Sei sulla pagina 1di 24

Hi-Performance Fan Coils 400 - 2,200 CFM

Table of Contents

Airtherm Fan Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1


Hi-Performance Vertical Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features & Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Equipment Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ARI Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Heating Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Coil Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Weights & Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

ARI Certified
Airtherm Hi-Performance fan coils are labeled and approved by the Air Conditioning
and Refrigeration Institute (ARI). This designation signifies that Airtherm Superior
Performance fan coil units have been examined by ARI and comply with the organization’s
applicable standards.

UL Listing
Airtherm Hi-Performance fan coils are listed by Underwriters Laboratories, Inc. (UL).
The UL listing ensures that Airtherm Hi-Performance fan coil units have been examined
R

by UL and comply with the organization’s applicable standards. UL’s re-examination


service includes periodic visits by UL inspectors to Airtherms’ factory to ensure contin-
ued compliance for all listed products.

C-UL US Listing
C R US Hi-P
(ULC). The C-UL US listing ensures that Airtherm Hi-Performance fan coil units have
LISTED
been examined by UL and are in compliance with both the U.S. and Canadian organiza-
tions’ applicable standards.

Materials and equipment acceptance for use by the New York Department
of Buildings:

SV004-008, SV006-022 MEA 411-05-E


SV004-022 MEA 409-05-E

Hi-Performance
® Fan Coils
F an Coils and Air Handlers

Applied Products
...more than just fan coils.

For 90 years, Airtherm has been a market Served by company factories in Colton,
leader in providing high quality HVAC California and Phoenix, Arizona, the Ap-
products for residential and commercial plied Products Group uses the resources
buildings. Today, the Applied of nearly 600,000 square feet of manufac-
Products turing and warehouse facilities to provide
Group high quality products to some of the most
continues discriminating customers in the world.
the proud
tradition The Applied Products Group
by offer- pledge is to
ing to the commercial/industrial market provide com-
more configurations and size options of plete, high
quality fan coils and blower coils/air han- quality and
dlers than any other HVAC company in timely support
North America. for the success-
ful completion of your construction proj-
The Applied Products Group, ects involving engineered products offered
based in Oklahoma City, Oklahoma, serves by Airtherm. We believe in a partnering
all US and overseas markets with complete attitude that creates superior projects and
application engineering, sales, marketing and high levels of satisfaction.
administrative services.


Hi-Performance Vertical Models - SV Series

400 - 2200 CFM

SVTB - Vertical Basic

The Vertical Basic (SVTB) is a high static, ducted vertical cased


fan coil with bottom return. Primarily used in vertical floor-
mounted or hideaway applications, the Vertical Basic is furred
into partition walls or hidden in closets, utility rooms and other
concealed locations with a ducted discharge. A removable front
access panel facilitates easy servicing. A one-inch discharge duct
flange is standard on the top panel of each unit. Front Return
SVTB Basic also available.

SDTB - Vertical Deluxe


The Vertical Deluxe (SDTB) is our Basic model primarily used
in floor-mounted or exposed applications. The Vertical Deluxe
is finished in a soft white, powder coat epoxy and subjected to a
1500-hour salt spray test in accordance with ASTM B117. Front
Return Deluxe is also available.

SDTB

SCTF - Vertical Front Return


The Vertical Front Return (SCTF) is a high static, ducted vertical
fan coil for installation in a closet-type enclosure. The front panel
is removable for easy service access to the slide-out blower assem-
bly, with quick-connect plug. Vertical Front Return with return-air
grille option allows unit to be furred-in. Grille mounts to drywall
for easy access without the expense of a closet door. Vertical
Front Return Deluxe also available.
SCTF

4
Features and Benefits

Standard Features
• Heavy-gauge galvanized steel cabinet with
neoprene-coated 1/2” thick fiberglass insulation with
3.35 PCF density.

• Coils are made of 1/2” OD copper tube with


aluminum fins (12 FPI) equipped with manual-air
vent. DX and steam coils do not include manual-air
vent. Coils are 100% underwater pressure tested at
350 PSI with a 300 PSI working pressure.

• Galvanized drain pan is powder-coated epoxy and


subjected to a 650-hour salt spray test in accordance
with ASTM-B117. Also comes with 1/8” thick
closed-cell insulation and primary and secondary
drain connections.

• Three-speed, 115/1/60 PSC motor with


quick-connect plug.

• Controls and motors are factory-wired and


terminated in a junction box for single-point
power supply.

• One-inch, reinforced duct collar on return- and


supply-air openings.

• Swing-down, hinged return-air grille/access door


on Deluxe and Flush models.

• Deluxe unit has single-deflection supply-air grille.

• One-inch fiberglass, throwaway filter, except


Horizontal Basic.

• Individually tagged, crated and shipped as


scheduled for installation.

• UL and C-UL approved, ARI certified and


100% factory tested.

Hi-Performance
® Fan Coils
Equipment Options

Options
• Soft-white, powder-coated epoxy cabinet that’s
subjected to a 1500-hour salt spray test in accordance
with ASTM-B117.

• Drain Pans - stainless steel.

• Insulation - fiberglass, foil-face, elastomeric


and double-wall (solid or perforated) in 1/2” and
1” thicknesses.

• Coils - copper fins/tubes, stainless steel fins/tubes,


phenolic coated, stainless steel end plates. All
options are available on one- to six-rows.

