Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Indian Standard
DESIGNANDINSTALLATIONOF
FIXEDFOAMFIREEXTINGUISHING
SYSTEM-CODEOFPRACTICE
PART 1 LOW EXPANSION FOAM
UDC 614’845’5
- ..
@ BIS 1991
r’
FOREWORD
This Indian Standard ( Part 1 ) was adopted by the Bureau of Indian Standards on 20 August
1989, after the draft finalized by the Fire Fighting Sectional Committee had been approved by the
Civil Engineering Division Council.
Fixed fire extinguishing installations are employed for protecting public buildings and industrial
premises where it is desired to keep fire losses to the minimum by automatic discharge of fire
extinguishing media immediately upon an outbreak of fire particularly when the premises are
unoccupied, as at night and during weekends and holidays, or in particular parts of the premises
which are at times unattended. Such installations are also employed for fire protection in pre-
mises or risks where it is not possible to fight the fire manually.
There are various types of fixed fire extinguishing installations, like carbondioxide, sprinklers, dry
powder, foam and halon. This standard covers the requirements of fixed foam fire extinguishing
installations. This standard is being prepared in two parts - Part 1 covering low expansion foam
and Part 2 other types.
Fixed foam fire extinguishing installations are suitable as extinguishing system for the fire risk like
flammable liquid processes and their storage areas, industrial chemical complexes, vehicle loading
bays, etc. Such types of systems can also be used to aircraft hangars not exceeding 7’5 m in height
or 1 600 m2 in area. This standard gives guidance to those who are responsible for the selection,
design installation and maintaining such systems. Adherence of this standard will ensure that these
systems will be effective in controlling and extinguishing the types of fires for which they are
designed.
For the purpose of deciding whether a particular requirement of this standard is complied with,
the final value, observed or calculated, expressing the result of a test, or analysis, shall be rounded
off in accordance iwith IS 2 : 1960 ‘Rules for rounding off numerical values ( revised )‘. The
number of significant places retained in the rounded off value should be the same as that of the
specified value in this standard.
IS 12835( Part 1 ) : 1939
Indian Standard
DESIGNANDINSTALLATIONOF
FIXEDFOAMFIREEXTINGUISHING
SYSTEM.-CODEOFPRACTICE
PART 1 LOW EXPANSION FOAM
I
IS 12835( Part 1 ) : 1989
c) Most aqueous foams are not suitable for b) Fluoroprotein Foam Concentrates (FP)
use on water-miscible flammable liquids, [ see IS 4989 ( Part 3 > : 1987 ]
which can cause rapid breakdown of the These are made from protein-based con-
foam by extraction of the water from the centrates by the addition of fluorinated
bubble walls. For these flammable liquids, and other types of surface active agents.
specially stabilized foam concentrates are An effect of adding these surfactants is to
used. give a foam of lower shear stress whilst
d) Foams are not suitable for use on fires retaining satisfactory heat resistance. This
involving gases, or liquefiable gases with results in the foam flowing more quickly
boiling points below 0°C or cryogenic than protein foams across the fuel surface
liquids. and around any obstructions giving faster
control and extinction. The improved
4 Because foams are made from aqueous flow properties and the higher surface
solutions they may be dangerous to use on activity gives the foam self sealing pro-
materials which react violently with water, perties, that is, if the foam blanket is bro-
such as metallic sodium or potassium. ken the foam will flow readily to reform a
They can, however, sometimes be used complete blanket. A further advantage of
with care on magnesium fires to help fluoroprotein foams over protein foams is
restrict burning by cooling the residual that they are far less vulnerable to conta-
metal. mination by hydrocarbon fuels, and are
suitable for use in sub-surface systems.
f) Low expansion foam is a good conductor These foam concentrates are usually avail-
and should not be used on energized elec- able for use in 6 percent concentrations.
trical equipment. Fluoroprotein foams exhibit good sealing
against hot metal edges.
s) Certain wetting agents and some extin-
guishing powders may be incompatible
with foams, causing a rapid breakdown of c) Aqueous Film Forming Foam Concentrates
the latter. Only agents which are substan- (AFFF) [ see IS 4989 ( Part 2 ) : 1984 ]
tially compatible with these foams should These foam concentrates, which may
be used in conjunction with them. In such also be referred to as fluorochemical
cases AFFF should only be used. foam concentrates, are based on fluori-
nated surface active materials in com-
h) Only certain types of foam concentrates are bination with other surface active agents
suitable for storage in the diluted or pre- and stabilizers. The foams produced are
mixed condition. AFFF can be kept in more fluid than fluoroprotein foams,
premixed condition up to 1 year. Protein having low critical shear stress values and
base foams are unsuitable for keeping in also short drainage times. They give very
premixed condition. quick control and extinction, but the fast
j) Simultaneous use of water jets or sprays drainage means that they do not have
may adversely affect a foam blanket, and high heat resistance and they may have
their use should not be envisaged in con- less burnback resistance than protein and
