Sei sulla pagina 1di 1

D I A M O N S

-1/1- APPENDIX B
Technical Data: PD coupler installation
DIAGNOSIS & MONITORING SERVICES

Phase name U V W N Comments


Color code Green White Red Pink
Coupler type CC15 CC15 CC15 N/A
PDT-
PDT-15-
15- PDT-
PDT-15-
15- PDT-
PDT-15-
15-
Serial number 13--1113
13 1113 13--1114
13 1114 13--1115
13 1115
N/A
Phase capacitance --- --- --- ---
Coupler capacitance 1 1 1 N/A
Surge capacitance [nF] --- --- --- N/A No surge capacitor installed
CPDC-CTB --- --- --- N/A PD coupler – Connection box
CCTB-PDT --- --- --- N/A Connection box – PD detector
LM-T 0.3 0.3 0.3 N/A Maschine - Terminal
LT-SG > 10 > 10 > 10 N/A Terminal - Switchgear
LT-SC [m] N/A N/A N/A N/A Terminal – Surge capacitor
LT-PDC 0.2 0.2 0.2 N/A Terminal – PD coupler
LPDC-CTB 11 11 11 N/A PD coupler – Connection box
LCTB-PDD 5 5 5 N/A Connection box – PD detector
2 x RPDC-CTB [Ω] 0.7 1.1 0.9 N/A Measured on one cable side, 0 ohm at CTB

RI-S 1) > 275 > 275 > 275 N/A Inner conductor - Shield
RS-G 1) [MΩ] > 275 > 275 > 275 N/A Shield - Ground
RI-G 1) > 275 > 275 > 275 N/A Inner conductor - Ground
UCTB [V] 5.18 6.10 5.13 N/A 50/60 Hz during operation
1) Insulation resistance of BNC-cables measured with 250 VDC, for 10 seconds

LM-T LT-SG

LT-PDC
LT-SC Switchgear
Machine

CTB PD-Detector
Surge capacitor
LPDC-CTB LCTB-PDD
PD coupler
Connection box PD detector

Remarks and Comments

Document prepared Document checked and released

Christoph Wendel Stephane Betrisey


(RMTS, Rotating Machines Technical Specialist) (Field Service Engineer)

DIAMONS, Diagnosis & Monitor


Monitoring Services from Qualitrol

B CAHUA, SN POWER, 2013-06-04, G1, 50111027, C-INST_EN._.DOC