• Three-speed, 208-230/1/50-60 or 277/1/60 PSC


motor with quick-connect plug.

• Systems - two- or four-pipe, hydronic cooling/


heating, steam, direct-expansion (DX) and/or
electric heat.

• Cabinet - Deluxe, Flush and custom colors.

• Controls - wide selection of factory-mounted


valves and controls.

• Filters - two-inch thick throwaway, washable and metallic.

• Flow-control circulator for water heating applications.

• Grilles available as double-deflection and in


custom colors.

• Electric Strip Heat from 0.5 to 5 kW.

6
AHRI Cooling Capacity - SV Series

ARI Certified Cooling Capacity


Airtherm SV Series Hi-Performance Vertical fan coils have been rated in accordance with ARI Standard
440-2005 for room fan-coils air-conditioners and are certified by the Air-Conditioning and Refrigeration
Institute to meet the following product performance ratings:
ARI APPROVED STANDARD RATINGS COOLING CAPACITY
POWER
SERIES / TOTAL SENSIBLE INPUT
RATED WPD
SIZE MOTOR STYLE GPM COOLING COOLING (WATTS)
CFM (FT./H2O)
TYPE / # (BTUH) (BTUH)

B, D 530 3.2 2.1 15,930 11,690 175


SV Series
004 F, R 550 2.9 4.3 14,260 11,040 228
Standard (1)
G, Q 660 3.5 1.6 17,330 13,630 227
B, D 600 3.5 2.4 17,540 13,130 181
SV Series
006 F, R 750 3.5 6.4 17,460 14,410 260
Standard (1)
G, Q 800 4.0 2.0 20,030 16,200 256
B, D 760 4.2 3.1 20,820 17,190 316
SV Series
008 F, R 960 4.8 3.5 24,080 19,570 360
Standard (1)
G, Q 890 4.3 2.2 21,550 17,730 360
B, D 900 4.9 4.6 24,650 20,290 356
SV Series
010 F, R 1,060 5.7 5.3 28,480 23,560 383
Standard (1)
G, Q 1,080 6.2 4.4 31,080 24,950 398
B, D 970 5.2 5.0 25,990 21,580 413
SV Series
012 F, R 1,310 7.8 8.8 39,100 30,780 540
Standard (1)
G, Q 1,280 6.9 5.1 34,680 26,470 536
B, D 1,616 10.0 5.1 49,865 40,095 529
SV Series
015 F, R 1,550 9.7 7.9 48,624 37,500 553
Standard (2)
G, Q 1,602 9.9 5.6 49,500 39,796 529
B, D 1,898 12.4 7.0 62,141 48,454 736
SV Series
018 F, R 1,898 13.0 10.9 65,009 49,559 736
Standard (2)
G, Q 1,864 12.3 6.9 61,440 47,756 736
B, D 2,075 14.4 8.8 71,879 54,529 1035
SV Series
022 F, R 2,075 14.4 8.8 71,879 54,529 1035
Standard (2)
G, Q 2,088 13.4 5.6 66,915 52,774 1035

Notes: 1) Based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F temperature rise, high fan speed. Motor voltage
115/1/60 power source. Air flow under dry coil conditions. Water pressure drops shown in feet of water.
All units are listed under UL Category Control No. LZFE.
2) Ratings are based on actual CFM. Standard coils for 004 is 3 rows and 006-022 is 4 rows.
3) Legend - B = SVTB; D = SDTB; F = SCTF; R = Front return deluxe; G = Rear return and bottom supply;
Q = Rear return and bottom supply deluxe.

7
Heating Performance - CV Series

Heating Performance
Heating Performance

SERIES / COIL ROWS/ RATED WPD


SIZE MBH GPM
MODEL (FPI) CFM (FT./H2O)

SV Series 1 Row (12) 525 26.7 1.3 1.8


004
(Basic / Deluxe) 2 Rows (12) 525 40.1 2.0 1.3
SV Series 1 Row (12) 610 33.6 1.7 2.9
(Basic / Deluxe) 2 Rows (12) 610 49.9 2.5 2.1
006
SV Series 1 Row (12) 750 37.8 1.9 3.3
(Front Return) 2 Rows (12) 750 57.3 2.8 2.4
SV Series 1 Row (12) 780 35.3 1.8 2.7
(Basic / Deluxe) 2 Rows (12) 780 55.3 2.7 2.0
008
SV Series 1 Row (12) 975 38.7 1.9 3.1
(Front Return) 2 Rows (12) 975 62.3 3.1 2.3
SV Series 1 Row (12) 930 36.4 1.8 3.3
(Basic / Deluxe) 2 Rows (12) 930 59.1 2.9 2.5
010
SV Series 1 Row (12) 1,100 39.0 1.9 3.7
(Front Return) 2 Rows (12) 1,100 64.4 3.2 2.8
SV Series 1 Row (12) 1,135 43.2 2.2 4.9
(Basic / Deluxe) 2 Rows (12) 1,135 70.7 3.5 3.7
012
SV Series 1 Row (12) 1,350 38.5 1.9 0.7
(Front Return) 2 Rows (12) 1,350 69.3 3.4 1.2
SV Series 1 Row (12) 1,625 62.8 3.1 4.0
(Basic / Deluxe) 2 Rows (12) 1,625 100.9 5.0 3.4
015
SV Series 1 Row (12) 1,625 62.8 3.1 5.2
(Front Return) 2 Rows (12) 1,625 103.7 5.2 5.4
SV Series 1 Row (12) 1,910 75.5 3.8 5.4
(Basic / Deluxe) 2 Rows (12) 1,910 121.5 6.0 4.5
018
SV Series 1 Row (12) 1,910 54.2 2.6 0.9
(Front Return) 2 Rows (12) 1,910 124.2 6.2 7.0
SV Series 1 Row (12) 2,090 86.8 4.3 6.8
(Basic / Deluxe) 2 Rows (12) 2,090 138.8 6.9 5.7
022
SV Series 1 Row (12) 2,090 63.9 3.2 1.2
(Front Return) 2 Rows (12) 2,090 138.8 6.9 5.7