junction with these foams unless it has fluoroprotein foams. A feature of these
been shown that this will not occur. foams is that the solution draining out of
the foam is capable of forming a floating
3.8 The following types of low expansion foam film on the surface of some liquid fuels.
concentrates are covered in this standard: This can give protection against re-ignition
and give re-sealing properties should the
a) Protein Foam Concentrates (P) [ see IS 4989 foam blanket be broken. These concen-
( Part 1 ) : 1985 I trates are usually available for use in
These are liquids containing hydrolized 6 percent concentrations. They may be
protein materials with the addition of used for sub-surface systems.
2
IS 12835 ( Part 1 ) : 1989
FOAM MAkER
OR NOZZLF
3
IS 12835( Part 1) : 1989
TANK ISOLATING
VALVE (OPEN)
PRESSURE 7
HIGH BACK
PRESSURE FOAM
GENERATOR
( FOR DETAILS \
SEE FIG 28)
WATER/FOAM ’
SOLUTION
WATER/FOAM/AIR
FLOW MIXTURE -
more than one injection point pergenerator then 6 BASIC TYPES OF SYSTEM
the foam should be sampled on the line leading
to the most remote point. It is essential that 6.0 General
the foam generator discharged should be known
( see Fig. 2B >. A foam system consists of an adequate water
supply that can be pressurized, a supply of foam
5.1.1.2 Calculation liquid concentrate, a device to proportion
Using the formula Q = K/P correctly the water and foam concentrate and
pipework or hose connected to equipment de-
where Q is the foam solution flow rate - signed to produce and to distribute foam over
I/mm the risk.
and P is steady state inlet pressure-bar
Divide Q by the area ( in square metrcs > Self-contained systems are those in which all
protected by the injection point under test. components including water and foam concen-
trate are contained within the system. Such
5.2 Foam Distribution system often have water and foam concentrate
A check should be made to ensure that the foam stored as a premix solution in a tank which is
injection points are hydraulically balanced. pressurized by compressed gas when operated or
4
IS 12835 ( Part 1) : 1989
the foam concentrate can be stored and pressu- 4 System operating time.
rized separately.
f ) Quantity of foam concentrate required
There are three basic types of systems and each for extinction.
may be used inside or outside buildings:
a) Installed, fixed or semi-fixed; 22)Most suitable proportioning method(s).
5
.IS 12835( Part 1 ) : 1989
within 24 hours of operation. This supply may with a taper thread. Where gaskets are required
be stored in separate tanks, in drums or cans on they should be fabricated from a material which
the premises, or be available from an outside is non-combustible when tested in accordance
source. with relevant Indian Standard.
9.2.2 Adequate loading and transportation faci- Foam concentrates have a lower surface tension
litie’s&ould be’assured at all times. / than.water,.and they may cause internal pipe
scale or sediment to loosen, with the risk of
9*2*3 Other equipment which may be necessary blockage of sprayers, proportioning equipment,
to re-commission the system, such as bottles of etc. Pipes and fittings should be carefully clean-
nitrogen or carbondioxide for premix systems, ed before assembly, and any loose jointing
should also be readily available. material should be removed.
9.3 Foam Concentrate Pumps 10.2 Pipe Size, Run and Supports
9.3.1 Pumps used for foam concentrates should 10.2.1 The pipework for each system should be
be as reliable as fire pumps. They should be hydraulically calculated and sized in order to
centrifugal type self-priming, and driven by any ensure that pressure losses are kept within design
suitable prime mover conforming to relevant limits and that a reasonably uniform distribu-
Indian Standard. tion is obtained. In this way, the cost will b,o
kept to a minimum while ensuring that each
9.3.2 Materials of construction should be suit- foam generator works most efficiently. ( Rele-
able for use with the type and grade of foam vant Indian Standards in this regard be
concentrate without risk of corrosion, foaming followed. )
or sticking. Special attention should be paid to
the type of steel used. Stainless steel pumps 10.2.2 In locations where pipework may be ex-
are preferred. posed to fire or explosion, it should be coated
to afford the best protection against damage.
9.3.3 Pumps should have adequate capacities to This can be accomplished by running it close to
meet the maximum system requirements. To major structural members. In such locations,
ensure positive injection, the discharge pressure special consideration should be given to the
rating at design discharge capacity should be spacing and type of pipe supports used. Use of
sufficiently in excess of the maximum water cover pipe and where required pipework may
pressure likely under any condition at the point be encased in suitable resisting material.
of injection of the concentrate.
