Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Chapter
2
EQUIPMENT EARTHING
1. General
In the preceding chapter, the principles of system earthing have been discussed. Also,
the performance of the earthed and isolated systems under fault conditions has been
explained. Thus, the advantages and disadvantages of neutral earthing have been
presented.
In this chapter, specific equipment earthing is explained. Two important examples of
equipment are dealt with here, namely, the transformer neutral point earthing and
earthing of the equipment of a high voltage laboratory or similar.
2. Transformer neutral point earthling
It has been found through practice that single live to ground faults represents from 70
to 90 of the total network faults. Hence, the earthing of the transformer neutral point is
of considerable importance.
The selection of the earthing of the neutral point depends on the system voltage as well
as on the system MVA capacity. Thus, the neutral point of a transformer is earthed by
one of the following methods:
1. Direct earthing to ground.
2. Earthing through a suitable impedance.
a. Resistance grounding.
b. Reactance grounding.
c. Tuned reactor or Peterson coil.
2.1 Direct earthing
This method is called earthing or solidly grounding and can be used when the
transformer capacity is too small compared to the system capacity to help stabilizing the
voltage when a phase is short circuited to ground. It generally provides for almost equal
voltages for the 3-phases however the current is different in them.
As well, direct earthing is used for earthing transformers in case of isolated systems to
provide a feeding source for the protective relays.
Effective grounding in such a system is appropriate.
Ch.#2
1
EQUIPMENT EARTHING
It is clear that earthing the neutral point directly is the cheapest for the following
reasons:
1. No equipment like a resistor or inductor.... etc. is required.
2. Only an arrester is used in parallel with the neutral point isolating switch to absorb
over voltages at the neutral point.
3. Case of winding Y connection, the cost is minimum, case of A connection an
earthing transformer can be used increasing the cost to a limited extent.
Advantages
A major advantage for this method of earthing is that the resulting short circuit current
under all types of S.C. faults, is sufficient to operate the protective relays.
Disadvantages
1. Single line to ground faults may result in high current values exceeding the 3-ph S.C.
current, requiring higher S.C. capacity circuit breakers.
2. High S.C. currents may contain “high frequency oscillations, interfering with
communication circuits.
This disadvantages could be overcome by using high speed circuit breakers, working at
very short times, thus not affected by high frequency oscillations. In this case, the S.C.
capacity required is the 3-ph S.C. capacity.
2.2 Earthing through a suitable impedance
As a single line to ground S.C. takes place, the S.C. current shall be too high to reduce
the S.C. current by a defined value, an impedance is connected by the transformer
neutral point and the ground. This impedance can be:
1. A resistance.
2. A reactance, see Fig (2).
Thus, it is noted here that a better performance of the system is obtained with earthing
through a suitable impedance other than in cases of an insulated system or a directly
earthed one.
The effective grounding can be defined from sec. 32 - 1.05 of AIEE standard No 32
May 1974.
Ch.#2
2
EQUIPMENT EARTHING
Example:
In case of earthing through suitable impedance, there is no danger for supply continuity
as the current at the fault point does not cause rapid breakdown. The S.C. current is the
sum of the capacitive current and the current through the neutral point impedance.
Ch.#2
3
EQUIPMENT EARTHING
Fig. 2
In many cases, the earthing impedance may be increased to the extent that only normal
active currents pass through the point of S.C. fault. Further as a result of only active
current flow through the arcing fault point the arcing is less rigorous and can be
allowed for the short duration required for the protective gear to operate.
