DESIGN DATA

SUMMER OUTSIDE INSIDE DIFFERENCE

DRY BULB 87.62 75.2 12.42

WET BULB 11.88


COOLING AND HEATING LOAD ESTIMATE SHEET
DEW POINT
78.08

74.87
66.2

64.4 10.47
FOURTH FLOOR
RELATIVE HUMIDITY 0.65 0.4 0.25 ADAMSON UNIVERSITY COMPUTER ROOM
TOTAL ENTHALPY BTU
PER LB. OF DRY AIR
0 MECHANICAL ENGINEERING DEPARTMENT
GRAINS OF MOISTURE
0
PER LB OF DRY AIR

WINTER 0 TRANSMISSION AND SENSIBLE HEAT GAIN HEAT LOSS

LATITUDE 14° 35" TIME 2:00 AM PMü ITEM NO ITEM AREA SQ. FT. TEMP. DIFF. U' FACTOR BTU/HR. TEMP DIFF. U FACTOR BTU/HR

WALL COLOR ROOF COLOR WINDOWS 1 EXTERIOR WALL N 234.963456 17 1797.4704384


0.45

LIGHT LIGHT AWNINGS 2 EXTERIOR WALL E 0

MEDIUM MEDIUM SHADES 3 EXTERIOR WALL S 171.05856 17 0.45 1308.597984

DARK DARK BARE 4 EXTERIOR WALL W 348.57216 17 0.45 2666.577024

SUMMARY OF HEAT GAINS 5 ROOF 0

ITEM NO. ITEM SENSIBLE LATENT GLASS SUMMARY CALCULATIONS

24 TRANS. AND SOLAR 6194.8696128 6 EXTERIOR GLASS N 36.148224 10 112.0594944


0.31
25 TRANSMISSION 0 7 EXTERIOR GLASS E

26 DUCTS 8 EXTERIOR GLASS S 100.05312 10 0.31 310.164672

27 BODY 11000 11500 9 EXTERIOR GLASS W

28 EQUIPMENT 7680 10 EXTERIOR GLASS


29 INFILTRATION 11 TOTAL TRANSMISSION AND SOLAR 6194.8696128 TOTAL HEAT LOSS

30 TOTAL SENSIBLE 24874.8696128 TRANSMISSION SENSIBLE HEAT


31 TOTAL LATENT 11500 12 FLOORS 0

32 TOTAL HEAT GAINS 36374.8696128 13 CEILINGS 0

SENSIBLE HEAT RATIO 14 PARTITIONS 0

ITEM 30 24874.8696128 15 GLASS IN PARTITIONS 0


33 2.16303214024348
ITEM 32 11500 16 MISCILLEANOUS 0

34 DRY BUL TEMP. OF SUPPLY AIR 50 17 TOTAL TRANSMISSION 0

35 WET BULB TEMP. OF SUPPLY AIR 50 BODY HEAT GAINS NO OF PEOPLE HEAT BTU/HR SENSIBLE LATENT

RISE IN DRY BULB TEMP.


36 22.5 18 50 220 11000
OF SUPPLY AIR SENSIBLE
37 TOTAL AIR SUPPLY 1005.04523688081 19 LATENT(QUIET) 50 230 11500

HEAT LOAD OF VENTILATION AIR 20 LATENT(ACTIVE) 0

NO OF PEOPLE CFM/PERSON 21 TOTAL BODY HEAT GAIN 11000 11500


38
50 15 750 EQUIPMENT HEAT GAINS WATTS MULTIPLIER

TOTAL COOLING LOAD ON COILS AND REFR. APPR. 22 ELCTRIC LIGHTS 960 8 7680

ITEM 32 36374.8696128 23 TOTAL EQUIPMENT GAIN 7680

ITEM 38 31353.75

39 TOTAL COOLING LOAD 67728.6196128


CREATED FOR THE DESIGN OF A CENTRALIZED AIR-CONDITIONING OF COLLEGE OF ENGINEERING BUILDING OF THE TECHNOLOGICAL UNIVERSITY OF THE PHILIPPINES
TONNAGE EQUIVALENT OF COOLING LOAD

ITEM 39 67728.6196128 CAOILE - OROBIA - TUAZON - 2018


40 5.6440516344
12000 12000
DESIGN DATA

SUMMER OUTSIDE INSIDE DIFFERENCE

DRY BULB 92.3 77 15.3

WET BULB 78.44 62.75 15.69 COOLING AND HEATING LOAD


DEW POINT 17.74

RELATIVE
71.6 53.86
ESTIMATE SHEET
0.26
HUMIDITY 0.76 0.5

TOTAL
ENTHALPY
ADAMSON UNIVERSITY
0
BTU PER LB.
OF DRY AIR MECHANICAL ENGINEERING DEPARTMENT
GRAINS OF
MOISTURE
0
PER LB OF
DRY AIR

WINTER 0 TRANSMISSION AND SENSIBLE HEAT GAIN

LATITUDE 14°TIME
35" 2:00 AM PMü ITEM NO ITEM AREA SQ. FT. TEMP. DIFF.

WALL COLOR ROOF COLOR WINDOWS 1 EXTERIOR WN

LIGHT LIGHT AWNINGS 2 EXTERIOR WE

MEDIUM MEDIUM SHADES 3 EXTERIOR WS

DARK DARK BARE 4 EXTERIOR WW


SUMMARY OF HEAT GAINS 5 ROOF
ITEM NO. ITEM SENSIBLE LATENT GLASS SUMMARY CALCULATIONS

24 TRANS. AND 0 6 EXTERIOR G N


25 TRANSMISSIO 0 7 EXTERIOR G E
26 DUCTS 8 EXTERIOR G S
27 BODY 0 0 9 EXTERIOR G W
28 EQUIPMENT 0 10 EXTERIOR GLASS
29 INFILTRATION 11 TOTAL TRANSMISSION AND SOLAR

30 TOTAL SENSIB 0 TRANSMISSION SENSIBLE HEAT


31 TOTAL LATENT 0 12 FLOORS
32 TOTAL HEAT G 0 13 CEILINGS
SENSIBLE HEAT RATIO 14 PARTITIONS

ITEM 30 0 15 GLASS IN PARTITIONS


33 #DIV/0!
ITEM 32 0 16 MISCILLEANOUS
34 DRY BUL TEMP. OF SUPPLY A 17 TOTAL TRANSMISSION
35 WET BULB TEMP. OF SUPPLY BODY HEAT GAINS NO OF PEOPLEHEAT BTU/HR

RISE IN DRY
BULB TEMP.
36 18
OF SUPPLY
AIR SENSIBLE
37 TOTAL AIR SUPPLY #VALUE! 19 LATENT(QUIET)

HEAT LOAD OF VENTILATION AIR 20 LATENT(ACTIVE)


NO OF PEOPLECFM/PERSON 21 TOTAL BODY HEAT GAIN
38
0 0 0 EQUIPMENT HEAT GAINS WATTS MULTIPLIER

TOTAL COOLING LOAD ON COILS AND REFR. APPR. 22 ELCTRIC LIGHTS


ITEM 32 0 23 TOTAL EQUIPMENT GAIN
ITEM 38 0
39 TOTAL COOLING LOAD 0
CREATED FOR THE DESIGN OF A CENTRALIZED AIR-CONDITIONING OF COLLEGE OF ENGINEERING BUILDING
TONNAGE EQUIVALENT OF COOLING LOAD

ITEM 39 0 CARASIG - DE VERA - GUIBELONDO - QUIMQUE - RETON


40 0
12000 12000
GROUND FLOOR

BLE HEAT GAIN HEAT LOSS

U' FACTOR BTU/HR. TEMP DIFF. U FACTOR BTU/HR

RY CALCULATIONS

0 TOTAL HEAT LOSS

N SENSIBLE HEAT
0

SENSIBLE LATENT

0
0 0

F COLLEGE OF ENGINEERING BUILDING OF THE TECHNOLOGICAL UNIVERSITY OF THE PHILIPPINES

RA - GUIBELONDO - QUIMQUE - RETONEL - 2017