10.3 Drainage
9.3.4 Pumps should be provided with adequate
means of pressure and flow relief from the dis- 10.3.1 All dry piping should be arranged to drain
charge to the suction side of the circuit to pre- atld should have a minimum pitch towards the
vent excessive pressure and temperature. drain of 1 in 120.
,9.3.5 Pumps which are arranged to stand dry 10.3.2 Drain valves should be provided for
should have means provided for flushing with premix or finished foam lines at low points in
clean water after use. They should be provided piping, whether below or above ground.
with a drain down cock.
10.4 Corrosion Protection
9.4 Foam Concentrate Proportioning Systems
10.4.1 Internal Protection
Recommendations are given in Annex A.
7
IS 12835-( Part 1 ) : 1989
p’lastics or stainless steels, or Should be protect- are authorized to operate the system should be
ed externally by red oxide primer, undercoat thoroughly trained in its function and method
and two top coats of paint suitable for exterior of operation at least once in a month.
use in the prevailing atmosphere of the risk.
11.3 Manually-Operated Systems
10.4.2.2 The use of dissimilar metals should be
avoided, and an inert insulating means should be Controls for these systems should be located in
used to limit electrolytic action. an accessible place sufficiently removed from the
hazard zone to permit them to be safely operated
10.5Colour Coding of Pipework in emergency, yet close enough to ensure
that the operator knows the fire-ground condi-
The pipes should be colour coded in accordance tions. The location and purposes of the controls
with relevant Indian Standard. should be plainly indicated, and should be relat-
ed to the operating instructions.
10.6 Flushing
11.3.1 All operating devices whether manual or
10.6.1 Provision should be made in the design automatic should be suitable for the service con-
to permit the flushing with clean water after the ditions they will encounter. They should not
use of any lines which are normally empty but be readily rendered inoperative, nor be suscep-
which have contained foam concentrate, premix tible to inadvertent operation by environmen-
solution or made foam. tal factors such as high or low temperature,
10.6.2 Water supply mains, both underground atmospheric pollution, humidity, or marine
and above ground, should be flushed thoroughly environments.
at the maximum practicable rate of flow, before
connection is made to system piping, in order 11.4 Automatically-Operated Systems
to remove foreign materials which may have 11.4.1 Automatic systems should be operated by
entered during installation. a detection system ( see 11.5 ) which shall give
10.4.3 The minimum rate of flow for flushing a local alarm as well as an alarm at the plant or
should be not less than the water demand rate fire control centre.
of the system, as determined by the system 11.42 They should incorporate a manual
design and the available water supply. The flow operating device capable of overriding the
should be continued for a sufficient time to automatic control ( but not the alarm signal )
ensure thorough cleaning. Flushing water should if required. The manual override should be
be disposed of outside the system. All foam relayed to the plant or fire control centre.
system piping should be flushed after installa-
tion, using its normal water supply with foam- 11.4.3 Where foam is used for total flooding of
forming materials shut off, unless the hazard an area in which personnel are normally present,
cannot be subjected to water flow. Where flush- the system should be locked-off from auto-
ing cannot be accomplished, pipe interiors matic operation unless a suitable delay period
should be carefully examined for cleanliness is arranged between alarm and system operation,
during installation. SO that personnel may evacuate the effected area
before foam is discharged.
10.6.4 Pipework scale traps should be provided
in the line upstream of foam making equipment. 11.4.4 All operating devices whether manual or
Strainers should be inspected and cleaned after automatic should be suitable for the service con-
each USC. ditions they will encounter. They should not be
readily rendered inoperative, nor be susceptible
10.7 Tanks and pipes which are normally filled to inadvertent operation, by environmental fac-
with liquid should be protected against freezing tors such as high or low temperature, atmosphe-
where appropriate. ric pollution., humidity, or marine environments.
11 OPERATION 11.5 Requirements and Recommendations for
Fire Detectors, Alarms and Controls
11.1 Method
Foam system should be operated manually or
a>Detection and alarm equipment may be
electrical, pneumatic, hydraulic or mecha-
automatically, dependent upon the type and nical like link, line type.
location of the risk. In general, the choice will
be governed by the likely rate of fire devclop- b) Other than link/line systems, automatic
ment, the potential spread to other risks, and detection and control equipment should
the likely life hazard. be designed to give a positive warning of
any fault or abnormality which may ren-
11.2 Operatiag Instructions and Training der the system inoperative like loss of
power.
The operating instructions for any system,
whether manual or automatic, should be located 4 Automatic detection and control equip-
at the control equipment itself, and also at the ment should comply with relevant Indian
plant of fire control centre. All persons who Standards ( see IS 2189 : 1988 ).
