Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
High Impedance
Differential Protection
ABCD
blank page
MX3DVZ3A MDE/B133 2511 001
CONTENTS
1. TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. GENERAL CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Selecting rated values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Single-phase overcurrent protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Undervoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 X2/DVZ3R Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.5 Breaker failure protection (BF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Main and spare settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. ADDITIONAL FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Output circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 LED signalling circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.5 Additional timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.6 Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.7 Event logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.8 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.9 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.10 Alphanumeric user identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.11 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.12 LCD settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.13 Inhibiting operation - Deconfiguration via network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.14 Serial communication on LONWORKS (TM) bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.15 RS485 serial communication and MODBUS protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.16 Fault recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.17 Checking tripping circuits for continuity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5. LOCAL INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
pag. 3
MX3DVZ3A MDE/B133 2511 001
8. INSTALLATION - TRANSPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.1 ESD Electrostatic Charges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.2 Acceptance - storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.3 Assembling and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.4 X2/DVZ3R Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
pag. 4
MX3DVZ3A MDE/B133 2511 001
Measurement functions:
VOLTAGE MEASUREMENT INPUTS
effective values of single-pole currents (IA, IB, IC) expressed rated voltage: Un: 40 ÷ 130 V
in multiples of In measurement range: 0 ÷ 200 V
effective values of single-pole voltages (UA, UB, UC) ex- continuous thermal withstand: 200 V
short-time (10 sec.) thermal withstand: 250 V
pressed in multiples of Un
burden at 100 V: ≤ 0.6 VA per phase
max. values of single-pole currents (IA, IB, IC) expressed in
multiples of In
OVERCURRENT PROTECTION
max. values of single-pole voltages (UA,UB,UC) expressed
input IA
in multiples of Un first threshold IA>: 0.02÷2 In / OFF
logging of the latest 8 occurrences (events), with storage of starting signalling delay tstart: 0.00 ÷ 9.99 s
tripped threshold values, date, time. operating time t1: 0.02 ÷ 600 s
second threshold IA>>: 0.02÷10 In / OFF
Fault recorder: recording, for a total time of 2.5 s, of the
instant values (12 samples per period) taken by all input input IB
quantities and logical states of end relays, LED's, digital first threshold IB>: 0.02÷2 In / OFF
inputs and auxiliary timers. starting signalling delay tstart: 0.00 ÷ 9.99 s
operating time t2: 0.02 ÷ 600 s
RCE: recording of the latest 32 changes of state (followed
second threshold IB>>: 0.02÷10 In / OFF
by the related date and time values); which may solely be
acceded to via PC or network-connection. input IC
first threshold IC>: 0.02÷2 In / OFF
starting signalling delay tstart: 0.00 ÷ 9.99 s
operating time t3: 0.02 ÷ 600 s
second threshold IC>>: 0.02÷10 In / OFF
pag. 5
MX3DVZ3A MDE/B133 2511 001
input UB
Digital inputs
first threshold UB>: 0.01÷1.5 Un / OFF
starting signalling delay tstart: 0.00 ÷ 9.99 s MX3DVZ3A.11, .61 and .71 versions
operating time t5: 0.02 ÷ 600 s Uaux IN DIG: 19 ÷ 100 Vcc
input resistance: 9 kohm
input UC MX3DVZ3A.12, .62 and .72 versions
first threshold UC>: 0.01÷1.5 Un / OFF Uaux IN DIG: 64 ÷ 264 Vcc
starting signalling delay tstart: 0.00 ÷ 9.99 s input resistance: 48 kohm
operating time t6: 0.02 ÷ 600 s
settings step 0.01 Errors of measuring equipment
Current thresholds
UNDERVOLTAGE PROTECTION relative error : ≤ 3 % of set value + 0.1% In
Input UA consistency: ≤ 1 % of set value + 0.1% In
first threshold UA<: 0.05÷1 Un / OFF Voltage thresholds
steps 0.01 Un relative error : ≤ 2.5% of set value + 0.02 V
starting signalling delay tstart: 0.00 ÷ 9.99 s consistency: ≤ 1% of set value + 0.02 V
operating time t7: 0.02 ÷ 600 s
time steps 0.01 s
Error variation
input UB as frequency varies within the ± 5% fn range with ≤ 5% distortion factor
first threshold UB<: 0.05÷1 Un / OFF Overcurrent threshold
steps 0.01 Un
relative error: ≤ 1 % of set value + 0.05% In
starting signalling delay tstart: 0.00 ÷ 9.99 s
operating time t8: 0.02 ÷ 600 s Voltage threshold
time steps 0.01 s relative error: ≤ 1% of set value + 0.02 V
Operating ranges
Auxiliary supply
service temperature: -10 °C ÷ +60 °C
MX3DVZ3A.11, .61 and .71 versions storage and transport temperature: -25 °C ÷ +80 °C
Uaux: 19 ÷ 100 Vcc relative humidity: < 95% with no formation of condensate
Uaux: 19 ÷ 72 Vca vibration: IEC255-21-1; class 2; 0.075mm 10-60Hz; 1g 60-500Hz
MX3DVZ3A.12, .62 and .72 versions
Uaux: 64 ÷ 300 Vcc
Uaux: 64 ÷ 275 Vca Weight
frequency for Uaux in a.c.: 47 ÷ 63 Hz total: 2.5 Kg
burden (min./max.) in d.c.: 5 W / 10 W
burden (min./max.) in a.c.: 10VA / 20VA
pag. 6
MX3DVZ3A MDE/B133 2511 001
pag. 7
MX3DVZ3A MDE/B133 2511 001
pag. 8
MX3DVZ3A MDE/B133 2511 001
pag. 9
MX3DVZ3A MDE/B133 2511 001
The output relays, except for the diagnostic relay, can all be 4.6 Counters
simultaneously set to "normally energized" (NORMAL.ON=ON)
Each tripping threshold is associated with a partial and total
or "normally de-energized" (NORMAL.ON=OFF): this selection
counter.
