Sei sulla pagina 1di 11

685.

14 ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS

Table 685.3 Application of Other Articles


Fuse DC-to-DC PV or DC-to-DC
Conductor/Equipment Section converter converter
(optional output circuit
More than one building or 225, Part II location)
other structure
Ground-fault protection of 230.95, Exception
equipment PV source
Protection of conductors 240.4 circuit
Electrical system coordination 240.12
Solar
Ground-fault protection of 240.13(1)
cells
equipment
Grounding ac systems of 250.21
50 volts to less than
1000 volts Module
Equipment protection 427.22
Orderly shutdown 430.44
Disconnection 430.75, Exception Nos. 1 and 2 Panel
Disconnecting means in sight 430.102(A), Exception No. 2
from controller
Array, subarray, or
Energy from more than one 430.113, Exception Nos. 1 and 2 PV power source
source
Disconnecting means 645.10, Exception
Uninterruptible power 645.11(1)
supplies (UPS) Notes:
Point of connection 705.12 (1) These diagrams are intended to be a means of identification for PV
power source components, circuits, and connections that make up the PV
power source.
685.14 Ungrounded Control Circuits. Where operational (2) Custom PV power source designs occur, and some components are
continuity is required, control circuits of 150 volts or less from optional.
separately derived systems shall be permitted to be ungroun‐
ded. FIGURE 690.1(a) Identification of PV Power Source
Components.

Bipolar Photovoltaic Array. A dc PV array that has two outputs,


each having opposite polarity to a common reference point or
ARTICLE 690 center tap.

Solar Photovoltaic (PV) Systems DC-to-DC Converter. A device installed in the PV source
circuit or PV output circuit that can provide an output dc volt‐
age and current at a higher or lower value than the input
Part I. General dc voltage and current.
690.1 Scope. This article applies to solar PV systems, other N DC-to-DC Converter Output Circuit. Circuit conductors
than those covered by Article 691, including the array between the dc-to-dc converter source circuit(s) and the inver‐
circuit(s), inverter(s), and controller(s) for such systems. [See ter or dc utilization equipment.
Figure 690.1(a) and Figure 690.1(b).] The systems covered by this N DC-to-DC Converter Source Circuit. Circuits between dc-to-dc
article may be interactive with other electrical power produc‐
converters and from dc-to-dc converters to the common
tion sources or stand-alone or both, and may or may not be
connection point(s) of the dc system.
connected to energy storage systems such as batteries. These
PV systems may have ac or dc output for utilization. Direct-Current (dc) Combiner. A device used in the PV source
and PV output circuits to combine two or more dc circuit
Informational Note: Article 691 covers the installation of large-
scale PV electric supply stations. inputs and provide one dc circuit output.

690.2 Definitions. Diversion Charge Controller. Equipment that regulates the


charging process of a battery by diverting power from energy
Alternating-Current (ac) Module (Alternating-Current Photo‐ storage to direct-current or alternating-current loads or to an
voltaic Module). A complete, environmentally protected unit interconnected utility service.
consisting of solar cells, optics, inverter, and other components,
exclusive of tracker, designed to generate ac power when Electrical Production and Distribution Network. A power
exposed to sunlight. production, distribution, and utilization system, such as a utility
system and connected loads, that is external to and not control‐
Array. A mechanically integrated assembly of module(s) or led by the PV power system.
panel(s) with a support structure and foundation, tracker, and
other components, as required, to form a dc or ac power- Functional Grounded PV System. A PV system that has an elec‐
producing unit. trical reference to ground that is not solidly grounded.

70 –558 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS 690.2

Interactive inverter PV system disconnect Informational Note: A functional grounded PV system is often
connected to ground through a fuse, circuit breaker, resistance
Electric device, non-isolated grounded ac circuit, or electronic means
production and that is part of a listed ground-fault protection system. Conduc‐
Inverter output circuit distribution
PV power source tors in these systems that are normally at ground potential may
network have voltage to ground during fault conditions.
Interactive system
N Generating Capacity. The sum of parallel-connected inverter
Inverter output circuit
maximum continuous output power at 40°C in kilowatts.
Electric production
and distribution network Interactive System. A PV system that operates in parallel with
PV system and may deliver power to an electrical production and distribu‐
disconnect tion network.
AC module (includes inverter) N Interactive Inverter Output Circuit. The conductors between
AC module system Array (of AC modules) the interactive inverter and the service equipment or another
electrical power production and distribution network.
PV power PV system Interactive system
Inverter. Equipment that is used to change voltage level or
source disconnect Multimode disconnect
inverter waveform, or both, of electrical energy. Commonly, an inverter
Electric production
and distribution [also known as a power conditioning unit (PCU) or power
network conversion system (PCS)] is a device that changes dc input to
Stand-alone an ac output. Inverters may also function as battery chargers
DC loads system that use alternating current from another source and convert it
Energy storage
Inverter loads into direct current for charging batteries.
output
system disconnect circuits Inverter Input Circuit. Conductors connected to the dc input
Energy storage system of an inverter.

DC coupled multimode system Inverter Output Circuit. Conductors connected to the


ac output of an inverter.
PV power Interactive
source inverter Inverter output circuit Module. A complete, environmentally protected unit consist‐
ing of solar cells, optics, and other components, exclusive of
PV system
disconnect
tracker, designed to generate dc power when exposed to
sunlight.
Energy storage Multimode
system inverter Monopole Subarray. A PV subarray that has two conductors in
Electric the output circuit, one positive (+) and one negative (−). Two
production and monopole PV subarrays are used to form a bipolar PV array.
distribution
Energy storage network Multimode Inverter. Equipment having the capabilities of both
system disconnect Interactive system the interactive inverter and the stand-alone inverter.
AC coupled multimode system disconnect
Panel. A collection of modules mechanically fastened together,
PV power PV system Stand-alone wired, and designed to provide a field-installable unit.
source disconnect inverter Inverter
Photovoltaic Output Circuit. Circuit conductors between the
output
circuit
PV source circuit(s) and the inverter or dc utilization equip‐
ment.
PV system Stand-alone
DC circuit(s) DC loads system loads Photovoltaic Power Source. An array or aggregate of arrays
Energy storage that generates dc power at system voltage and current.
system disconnect
Photovoltaic Source Circuit. Circuits between modules and
Energy storage system from modules to the common connection point(s) of the dc
system.
Stand-alone system

Notes:
N Photovoltaic System DC Circuit. Any dc conductor supplied by
(1) These diagrams are intended to be a means of identification for PV a PV power source, including PV source circuits, PV output
system components, circuits, and connections. circuits, dc-to-dc converter source circuits, or dc-to-dc converter
(2) The PV system disconnect in these diagrams separates the PV system output circuits.
from all other systems. •
(3) Not all disconnecting means required by Article 690, Part III are shown. Solar Cell. The basic PV device that generates electricity when
(4) System grounding and equipment grounding are not shown. See Article exposed to light.
690, Part V.
(5) Custom designs occur in each configuration, and some components are Stand-Alone System. A solar PV system that supplies power
optional. independently of an electrical production and distribution
network.
FIGURE 690.1(b) Identification of PV System Components
in Common Configurations. Subarray. An electrical subset of a PV array.

