Low Voltage Switchgear

Update the Ingress Protection for switchgear from 21 to be 42

M. Gamal  BAMAG-MENA  14/2013


 Low Voltage Switchgear

mm. The rated current is 3200/630/16/270


Low Voltage ampere with rated voltage 400 volt and 50
hertz. The panel is located in dry electrical

Switchgear room with IP21.


Low Voltage Distribution Board
LV02 is the switchgear feeding the power
Update the Ingress Protection for for sludge dewatering and pre-treatment.
The panel consists of 20 cells each cell with
switchgear from 21 to be 42 dimension of (Width x Depth x Height) 800
x 600 x 2000 mm. The panel comprises of
one corner cell with dimension of (Width x
Depth x Height) 600 x 600 x 2000 mm and
For Low Voltage Switchgear of: two adaptation cells each cell with
- Main Distribution Board. dimension of (Width x Depth x Height) 600
- Low Voltage Distribution Board x 600 x 2000 mm. The rated current is
LV01. 800/630/250/270 ampere with rated
- Low Voltage Distribution Board voltage 400 volt and 50 hertz. The panel is
LV02. located in humid electrical room with IP54.
Low Voltage Distribution Board
- Low Voltage Distribution Board
LV03 is the switchgear feeding the power
LV03. for aeration stage two. The panel consists
- Low Voltage Distribution Board (BS) of 22 cells each cell with dimension of
These panels have been delivered to (Width x Depth x Height) 800 x 600 x 2000
the site on two packages, the first on mm. The rated current is 2500/630/16/289
19.08.2009 with inspection report no. 08 ampere with rated voltage 400 volt and 50
and the other on 11.01.2010 with hertz. The panel is located in dry electrical
room with IP21.
inspection report no. 12.
Low Voltage Distribution Board (BS)
According to consultant letter No. is the switchgear feeding the power for
BAMAG/896 dated 24.01.2010 and the Building Service. The panel consists of 4
contract document page 33/131; we shall cells each cell with dimension of (Width x
upgrade the protection degree of these Depth x Height) 800 x 600 x 2000 mm. The
panels to be IP42 for dry electrical rated current is 800 ampere with rated
operating room and IP54 for humid rooms. voltage 400 volt and 50 hertz. The panel is
located in dry electrical room with IP21.

Low Voltage Switchgear Description


Degrees of protection provided by
Main Distribution Board (MDB) is the enclosures (IP Code)
main switchgear feeding the power for the Definition of the IP code is given by
whole system in the plant. The panel a coding system to indicate the degrees of
consists of 10 cells each cell with protection provided by an enclosure
dimension of (Width x Depth x Height) 800 against access to hazardous parts, ingress
x 600 x 2000 mm. The rated current is of solid foreign objects, and ingress of
3200 ampere with rated voltage 400 volt water and to give additional information in
and 50 hertz. The panel is located in dry connection with such protection.*
electrical room with IP21. The degree of protection provided
Low Voltage Distribution Board by an enclosure is indicated by the IP Code
LV01 is the switchgear feeding the power as following: **
for aeration stage one. The panel consists - Code letters (IP)
of 22 cells each cell with dimension of - First characteristic numeral
(Width x Depth x Height) 800 x 600 x 2000 (numerals 0 to 6, or letter X)

 Page 2
 Low Voltage Switchgear

- Second characteristic numeral For ambient conditions, it’s recommended


(numerals 0 to 8, or letter X) to be as follow:
The difference between the degree of - Temperature : 15 °C to 35
protection for:
°C
Against
Against ingress Against - Relative humidity: 25 % to 75 %
IP access to
of solid foreign ingress - Air pressure: 0.86 bar to 1.06 bar
Code hazardous
objects of water Tools to be prepared for test:
parts with
≥12,5 mm vertically o Electrode with 1mm2 cross
21 finger
diameter dripping section area and with
dripping isolated handle shall be used
≥1,0 mm
42 wire (15° for test the first
diameter
tilted)
characteristic numeral of IP.
splashin
54 dust-protected wire o Diameter measurement tool
g
* Clouse 3.4 such as Vernier Calipers.
** Clouse 4 o Drip box with dimension of
60cm x 60cm with height of
50cm, and holes of diameter
Upgrade the degrees of protection
0.5mm.
Through an extensive water sealing o The drip box material shall
study, many materials were evaluated for
be PVC.
initial sealing effectiveness. A high-demand
scenario was simulated of water pressure o Insulation tester.
on a 6.35 mm wide gasket using materials Equipment needs for test:
of medium firmness compressed to various - Forklift to transport the panels.
compressions. - Base frame or support under the
Sealing should be applied for the tested items.
door and any other opening for ventilation.
- Lifting equipment to adjust the
Good sealing of fan filter, to be prevent
dust and water drop. panel at 15°.

Which panels shall be upgrade Test Procedure


There are four panels as follow shall For protection against solid foreign
be upgrade to be IP42: objects indicated by the first characteristic
1. Main Distribution Board. numeral, the access probe is pushed
2. Low Voltage Distribution Board against or inserted through any openings
LV01. of the enclosure with the force of 1N.
Tests for protection against water
3. Low Voltage Distribution Board indicated by the second characteristic
LV03. numeral, the tests are conducted with
4. Low Voltage Distribution Board (BS) fresh water. During the the water
The sample for each panel shall be temperature should not differ by more than
tested with 25% of the total no. of cells and 5 K from the temperature of the specimen
three cells as minimum quantity. For item under test.
one and four, three cells shall be tested. The test is made with a device
For item two and three, six cells shall be which produces a uniform flow of water
tested. drops over the whole area of the enclosure.
An example of such a device is shown in
attached drawing.
Requirements for test

 Page 3
 Low Voltage Switchgear

The enclosure under test is placed


in its normal operating position under the
drip box with distance of 20 cm.
The enclosure is tested for 2.5 min
in each of four fixed positions of tilt. These
positions are 15° on either side of the
vertical in two mutually perpendicular
planes.

Test acceptance
After testing in accordance with the
appropriate requirements of IEC-60529, the
first characteristic numeral protection is
satisfactory if the full diameter of the probe
does not pass through any opening. The
second characteristic numeral protection is
satisfactory if there is no water within the
enclosure.
If traces of water are readily
observable within the enclosure
immediately after the test for water
ingress, then the dielectric properties shall
be verified by test in accordance.

 Page 4