is made by acting on the S1 jumper, which can only be reached
The counters work within the 0-9999 range; if number 9999 is
when the relay is pulled out (see fig. 2a, 2b).
exceeded, the counter is automatically reset and the count
restarts from the beginning.
4.3 LED signalling circuits All of the partial counters can be reset by acting through the
The signalling circuits are made of twelve LED's (see fig. 3). keyboard, a Personal Computer or via network.
Four LED's are rigorously assigned to previously established
signalling functions: 4.7 Event logging
- (Uaux) green LED ON in the presence of input voltage and
When a tripping event occurs, the following information is
with correct feeder output voltage values
stored in the circulating memory:
- (RUN) green LED ON with fixed light in normal conditions
- first operated threshold
and blinking during setting changing and testing functions
- day, month, year, time, minute, second and millisecond
- (RUN) red LED ON with fixed light when the diagnostic
identifying the tripping moment.
detects a fault or a condition of inhibition.
- the input current and voltage values measured when the
- (Rx Tx) green LED ON with fixed light when the device is
tripping occurred.
correctly connected, blinking with the communication
board not enabled or not properly set; OFF when the
Warning: in differential applications, the current measured
communication board is not present on the device.
during the events does not match the total fault current, as there
Each of the eight LED's left, if duly programmed from the
is no need to also consider the share that is absorbed by the
keyboard, a Personal Computer or the network, can be:
attachment X2/DVZ3R and by the system CT's (see paragraph
- set to perform one or more functions
7). Similarly, the measured voltages in the application of the
- preset for:
thresholds UA>, UB> and UC> to monitor the current circuits
- monostable operation; it immediately goes off when the
are affected by the divider and by the voltage limiter provided
cause that made it go on is removed
in the X2/DVZ3R attachment.
- bistable (MEMOR) operation; the LED remains ON until a
The information concerning one trip is called event.
reset signal is sent from the front push-button, the digital
The circulating memory allows the last 8 events to be stored,
input or the serial connection. Any failure of auxiliary voltage
and when this number is exceeded, a new record replaces the
only entails a momentary loss of the luminous signals,
older: the last event is stored as EVENT 1.
which come back again as soon as voltage is restored.
The stored events can be read from the front display unit or from
A pocket is provided close to the LED's, where LED describing
a PC serially connected to the device.
labels can be placed.
The device can also record the latest 32 changes of state (with
related date and time) and make them available exclusively
4.4 Digital Inputs through PC or via network.
Each of the three optoinsulated inputs can be associated with
one or more protection functions by duly programming them 4.8 Measurements
through keyboard, Personal Computer or via network. The
The device can display the instant values on the inputs cur-
input voltage may happen not to match the auxiliary voltage of
rents and voltages, expressed in multiples of the rated current
the device.
In and the rated voltage Un. Moreover, it can display the
The digital inputs can be programmed to be enabled by normal
maximum values they have reached since the last reset,
energizing or normal de-energizing.
always expressed in multiples of the respective rated values.
pag. 10
MX3DVZ3A MDE/B133 2511 001
- the relay test allows the output relays X1 to X5 to be 4.14 Serial communication on LONWORKS (TM) bus
sequentially selected and checked for correct operation. In
The device, in the version including the special bus board, can
this way, any external signalling or control circuit can be
communicate with a central monitoring and control system at
tested, too.
a speed equalling 1.2 5 Mbaud. The connection to the field bus
The tested relay remains energized for 150 to 200 ms.
is made through terminals: 42, 43, 44 and 45.
If starting or tripping commands are already present, the
The communication board, which can be also added later, is
test is not carried out and a dedicated message appears on
only enabled if the special S6 jumper is correctly connected,
the display unit.
while it is not in the case the jump is connected in vertical
The test on auxiliary relays does not affect counters, event
position across S5 and S6 (see fig. 2).
logs and LED's.
If the S6 jumper is connected when the communication board
is not present, the diagnostic function displays a message of
4.10 Alphanumeric user identifier failure, behaving as if the board was present and faulty.
The device can be identified in the plant by an alphanumeric Appendix A lists the parameters available for the network.
code, which can be set by the user directly on the equipment
or from a PC. With a network-linked device, the alphanumeric
code can only be modified by operating through the network.