2017 Edition NATIONAL ELECTRICAL CODE 70 –559


690.4 ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS

690.4 General Requirements. PV module–rated open-circuit voltage of the series-


connected modules corrected for the lowest expected
(A) Photovoltaic Systems. Photovoltaic systems shall be ambient temperature using the correction factor provi‐
permitted to supply a building or other structure in addition to ded in Table 690.7(A)
any other electrical supply system(s). (3) PV systems of 100 kW or larger: For PV systems with a
(B) Equipment. Inverters, motor generators, PV modules, generating capacity of 100 kW or greater, a documented
PV panels, ac modules, dc combiners, dc-to-dc converters, and and stamped PV system design, using an industry stand‐
charge controllers intended for use in PV systems shall be listed ard method and provided by a licensed professional elec‐
or field labeled for the PV application. trical engineer, shall be permitted.

(C) Qualified Personnel. The installation of equipment and Informational Note: One industry standard method for calculat‐
all associated wiring and interconnections shall be performed ing maximum voltage of a PV system is published by Sandia
National Laboratories, reference SAND 2004-3535, Photovoltaic
only by qualified persons. Array Performance Model.
Informational Note: See Article 100 for the definition of quali‐
fied person.
The maximum voltage shall be used to determine the volt‐
age rating of conductors, cables, disconnects, overcurrent
(D) Multiple PV Systems. Multiple PV systems shall be permit‐ devices, and other equipment.
ted to be installed in or on a single building or structure.
Where the PV systems are remotely located from each other, a (B) DC-to-DC Converter Source and Output Circuits. In a dc-
directory in accordance with 705.10 shall be provided at each to-dc converter source and output circuit, the maximum volt‐
PV system disconnecting means. age shall be calculated in accordance with 690.7(B)(1) or
• (B)(2).
N (E) Locations Not Permitted. PV system equipment and
disconnecting means shall not be installed in bathrooms. (1) Single DC-to-DC Converter. For circuits connected to the
• output of a single dc-to-dc converter, the maximum voltage
690.6 Alternating-Current (ac) Modules. shall be the maximum rated voltage output of the dc-to-dc
converter.
(A) Photovoltaic Source Circuits. The requirements of Article
690 pertaining to PV source circuits shall not apply to ac (2) Two or More Series Connected DC-to-DC Converters. For
modules. The PV source circuit, conductors, and inverters shall circuits connected to the output of two or more series-
be considered as internal wiring of an ac module. connected dc-to-dc converters, the maximum voltage shall be
determined in accordance with the instructions included in the
(B) Inverter Output Circuit. The output of an ac module listing or labeling of the dc-to-dc converter. If these instructions
shall be considered an inverter output circuit. do not state the rated voltage of series-connected dc-to-dc

converters, the maximum voltage shall be the sum of the maxi‐
mum rated voltage output of the dc-to-dc converters in series.
Part II. Circuit Requirements •
(C) Bipolar Source and Output Circuits. For 2-wire dc circuits
690.7 Maximum Voltage. The maximum voltage of PV system connected to bipolar PV arrays, the maximum voltage shall be
dc circuits shall be the highest voltage between any two circuit the highest voltage between the 2-wire circuit conductors
conductors or any conductor and ground. PV system dc circuits where one conductor of the 2-wire circuit is connected to the
on or in one- and two-family dwellings shall be permitted to functional ground reference (center tap). To prevent overvolt‐
have a maximum voltage of 600 volts or less. PV system dc age in the event of a ground-fault or arc-fault, the array shall be
circuits on or in other types of buildings shall be permitted to
have a maximum voltage of 1000 volts or less. Where not loca‐
ted on or in buildings, listed dc PV equipment, rated at a maxi‐ Table 690.7(A) Voltage Correction Factors for Crystalline and
mum voltage of 1500 volts or less, shall not be required to Multicrystalline Silicon Modules
comply with Parts II and III of Article 490.
(A) Photovoltaic Source and Output Circuits. In a dc PV Correction Factors for Ambient Temperatures Below 25°C (77°F).
source circuit or output circuit, the maximum PV system volt‐ (Multiply the rated open-circuit voltage by the appropriate
age for that circuit shall be calculated in accordance with one correction factor shown below.)
of the following methods: Ambient Ambient
Informational Note: One source for lowest-expected, ambient Temperature (°C) Factor Temperature (°F)
temperature design data for various locations is the chapter 24 to 20 1.02 76 to 68
titled Extreme Annual Mean Minimum Design Dry Bulb 19 to 15 1.04 67 to 59
Temperature found in the ASHRAE Handbook — Fundamentals,
14 to 10 1.06 58 to 50
2013. These temperature data can be used to calculate maxi‐
mum voltage. 9 to 5 1.08 49 to 41
4 to 0 1.10 40 to 32
(1) Instructions in listing or labeling of the module: The sum –1 to –5 1.12 31 to 23
of the PV module–rated open-circuit voltage of the series- –6 to –10 1.14 22 to 14
connected modules corrected for the lowest expected –11 to –15 1.16 13 to 5
ambient temperature using the open-circuit voltage –16 to –20 1.18 4 to –4
temperature coefficients in accordance with the instruc‐ –21 to –25 1.20 –5 to –13
tions included in the listing or labeling of the module –26 to –30 1.21 –14 to –22
(2) Crystalline and multicrystalline modules: For crystalline –31 to –35 1.23 –23 to –31
and multicrystalline silicon modules, the sum of the –36 to –40 1.25 –32 to –40