8
IS 12835 ( Part 1 ) : 1989
12 COMMISSIONING AND PERFORMANCE This covers systems in which the foam is applied
TESTS through fixed, portable, or mobile or sortable
foam branch pipes to provide primary pro-
12.1 General tection for flammable liquid spills, bund areas
and storage tank fires.
The completed system should be inspected and
tested to determine that it is properly installed, NOTE - Portable foam branch pipes arc also
and that it will function as designed. A com- suitable for extinguishing rim fires in floating roof
tanks.
missioning test programme should be submitted
by the installer.
14.2 System Design
12.2 Inspection
14.2.1 General
A visual inspection should be conducted to en-
sure that the system has been installed correctly. Consideration should be given to the advantages
Inspection should include conformity with and limitations when selecting one of many vari-
design drawings and specifications, continuity of ations of this type of systems given in 14.2.2
pipework, checking, removal of temporary blinds, to 14.2.3.
accessibility of valves, control and gauges, and
proper installation of foam-makers, vapour seals, 14.2.2 Possible Advantages
and proportioning devices. All equipments
should be checked for correct indentification and a) Foam can be projected under favourable
operating instructions. circumstances, over considerable distances
and to significant heights.
12.3 Pressure Tests b) Portable and mobile monitor systems may
All pipework, except that handling expanded be housedout of the weather, are more like-
foam for other than base injection application, ly to be kept in a serviceable condition,
should be subjected to a hydrostatic pressure will be unaffected by explosion or flame
test at 14 bar or 1’5 times the maximum pres- exposure before fire fighting commences
sure anticipated, whichever is the greater for a and are available for use in all parts of the
period of 2 hours. All normally dry horizontal complex to be protected. They may also
pipework should be inspected for drainage. be set up in the most favourable upwind
position.
12.4 Component Inspections c) Oscillating monitors discharge foam even-
All operating devices and equipments should be ly over very large areas, automatically.
inspected for proper functioning and a record d) Fixed monitors may be remotely controll-
should be made to indicate that the required ed from considerable distances thus
performance will be met. rendering them suitable, for example, in
oil jetty protection and fire tug use.
12.5 Discharge Tests
Whenever possible, flow and distribution tests 14.2.3 Possible Limitations
should be conducted to ensure that the hazard
is fully protected in conformity with the design a) Foam discharge may be affected bv any
specification, and to determine the running pres- wind and fires updraught resulting iA dis-
charge outside the affected area.
sure, actual discharge rate, consumption rate of
foam concentrate, man power requirements and b) Tanks having ruptured roofs with only
other operating characteristics. Wherever pos- limited access for foam arc not easily ex-
sible the foam discharged should be inspected tinguished by monitor application from
and preferably tested to ensure that it is satis- ground level.
factory for the intended purpose performance.
c) Uniform foam distribution may not be
12.6 System Restoration achieved easily.
9
.
f) Foam monitors are not generally suitable determined by the following formulae:
for the primary protection of fixed roof Minimum quantity of foam concentrate
storage tanks of over 20 m diameter.
g) Monitor systems are not generally suitable Area X application rate X percent foam
for floating roof tank rim fires. ZZ concentrate X minimum discharge time
100
h) Where mobile or portable equipment is
used the time required to set up the equip- 14.5.1 The risk requiring the greatest quantity
ment may increase the fire preburn period of foam concentrate should be used to deter-
and may make extinction more difficult. mine the amount to be held at immediate readi-
ness.
14.3 Application Rates
Systems should be designed to deliver not less 14.5.2 Allowance should be made for the quan-
than the minimum foam solution rates specified tity of foam concentrate needed to fill the feed
in Table 1. lines installed between the source and the most
remote monitor or branchpipe. Where it is
14.4 Duration of Discharge desired to continue the water supply after the
foam concentrate is exhausted, in order to dis-
14.4.1 The system should be designed to ope- place the solution or concentrate in the feed
rate at the delivery rates given in Table 1 for the lines, no additional concentrate need be pro-
minimum periods of time given in Table 2. If vided.
the system discharges at a rate above the mini-
14.5.3 There should be a reserve supply of foam-
mum specified in Table 1 then the operating
producing materials readily available in accor-
time may be reduced proportionately, but should dance with 9.2.
not be less than 70 percent specified discharge
time. 14.6 Operation
14.5 Supply of Foam Concentrate 14.6.1 Automatfc Operation
The minimum quantity of foam concentrate Where systems are automatic in operation, pro-
which should be held in immediate readiness is vision of an audible alarm should be considered,
10
.
15.1 General
This applies to systems which are designed to
discharge foam in the form of a spray, and
which are intended to provide primary protec-
tion for specific hazards. Foam spray systems
are particulary suitable for hazards both out- FIG. 3 SELF-ASPIRATINGPENDANT
doors and indoors in which flammable liquid FOAM SPRAYER
may be spilled, sometimes in large quantities.