TOP SIDE
4.11 Language
The device can display information in four languages: Italian,
English, French and Spanish. The language can be selected
through the keyboard. RELAY
FRONT
4.12 LCD settings
The display can be set for fixed (OFF) or timed (ON) back-
lighting; in the last case, the display lights up for 300s any time
a key is pressed .
pag. 11
MX3DVZ3A MDE/B133 2511 001
4.15 RS485 serial communication and MODBUS protocol This parameters can be programmed in local or remote mode.
So, the following extension of the 'RELAY DATA' menu is
Concerning the communication of devices provided with
available:
software version 2.00 and subsequent, three different versions
are possible:
[MX3DVZ3A ] relay type
- whitout any communication card (version [Sw Vers 2.00/01] software version
MX3DVZ3A .11 e .12); ñ ò
- provided with LonWorks(TM) communication card (version [PLANT IDENTIFIER]
MX3DVZ3A .61 e .62); [GenPan ] ðplant identifier
- provided with Modbus communication card (version ñ ò
MX3DVZ3A .71 e .72); [SPEED 38400 Bb] ðspeed setting
The identification of the installed communication card is [PARITY NONE ] ðparity setting
automatic. ñ ò
When using an unit provided with LonWorks(TM) communication [DATA BIT 8 ] ðdata bit setting
card, it's required first to effect the relay wiring according to its [STOP BIT 1 ] ðstop bit setting
wiring diagram and later proceed with the configuration of all ñ ò
connected devices; the automatic configuration of connected [ADDRESS 111 ] ðaddress setting
[ ]
devices is possible by connecting a PC provided with PCLTA10
or SLTA10 card, in which CORMOX2 software has been On demand is available documentation about LonWorks(TM) and Modbus
installed. versions.
When using a device provided with Modbus communication
the configuration of each relay may be realized by the front
4.16 Fault recorder
interface, or by the IRMA2 program installed on a PC connected
The device can record the course of input currents (Ia, Ib, Ic, Io)
to the relay via front plug. The configuration may be realized
and the logic states of the 8 LED's, the 5 auxiliary relays, the
also on relays not jet connected together and may be eventually
3 digital inputs and the 3 additional timers. The total recording
organized in files together with all other settings.
time equals 2.5s, and can be divided into variable time before
start-up and variable time after start-up. The fault recorder
function can be started for: tstart, tripping, enabling of digital
Modbus communication card configuration requires:
inputs and timers. The selection of the starting parameters,
the graphic display and reset of fault recorder can be made
PARAMETER VALUE through a PC or a network. The function can even be reset by
interrupting the auxiliary voltage for a short while.
Speed 300 Baud
600 Baud
4.17 Checking tripping circuits for continuity
1200 Baud
2400 Baud The use of a digital input enabled by normal de-energizing
4800 Baud combined with one of the TX timers allows the tripping coil
9600 Baud circuit to be monitored for continuity, whether the breaker is
19200 Baud closed or open.
38400 Baud
Parity NONE
EVEN
ODD
Data Bit 7
8
Stop Bit 1
2
pag. 12
MX3DVZ3A MDE/B133 2511 001
pag. 13
MX3DVZ3A MDE/B133 2511 001
- Twelve LED's, four of which are rigorously dedicated to 6. LCD MENU STRUCTURE
general running functions.
- A four-pin connector in compliance with FCC 68. 6.1 MAIN READING MENU
By means of a special optoelectrical adapter, an optical The device has a main menu, leading to several sub-menus
fibre cable and a RS232 optical converter, it allows the (tree structure). All the displays can be made permanent .
device to be locally linked with a personal computer.
The P.C., through a special interface programme, makes [IA In] Current value of voltage A
it possible to read and change the settings, to read the [IB In] Current value of voltage B
measurements, the counters, the logged events, the diag- ñ ò
nostic information and the fault recorder. [MENU: ENGLISH] Dialogue language
[ ] ð change dialogue language
ñ ò
[DATE ] current date and time
[TIME ] ð change date and time
ñ ò
[SETTINGS IN USE:] display settings in use
[MAIN ]
ñ ò
[SETTINGS READING] ð display main settings
[MAIN ]
ñ ò
[SETTINGS READING] ð display spare settings
[SPARE ]
ñ ò
[ MEASUREMENTS ] ð display current
[ ] meas. values
ñ ò
[ COUNTERS ] ð display counters and
[ P=RESETTABLE ] reset partial counters
ñ ò
[ EVENTS ] ð display
[EVENT 1 = LAST ] stored events
ñ ò
[ OUTPUT RELAYS ] ð display
[ ] output relays settings
ñ ò
[ DIGITAL INPUTS ] ð display
[ ] digital inputs settings
ñ ò
[ LED ] ð display
[ ] LED configuration
ñ ò
[ RELAY DATA ] ð display software mod.-release
[ ] and alphanumeric code
ñ ò
[ DIAGNOSTIC ] ð display failures
[ ] last change date
All the following examples take their start from the main menu.
pag. 14
MX3DVZ3A MDE/B133 2511 001
b) By pressing the key ð the language change function is g) By pressing ï twice further, select the second digit that
enabled, and the following message appears on the display: makes up the date, and the display will show:
[MENU: ITALIAN ] [DATE 10/06/95]
[ ] [TIME 09:38:43]
c) By pressing ò or ñ you scroll the stored languages menu. h) By pressing ñ, change the selected value (upon reaching
For the purpose of our example, we must stop when the number 9, the tens will go up by one unit) until the display
following message is displayed: shows:
[MENU: ENGLISH ] [DATE 24/05/95]
[ ] [TIME 09:38:43]
d) By pressing ï you confirm the selected dialogue language i) Press ï until you move to the beginning of the line. The
and go back to the main menu. The following message appears display will show:
on the display: [DATE 24/05/95]
[MENU: ENGLISH ] [TIME 09:38:43]
[ ]
j) By pressing ò the "change time" function is enabled. The
steps are the same as those described in c) to i).