70 –560 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS 690.9

isolated from the ground reference and isolated into two 2-wire (2) After Application of Adjustment and Correction Factors.
circuits. The maximum currents calculated in 690.8(A) after the appli‐
• cation of adjustment and correction factors.
690.8 Circuit Sizing and Current.
N (3) Adjustable Electronic Overcurrent Protective Device. The
(A) Calculation of Maximum Circuit Current. The maximum rating or setting of an adjustable electronic overcurrent protec‐
current for the specific circuit shall be calculated in accordance tive device installed in accordance with 240.6.
with 690.8(A)(1) through (A)(6).
(C) Systems with Multiple Direct-Current Voltages. For a
Informational Note: Where the requirements of 690.8(A)(1)
and (B)(1) are both applied, the resulting multiplication factor
PV power source that has multiple output circuit voltages and
is 156 percent. employs a common-return conductor, the ampacity of the
common-return conductor shall not be less than the sum of the
(1) Photovoltaic Source Circuit Currents. The maximum ampere ratings of the overcurrent devices of the individual
current shall be calculated by one of the following methods: output circuits.
(1) The sum of parallel-connected PV module–rated short- (D) Sizing of Module Interconnection Conductors. Where a
circuit currents multiplied by 125 percent single overcurrent device is used to protect a set of two or more
(2) For PV systems with a generating capacity of 100 kW or parallel-connected module circuits, the ampacity of each of the
greater, a documented and stamped PV system design, module interconnection conductors shall not be less than the
using an industry standard method and provided by a sum of the rating of the single overcurrent device plus
licensed professional electrical engineer, shall be permit‐ 125 percent of the short-circuit current from the other parallel-
ted. The calculated maximum current value shall be connected modules.
based on the highest 3-hour current average resulting
from the simulated local irradiance on the PV array 690.9 Overcurrent Protection.
accounting for elevation and orientation. The current
(A) Circuits and Equipment. PV system dc circuit and inverter
value used by this method shall not be less than
output conductors and equipment shall be protected against
70 percent of the value calculated using 690.8(A)(1)(1).
overcurrent. Overcurrent protective devices shall not be
Informational Note: One industry standard method for calculat‐ required for circuits with sufficient ampacity for the highest
ing maximum current of a PV system is available from Sandia available current. Circuits connected to current limited
National Laboratories, reference SAND 2004-3535, Photovoltaic supplies (e.g., PV modules, dc-to-dc converters, interactive
Array Performance Model. This model is used by the System Advi‐ inverter output circuits) and also connected to sources having
sor Model simulation program provided by the National Renew‐ higher current availability (e.g., parallel strings of modules,
able Energy Laboratory.
utility power) shall be protected at the higher current source
(2) Photovoltaic Output Circuit Currents. The maximum connection.
current shall be the sum of parallel source circuit maximum
Exception: An overcurrent device shall not be required for PV modules
currents as calculated in 690.8(A)(1).
or PV source circuit or dc-to-dc converters source circuit conductors sized
(3) Inverter Output Circuit Current. The maximum current in accordance with 690.8(B) where one of the following applies:
shall be the inverter continuous output current rating. (1) There are no external sources such as parallel-connected source
(4) Stand-Alone Inverter Input Circuit Current. The maxi‐ circuits, batteries, or backfeed from inverters.
mum current shall be the stand-alone continuous inverter (2) The short-circuit currents from all sources do not exceed the
input current rating when the inverter is producing rated ampacity of the conductors and the maximum overcurrent protec‐
power at the lowest input voltage. tive device size rating specified for the PV module or dc-to-dc
converter.
(5) DC-to-DC Converter Source Circuit Current. The maxi‐
mum current shall be the dc-to-dc converter continuous output Informational Note: Photovoltaic system dc circuits are current
limited circuits that only need overcurrent protection when
current rating. connected in parallel to higher current sources. The overcur‐
N (6) DC-to-DC Converter Output Circuit Current. The maxi‐ rent device is often installed at the higher current source end of
mum current shall be the sum of parallel connected dc-to-dc the circuit.
converter source circuit currents as calculated in 690.8(A)(5). (B) Overcurrent Device Ratings. Overcurrent devices used in
(B) Conductor Ampacity. PV system currents shall be consid‐ PV system dc circuits shall be listed for use in PV systems. Over‐
ered to be continuous. Circuit conductors shall be sized to current devices, where required, shall be rated in accordance
carry not less than the larger of 690.8(B)(1) or (B)(2) or where with one of the following:
protected by a listed adjustable electronic overcurrent protec‐ (1) Not less than 125 percent of the maximum currents
tive device in accordance 690.9(B)(3), not less than the current calculated in 690.8(A).
in 690.8(B)(3). (2) An assembly, together with its overcurrent device(s), that
is listed for continuous operation at 100 percent of its
(1) Before Application of Adjustment and Correction Factors. rating shall be permitted to be used at 100 percent of its
One hundred twenty-five percent of the maximum currents rating.
calculated in 690.8(A) before the application of adjustment (3) Adjustable electronic overcurrent protective devices rated
and correction factors. or set in accordance with 240.6.
Exception: Circuits containing an assembly, together with its overcur‐ Informational Note: Some electronic overcurrent protective
rent device(s), that is listed for continuous operation at 100 percent of devices prevent backfeed current.
its rating shall be permitted to be used at 100 percent of its rating. •