Notes: Based on 70°F DB EAT, 180°F EWT, 40°F temperature drop, high fan speed. Motor voltage 115/1/60
power source. Air flow under dry coil conditions. Water pressure drops shown in feet of water.

8
Coil Data

Coil Data
Coils are made from ½” O.D. copper tubing with .016” wall thickness, and tubes are staggered for
maximum heat transfer. A manual air vent is standard on all hydronic coils. DX and steam coils do not
include manual-air vent. All coils are 100% underwater pressure tested to 350 PSIG with a 300 PSIG
working pressure. Steam coils are rated for up to 15 PSIG or 250ºF.

Coils are available in two- or four-pipe, and from one- to eight-row configurations for SPCV Series
units All units available with any combination of chilled or hot water, steam or direct expansion.
Custom circuiting is available.

Coil Rows 003 004 006 008 010 012 015 018 022

S T A N D A R D

Vertical SV Coil
Coil Rows 004 006 008 010 012 015 018 022
Single-Row Coil
Two-Row Coil S T A N D A R D
Three-Row Coil
Four-Row Coil
Five-Row Coil
Six-Row Coil O P T I O N A L
Seven-Row Coil
*Eight-Row Coil
* Seven-row coil maximum when selecting a DX coil with a hot water coil.

Coil Options:
• DX – Includes distributor and nozzle, TXV must be field furnished and installed
• Steam – 1-15 PSIG
• Opposite End Connection (E). Place the “E” - pipe-hand connection in the eleventh
digit of the model number - when ordering
• Preheat Coil Position (PREHEAT) – Standard coil is reheat position
• Phenolic Anti-Corrosion Coating (PAC) • Stainless Steel Tubes/Fins/End Plates
• Copper Fins/Tubes/End Plates • 6-16 Fins Per Inch (Standard is 12 FPI)

Coil connections on thehilled water side for SV004-SV006 is ½” and ¾” on SV008-022.


The hot water connection is ½” on the SV004-022.

9
Electric Heat

Electric Heat
Electric heat may be furnished with either hydronic, direct expansion or steam coils and is
factory-mounted, wired, and tested. Option-equipped with low-watt density (for long life) nichrome
wire elements. The heater has a built-in, high limit, and fusible link to provide maximum safety.

Vertical ( SV Series)
kW 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
Size
Voltage AMPS
115 8.7 13.0 17.4 21.7 26.1
004 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4
115 8.7 13.0 17.4 21.7 26.1
006 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1
115 8.7 13.0 17.4 21.7 26.1
008 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1
115 8.7 13.0 17.4 21.7 26.1
010 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.9 31.3 33.7 36.1 38.5
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7 23.9 26.1 28.3 30.4 32.6 34.8
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1 19.9 21.7 23.5 25.3 27.1 28.9
115 8.7 13.0 17.4 21.7 26.1
012 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.9 31.3 33.7 36.1 38.5 40.9 43.3
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7 23.9 26.1 28.3 30.4 32.6 34.8 37.0 39.1
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1 19.9 21.7 23.5 25.3 27.1 28.9 30.7 32.5
115 8.7 13.0 17.4 21.7 26.1
015 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.9 31.3 33.7 36.1 38.5 40.9 43.3
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7 23.9 26.1 28.3 30.4 32.6 34.8 37.0 39.1
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1 19.9 21.7 23.5 25.3 27.1 28.9 30.7 32.5
115 8.7 13.0 17.4 21.7 26.1
018 208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.9 31.3 33.7 36.1 38.5 40.9 43.3
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7 23.9 26.1 28.3 30.4 32.6 34.8 37.0 39.1
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1 19.9 21.7 23.5 25.3 27.1 28.9 30.7 32.5
115 8.7 13.0 17.4 21.7 26.1
208 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0 26.4 28.9 31.3 33.7 36.1 38.5 40.9 43.3
022
230 4.4 6.5 8.7 10.9 13.0 15.2 17.4 19.6 21.7 23.9 26.1 28.3 30.4 32.6 34.8 37.0 39.1
277 3.6 5.4 7.2 9.0 10.8 12.6 14.4 16.3 18.1 19.9 21.7 23.5 25.3 27.1 28.9 30.7 32.5

10
Air Flow Data

Air Flow Data


Air flow shown below is under dry coil conditions.