6.1.2 Change date and time
The device does not accept time or date settings that do not
Access to "change date/time" is denied when the protection is exist.
network-connected. If the network connection is made after The time counting starts upon moving from the digits that make
entering the change function, the local changes are not ena- up the time to the wording TIME at the beginning of the line.
bled.
Let us assume we wish to change the starting date 10/06/93 k) By pressing ï the changes made are confirmed and the
into 24/05/95. system moves back to the main menu. The display will show:
[DATE 24/05/95]
a) Press the key ò or ñ until the display shows: [TIME 09:38:43]
[DATE 10/06/93]
[TIME 09:38:43]
6.1.3 Display settings in use
a) Press ò or ñ until the display shows, for instance:
b) By pressing the key ð the change function is enabled and
[SETTINGS: ]
the following message appears on the display: [ MAIN]
[DATE 10/06/93]
[TIME 09:38:43]
The second line will display the group of settings the device
c) By pressing ð select the value to be changed. To select the currently uses.
last digit that makes up the date, pressð six times, the displays Any <!> possibly displayed, notwithstanding the contents of the
will show: second line, indicates the device is working with the SPARE
[DATE 10/06/93] settings.
[TIME 09:38:43]
[SETTINGS :]
[ <!> MAIN]
d) By pressing ñ, increase the selected value. Hold the key
pressed until the display shows:
[DATE 10/06/95] The device will continue working with the SPARE settings as
[TIME 09:38:43] long as the "change settings" command sent by the IN DIG1
digital input remains enabled. When the <!> characters disap-
pear, the device restarts working with the group of settings
e) By pressing ï , select the fourth digit that makes up the date,
displayed.
the display will show:
[DATE 10/06/95]
[TIME 09:38:43] 6.1.4 Display main settings
f) By pressing ò, decrease the selected value until the display a) Press ò or ñ until the display shows:
[SETTINGS READING]
shows:
[ MAIN ]
[DATE 10/05/95]
[TIME 09:38:43]
b) By pressing ð, the main settings display sub-menu is
entered, by pressing ò or ñ the following sub-menu is scrolled:
rated frequency fn
rated voltage Un
pag. 15
MX3DVZ3A MDE/B133 2511 001
pag. 16
MX3DVZ3A MDE/B133 2511 001
b) By pressing the key ð you enter the counter display sub- current value B in multiples of In
menu, and by pressing the key ò or ñ the following sub-menu when the trip occurred: IB_G
is vertically scrolled: current value C in multiples of In
when the trip occurred: IC_G
total trips of first overcurrent threshold A IA> T voltage value A in multiples of Un
partial trips of first overcurrent threshold A IA> P when the trip occurred: UA_G
total trips of second overcurrent threshold A IA>> T voltage value B in multiples of Un
partial trips of second overcurrent threshold A IA>> P when the trip occurred: UB_G
total trips of first overcurrent threshold B IB> T voltage value C in multiples of Un
partial trips of first overcurrent threshold B IB> P when the trip occurred: UC_G
total trips of second overcurrent threshold B IB>> T
partial trips of second overcurrent threshold B IB>> P Warning: in differential applications, the current measured in
total trips of first overcurrent threshold C IC> T the events does not match the total fault current, as the share
partial trips of first overcurrent threshold C IC> P
absorbed by the attachment X2/DVZ3R and by the system CT's
total trips of second overcurrent threshold C IC>> T
(see paragraph 7) need to be considered, too. Similarly, the
partial trips of second overcurrent threshold C IC>> P
total trips of overvoltage threshold A UA> T measured voltages in the application of thresholds UA>, UB>
partial trips of overvoltage threshold A UA> P and UC> to monitor current circuits are affected by the divider
total trips of overvoltage threshold B UB> T and by the voltage limiter provided in the attachment
partial trips of overvoltage threshold B UB> P
X2/DVZ3R.
total trips of overvoltage threshold C UC> T
partial trips of overvoltage threshold C UC> P
total trips of undervoltage threshold A UA< T d) By pressing ï anywhere in the sub-menu, you go back to
partial trips of undervoltage threshold A UA< P event display sub-menu; to display other events go through step
total trips of undervoltage threshold B UB< T c) again. By pressingï anywhere in the sub-menu you go back
partial trips of undervoltage threshold B UB< P to the main reading menu:
total trips of undervoltage threshold C UC< T [ EVENTS ]
partial trips of undervoltage threshold C UC< P [EVENT 1=LAST]
total breaker failure trips BF T
partial breaker failure trips BF P 6.1.9 Display output relays
a) Press ò or ñ until the display shows:
c) By pressing the RESET button, the partial counter being
displayed can be reset. [OUTPUT RELAYS]
[ ]
d) By pressing the key ï , you go back to the main display menu:
[ COUNTERS ] b) By pressing ð you enter the sub-menu that displays the
[ P =RESETTABLE ] allocation of the auxiliary output relays. The display shows:
[IA> START]
[REL X..3.5]
6.1.8 Display events
the first line displays the function that is associated with the
a) Press ò or ñ until the display shows:
relay or relays listed in the second line.
[ EVENTS ]
[EVENT 1=LAST] By pressing the keys ò or ñ the sub-menu is scrolled.