2017 Edition NATIONAL ELECTRICAL CODE 70 –561


690.9 ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS

(C) Photovoltaic Source and Output Circuits. A single over‐ than 30 volts within 30 seconds of rapid shutdown initiation.
current protective device, where required, shall be permitted to Voltage shall be measured between any two conductors and
protect the PV modules and conductors of each source circuit between any conductor and ground.
or the conductors of each output circuit. Where single overcur‐
rent protection devices are used to protect PV source or output (2) Inside the Array Boundary. The PV system shall comply
circuits, all overcurrent devices shall be placed in the same with one of the following:
polarity for all circuits within a PV system. The overcurrent (1) The PV array shall be listed or field labeled as a rapid
devices shall be accessible but shall not be required to be read‐ shutdown PV array. Such a PV array shall be installed and
ily accessible. used in accordance with the instructions included with
the rapid shutdown PV array listing or field labeling.
Informational Note: Due to improved ground-fault protection
required in PV systems by 690.41(B), a single overcurrent Informational Note: A listed or field labeled rapid shutdown PV
protective device in either the positive or negative conductors of array is evaluated as an assembly or system as defined in the
a PV system in combination with this ground-fault protection installation instructions to reduce but not eliminate risk of elec‐
provides adequate overcurrent protection. tric shock hazard within a damaged PV array during fire-fighting
• procedures. These rapid shutdown PV arrays are designed to
(D) Power Transformers. Overcurrent protection for a trans‐ reduce shock hazards by methods such as limiting access to
former with a source(s) on each side shall be provided in energized components, reducing the voltage difference between
accordance with 450.3 by considering first one side of the trans‐ energized components, limiting the electric current that might
former, then the other side of the transformer, as the primary. flow in an electrical circuit involving personnel with increased
resistance of the conductive circuit, or by a combination of such
Exception: A power transformer with a current rating on the side methods.
connected toward the interactive inverter output, not less than the rated
continuous output current of the inverter, shall be permitted without (2) Controlled conductors located inside the boundary or
overcurrent protection from the inverter. not more than 1 m (3 ft) from the point of penetration of
the surface of the building shall be limited to not more
690.10 Stand-Alone Systems. The wiring system connected to than 80 volts within 30 seconds of rapid shutdown initia‐
a stand-alone system shall be installed in accordance with tion. Voltage shall be measured between any two conduc‐
710.15. tors and between any conductor and ground.
• (3) PV arrays with no exposed wiring methods, no exposed
690.11 Arc-Fault Circuit Protection (Direct Current). Photo‐
voltaic systems operating at 80 volts dc or greater between any conductive parts, and installed more than 2.5 m (8 ft)
two conductors shall be protected by a listed PV arc-fault circuit from exposed grounded conductive parts or ground shall
interrupter orother system components listed to provide equiv‐ not be required to comply with 690.12(B)(2).
alent protection. The system shall detect and interrupt arcing The requirement of 690.12(B)(2) shall become effective
faults resulting from a failure in the intended continuity of a January 1, 2019.
conductor, connection, module, or other system component in
the PV system dc circuits. N (C) Initiation Device. The initiation device(s) shall initiate
• the rapid shutdown function of the PV system. The device “off”
Informational Note: Annex A includes the reference for the position shall indicate that the rapid shutdown function has
Photovoltaic DC Arc-Fault Circuit Protection product standard. been initiated for all PV systems connected to that device. For
Exception: For PV systems not installed on or in buildings, PV output one-family and two-family dwellings, an initiation device(s)
circuits and dc-to-dc converter output circuits that are direct buried, shall be located at a readily accessible location outside the
installed in metallic raceways, or installed in enclosed metallic cable building.
trays are permitted without arc-fault circuit protection. Detached struc‐ The rapid shutdown initiation device(s) shall consist of at
tures whose sole purpose is to house PV system equipment shall not be least one of the following:
considered buildings according to this exception.
(1) Service disconnecting means
690.12 Rapid Shutdown of PV Systems on Buildings. PV (2) PV system disconnecting means
system circuits installed on or in buildings shall include a rapid (3) Readily accessible switch that plainly indicates whether it
shutdown function to reduce shock hazard for emergency is in the “off” or “on” position
responders in accordance with 690.12(A) through (D).
• Informational Note: One example of why an initiation device
Exception: Ground mounted PV system circuits that enter buildings, of that complies with 690.12(C)(3) would be used is where a PV
which the sole purpose is to house PV system equipment, shall not be system is connected to an optional standby system that remains
required to comply with 690.12. energized upon loss of utility voltage.

N (A) Controlled Conductors. Requirements for controlled Where multiple PV systems are installed with rapid shutdown
conductors shall apply to PV circuits supplied by the PV system. functions on a single service, the initiation device(s) shall
consist of not more than six switches or six sets of circuit break‐
N (B) Controlled Limits. The use of the term array boundary in ers, or a combination of not more than six switches and sets of
this section is defined as 305 mm (1 ft) from the array in all circuit breakers, mounted in a single enclosure, or in a group
directions. Controlled conductors outside the array boundary of separate enclosures. These initiation device(s) shall initiate
shall comply with 690.12(B)(1) and inside the array boundary the rapid shutdown of all PV systems with rapid shutdown func‐
shall comply with 690.12(B)(2). tions on that service. Where auxiliary initiation devices are
(1) Outside the Array Boundary. Controlled conductors loca‐ installed, these auxiliary devices shall control all PV systems
ted outside the boundary or more than 1 m (3 ft) from the with rapid shutdown functions on that service.
point of entry inside a building shall be limited to not more

70 –562 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS 690.15

N (D) Equipment. Equipment that performs the rapid shut‐ N (F) Type of Disconnect.
down functions, other than initiation devices such as listed
disconnect switches, circuit breakers, or control switches, shall (1) Simultaneous Disconnection. The PV system disconnect‐
be listed for providing rapid shutdown protection. ing means shall simultaneously disconnect the PV system
conductors of the circuit from all conductors of other wiring
Informational Note: Inverter input circuit conductors often systems. The PV system disconnecting means shall be an exter‐
remain energized for up to 5 minutes with inverters not listed nally operable general-use switch or circuit breaker, or other
for rapid shutdown. approved means. A dc PV system disconnecting means shall be
marked for use in PV systems or be suitable for backfeed opera‐
tion.
Part III. Disconnecting Means
(2) Devices Marked “Line” and “Load.” Devices marked with
690.13 Photovoltaic System Disconnecting Means. Means “line” and “load” shall not be permitted for backfeed or reverse
shall be provided to disconnect the PV system from all wiring current.
systems including power systems, energy storage systems, and
utilization equipment and its associated premises wiring. (3) DC-Rated Enclosed Switches, Open-Type Switches, and
Low-Voltage Power Circuit Breakers. DC-rated, enclosed
(A) Location. The PV system disconnecting means shall be switches, open-type switches, and low-voltage power circuit
installed at a readily accessible location. breakers shall be permitted for backfeed operation.

Informational Note: PV systems installed in accordance with 690.15 Disconnection of Photovoltaic Equipment. Isolating
690.12 address the concerns related to energized conductors
entering a building.
devices shall be provided to isolate PV modules, ac PV modules,
fuses, dc-to-dc converters, inverters, and charge controllers
(B) Marking. Each PV system disconnecting means shall from all conductors that are not solidly grounded. An equip‐
plainly indicate whether in the open (off) or closed (on) posi‐ ment disconnecting means or a PV system disconnecting
tion and be permanently marked “PV SYSTEM DISCONNECT” means shall be permitted in place of an isolating device. Where
or equivalent. Additional markings shall be permitted based the maximum circuit current is greater than 30 amperes for
upon the specific system configuration. For PV system discon‐ the output circuit of a dc combiner or the input circuit of a
necting means where the line and load terminals may be ener‐ charge controller or inverter, an equipment disconnecting
gized in the open position, the device shall be marked with the means shall be provided for isolation. Where a charge control‐
following words or equivalent: ler or inverter has multiple input circuits, a single equipment
disconnecting means shall be permitted to isolate the equip‐
WARNING ment from the input circuits.
ELECTRIC SHOCK HAZARD Informational Note: The purpose of these isolating devices are
TERMINALS ON THE LINE AND LOAD for the safe and convenient replacement or service of specific
SIDES MAY BE PV system equipment without exposure to energized conduc‐
ENERGIZED IN THE OPEN POSITION tors.