Typical examples include loading racks, horizon- 15.2.2 Possible Advantages
tal tanks, pump rooms and dip tanks. Protec-
tion of aircraft hangars up to 1600 m2 floor area a) The foam can be distributed evenly over
and 7.5 m high may be achieved by systems the fuel surface producing rapid fire con-
designed in accordance with the requirements trol.
and recommendations of this standard. Larger
and/or higher structures may require special b) Hot surfaces in contact with the fuel can
consideration over and above that given in this often be more effectively cooled by a
section of the standard. spray discharge. Exposures may also be
This relates only to
protected from heat radiation by the foam
spray discharge of aspirated foam, since some
of the sprayers do not produce effective dis- spray discharge.
charge pattern when used with water and AFFF 4 The equipment may be readily designed
only ( sue Fig. 3, 4 and 5 ). for automatic operation.
15.2 System Design d) While low expansion foam is not consider-
ed an effective agent for extinguishing
15.2.1 General three dimensional running flammable
liquid fires, it can control the pool fire
The points listed in 15.2.2 and 15.2.3 should beneath the running fire, leaving control
be considered when selecting one of the many of the running fire to other means like
variations of this type of system. dry powder fire extinguishers.
ASELF ASPIRATING
,,I’
IS 12835 ( Part 1 ) :
GROUND LEVEL
-acz
CAP
lSCRE’UEO
RETAINER
\
WAX SEAL
ARnlINn
-..-.s..I
BLOW-OFF CAP
/-;Nop SOLUTION
e) With some flammable liquids the water should therefore be positioned or protect-
spray distributed by foam sprayers can ed to avoid this possibility.
provide effective fire control as in high
flash point hydrocarbons. g) These systems are not suitable for use on
water soluble liquids exceeding 25 mm in
15.2.3 Possible Limitations depth.
12
IS 12835 ( Part 1) : 1989
Table 4 Minimum Discharge Times for outdoor risks in which water sprays alone could
Low Expansion Foam Systems Using be marginally effective, but where the addition of
Fixed Aspirating Sprayers an AFFF foam concentrate would improve the
( CIause 15.4 >
extinguishing performance (see Fig. 6, 7, 8 & 9).
/
Risk Area Minimum Discharge
Time
( ma ) ( minutes )
Indoor contained ] < 50 ma 5
liquid hydrocarbon 7 50 ma 10
spills 1
Indoor open top 7
process tanks con- ) < 50m* 5
taining liquid , > 50 m* 10
hydrocarbons J
Outdoor applica- Any area 10
tions
NOTES
1 For open top tanks, provision for constant
freeboard not less than 100 mm should be made.
2 For hazards where a large spill area is likely to
be involved, the foam spray system may be sub-
divided into zones, each protecting a specific floor
area and actuated by a suitable fire detection
system.
15.6 Operation
16.1 General
This covers systems which are designed to pro-
duce, discharge or distribute foam solution in FIG. 7 TYPICAL WATER SPRAY NOZZLE IJSED
the form of a series of fixed sprayer. Such AS A NON-ASPIRATING FOAM SPRAYER
systems may be used on either indoor or ( IMPINGING-JET TYPE )
13
IS 12835 ( Part 1) : 1989
14
IS 12835 ( Part 1 ) : 1989
Table 5 Minimum Application Rates for 17 FIXED FOAM POURER SYSTEMS (see
Low Expansion Foam System Using Fig. 10 A)
Fixed Non-aspirating Sprayers
17.1 General
( Clauses 16.3 and 16.4 1
This covers the systems which are designed to
Foam Concentrate Flammable Minimum Application apply foam through pouring devices, and to
Liquid Rate provide primary protection for outdoor atmos-
( l/m*/minute ) pheric flammable and combustible liquids in
Height of Discharge fixed roof tanks including covered floating roof
Point Above Ihe Lowest tanks ( see Fig. 10B ). These systems are intend-
Point of the Hazard (m)
r_____h___--7 ed for use in tank farms, oil refineries and
Up to and Above 10 chemical plants, and are usually operated
Including 10 manually. Tanks containing liquids with flash-
Fluorochemical hydrocarbon 4 6.5 points above 60°C do not normally need to be
( AFFF ) protected by fixed foam systems unless these
liquids are heated to their flash points. Protec-
NOTES
tion of open top floating roof tanks is describ ed
1 For open top tanks. provision for constant free-
board not less than 100 mm should be made. in 18.
2 The application rates should be achieved under 17.2 Components of Systems
any adverse wind conditions.