The functions that can be associated with the output relays are:
b) By pressing ð you enter the sub-menu where the eight
events to be stored can be selected. The display shows: delayed starting of first overcurrent threshold A IA>START
[EVEN.1 DD/MM/YY ] first overcurrent threshold A trip IA>TRIP
[ hh:mm:ss.xxx ] second overcurrent threshold A trip IA>>TRIP
delayed start of first overcurrent threshold B IB>START
the first line displays the event number, the day, the month and first overcurrent threshold B trip IB>TRIP
second overcurrent threshold B trip IB>>TRIP
the year, whereas the second line lists the time, the minutes,
delayed start of first overcurrent threshold C IC>START
the seconds and thousandths of a second concerning the first overcurrent threshold C trip IC>TRIP
event. second overcurrent threshold C trip IC>>TRIP
delayed start of overvoltage threshold A UA>START
c) By pressing the key ò or ñ, select the event to be displayed. first overvoltage threshold A trip UA>TRIP
Once the selection is made, press ð ; thus, you enter the event delayed start of overvoltage threshold B UB>START
overvoltage threshold B trip UB>TRIP
display sub-menu, and by pressing ò or ñ the following sub-
delayed start of overvoltage threshold C UC>START
menu is scrolled: overvoltage threshold C trip UC>TRIP
delayed start of undervoltage threshold A UA<START
tripped threshold TRIP undervoltage threshold A trip UA<TRIP
current value A in multiples of In delayed start of undervoltage threshold B UB<START
when the trip occurred: IA_G undervoltage threshold B trip UB<TRIP
pag. 17
MX3DVZ3A MDE/B133 2511 001
delayed start of undervoltage threshold C UC<START c) By pressing the key ï anywhere in the sub-menu, you go
undervoltage threshold C trip UC<TRIP back to the main reading menu:
breaker failure trip BF TRIP [ DIGITAL ]
timer tX1 overtime t_X1 TRIP [ INPUTS ]
timer tX2 overtime t_X2 TRIP
timer tX3 overtime t_X3 TRIP
first digital input fed IN DIG 1 6.1.11 Display Led's
second digital input fed IN DIG 2
third digital input fed IN DIG 3 a) Press the key ò or ñ until the following message appears
on the display:
It is furthermore possible to display the output relays that bear [ LED ]
the following settings: [ ]
pag. 18
MX3DVZ3A MDE/B133 2511 001
6.1.12 Display relay information The following table provides the fault codes and the corre-
sponding fault description:
a) Press the key ò or ñ until the following message is
displayed:
Code fault description
[ RELAY DATA ]
[ ] A X1 relay coil interrupted or related driver
B X2 relay coil interrupted or related driver
b) By pressing the key ð you enter a sub-menu where the C X3 relay coil interrupted or related driver
protection model and the software release are displayed: D X4 relay coil interrupted or related driver
[MX3DVZ3A ] E X5 relay coil interrupted or related driver
[Soft Rel. 1.00]
F internal feeder failure
G EEPROM failure
c) By pressing the key ò once again, the second line will display
the alphanumeric identification code that the user gave to the H Internal RAM failure
device, for instance: I External RAM failure
[PLANT IDENTIFIER] J Analogue to Digital converter
[CELL No. 17bis ] K communication board failure or enabled but
not configured
d) By pressing the key ï anywhere in the sub-menu, you go
L internal clock failure
back to the main reading menu:
[ RELAY DATA ]
[ ] If jumper S6 (see fig.2) that enables the communication board
is connected when the board is not present, the K code shows
6.1.13 Diagnostic display up, as if a failure were detected in the board.
d) As far as the NON-VITAL FAULTS are concerned, by pressing
1) Fault location the key ï anywhere in the sub-menu you go back to the main
a) Press the key ò or ñ until the following message is display menu:
displayed: [ DIAGNOSTIC ]
[ DIAGNOSTIC ] [ ]
[ ]
whereas, as regards the VITAL FAULTS, you can only leave the
In the presence of VITAL FAULTS, the device automatically diagnostic sub-menu, if the device allows you to do that, by
displays the window, without needing to enter the diagnostic entering the “settings change” menu.
menu.
2) Inhibited device
b) By pressing the key ð you enter a sub-menu that displays The condition of “inhibited device” is displayed as follows:
the operating state of the relay. The display will show: [FAULT <!>]
[LAST SETTING ] [..............P ]
[DD/MM/YY hh:mm]
This condition can only be reset by entering the "settings
the second line displays the day, the month, the year, the time
change“ menu (it is however necessary to confirm when you
and the minutes of the time when last change was made to the
settings. are prompted to SAVE CHANGES, although no setting has
been changed).
c) By pressing the key ò once again, if the device has not
detected any failure, the following message will be displayed: Warning: even simply view the set parameters from the
“settings change” menu, since upon leaving this condition, the
[ RUNNING ] device will not be inhibited any longer.
[ ] If, beside inhibiting the device, you have also deconfigured it,
the return to operation causes a fault K message to be
If NON-VITAL FAULTS are detected, the following message will
displayed until the unit is configured anew (see paragraph
be displayed:
[FAULT ] 4.13).
[ABCDE.....KL ]
pag. 19
MX3DVZ3A MDE/B133 2511 001
6.2 MAIN SETTING CHANGE MENU If upon confirming the changes, a fault is detected, the settings
are not accepted as long as the fault event persists. This state
is signalled for 3s by the following message:
By pressing the key anywhere in the display menus
for at least 2s, the main settings change menu is entered. [SETTINGS CHANGE]
Thence, several sub-menus can be entered (tree- structure). [DELAYED ]
When the settings change function is enabled, the green LED
(RUN) lights up blinking. once the event is over, you are prompted to confirm the
If the settings change menu is already acceded through a PC changes made again.
or a network, any local change is inhibited, and the following If the transfer is interrupted is due to a digital input being
message will be displayed: enabled which cannot be disabled at the moment and you
need to change the settings, the device must be inhibited; after
[SETTINGS CHANGE]
that, you can start changing the settings (see paragraphs 4.14
[NOT AVAILABLE ]
and 6.1.13).