Vertical ( SV Series)
MODEL / COIL 0.00 0.05 0.10 0.15 0.20 0.25
SIZE
STYLE ROWS HI MED LOW HI MED LOW HI MED LOW HI MED LOW HI MED LOW HI MED LOW
004 SV Series 3 ROW 545 440 355 525 425 350 510 415 340 500 405 325 490 395 310 480 380 295
Basic / Deluxe (Standard) 4 ROW 535 430 345 515 415 340 500 405 340 90 395 315 480 385 300 470 370 285
006 SV Series 3 ROW 624 490 380 600 470 360 585 555 340 570 440 335 560 425 310 545 410 295
Basic / Deluxe (Standard) 4 ROW 614 480 370 590 460 350 575 545 330 560 430 315 550 415 300 535 400 285
006 SV Series 3 ROW 765 650 560 735 635 550 715 620 540 695 605 525 675 585 510 655 565 495
Front Return (Standard) 4 ROW 755 640 550 725 625 540 705 610 530 685 595 515 665 575 500 645 555 485
008 SV Series 3 ROW 790 620 515 775 610 505 765 600 500 745 590 490 725 575 485 705 560 465
Basic / Deluxe (Standard) 4 ROW 775 605 500 765 595 490 750 585 485 730 575 480 710 560 470 690 545 450
008 SV Series 3 ROW 985 875 685 970 845 675 950 825 660 925 805 645 900 785 630 875 765 615
Front Return (Standard) 4 ROW 970 860 670 960 830 660 935 810 645 910 790 630 885 770 615 860 750 600
010 SV Series 3 ROW 935 715 555 920 705 550 905 695 545 890 685 535 865 675 525 835 655 510
Basic / Deluxe (Standard) 4 ROW 920 700 540 905 690 535 890 680 530 875 670 520 850 660 510 820 640 495
010 SV Series 3 ROW 1110 980 800 1075 950 785 1045 920 765 1010 895 745 975 865 725 940 835 700
Front Return (Standard) 4 ROW 1095 965 785 1060 935 770 1030 910 750 1000 880 730 960 850 710 925 820 685
012 SV Series 3 ROW 1145 935 715 1125 920 705 1095 905 695 1065 885 685 1030 865 675 1005 835 655
Basic / Deluxe (Standard) 4 ROW 1130 920 700 1110 905 690 1080 890 680 1050 870 670 1020 850 660 990 820 640
012 SV Series 3 ROW 1370 1125 645 1330 1115 635 1295 1100 630 1255 1085 625 1215 1065 620 1185 1050 610
Front Return (Standard) 4 ROW 1355 1110 630 1315 1100 625 1280 1085 615 1240 1070 610 1200 1055 605 1170 1040 595
015 SV Series 3 ROW 1640 1345 1160 1600 1325 1140 1560 1305 1120 1520 1280 1100 1480 1250 1080 1435 1215 1040
Front Return (Standard) 4 ROW 1620 1325 1140 1580 1305 1120 1540 1285 1100 1500 1260 1080 1460 1230 1060 1415 1200 1020
018 SV Series 3 ROW 1920 1770 1535 1870 1730 1500 1815 1670 1450 1760 1610 1410 1690 1560 1360 1630 1510 1300
Front Return (Standard) 4 ROW 1900 1750 1515 1850 1710 1480 1795 1650 1430 1740 1590 1390 1670 1540 1340 1610 1490 1285
022 SV Series 3 ROW 2120 2000 1410 2035 1940 1390 1950 1870 1370 1890 1790 1335 1815 1725 1290 1750 1660 1240
Front Return (Standard) 4 ROW 2100 1980 1390 2015 1920 1370 1930 1850 1350 1870 1770 1315 1795 1705 1270 1730 1640 1220

Notes: Ratings and capacity tables based on nominal CFM.

11
Motor Data

Motor Data
Motors are wired to a junction box ready for single-point field connection. Outstanding features include:
• Quick-Connect Plug • 122ºF maximum operating temperature
• Permanent Split Capacitor • Custom motor mounts designed to reduce
• Thermal overload protection noise and eliminate vibration
• 1050 RPM for lower operating costs • Stators are epoxy-dipped for more efficient
• Oversized bearings and permanently motor cooling
lubricated and sealed

Optional motors:
• 208V-1Ø-60 motors • 230/220V-1Ø-60 motors
• 277V-1Ø-60 motors • 50-Hz motors in specified voltages