17.2.1 Fixed Foam Pourer ( Foam Discharge
Owlet )
Table 6 Minimum Discharge Times for
Low Expansion Foam Systems Using Equipment designed to discharge foam onto the
Fixed Non-aspirating Sprayers internal wall of a tank, so that it will flow down
gently onto the surface of the flammable liquid
( Clauses 16.4 and 20.4 ) without undue submergence of the foam or
Risk Area Minimum Discharge agitation of the surface. Some pourers arc
(ms) Time ( minute ) for designed to discharge the foam tangentially in
Pluorochemical order to create a circular motion, and thus pro-
( AFFF ) Foam mote foam distribution.
Indoor coniained 1
liquid hydrocarbon > < zOand ( 5o
17.2.2 Foam Chamber ( Vapour Seal Box )
spill J
Indoor open top 1 Equipment designed to prevent tank vapour
process tanks con- ’ > 5 and < 50 entering the foam pipework systems, while allow-
taining liquid t > 50 ing the foam to enter the tank without undue
hydrocarbon J resistance when required.
Outdoor applica- Any area 10
tions
17.3 System Design
NOTES
The items given in 17.3.1 and 17.3.2 should be
I Automatic systems should include the facility
for co-incidental automatic heat source shut down. considered when designing this type of system.
2 For hazards where a large spill area is likely to
be involved, the foam spray system may be sub- 17.3.1 Possible Advantages
divided into zones, each protecting a specific floor a) The total foam output may be applied to
area and actuated by a suitable fire detection fuel surface.
system. I
b) An even foam distribution may be achiev-
ed.
16.5 Supply of Foam Concentrate c) The system comprises simple equipment
The requirements are same as given in 14.5. capable of withstanding fire exposure.
d) Only moderate maintenance of the foam-
16.6 Operation making vapour seal box and pouring
16.6.1 Automatic Operation equipment is required.
17.3.2 Possible Limitations
Automatic operation is to bc preferred for non-
aspirated spray systems, especially those in Equipment attached to tanks might bc damaged
which the hazard is unmanned or is indoors, by explosion or fire exposure.
where a quick response is imperative ( see 11.4 17.4 Application Rates
and 11.5 )_
Systems should be designed to deliver not less
16.6.2 Manual Operation than the minimum foam solution delivery rates
specified in Table 7.
The details are given in 11.3.
17.5 Duration of Discharge
16.7 Special Consideration
The equipment should be designed to operate at
Corrosion protection should follow the recom- the delivery rates specified in Table 7 for the
mendations of 10.4. minimum period of time shown in Table 8. If the
15
IS 12835 (Part 1) : 1989
16
IS 12835 ( Part 1 ) : 1989
Table 8 Minimum Discbarge Times for Low normally be buried under at least 0’3 m depth
Expansion Foam Systems Using Fixed of earth, but may be permitted above ground if
Foam Pourers properly supported and protected against
mechanical damage as well as fire.
( Clause 17.5 j
Minimum Discharge Time
17.8.2.2 All pipework within the bunded area or
Risk
c---- h--_--y within 15 m of the tank to be protected should
Protein ( P ) Fluoroprotein be designed to withstand the upward shock due
( minute ) (Fe) to a tank roof rupture. All welded steel pope
Fluorochemical
( AFFF )
construction is to be preferred.
( minute )
Indoor and outdoor spill pro- 10
17.8.2.3 When pipework is burried, a metal
10
tection flexible joint should be provided at the base of
Tanks containing liquid hydro- each tank riser. The flexible joint should consist
carbons: of a system of suitable standard weight fittings
Flash point below 40°C made from steel, or ductile, or malleable iron.
55 45
Gasoline, etc I
Flash point above 40°C 17.8.2.4 When pipework is supported above
30 30 ground, it should have the necessary upward
Kerosene, etc )
and lateral support but should not be held down
within a distance of 15 m from the tank shell, so
in a vertical fuel storage tank. They are not as to permit sufficient flexibility in an upward
suitable for discharging foam onto horizontal or direction to obviate the need for a flexible joint.
pressure tanks. If threaded connections are used within this
Foam pourers should be securely attached to the distance, they should be back welded for
inside wall of the tank shell, adjacent to the top. strength.
They should be mounted in such a way as to
ensure that displacement of the tank roof will 17.8.2.5 When tank risers are of 100 mm dia-
not damage them sufficienfly to render them meter or larger, they should be welded to the
inoperative. Their location should be such tank by means of steel brace plates positioned
as to preclude the possibility of the tank over- perpendicular to the tank, and centred on the
flowing onto the foam lines. Where more than riser pipe. One brace should be provided at
one pourer is required, they should be spaced each shell course. The design may be used
equally around the tank periphery and should instead of swing joints, or unconstrained pipe-
discharge foam at approximately the same rate. work as described above.