The warning sign(s) or label(s) shall comply with 110.21(B). (A) Location. Isolating devices or equipment disconnecting
means shall be installed in circuits connected to equipment at
(C) Suitable for Use. If the PV system is connected to the a location within the equipment, or within sight and within 3 m
supply side of the service disconnecting means as permitted in (10 ft) of the equipment. An equipment disconnecting means
230.82(6), the PV system disconnecting means shall be listed as shall be permitted to be remote from the equipment where the
suitable for use as service equipment. equipment disconnecting means can be remotely operated
(D) Maximum Number of Disconnects. Each PV system from within 3 m (10 ft) of the equipment.
disconnecting means shall consist of not more than six switches N (B) Interrupting Rating. An equipment disconnecting means
or six sets of circuit breakers, or a combination of not more shall have an interrupting rating sufficient for the maximum
than six switches and sets of circuit breakers, mounted in a short-circuit current and voltage that is available at the termi‐
single enclosure, or in a group of separate enclosures. A single nals of the equipment. An isolating device shall not be
PV system disconnecting means shall be permitted for the required to have an interrupting rating.
combined ac output of one or more inverters or ac modules in
an interactive system. N (C) Isolating Device. An isolating device shall not be required
to simultaneously disconnect all current-carrying conductors of
Informational Note: This requirement does not limit the
number of PV systems connected to a service as permitted in
a circuit. The isolating device shall be one of the following:
690.4(D). This requirement allows up to six disconnecting (1) A connector meeting the requirements of 690.33 and
means to disconnect a single PV system. For PV systems where listed and identified for use with specific equipment
all power is converted through interactive inverters, a dedicated (2) A finger safe fuse holder
circuit breaker, in 705.12(B)(1), is an example of a single (3) An isolating switch that requires a tool to open
PV system disconnecting means.
(4) An isolating device listed for the intended application
(E) Ratings. The PV system disconnecting means shall have
An isolating device shall be rated to open the maximum
ratings sufficient for the maximum circuit current available
circuit current under load or be marked “Do Not Disconnect
short-circuit current, and voltage that is available at the termi‐
Under Load” or “Not for Current Interrupting.”
nals of the PV system disconnect.
N (D) Equipment Disconnecting Means. An equipment discon‐
necting means shall simultaneously disconnect all current-
carrying conductors that are not solidly grounded of the circuit

2017 Edition NATIONAL ELECTRICAL CODE 70 –563


690.31 ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS

to which it is connected. An equipment disconnecting means (1) Identification. PV system circuit conductors shall be iden‐
shall be externally operable without exposing the operator to tified at all accessible points of termination, connection, and
contact with energized parts, shall indicate whether in the splices.
open (off) or closed (on) position, and shall be lockable in
accordance with 110.25. An equipment disconnecting means The means of identification shall be permitted by separate
shall be one of the following devices: color coding, marking tape, tagging, or other approved means.
Only solidly grounded PV system circuit conductors, in accord‐
(1) A manually operable switch or circuit breaker ance with 690.41(A)(5), shall be marked in accordance with
(2) A connector meeting the requirements of 690.33(E)(1) 200.6.
(3) A load break fused pull out switch
(4) A remote-controlled circuit breaker that is operable Exception: Where the identification of the conductors is evident by spac‐
locally and opens automatically when control power is ing or arrangement, further identification shall not be required.
interrupted •
(2) Grouping. Where the conductors of more than one
For equipment disconnecting means, other than those PV system occupy the same junction box or raceway with a
complying with 690.33, where the line and load terminals can removable cover(s), the ac and dc conductors of each system
be energized in the open position, the device shall be marked shall be grouped separately by cable ties or similar means at
in accordance with the warning in 690.13(B). least once and shall then be grouped at intervals not to exceed
• 1.8 m (6 ft).
Exception: The requirement for grouping shall not apply if the circuit
Part IV. Wiring Methods enters from a cable or raceway unique to the circuit that makes the
690.31 Methods Permitted. grouping obvious.

(A) Wiring Systems. All raceway and cable wiring methods (C) Single-Conductor Cable.
included in this Code, other wiring systems and fittings specifi‐ (1) General. Single-conductor cable Type USE-2 and single-
cally listed for use on PV arrays, and wiring as part of a listed conductor cable listed and identified as photovoltaic (PV)
system shall be permitted. Where wiring devices with integral wire shall be permitted in exposed outdoor locations in
enclosures are used, sufficient length of cable shall be provided PV source circuits within the PV array. PV wire shall be
to facilitate replacement. installed in accordance with 338.10(B)(4)(b) and 334.30.
• (2) Cable Tray. PV source circuits and PV output circuits
Where PV source and output circuits operating at voltages
greater than 30 volts are installed in readily accessible loca‐ using single-conductor cable listed and identified as
tions, circuit conductors shall be guarded or installed in photovoltaic (PV) wire of all sizes, with or without a cable
Type MC cable or in raceway. For ambient temperatures tray marking/rating, shall be permitted in cable trays
exceeding 30°C (86°F), conductor ampacities shall be correc‐ installed in outdoor locations, provided that the cables
ted in accordance with Table 690.31(A). are supported at intervals not to exceed 300 mm (12 in.)
• and secured at intervals not to exceed 1.4 m (41∕2 ft).
(B) Identification and Grouping. PV source circuits and
Informational Note: Photovoltaic wire and PV cable have a
PV output circuits shall not be contained in the same raceway, nonstandard outer diameter. Table 1 of Chapter 9 contains the
cable tray, cable, outlet box, junction box, or similar fitting as allowable percent of cross section of conduit and tubing for
conductors, feeders, branch circuits of other non-PV systems, conductors and cables.
or inverter output circuits, unless the conductors of the differ‐
ent systems are separated by a partition. PV system circuit (D) Multiconductor Cable. Jacketed multiconductor cable
conductors shall be identified and grouped as required by assemblies listed and identified for the application shall be
690.31(B)(1) through (2). The means of identification shall be permitted in outdoor locations. The cable shall be secured at
permitted by separate color coding, marking tape, tagging, or intervals not exceeding 1.8 m (6 ft).
other approved means.