Vertical ( SV Series)
60 Hertz Single-Phase Voltage/Watts
Motors (1100 RPM) 115V 208V 230V 277V
Series / Model /
Size HP (Qty) Blowers AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS
Motor Type
SV Front Return (Std) 1/10 (1) 1 1.5 175 0.80 175 0.7 175 0.5 175
004
SV Front Return (Std) 1/10 (1) 1 1.4 228 0.70 228 0.6 228 0.5 228
SV Basic/Deluxe (Std) 1/10 (1) 1 1.6 181 0.90 181 0.8 181 0.8 181
006
SV Front Return (Std) 1/6 (1) 1 2.3 260 1.20 260 1.1 260 0.8 260
SV Basic/Deluxe (Std) 1/6 (1) 1 2.2 316 1.10 316 1.0 316 1.3 316
008
SV Front Return (Std) 1/4 (1) 1 3.2 360 1.60 360 1.5 360 1.2 360
SV Basic/Deluxe (Std) 1/6 (1) 1 2.4 356 1.20 356 1.1 356 1.5 356
010
SV Front Return (Std) 1/4 (1) 1 3.3 383 1.80 383 1.6 383 1.3 383
SV Basic/Deluxe (Std) 1/4 (1) 1 3.2 413 1.70 413 1.5 413 1.7 413
012
SV Front Return (Std) 1/3 (1) 1 4.5 540 2.60 540 2.4 540 1.8 540
SV Basic/Deluxe (Std) 1/6 (2) 2 4.6 547 2.30 547 2.1 547 1.6 547
015*
SV Front Return (Std) 1/6 (2) 2 4.6 553 2.40 553 2.2 553 1.6 553
SV Basic/Deluxe (Std) 1/4 (2) 2 6.4 644 3.30 644 3.0 644 2.4 644
018*
SV Front Return (Std) 1/4 (2) 2 6.4 654 3.30 654 3.0 654 2.6 654
SV Basic/Deluxe (Std) 1/3 (2) 2 9.0 793 5.30 793 4.8 793 3.6 793
022*
SV Front Return (Std) 1/3 (2) 2 9.0 798 5.30 798 4.8 798 3.6 798
* Data reflects combined performance of (2) motors for both Horizontal and Vertical units.
Notes: Motor full load amps listed refer to NEC amps. Actual motor nameplate amps may vary.
13
12
Sound Data

Sound Data

Vertical (SV Series)


OCTAVE BAND
Size Series / Fan 2 3 4 5 6 7 8
Model Speed CENTER FREQUENCY (CPS)
125 250 500 1000 2000 4000 8000
High 58.1 51.8 48.6 44.5 36.3 32.5 30.8
SV Series
004 Medium 54.5 39.5 38.1 33.6 27.3 24.3 26.3
Basic / Deluxe
Low 49.6 38.5 37.2 32.1 26.1 22.7 24.6
High 59.5 50.1 49.1 43.2 38.1 34.7 35.1
SV Series
Medium 56.3 47.3 44.6 38.8 33.4 32.0 33.4
Basic / Deluxe
Low 50.9 45.5 41.2 35.6 30.7 27.3 26.1
006
High 59.2 52.1 51.6 46.4 41.4 36.0 33.6
SV Series
Medium 53.6 49.3 47.7 41.5 35.5 33.8 26.0
Front Return
Low 51.8 47.1 44.3 36.4 34.2 31.5 24.4
High 62.1 56.6 53.3 48.3 44.2 40.8 36.5
SV Series
Medium 56.6 48.2 45.7 41.6 38.2 32.9 29.7
Basic / Deluxe
Low 51.8 44.6 39.6 36.2 33.8 27.8 24.4
008
High 60.1 57.0 55.7 53.0 49.7 45.0 37.0
SV Series
Medium 56.7 52.3 47.0 45.4 41.2 34.2 27.8
Front Return
Low 53.4 46.5 43.7 42.2 39.6 32.7 25.4
High 63.2 56.9 57.3 53.1 47.3 41.8 39.8
SV Series
Medium 58.1 51.7 53.8 48.3 42.4 37.2 31.7
Basic / Deluxe
Low 55.5 46.9 46.1 41.4 35.6 32.3 29.1
010
High 61.5 59.8 57.2 56.0 52.1 47.1 39.1
SV Series
Medium 57.2 54.1 52.2 49.3 42.1 38.9 27.3
Front Return
Low 54.1 48.6 45.8 44.5 39.7 36.7 26.1
High 65.3 61.4 60.1 56.5 49.9 45.1 43.1
SV Series
Medium 60.4 55.9 54.2 52.1 44.7 41.1 35.4
Basic / Deluxe
Low 56.3 51.7 46.8 44.3 36.9 35.6 30.1
012
High 62.5 61.3 59.8 57.8 54.7 47.6 40.8
SV Series
Medium 58.8 57.2 54.1 50.3 44.1 38.6 28.7
Front Return
Low 54.3 53.7 48.6 46.5 41.4 34.2 27.7
High 58.5 55.5 53.0 49.0 47.0 45.0 40.8
SV Series
015 Medium 54.3 51.4 48.1 44.3 42.1 38.9 29.0
Front Return
Low 51.0 48.4 45.4 41.2 38.7 35.4 26.8
High 61.0 57.5 55.5 51.5 50.0 47.0 42.4
SV Series
018 Medium 56.2 53.3 52.1 49.1 46.4 42.0 32.1
Front Return
Low 52.4 50.5 49.4 46.4 41.4 38.5 30.8
High 62.5 60.0 58.6 53.2 51.7 48.4 45.6
SV Series
022 Medium 58.0 56.4 55.3 51.4 49.5 44.1 32.7
Front Return
Low 53.1 51.5 50.4 47.4 45.4 41.8 31.9

Notes: 1) Power levels are in dB RE 10-12 watts.


2) Sound data tested in accordance with ASHRAE Standard 68 and ARI Standard 260 and 350.
3) Air Flow under dry coil conditions.