Earthing through a suitable impedance can be:
1. Resistance grounding.
2. Reactor grounding.
3. Tuned reactor or Peterson coil.
2.2.1 Resistance Grounding
In this system, a suitable resistance is connected between the neutral point and the
ground. In most cases the earthing resistance value is taken larger than the system
reactance. The single line to ground S.C. current is defined according to the earthing
resistance. As well, the earthing resistance can be defined according to the value of the
S.C. current allowed to flow during the S.C. period, Fig (3). The power loss in the
resistor during a S.C. fault should be considered. Fig. (4) presents for example the
relation between the power loss (as percentage of the system capacity) and the
grounding resistance value (as percentage of the system impedance). Ch.#2
4
EQUIPMENT EARTHING
Fig. 4
Example:
In the given system
X1=X2=16% X1=X2=x0=8%
Z0=3R+j8
Z1 =Z2=j(16+8)=j24
3 100 300
PermitFaultCurrent I f = =
3R + j8 + j 24 + j 24 3R + j 56
5
EQUIPMENT EARTHING
Fig. 5
6
EQUIPMENT EARTHING
Fig. 7
L = 25 - 30 cms
8
EQUIPMENT EARTHING
Fig. 8:
Fig.9
In this case, the neutral point is grounded through a reactance. In many cases, this
taked the form of a grounding transformer which is normally used to ground delta
connected transformers.
The earthing transformer is a short-time device, i.e. operates during short durations of
the faults. Therefore, its size and cost is much less than a power transformer having the
Ch.#2
9
EQUIPMENT EARTHING
same capacity but continuous duty one. The earthing transformer can be two windings
of transformation ratio 1:1, Z connected as in Fig (10).
The specifications of a typical earthing transformer are as follows:
• Class A.
• 3-phase.
• 50Hz.
• Voltage rating 11000 v zig zag.
• Designed to introduce 22 - 29 ohm impedance between each line terminal and
neutral.
• To carry 850 amp through the neutral bushing to ground for 10 sec without exceeding
a final temperature of218°C.
Fig. 10
10
EQUIPMENT EARTHING
The neutral points in H.V. networks are usually isolated. To operate the protection
equipment during faults, it is due to add an arc suppression coil between the neutral
point of the power transformer and the ground. Through this coil, called Peterson Coil,
the coil current IL compensates the capacitive current IC such that the difference
between them, which is the arc current (fault current) shall be very small, and the arc is
suppressed at the fault point, avoiding burning of conductors and breakdown of
insulation.
Ch.#2
11
EQUIPMENT EARTHING
Multilayer earthing network has been provided, use is made of the steel reinforcement
bars as an earthing network. The oxide layer acts chemically with the concrete and the
bar surface becomes conducting. As special steel is used for reinforcement it was not
permitted to weld to it. The following procedures has been adopted:
3.1 First Earthing Layer
A network composed of soft iron bars (two bars 10 mm 0 each) laid over the steel
reinforcement spaced 1.35 m apart & wrapped to the upper layer by soft iron wire.
The cross points of the soft iron mesh should be electrically welded. Each cross point
welding should be carefully checked to ensure solid connection (mechanical test is
sufficient).
Ch.#2
12
EQUIPMENT EARTHING
Copper bars of 100 mm2 section (25 x 4mm) are laid at a spacing of 2.7 m. over the soft
iron network as shown in the sketch.
The copper bars are brazed at the cross points via copper to copper and copper to soft
iron at all cross points.
Ch.#2
13
EQUIPMENT EARTHING
Important note:
All welding and brazing at cross points should be well checked point by point to ensure
good mechanical and electrical connection.
At the cross points (cu - cu) two earthing leads of flexible copper cable are brought out
to connect: a) the flanged pipe pieces which support the columns of the protecting
earthed fence, b) to the final expanded copper mesh layer which forms the 3rd earthed
layer.
Copper network & earthed flanged pipe pieces Sketch of flanged pipe pieces placed at
2.7 m distance to serve as support for protecting earthed fence.
14
EQUIPMENT EARTHING
Expanded copper mesh pieces 80cm length 25mm width brazed to the flanged pipe
piece. The arms are brazed 10 the expanded metal copper mesh layer.
Ch.#2
15
EQUIPMENT EARTHING
Bitail of copper mesh arms of the flanged arms of the flanged pipe piece
3.5 Suggestions for desert areas
As the site of the projected lab is in a desert area where the earth resistance may
be high, earthing electrodes at the corners of the lab building with copper
electrode inside steel pipe reaching the subsoil level, electrode & pipe connected
electrically together.
Ch.#2
16