N Table 690.31(A) Correction Factors

Temperature Rating of Conductor


Ambient Temperature 60°C 75°C 90°C 105°C Ambient Temperature
(°C) (140°F) (167°F) (194°F) (221°F) (°F)
30 1.00 1.00 1.00 1.00 86
31–35 0.91 0.94 0.96 0.97 87–95
36–40 0.82 0.88 0.91 0.93 96–104
41–45 0.71 0.82 0.87 0.89 105–113
46–50 0.58 0.75 0.82 0.86 114–122
51–55 0.41 0.67 0.76 0.82 123–131
56–60 — 0.58 0.71 0.77 132–140
61–70 — 0.33 0.58 0.68 141–158
71–80 — — 0.41 0.58 159–176

70 –564 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS 690.33

(E) Flexible Cords and Cables Connected to Tracking (3) Conduit bodies in which any of the available conduit
PV Arrays. Flexible cords and flexible cables, where connec‐ openings are unused
ted to moving parts of tracking PV arrays, shall comply with
Article 400 and shall be of a type identified as a hard service (4) Marking and Labeling Methods and Locations. The labels
cord or portable power cable; they shall be suitable for extra- or markings shall be visible after installation. The labels shall
hard usage, listed for outdoor use, water resistant, and sunlight be reflective, and all letters shall be capitalized and shall be a
resistant. Allowable ampacities shall be in accordance with minimum height of 9.5 mm (3∕8 in.) in white on a red back‐
400.5. Stranded copper PV wire shall be permitted to be ground. PV system dc circuit labels shall appear on every
connected to moving parts of tracking PV arrays in accordance section of the wiring system that is separated by enclosures,
with the minimum number of strands specified in Table walls, partitions, ceilings, or floors. Spacing between labels or
690.31(E). markings, or between a label and a marking, shall not be more
• than 3 m (10 ft). Labels required by this section shall be suita‐
(F) Small-Conductor Cables. Single-conductor cables listed ble for the environment where they are installed.
for outdoor use that are sunlight resistant and moisture resist‐
ant in sizes 16 AWG and 18 AWG shall be permitted for module (H) Flexible, Fine-Stranded Cables. Flexible, fine-stranded
interconnections where such cables meet the ampacity require‐ cables shall be terminated only with terminals, lugs, devices, or
ments of 400.5. Section 310.15 shall be used to determine the connectors in accordance with 110.14.
cable ampacity adjustment and correction factors. (I) Bipolar Photovoltaic Systems. Where the sum, without
(G) Photovoltaic System Direct Current Circuits on or in a consideration of polarity, of the voltages of the two monopole
Building. Where PV system dc circuits run inside a building, subarrays exceeds the rating of the conductors and connected
they shall be contained in metal raceways, Type MC metal-clad equipment, monopole subarrays in a bipolar PV system shall be
cable that complies with 250.118(10), or metal enclosures from physically separated, and the electrical output circuits from
the point of penetration of the surface of the building to the each monopole subarray shall be installed in separate raceways
first readily accessible disconnecting means. The disconnecting until connected to the inverter. The disconnecting means and
means shall comply with 690.13(B) and (C) and 690.15(A) and overcurrent protective devices for each monopole subarray
(B). The wiring methods shall comply with the additional output shall be in separate enclosures. All conductors from
installation requirements in 690.31(G)(1) through (4). each separate monopole subarray shall be routed in the same
raceway. Solidly grounded bipolar PV systems shall be clearly
(1) Embedded in Building Surfaces. Where circuits are marked with a permanent, legible warning notice indicating
embedded in built-up, laminate, or membrane roofing materi‐ that the disconnection of the grounded conductor(s) may
als in roof areas not covered by PV modules and associated result in overvoltage on the equipment.
equipment, the location of circuits shall be clearly marked
using a marking protocol that is approved as being suitable for Exception: Listed switchgear rated for the maximum voltage between
continuous exposure to sunlight and weather. circuits and containing a physical barrier separating the disconnecting
means for each monopole subarray shall be permitted to be used instead
(2) Flexible Wiring Methods. Where flexible metal conduit of disconnecting means in separate enclosures.
(FMC) smaller than metric designator 21 (trade size 3∕4) or •
Type MC cable smaller than 25 mm (1 in.) in diameter contain‐ 690.32 Component Interconnections. Fittings and connectors
ing PV power circuit conductors is installed across ceilings or that are intended to be concealed at the time of on-site assem‐
floor joists, the raceway or cable shall be protected by substan‐ bly, where listed for such use, shall be permitted for on-site
tial guard strips that are at least as high as the raceway or cable. interconnection of modules or other array components. Such
Where run exposed, other than within 1.8 m (6 ft) of their fittings and connectors shall be equal to the wiring method
connection to equipment, these wiring methods shall closely employed in insulation, temperature rise, and fault-current
follow the building surface or be protected from physical withstand, and shall be capable of resisting the effects of the
damage by an approved means. environment in which they are used.

(3) Marking and Labeling Required. The following wiring 690.33 Connectors. Connectors, other than those covered by
methods and enclosures that contain PV system dc circuit 690.32, shall comply with 690.33(A) through (E).
conductors shall be marked with the wording WARNING: (A) Configuration. The connectors shall be polarized and
PHOTOVOLTAIC POWER SOURCE by means of permanently shall have a configuration that is noninterchangeable with
affixed labels or other approved permanent marking: receptacles in other electrical systems on the premises.
(1) Exposed raceways, cable trays, and other wiring methods (B) Guarding. The connectors shall be constructed and instal‐
(2) Covers or enclosures of pull boxes and junction boxes led so as to guard against inadvertent contact with live parts by
persons.
(C) Type. The connectors shall be of the latching or locking
type. Connectors that are readily accessible and that are used in
N Table 690.31(E) Minimum PV Wire Strands circuits operating at over 30 volts dc or 15 volts ac shall require
a tool for opening.
PV Wire AWG Minimum Strands
(D) Grounding Member. The grounding member shall be the
18 17 first to make and the last to break contact with the mating
16–10 19 connector.
8–4 49
2 130 (E) Interruption of Circuit. Connectors shall be either (1) or
1 AWG–1000 MCM 259 (2):

2017 Edition NATIONAL ELECTRICAL CODE 70 –565


690.34 ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS

(1) Be rated for interrupting current without hazard to the less of voltage. Equipment grounding conductors and devices
operator. shall comply with 690.43(A) through (C).
(2) Be a type that requires the use of a tool to open and
marked “Do Not Disconnect Under Load” or “Not for (A) Photovoltaic Module Mounting Systems and Devices.
Current Interrupting.” Devices and systems used for mounting PV modules that are
also used for bonding module frames shall be listed, labeled,
690.34 Access to Boxes. Junction, pull, and outlet boxes loca‐ and identified for bonding PV modules. Devices that mount
ted behind modules or panels shall be so installed that the adjacent PV modules shall be permitted to bond adjacent
wiring contained in them can be rendered accessible directly PV modules.
or by displacement of a module(s) or panel(s) secured by
removable fasteners and connected by a flexible wiring system. (B) Equipment Secured to Grounded Metal Supports.
• Devices listed, labeled, and identified for bonding and ground‐
ing the metal parts of PV systems shall be permitted to bond
Part V. Grounding and Bonding the equipment to grounded metal supports. Metallic support
structures shall have identified bonding jumpers connected
690.41 System Grounding. between separate metallic sections or shall be identified for
• equipment bonding and shall be connected to the equipment
(A) PV System Grounding Configurations. One or more of grounding conductor.
the following system grounding configurations shall be
employed: (C) With Circuit Conductors. Equipment grounding conduc‐
(1) 2-wire PV arrays with one functional grounded conductor tors for the PV array and support structure (where installed)
(2) Bipolar PV arrays according to 690.7(C) with a functional shall be contained within the same raceway, cable, or otherwise
ground reference (center tap) run with the PV array circuit conductors when those circuit
(3) PV arrays not isolated from the grounded inverter output conductors leave the vicinity of the PV array.