The minimum number of pourers should be as 17.8.2.6 One flanged or union joint should be
shown in Table 9. The maximum distance bet- provided in each riser within 15 m of the ground
ween pourers should be not greater than 24 m. to permit hydrostatic testing of the pipework
system up to this joint. ( With allm,welded cons-
Table 9 Minimum Number of Foam truction, this may be the only joint that can be
Pourers opened ).
( Clause 17.8.1 )
17.8.2.7 In systems with semi-fixed equipment
Tank Diameter ( m ) Minimum Number of on fixed roof tanks, the foam or solution laterals
Foam Pourers to each vapour seal should terminate in a con-
Up to 24 nection which is outside the bund walls and at
Over 24 to 36 I
Over 36 to 42 least 15 m from tanks of IS m diameter or less,
Over 42 to 48 : and one tank diameter from the shell of larger
Over 48 to 54 tanks. The inlet to the pipework should be
Over 54 to 60 2 fitted with corrosion resistant metal connections
provided with plugs or caps.
For tanks over 60 m in diameter, at least one
additional foam pourer should be added for 17.8.3 Valves
each additional 460 m2 of flammable liquid sur- All valves, except hydrant valves, should be
face, located to give even foam distribution. indicator type valves. The laterals to each foam
Central sub-surface application may be used to vapour seal box on fixed roof tanks should be
give protection to the central area of the fuel equipped with separate valves, which should be
surface, outside the bund in fixed installations. Control
Fixed foam pourers should be equipped with an valves to divert the foam or solution to the app-
effective and durable seal, frangible under low ropriate tank may be either in a central control
pressure to prevent entry of vapour into the house, or at points where lateral to the protected
foam pourer and pipe lines. Access should be tanks branch from a main feed line. Control
provided to permit inspection and maintenance, valves should be located outside bunds and
including replacement of the vapour seals, should be not less than the following distances
from the shell of the tank which they serve:
17.8.2 Foam System Piping
15 m for tanks less than 15 m in diameter; 1
17.8.2.1 All pipework inside bund areas and diameter for tanks 15 m in diameter or larger,
within 15 m of non-bunded tanks should except that control valves may be permitted
17
.
at less than the above distances where they 18.2.1 Possible Advantages
are adequately protected against fire. Where
two or more foam proportioners or foam a) Total foam output reaches the rim seal
generators are installed in parallel discharg- area.
ing into the same outlet header, valves should b) Using foam pourers and a foam dam, the
be provided between the outlet of each device equipment is simple and requires only
and the header. The water line to each foam moderate maintenance.
proportioner or foam generator inlet should
be equipped with a separate valve. c) Foam is applied gently without severe
mixing with the fuel.
18 FIXED FOAM POURER - FOR OPEN
TOP FLOATING ROOF TANKS 18.2.2 Possible Limitations
18.0 General a) Where foam is injected below the panto-
graph or weather shield a foam generator
This covers fixed foam pourers for the primary might not be capable of operating against
protection of open top floating roof tanks. the pressure required to force foam
Tanks of this design have a good fire record and around the rim seal area.
normally do not require fixed protection but if
fixed protection is specified it need only be for b) Where foam is injected into the rim seal
the rim seal area. area, special pipework is needed to con-
18.1 Floating roof seals may be of the panto- duct foam from outside the shell onto
graph type or may be a tube seal with metal the roof area. This needs to be hinged or
weather shield. Foam should be discharged jointed to allow for movement of the roof,
into the seal area behind a foam dam secured to and has to be protected or designed to
the floating roof, or should be injected below withstand the effects of a rim seal fire.
the pantograph seal, or behind the metal weather
shield into the rim seal area in the case of tube 4 Adverse winds and obstructions project-
seal designs ( see Fig. 11 ). ing through the fuel surface may reduce
the effectiveness of the system and allow-
18.2 Systems Design ance should be made in the rate of appli-
cation of foam.
Consideration should be given to the advantag-
es and limitations given in 18.2.1 and 18.2.2
when selecting this type of system.
SEAL FABRICATE
SD35Ai%-O-FOAM
ING
Ic--
FOAM DAM
FIG. 11 FIXED FOAM POURER - FOR OPEN TOP FLOATING ROOF TANKS
18
IS 12835 ( Part 1 ) : 1989
In both cases systems should be designed to 18.7.5 Location of Foam Pourers or Outlets
deliver not less than 20 l/m2/minute of foam.
Foam pourers or outlets should be equally spaced
18.4 Duration of Discharge around the periphery of the tank, and should be
designed to deliver foam at approximately equal
18.4.1 Foam Applied Above the Seal Between the rates:
Foam Dam and Tank Shell
a) Where foam pourers are used to apply
The system should be designed to be capable of foam above the seal into the area behind
operation for at least 20 minutes. the dam, the following spacing should
be used:
18.4.2 Foam Injected into the Seal Area Without
a Foam Dam Dam Height ( m ) Maximi;r;tI;Spucing
0.3 to 0’6
The system should be designed to operate at the Above 0’6 24 m
rate specified in 18.3 for at least 10 minutes.
b) Foam injection below a pantograph type
18.5 Supply of Foam Concentrate seal - The maximum spacing between
foam applicators should be 40 m, measured
The requirements are same as given in 14.5. around the circumference of the tank.