By pressing ï all the changes made are discarded, whereas b) By pressing the key ð , you enter the main settings change
by pressing ð the changes made are confirmed. sub-menu, which contains all the parameters already listed in
The green LED (RUN) stops blinking and becomes perma- § 6.1.4
nent.
pag. 20
MX3DVZ3A MDE/B133 2511 001
c) By pressing the keys ò or ñ , you can vertically scroll the sub- By pressing the key ï select the first digit of the value, the
menu, and by pressing the key ð you can start changing the display will show:
displayed parameter. The change can be made by pressing
the keys ò or ñ . [IA> ON ]
[IA> 0.05 In]
d) By repeatedly pressing the key ï anywhere in the sub- By pressing the key ñ, the number is changed, until the display
menu, you go back to the main changing menu: shows:
[SETTINGS CHANGE]
[MAIN ]
[IA> ON ]
[IA> 1.05 In]
Example of setting
Suppose we must enable and set the overcurrent threshold By pressing the key ï, the cursor moves to the beginning of the
AI> to 1.05 starting from the initial setting of 0.80, OFF. line and the main settings change menu is displayed:
Go through steps a) and b)
Press the key ò or ñ until the threshold to be changed is [SETTINGS CHANGE]
[MAIN ]
selected on the display:
pag. 21
MX3DVZ3A MDE/B133 2511 001
[IA> TRIP]
[REL X....5] 6.2.7 Set alphanumeric code
a) Press the key ò or ñ until the display shows:
By pressing ï you move back to the beginning of the line and [ RELAY DATA ]
reach the main settings change menu: [ ]
pag. 22
MX3DVZ3A MDE/B133 2511 001
6.2.8 LCD back-lighting The LED and display test makes them light up for two seconds.
Therefore, it can be run at any time during operation
a) Press the key ò or ñ until the display shows:
[ LCD ]
[AUTOMATIC RETURN] By pressing the two keys for two seconds
[TEST LED]
[ YES >] ð TEST LED’s L1-L8 and display
ñ ò
[TEST RELAY X1]
[ YES >] ð TEST relay X1
ñ ò
[TEST RELAY X2]
[ YES >] ð TEST relay X2
ñ ò
[TEST RELAY X3]
[ YES >] ð TEST relay X3
ñ ò
[TEST RELAY X4]
[ YES >] ð TEST relay X4
ñ ò
[TEST RELAY X5]
[ YES >] ð TEST relay X5
The test to be carried out on the auxiliary relay X.. makes the
latter trip, so that the associated command and/or signal can
be sent. That is why, before running it, the systems prompts
you to further confirm its execution:
[ ARE YOU SURE? ]
[< NO YES >]
pag. 23
MX3DVZ3A MDE/B133 2511 001
pag. 24
MX3DVZ3A MDE/B133 2511 001
pag. 25
MX3DVZ3A MDE/B133 2511 001
8.1 ESD Electrostatic Charges The attachment is only available for surface-mounting with
screw terminals available on front or rear (see figure 7).
The relay uses electronic components that are highly sensitive
The parts making up the attachment may reach high tempera-
to electrostatic charges. Therefore, the operator who happens
tures and is therefore advisable to mount it in a ventilated area.
to handle the moving part of the equipment and come in contact
To set the impedance value, please refer to the diagrams given
with the electronic circuits, must take preventive measures to
in figure 7.
avoid damaging the relay:
Connect the ground screw of the unit to the protection ground
- before removing the movable part, the operator must reach
of the panel with a connection of suitable gauge(>4mm2) and
the same potential as the equipment by touching the case
as short as possible (<1m).
- avoid touching electronic components, printed circuit
boards and connectors, as far as this is possible. Handle
it by using the mechanical frame.
- lay the device on surfaces that are antistatic or feature the
same potential as the operator's.
- only store and transport the relay by using the special
antistatic bag.
pag. 26
MX3DVZ3A MDE/B133 2511 001
9. SETTING THE UNIT AT WORK The following tests are however recommended:
The relay is supplied with factory settings and configurations Power supply unit test
as indicated in tables A, B and C (factory settings). - Check that the burden of the auxiliary voltage circuit falls
These settings may happen not to match the specific system within the 5 to 10W range as far as the d.c. supply is
where the unit is to be placed. Therefore, the relay settings concerned, and within the 10 to 20VA range as far as the a.c.
must be changed in compliance with the tables D, E and F for supply is concerned.
customer’s use, which must be used as a support to develop The feeder is protected by a special 5x20 2 A rapid fuse,
a customized setting scheme. class IEC127/II, as regards the unit with 19-100Vcc (or 19-
72Vca) auxiliary voltage, and a 1A fuse as regards the unit
9.1 Safety regulations with 64-300Vcc (or 64-275Vca) auxiliary voltage.
During the equipment tests and the start-up, the general safety Connection test
regulations applicable to electrical systems must be com- - Test each output relay according to the procedure de-
plied with. Failure to comply with these regulations might scribed in the paragraph TEST MENU, and simultaneously
cause harm to the working staff and damage to property. All the test the related external circuit.
inspections and tests must only be carried out by specially - Check the digital input wiring to ensure it matches the
trained staff. provisions of the design plans.