13
Certified Dimensional Drawings - SVTB & SDTB Series

HI-PERFORMANCE CASED VERTICAL - BASIC/DELUXE BOTTOM RETURN


400 - 800 CFM









 


  

   











 










 





 

 

         


 
 
MODEL 
FILTER

BASIC / DELUXE A B 
C D E F G SIZE
400 20-5/32 14-5/32 57-5/8 
10-15/32 7-3/32 2-7/32 3-1/32 16X16X1

600 20-5/32 14-5/32 57-5/8 10-15/32 8-15/32 2-7/32 3-1/32 16X20X1
800 20-5/32 14-5/32 57-5/8 10-15/32 9-13/32 2-7/32 3-1/32 20X20X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW and HW on 004-008.
14
Certified Dimensional Drawings - SVTF & SDTB Series

HI-PERFORMANCE CASED VERTICAL - BASIC/DELUXE BOTTOM RETURN


1000 - 2200 CFM







 



 
   















 










 






  


         


 
MODEL
 FILTER


BASIC / DELUXE A B C D E F G SIZE


1000 20-11/32 20-5/16 57-5/8 10-3/8 11/15/16 2-1/8 3-1/16 20X20X1
1200 20-11/32 
20-5/16 57-5/8 10-3/8 11/15/16 2-1/8 3-1/16 20X20X1
1500 36 24-5/8 
62-3/4 24 10-1/2 3 3 30X24X1

1800 36 24-5/8 62-3/4 24 10-1/2 3 3 30X24X1
2200 36 24-5/8 62-3/4 24 10-1/2 3 3 30X24X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW on CV010; 3/4” on 012-022 and 1/2” HW on 010-022.
15
Certified Dimensional Drawings - SVTF & SDTF Series

HI-PERFORMANCE CASED VERTICAL - BASIC FRONT RETURN


400 - 800 CFM

MODEL FILTER
BASIC / DELUXE A B C D E F G SIZE
400 20-5/32 14-5/32 57-5/8 10-15/32 7-3/32 2-7/32 3-1/32 16X16X1
600 20-5/32 14-5/32 57-5/8 10-15/32 8-15/32 2-7/32 3-1/32 16X20X1
800 20-5/32 14-5/32 57-5/8 10-15/32 9-13/32 2-7/32 3-1/32 20X20X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW and HW on 004-008. 16
Certified Dimensional Drawings - SVTF & SDTF Series

HI-PERFORMANCE CASED VERTICAL - BASIC FRONT RETURN


1000 - 2200 CFM

MODEL FILTER
BASIC / DELUXE A B C D E F G SIZE
1000 20-11/32 20-5/16 57-5/8 10-3/8 11/15/16 2-1/8 3-1/16 20X20X1
1200 20-11/32 20-5/16 57-5/8 10-3/8 11/15/16 2-1/8 3-1/16 20X20X1
1500 36 24-5/8 62-3/4 24 10-1/2 3 3 30X24X1
1800 36 24-5/8 62-3/4 24 10-1/2 3 3 30X24X1
2200 36 24-5/8 62-3/4 24 10-1/2 3 3 30X24X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW on CV010; 3/4” on 012-022 and 1/2” HW on 010-022.
17
Certified Dimensional Drawings - SCTF Series

HI-PERFORMANCE CASED VERTICAL - FRONT RETURN/TOP SUPPLY


600 - 1200 CFM

MODEL FILTER
FRONT RETURN / TOP
A B C D SIZE
SUPPLY
600 21 42 12-1/4 4-3/8 16X16X1
800 25 42 12-1/4 6-3/8 16X20X1
1000 25 45 12-1/4 6-3/8 20X20X1
1200 30 45 12-1/4 8-7/8 20X25X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW for 006; 3/4” on 008-022 chilled water. 1/2” HW on 006-022 hot water.
18
Certified Dimensional Drawings - SCTF Series

HI-PERFORMANCE CASED VERTICAL - FRONT RETURN/TOP SUPPLY


1500 - 2200 CFM

MODEL FILTER
FRONT RETURN / TOP
A B C D SIZE
SUPPLY
1500 37 48 25-1/4 5-7/8 25X25X1
1800 37 48 32-1/4 2-3/8 (2) 25X16X1
2200 41 48 36-1/4 2-3/8 (2) 25X20X1

• All sizes shown in inches.


• Right-hand unit shown, left-hand unit opposite.
• Coil connections determined by facing the supply-air opening.
• Electrical junction box is located on the same side as the coil connections.
• Unit must be installed level and condensate drain lines should be trapped.
• Drain pan is powder-coated epoxy with a 1/8” thick closed-cell insulation and has 3/4” NPT
primary and secondary drain connections.
• Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
• Coil Connections: 1/2” CW for 006; 3/4” on 008-022 chilled water. 1/2” HW on 006-022 hot water.
19
Weights and Measures