19
.
c) Foam injection between tube seal and 4 Only foams which will tolerate severe
weather shfeld-The maximum spacing mixing with fuel are suitable for sub-
betweeil applicators. should be 18 m, surface application into a wide range of
measured around the circumference of tanks of various heights and diameters.
the tank.
d) The foam needs to be injected above any
water in the base of the storage tank, in
19 SUB-SURFACE FOAM SYSTEMS
order to prevent the foam being destroyed.
19.1 General 4 Sub-surface systems may not be suitable
for certain high viscosity fuels.
This covers systems for the protection of fuel
storage tanks, by which foam is injected at the 19.3 Application Rates
base of the tank with sufficient pressure to over-
come the head of fuel. A special foam inlet Systems should be designed to deliver not less
pipe may be used. than the minimum foam solution application
rate specified in Table 10.
19.1.1 These should be used provided that it can
be ensured that the isolating stop valve at the
base of the tank is normally kept open. Table 10 Minimum Application Rates for LOW
Expansion Foam in Sub-surface Systems
19.1.2 This type of protection is suitable for ( Clauses 19.3 and 19.4 )
fixed roof tanks, but is not suitable for floating
roof tanks with or without fixed roofs. Flammable Liquid Foam Concentrate Minimum
Application
19.1.3 Sub-surface application is not suitable for Rate
the protection of water-miscible fuels and only ( l/ma/minute)
Hydrocarbon Fluoroprotein (FP) 4
fluoroprotein and AFFF type foam concentrate Fluorochemical (AFFF)
and suitable for this purpose.
19.4 Duration of Discharge
19.2 System Design
The advantages and limitations given in 19.2.1 The system should be designed to operate at the
and 19.2.2 be considered in selection of this delivery rates specified in Table 10 for the mini-
type of system. mum periods of time shown in Table 1I. If the
foam application rate is above the minimum
specified, the duration of discharge may be
19.2.1 Possible Advantages reduced proportionately, but in any case should
4 The total foam output reaches the tank, be not less than 70 percent of the specified dis-
charge time.
b) With large tanks, suitably arranged inlets
allow even foam distribution over the Table 11 Minimum Discharge Time for Low
whole free surface area of the fuel. Expansion Foam in Sub-surface systems
c) The system is essentially simple and, being ( Clause 19.4 )
at ground level, is less likely to be damag-
ed by fire or explosion. Risk Minimum
Discharge Time
( minutes )
d) The circulation of cold fuel from the base Tanks containing liquid hydrocarbons
of the tank to the burning surface caused
by the rising foam stream can be utilized a) Flash point below 40°C
gasoline, etc 45
to assist extiction and to dissipate hot fuel
layers at the burning surface. b) Flash point above 40°C
kerosene. etc 30
e) Essential equipment and operating per-
sonnel may be located at safe distance 19.5 Sopply of Foam Concentrate
from the fire.
The requirements are same as given in 14.5.
f ) It may be possible to use the normal pro-
duct line for foam injection. 19.6 Operation
8) The system is easy to check and maintain. The requirements are given in 11.
19.2.2 Possible Limitations 19.7 Special Considerations
a) Sub-surface systems are not suitable for The addition to the special considerations of the
water-miscible fuels. following shall be noted.
b) Sub-surface systems are not suitable for 19.7.1 Foam outlets positioned at the tank shell
the protection of floating roof tanks be- or inside the tank via a manifold should dis-
cause the roof will prevent complete foam charge foam above any water layer present in
distribution. the tank.
20
.
19.7.2 With some fuels where there has been a bund wall provided the controls are located in
long preburn prior to the application of foam an accessible and safe position outside the bund.
a hot zone may exist near the burning surface A non-rettirn valve should be located between
at temperatures in excess of 100°C. In order to the tank isolating valve and the high back-
avoid frothing and slop-over, continuous appli- pressure generator.
cation of foam should be avoided in the inrtial
stages. Intermittent application of the foam can 19.7.5 Friction Losses
induce circulation of the fuel in the tank, there-
by bringing the cooler layers of fuel to the System design should be such that the total back
surface. The foam injected intermittently will pressure due to the head of fuel and to friction
disperse without sufficient steam formation to losses in the foam carrying pipework does not
produce frothing. Table 12 gives requirements exceed the pressures of the foam producedby
for the number of foam injection points. the high back-pressure generators. