05
B01

HVAC L.C
ELEC ELEC SHAFT SHAFT PROJECT :
SHAFT SHAFT

F F
TELECOM EGYPT REGIONAL HUB
DATA CENTER

4.48-m
DN

F.F.L
PART02
PART01

1 2 3 4 5 6 7 8 9 10 11 NO.: ABBR.: BUILDING NAME :

-- EC Regional Cloud Hub - RCH

DRAWING TITLE :
FIRST BASEMENT FLOOR PLAN
FEEDER ROUTING SYSTEM LAYOUT
OVERALL

DRAWN AHMED AWAD SCALE 1/100 DATE FEB.2020


CHECKED PETER APPROVED AMR SHAHEEN
--- REV.
COMPANY PROJECT DWG. TYPE DISCIPLINE DWG. SEQUENCE
0
SCG 19060 EC B1 00