Weights and Measures

The following SV Series weights and measures are based on fan coil units only. Add approximately 20%
for packaging and crating.
Dimensions / Inches Weight/lbs. Dimensions / Millimeters Weight/kg
Unit Model Rows Height Width Depth Dry Wet Height Width Depth Dry Wet
004 3 59 21 15 104 109 1,499 533 381 47 50
004 4 59 21 15 109 116 1,499 533 381 49 53
006 3 59 21 15 110 115 1,499 533 381 50 52
006 4 59 21 15 116 122 1,499 533 381 52 55
008 3 59 21 15 142 147 1,499 533 381 64 67
008 4 59 21 15 147 154 1,499 533 381 67 70
SV & DF Series 010 3 59 21 21 151 156 1,499 533 533 58 71
Basic / Deluxe 010 4 59 21 21 156 163 1,499 533 533 71 74
012 3 59 21 21 167 172 1,499 533 533 76 78
012 4 59 21 21 172 179 1,499 533 533 78 81
015 3 59 22 30 224 234 1,499 559 762 102 106
015 4 59 22 30 230 243 1,499 559 762 104 110
018 3 59 22 30 234 244 1,499 559 762 106 111
018 4 59 22 30 240 253 1,499 559 762 109 115
022 3 59 22 30 234 244 1,499 559 762 106 111
022 4 59 22 30 240 253 1,499 559 762 109 115
004 3 43 21 15 116 121 1,092 533 508 53 55
004 4 43 21 15 121 128 1,092 533 508 55 58
006 3 43 21 15 116 121 1,092 533 508 53 55
006 4 43 21 15 121 128 1,092 533 508 55 58
008 3 43 25 15 131 136 1,092 635 508 59 62
008 4 43 25 15 136 143 1,092 635 508 62 65
SCTF Series 010 3 46 25 21 141 146 1,168 635 508 64 66
Front Return 010 4 46 25 21 146 153 1,168 635 508 66 70
012 3 46 30 21 152 157 1,168 762 508 69 71
012 4 46 30 21 157 164 1,168 762 508 71 75
015 3 49 37 30 202 212 1,245 940 508 92 96
015 4 49 37 30 208 221 1,245 940 508 94 100
018 3 49 37 30 213 223 1,245 940 508 97 101
018 4 49 37 30 219 232 1,245 940 508 99 105
022 3 49 41 30 230 240 1,245 1041 508 104 109
022 4 49 41 30 236 249 1,245 1041 508 107 113

20
Guide Specifications

General OPTION: Provide Elastomeric Closed Cell Foam


Insulation in lieu of standard. Insulation shall con-
Furnish and install Airtherm SV Series Vertical form to UL 181 for erosion and NFPA 90A for fire,
Direct Drive Fan Coil units as indicated on the smoke and melting, and comply with a 25/50 Flame
plans and in the specifications. All units shall be Spread and Smoke Developed Index per ASTM
completely factory-assembled, tested and shipped E-84 or UL 723. Additionally, insulation shall
as one working unit. All units shall be capable of comply with Anti-microbial Performance Rating of
meeting or exceeding the scheduled capacities for zero, no observed growth, per ASTM G21. Polyeth-
cooling, heating and air delivery. Dimensions for ylene insulation is not acceptable.
each model and size shall be considered maximums.
Units shall be UL listed and also in compliance with OPTION: For exposed units, the bottom access
UL/ANSI Standard 1995, and be certified as com- panels shall be attached with quick open fasteners
plying with the latest edition of ARI Standard 440. to allow for easy removal and access for service.

OPTION: For exposed units, provide double de-


Construction flection discharge grille and either a rear return or
bottom return single deflection grille. Supply and
All unit chassis shall be fabricated of heavy gauge return duct connections are available.
galvanized steel panels able to meet 125-hour salt
spray test per ASTM B-117. All exterior panels shall Unit mounting shall be by hanger and slotted
be insulated with 1/2” thick, 3.35 pound per cubic hanging brackets provided at four locations. For
foot, dual density fiberglass insulation rated for a easy installation, exposed units provided with 1/2”
maximum air velocity of 3600 f.p.m. Insulation mounting knockouts in four places.
shall conform to UL 181 for erosion and NFPA
90A and 90B for flame spread (25) and smoke Painted Finish
developed (50) rating per ASTM E-84 and UL 723
and CAN./ULC, S102-M88. All exposed cabinet exterior panels shall be provid-
ed with soft-white powder-coated epoxy finish and
All concealed units shall have a minimum 1” duct subjected to a 1500-hour salt spray test in accor-
collar on the discharge. Plenum units shall have a dance with ASTM B117.
minimum 1” duct collar on the return.
Sound
All exposed units shall have exterior panels fabri-
cated of cold-rolled steel. The fan and filter bottom Units shall have published sound power level data
access panel has two screws for easy removal and tested in accordance with ARI Standard 350-2000
access for service and is also equipped with a (non-ducted equipment) and ARI Standard 260-
safety chain. 2001 (ducted equipment).
OPTION: Provide foil-faced insulation in lieu of
standard. Foil insulation shall meet or exceed the Fan Assembly
requirements stated above, and in addition, meet
ASTM Standards C665 and C-1136 for biological Unit fan shall be a dynamically balanced, forwardly
growth in insulation. Insulation shall be lined with curved, DWDI centrifugal type constructed of
aluminum foil, fiberglass scrim reinforcement, and heavy gauge zinc coated galvanized steel for cor-
30-pound kraft paper laminated together with a rosion resistance. Motors shall be high efficiency,
flame resistant adhesive. All exposed edges shall permanently lubricated sleeve bearing, permanent
be sealed to prevent any fibers from reaching the split-capacitor type with UL and C-UL listed auto-
air stream. matic reset thermal overload protection and three