Overcurrent protection:
9.2 Checking nameplate ratings - Inject a current signal into the line CT's and check it for the
Inquire whether the equipment ratings are consistent with correspondence with the data displayed in the MEASURE-
those of the system, namely: MENTS menu
- auxiliary voltage Overvoltage-undervoltage protection:
- rated phase current; this check must be performed by check- - Inject a voltage signal into the line VT's it for the correspond-
ing the position of the jumpers located on the boards (see ence with the data displayed in the MEASUREMENTS
figures. 4a, 4b). menu:
- the setting of the output relays (if normally energized or - Test all the CT's for the same turn ratio and the bus bar
normally de-energized); this check must be performed by feeding CT's poles and utilities to ensure they mirror the bus
checking the position of the jumper located on the card (see bar.
figures 4c, 4d). - Isolate and short-circuit all CT's, hence inject into each line
- the presence of the special S6 jumper, see figure 2, if the CT's a current signal and test the consistency of the data
communication card is supplied and if the network is present. displayed in the MEASUREMENTS menu. To avoid danger-
ous overheating, but above all to avoid the protection's
I CAUTION measurements being much too affected by the absorption
hazardous voltages can remain in the unit even in the on non-linear elements provided in the attachment X2/
absence of power supply, or after it has been pulled out of DVZ3R, it is advisable to inject :
its casing (capacitor's storage) 100 mA with 500 ohm resistance
60 mA with 1000 ohm resistance
9.3 Final inspection 40 mA with 2000 ohm resistance
Inject auxiliary voltage into the device. An imperfect match between the injected current value and
On switching on, after a long time of power failure, the device the value displayed by the instrument is due to the display
can indicate an 'L' type fault (internal clock), a NON-VITAL that is limited to the second decimal digit, with inaccuracy
FAULT which does not affect the remaining functions: by of 1-digit inaccuracy and also at extremely low test currents.
updating DATE and TIME, the normal service conditions are Alternatively, an ammeter with a finer resolution can be
restored. series-connected to the MX3DVZ3A unit, or greater current
signals may be injected, taking care to cut out the attach-
If the system is running and the relay settings are unknown, the
ment to avoid dangerous overheating.
unit must be inhibited from operating before feeding it with
If the monitoring of the current circuits is also provided on
voltage by pressing the “settings change” key (see § 4.13 and
injecting the above-mentioned currents, the displayed
6.1.13 clause 2) to avoid troubles.
voltage measurements shall approximate the following
Select the rated frequency of the system on the device, set the
values, respectively: 30V, 36V e 47V. The voltage test may
rated current and the rated voltage.
be carried out on testing one sole CT triad.
Load the settings and configure the relays, the LED’s and the
digital inputs as per the design plans.
Since the unit is equipped with a self-monitoring system, all
hardware and software failures possibly occurring are auto-
matically detected; this makes it useless to test the thresholds
for accuracy, which can however be tested by making refer-
ence to the tolerances specified on the catalogue.
pag. 27
MX3DVZ3A MDE/B133 2511 001
Warning:
Short-circuiting a current input without first isolating it causes
the differential protection to be cut out.
Hence, check all CT's for the correct state before starting the
tests and, above all, before finally setting the unit at work.
pag. 28
MX3DVZ3A MDE/B133 2511 001
10000
1000
TENSIONE (V)
VOLTAGE (V)
100
10
1
0,001 0,01 0,1 1 10 100 1000
CORRENT E (A)
CURRENT (A)
fig. 3
pag. 29
MX3DVZ3A MDE/B133 2511 001
RELAY RELAY
FRONT FRONT
fig. 4a fig. 4b
RELAY RELAY
FRONT FRONT
fig. 4c fig. 4d
pag. 30
MX3DVZ3A MDE/B133 2511 001
pag. 31
MX3DVZ3A MDE/B133 2511 001
OVERALL DIMENSIONS
fig. 6
pag. 32
MX3DVZ3A MDE/B133 2511 001
OVERALL DIMENSIONS
fig.7
pag. 33
MX3DVZ3A MDE/B133 2511 001
WARNING:
The factory settings may prove not to suit the system. Therefore, the device must be configured anew upon installation
pag. 34
MX3DVZ3A MDE/B133 2511 001
AWARNING:
The factory settings may prove not to suit the system. Therefore, the device must be configured anew upon installation
/ not to be allocated
X allocated
pag. 35
MX3DVZ3A MDE/B133 2511 001
WARNING:
The factory settings may prove not to suit the system. Therefore, the device must be configured anew upon installation
pag. 36
MX3DVZ3A MDE/B133 2511 001
tab. D
pag. 37
MX3DVZ3A MDE/B133 2511 001
tab. E
/ not to be allocated
pag. 38
MX3DVZ3A MDE/B133 2511 001
tab. F
TABLE OF SETTINGS
DESCRIPTION FUNCTION MAIN SPARE
ON OFF VALUE ON OFF VALUE
rated current In / / /
rated frequency fn / / /
rated voltage Un / / /