circuit 690.45 Size of Equipment Grounding Conductors. Equip‐
(4) Ungrounded PV arrays ment grounding conductors for PV source and PV output
(5) Solidly grounded PV arrays as permitted in 690.41(B) circuits shall be sized in accordance with 250.122. Where no
Exception overcurrent protective device is used in the circuit, an assumed
(6) PV systems that use other methods that accomplish equiv‐ overcurrent device rated in accordance with 690.9(B) shall be
alent system protection in accordance with 250.4(A) with used when applying Table 250.122. Increases in equipment
equipment listed and identified for the use grounding conductor size to address voltage drop considera‐
(B) Ground-Fault Protection. DC PV arrays shall be provided tions shall not be required. An equipment grounding conduc‐
with dc ground-fault protection meeting the requirements of tor shall not be smaller than 14 AWG.
690.41(B)(1) and (2) to reduce fire hazards. 690.46 Array Equipment Grounding Conductors. For
Exception: PV arrays with not more than two PV source circuits and PV modules, equipment grounding conductors smaller than
with all PV system dc circuits not on or in buildings shall be permitted 6 AWG shall comply with 250.120(C).

without ground-fault protection where solidly grounded. 690.47 Grounding Electrode System.
(1) Ground-Fault Detection. The ground fault protective (A) Buildings or Structures Supporting a PV Array. A building
device or system shall detect ground fault(s) in the PV array dc or structure supporting a PV array shall have a grounding elec‐
current–carrying conductors and components, including any trode system installed in accordance with Part III of Article 250.
functional grounded conductors, and be listed for providing
PV ground-fault protection. PV array equipment grounding conductors shall be connec‐
• ted to the grounding electrode system of the building or struc‐
(2) Isolating Faulted Circuits. The faulted circuits shall be ture supporting the PV array in accordance with Part VII of
isolated by one of the following methods: Article 250. This connection shall be in addition to any other
(1) The current-carrying conductors of the faulted circuit equipment grounding conductor requirements in 690.43(C).
shall be automatically disconnected. The PV array equipment grounding conductors shall be sized
(2) The inverter or charge controller fed by the faulted in accordance with 690.45.
circuit shall automatically cease to supply power to output For PV systems that are not solidly grounded, the equipment
circuits and isolate the PV system dc circuits from the grounding conductor for the output of the PV system, connec‐
ground reference in a functional grounded system. ted to associated distribution equipment, shall be permitted to

690.42 Point of System Grounding Connection. Systems with be the connection to ground for ground-fault protection and
a ground-fault protective device in accordance with 690.41(B) equipment grounding of the PV array.
shall have any current-carrying conductor-to-ground connec‐ For solidly grounded PV systems, as permitted in 690.41(A)
tion made by the ground-fault protective device. For solidly (5), the grounded conductor shall be connected to a ground‐
grounded PV systems, the dc circuit grounding connection ing electrode system by means of a grounding electrode
shall be made at any single point on the PV output circuit. conductor sized in accordance with 250.166.

690.43 Equipment Grounding and Bonding. Exposed non– Informational Note: Most PV systems installed in the past
current-carrying metal parts of PV module frames, electrical decade are actually functional grounded systems rather than
equipment, and conductor enclosures of PV systems shall be solidly grounded systems as defined in this Code. For functional
grounded in accordance with 250.134 or 250.136(A), regard‐ grounded PV systems with an interactive inverter output, the ac
equipment grounding conductor is connected to associated
grounded ac distribution equipment. This connection is often

70 –566 NATIONAL ELECTRICAL CODE 2017 Edition


ARTICLE 690 — SOLAR PHOTOVOLTAIC (PV) SYSTEMS 690.56

the connection to ground for ground-fault protection and 690.55 Photovoltaic Systems Connected to Energy Storage
equipment grounding of the PV array. Systems. The PV system output circuit conductors shall be
N (B) Additional Auxiliary Electrodes for Array Grounding. marked to indicate the polarity where connected to energy
Grounding electrodes shall be permitted to be installed in storage systems.
accordance with 250.52 and 250.54 at the location of ground- 690.56 Identification of Power Sources.
and roof-mounted PV arrays. The electrodes shall be permitted
to be connected directly to the array frame(s) or structure. The (A) Facilities with Stand-Alone Systems. Any structure or
grounding electrode conductor shall be sized according to building with a PV power system that is not connected to a util‐
250.66. The structure of a ground-mounted PV array shall be ity service source and is a stand-alone system shall have a
permitted to be considered a grounding electrode if it meets permanent plaque or directory installed on the exterior of the
the requirements of 250.52. Roof mounted PV arrays shall be building or structure at a readily visible location. The plaque or
permitted to use the metal frame of a building or structure if directory shall indicate the location of system disconnecting
the requirements of 250.52(A)(2) are met. means and that the structure contains a stand-alone electrical
• power system.
690.50 Equipment Bonding Jumpers. Equipment bonding
jumpers, if used, shall comply with 250.120(C). (B) Facilities with Utility Services and Photovoltaic Systems.
Plaques or directories shall be installed in accordance with
705.10.
Part VI. Marking (C) Buildings with Rapid Shutdown. Buildings with PV
690.51 Modules. Modules shall be marked with identification systems shall have permanent labels as described in 690.56(C)
of terminals or leads as to polarity, maximum overcurrent (1) through (C)(3).
device rating for module protection, and with the following N (1) Rapid Shutdown Type. The type of PV system rapid shut‐
ratings: down shall be labeled as described in 690.56(C)(1)(a) or
(1) Open-circuit voltage (1)(b):
(2) Operating voltage (a) For PV systems that shut down the array and conduc‐
(3) Maximum permissible system voltage tors leaving the array:
(4) Operating current
(5) Short-circuit current SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUT‐
(6) Maximum power DOWN.
TURN RAPID SHUTDOWN SWITCH TO THE “OFF” POSI‐
690.52 Alternating-Current Photovoltaic Modules. TION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK
Alternating-current modules shall be marked with identifica‐ HAZARD IN ARRAY.
tion of terminals or leads and with identification of the follow‐
ing ratings: The title “SOLAR PV SYSTEM IS EQUIPPED WITH RAPID
SHUTDOWN” shall utilize capitalized characters with a mini‐
(1) Nominal operating ac voltage mum height of 9.5 mm (3∕8 in.) in black on yellow background,
(2) Nominal operating ac frequency and the remaining characters shall be capitalized with a mini‐
(3) Maximum ac power mum height of 4.8 mm (3∕16 in.) in black on white background.
(4) Maximum ac current [See Figure 690.56(C)(1)(a).]
(5) Maximum overcurrent device rating for ac module (b) For PV systems that only shut down conductors leav‐
protection ing the array:
690.53 Direct-Current Photovoltaic Power Source. A perma‐ SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUT‐
nent label for the dc PV power source indicating the informa‐ DOWN
tion specified in (1) through (3) shall be provided by the TURN RAPID SHUTDOWN SWITCH TO THE “OFF” POSI‐
installer at dc PV system disconnecting means and at each TION TO SHUT DOWN
dc equipment disconnecting means required by 690.15. Where CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS IN
a disconnecting means has more than one dc PV power source, ARRAY REMAIN
the values in 690.53(1) through (3) shall be specified for each ENERGIZED IN SUNLIGHT.
source.
The title “SOLAR PV SYSTEM IS EQUIPPED WITH RAPID
(1) Maximum voltage
SHUTDOWN” shall utilize capitalized characters with a mini‐
Informational Note to (1): See 690.7 for voltage. mum height of 9.5 mm (3∕8 in.) in white on red background,
and the remaining characters shall be capitalized with a mini‐
(2) Maximum circuit current mum height of 4.8 mm (3∕16 in.) in black on white background.
Informational Note to (2): See 690.8(A) for calculation of maxi‐ [See Figure 690.56(C)(1)(b).]
mum circuit current.
The labels in 690.56(C)(1)(a) and (b) shall include a simple
(3) Maximum rated output current of the charge controller diagram of a building with a roof. The diagram shall have
or dc-to-dc converter (if installed) sections in red to signify sections of the PV system that are not
• shut down when the rapid shutdown switch is operated.
690.54 Interactive System Point of Interconnection. All inter‐
active system(s) points of interconnection with other sources The rapid shutdown label in 690.56(C)(1) shall be located
shall be marked at an accessible location at the disconnecting on or no more than 1 m (3 ft) from the service disconnecting
means as a power source and with the rated ac output current means to which the PV systems are connected and shall indi‐
and the nominal operating ac voltage.

2017 Edition NATIONAL ELECTRICAL CODE 70 –567


690.56 ARTICLE 691 — LARGE-SCALE PHOTOVOLTAIC (PV) ELECTRIC POWER PRODUCTION FACILITY

Part VII. Connection to Other Sources


SOLAR PV SYSTEM EQUIPPED N 690.59 Connection to Other Sources. PV systems connected
to other sources shall be installed in accordance with Parts I
WITH RAPID SHUTDOWN •
and II of Article 705.

TURN RAPID SHUTDOWN


Part VIII. Energy Storage Systems
SWITCH TO THE SOLAR ELECTRIC 690.71 General. An energy storage system connected to a
“OFF” POSITION TO PV PANELS PV system shall be installed in accordance with Article 706.
SHUT DOWN PV SYSTEM •
AND REDUCE 690.72 Self-Regulated PV Charge Control. The PV source
SHOCK HAZARD circuit shall be considered to comply with the requirements of
IN THE ARRAY. 706.23 if:
(1) The PV source circuit is matched to the voltage rating
and charge current requirements of the interconnected
battery cells and,
(2) The maximum charging current multiplied by 1 hour is
N FIGURE 690.56(C)(1)(a) Label for PV Systems that Shut less than 3 percent of the rated battery capacity expressed
Down the Array and the Conductors Leaving the Array. in ampere-hours or as recommended by the battery
manufacturer

cate the location of all identified rapid shutdown switches if not
at the same location.
N (2) Buildings with More Than One Rapid Shutdown Type.
For buildings that have PV systems with both rapid shutdown
types or a PV system with a rapid shutdown type and a
N ARTICLE 691
PV system with no rapid shutdown, a detailed plan view Large-Scale Photovoltaic (PV) Electric
diagram of the roof shall be provided showing each different Power Production Facility
PV system and a dotted line around areas that remain ener‐
gized after the rapid shutdown switch is operated.
N (3) Rapid Shutdown Switch. A rapid shutdown switch shall 691.1 Scope. This article covers the installation of large-scale
have a label located on or no more than 1 m (3 ft) from the PV electric power production facilities with a generating
switch that includes the following wording: capacity of no less than 5000 kW, and not under exclusive util‐
ity control.
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
Informational Note No. 1: Facilities covered by this article have
The label shall be reflective, with all letters capitalized and specific design and safety features unique to large-scale PV facili‐
having a minimum height of 9.5 mm (3∕8 in.), in white on red ties and are operated for the sole purpose of providing electric
background. supply to a system operated by a regulated utility for the transfer
of electric energy.
Informational Note No. 2: Section 90.2(B)(5) includes informa‐
tion about utility-owned properties not covered under this Code.
For additional information on electric supply stations, see
ANSI/IEEE C2-2012, National Electrical Safety Code.
691.2 Definitions.
SOLAR PV SYSTEM EQUIPPED Electric Supply Stations. Locations containing the generating
WITH RAPID SHUTDOWN stations and substations, including their associated generator,
storage battery, transformer, and switchgear areas.
Generating Capacity. The sum of the parallel-connected inver‐
TURN RAPID SHUTDOWN
ter rated maximum continuous output power at 40°C in kilo‐
SWITCH TO THE
SOLAR ELECTRIC
watts (kW).
“OFF” POSITION TO
PV PANELS
SHUT DOWN CONDUCTORS Generating Station. A plant wherein electric energy is
OUTSIDE THE ARRAY. produced by conversion from some other form of energy (e.g.,
CONDUCTORS WITHIN chemical, nuclear, solar, wind, mechanical, or hydraulic) by
THE ARRAY REMAIN means of suitable apparatus.
ENERGIZED IN SUNLIGHT.
691.4 Special Requirements for Large-Scale PV Electric Supply
Stations. Large-scale PV electric supply stations shall be acces‐
sible only to authorized personnel and comply with the follow‐
ing:
N FIGURE 690.56(C)(1)(b) Label for PV Systems that Shut
Down the Conductors Leaving the Array Only.

70 –568 NATIONAL ELECTRICAL CODE 2017 Edition

Potrebbero piacerti anche