21
Guide Specifications

separate horsepower taps. Single speed motors are re-heat or pre-heat position on the unit with chilled
not acceptable. water coils, and DX heating coil shall be in pre-heat
position only.
The fan assembly shall be easily removable for
servicing the motor and blower at or away from the Drain Pans
unit. The entire fan assembly shall be able to come
out of the unit by removing two wing nuts and Primary condensate drain pans shall be single wall,
unplugging the motor. heavy gauge, powder-coated epoxy subjected to a
650-hour salt spray test in accordance with ASTM
Plenum unit fan assemblies shall be easily serviced B117, and shall extend under the entire cooling coil.
through an access panel provided. Drain pans shall be of one-piece construction and
be positively sloped for condensate removal.
OPTION: Devices used to energize and de-en- Drain pans shall have primary and secondary
ergize (switch) fan speeds must be totally silent. drain connections.
Mercury and/or quiet relays and/or contactors are
not acceptable. The drain pan shall be externally insulated with a
closed cell foam insulation. The insulation shall
Coils carry no more than a 25/50 Flame Spread and
Smoke Developed Rating per ASTM E-84 and
All cooling and heating coils shall optimize rows UL 723 and fungi resistant per ASTM G21/C1338,
and fins per inch to meet the specified capacity. bacteria resistant per ASTM G22 and mold growth
Coils shall have seamless copper tubes and shall be per UL 181.
mechanically expanded to provide an efficient, per-
manent bond between the tube and fin. Fins shall OPTION: Provide a single wall primary drain pan
have high efficiency aluminum surface optimized constructed entirely of heavy gauge type 304 stain-
for heat transfer, air pressure drop and carryover. less steel for superior corrosion resistance. Stainless
steel drain pans shall be externally insulated and
All coils shall be hydrostatically tested at 350 PSIG meet or exceed the requirements stated above.
air pressure under water, and rated for a maximum
of 300 PSIG working pressure at 200°F maximum Provide a secondary drain connection on the prima-
water temperature. Direct expansion cooling coils ry drain pan for condensate overflow.
shall include a fixed orifice distributor and nozzle.
OPTION: Provide a condensate overflow switch in
Steam coils shall be standard steam type suitable for the primary drain pan for condensate overflow.
temperatures above 35°F and 15 PSIG maximum
working pressure. Filters
OPTION: Coil casing shall be fabricated from 304 All plenum and exposed units shall be furnished
Stainless Steel. All coils shall be provided with a with a minimum 1” nominal glass fiber throwaway
manual-air vent fitting to allow for coil venting. filter. Filters shall be tight fitting to prevent air by-
pass. Plenum and exposed unit filters shall be
OPTION: Provide automatic air vents in lieu of easily removable from the bottom or rear of the
manual-air vents. unit without the need for tools.
Cooling and heating coils shall be in the common OPTION: Provide unit with 1” pleated filters
coil casing, heating coils shall be furnished in the rated at 25-30% efficiency and MERV 6 based on
ASHRAE 52.2 - 1999.

22
Guide Specifications

Electrical (Option) power wiring capable of carrying 125% of the cal-


culated load current.
Units shall be furnished with single point power
connection. Provide an electrical junction box with OPTION: Devices used to energize and de-en-
terminal strip for motor and other electrical termi- ergize (switch) electric heat must be totally silent.
nations. Mercury and/or quiet relays and/or contactors are
not acceptable.
OPTION: The factory-mounted terminal wiring
strip consists of a multiple position screw terminal
block to facilitate wiring terminations for the elec- Piping Packages (Option)
tric control valves and thermostats.
Provide a factory assembled valve piping package to
Electric Heat consist of a 2 or 3 way, on/off, motorized electric
control valve and two ball isolation valves. Control
Furnish an electric resistance heating assembly as valves are piped normally closed to the coil. Maxi-
an integral part of the fan coil unit, with the heat- mum entering water temperature on the control
ing capacity, voltage and kilowatts scheduled. The valve is 180°F, and maximum close-off pressure is
heater assembly shall be designed and rated for 75 PSIG (1/2”) or 50 PSIG (3/4”). Maximum oper-
installation on the fan coil unit without the use of ating pressure shall be 300 PSIG.
duct extensions or transitions, and be located in the
unit as to not expose the fan assembly to excessive OPTION: Provide 3-wire floating point modu-
leaving air temperatures that could affect motor lat-ing control valve in lieu of standard 2-position
performance. control valve with factory assembled valve
piping package.
The heater and unit assembly shall be listed for zero
clearance and meet all NEC requirements, and be OPTION: Provide either a fixed or adjustable flow
UL listed with the unit as an assembly in compli- control device for each piping package.
ance with UL/ANSI Standard 1995.
OPTION: Provide pressure-temperature ports for
All heating elements shall be open coil type each piping package.
Nichrome wire mounted in ceramic insulators and
located in an insulated heavy gauge galvanized steel Piping packages are shipped installed on all units
housing. All elements shall terminate in a machine and can be shipped separately by request only.
staked stainless steel terminal secured with stainless
steel hardware for corrosion resistance. The element
support brackets shall be spaced no greater than 3-
1/2” on center. All internal wiring shall be rated for
105°C minimum.

All heaters shall include over temperature protec-


tion consisting of an automatic reset primary ther-
mal limit and back up secondary thermal limit. All
heaters shall be single stage.

An incoming line power distribution block shall


be provided and designated to accept single point

23
AIRTHERM Corporation
division of Mestek Corporation

www.airthermhvac.com

260 North Elm Street, Westfield MA 01085


Tel: (413) 564-5535 Fax: (413) 562-8437

Potrebbero piacerti anche