settings in use: MAIN Timed LCD back-lighting: ON / not to be allocated: the same settings as
the MAIN settings apply
settings in use: SPARE Timed LCD back-lighting: OFF
pag. 39
MX3DVZ3A MDE/B133 2511 001
Identification
commercial name relay--> centre AR
plant identifier relay--> centre AR
rated current relay--> centre AR
rated voltage relay--> centre AR
pag. 40
MX3DVZ3A MDE/B133 2511 001
Present measurements
current IA relay--> centre T and AR
current IB relay--> centre T and AR
current IC relay--> centre T and AR
voltage UA relay--> centre T and AR
voltage UB relay--> centre T and AR
voltage UC relay--> centre T and AR
Event logging
event date / time relay--> centre VP and AR
IA> start relay--> centre VP and AR
IA> trip relay--> centre VP and AR
IA>> start relay--> centre VP and AR
IA>> trip relay--> centre VP and AR
IB> start relay--> centre VP and AR
IB> trip relay--> centre VP and AR
IB>> start relay--> centre VP and AR
IB>> trip relay--> centre VP and AR
IC> start relay--> centre VP and AR
IC> trip relay--> centre VP and AR
IC>> start relay--> centre VP and AR
IC>> trip relay--> centre VP and AR
UA> start relay--> centre VP and AR
UA> trip relay--> centre VP and AR
UB> start relay--> centre VP and AR
UB> trip relay--> centre VP and AR
UC> start relay--> centre VP and AR
UC> trip relay--> centre VP and AR
UA< start relay--> centre VP and AR
UA< trip relay--> centre VP and AR
UB< start relay--> centre VP and AR
UB< trip relay--> centre VP and AR
UC< start relay--> centre VP and AR
UC< trip relay--> centre VP and AR
BFstart relay--> centre VP and AR
BF trip relay--> centre VP and AR
digital input 1 state relay--> centre VP and AR
digital input 2 state relay--> centre VP and AR
digital input 3 state relay--> centre VP and AR
timer t_X1 state relay--> centre VP and AR
timer t_X2 state relay--> centre VP and AR
timer t_X3 state relay--> centre VP and AR
States
IA> trip relay--> centre VP and AR
IA>> trip relay--> centre VP and AR
IB> trip relay--> centre VP and AR
IB>> trip relay--> centre VP and AR
IC> trip relay--> centre VP and AR
IC>> trip relay--> centre VP and AR
UA> trip relay--> centre VP and AR
UB> trip relay--> centre VP and AR
UC> trip relay--> centre VP and AR
UA< trip relay--> centre VP and AR
UB< trip relay--> centre VP and AR
UC< trip relay--> centre VP and AR
BF trip relay--> centre VP and AR
pag. 41
MX3DVZ3A MDE/B133 2511 001
Blocks
current thresholds block centre--> relay AV
undervoltage thresholds block centre--> relay AV
overvoltage thresholds locks centre--> relay AV
Counters
Events
date relay--> centre AR
time relay--> centre AR
operated threshold relay--> centre AR
IA fault current value relay--> centre AR
IB fault current value relay--> centre AR
IC fault current value relay--> centre AR
UA fault voltage value relay--> centre AR
UB fault voltage value relay--> centre AR
UC fault voltage value relay--> centre AR
Output relays
X1 setting relay--> centre--> relay AR
X2 setting relay--> centre--> relay AR
X3 setting relay--> centre--> relay AR
X4 setting relay--> centre--> relay AR
X5 setting relay--> centre--> relay AR
pag. 42
MX3DVZ3A MDE/B133 2511 001
LED's
L1 setting relay--> centre--> relay AR
L2 setting relay--> centre--> relay AR
L3 setting relay--> centre--> relay AR
L4 setting relay--> centre--> relay AR
L5 setting relay--> centre--> relay AR
L6 setting relay--> centre--> relay AR
L7 setting relay--> centre--> relay AR
L8 setting relay--> centre--> relay AR
digital inputs
input 1 setting relay--> centre--> relay AR
input 1 setting enabled HIGH/LOW relay--> centre--> relay AR
input 2 setting relay--> centre--> relay AR
input 2 setting enabled HIGH/LOW relay--> centre--> relay AR
input 3 setting relay--> centre--> relay AR
input 3 setting enabled HIGH/LOW relay--> centre--> relay AR
Reset
LED centre--> relay AR
relay centre--> relay AR
resettable counters centre--> relay AR
Commands
output relay enable centre--> relay AV e AR
settings switch centre--> relay AV
settings switch survival time centre--> relay AR
Fault recorder
fault recorder starting parameters relay--> centre--> relay AR
fault recorder pre-trigger delay relay--> centre--> relay AR
fault recorder trigger command centre--> relay AR
fault recorder reset command centre--> relay AR
fault recorder data relay--> centre AR
Clock
date centre--> relay S
time centre--> relay S
date relay--> centre AR
time relay--> centre AR
LEGEND
AR aperiodic message
AV (a.p.) aperiodic variable transmitted upon high-priority variation
AV aperiodic variable transmitted upon variation
VP variable on request
T periodic variable with periods programmable between 1 and 5 s
S synchronization
pag. 43
MX3DVZ3A MDE/B133 2511 001
pag. 44
ALSTOM T&D Protection & Côntrole is bound by the foregoing specifications, dimensions and diagrams only after confirmation.
ABCD
ALSTOM FIR S.p.a. - via Viscardi, 5 - 24016 SAN PELLEGRINO T. - BG - ITALIA
Tel. ++39 0345 28111 - Fax ++39 0345 22590 - Telex 301152 FIR I - E-mail: alstom.fir@tde.alstom.com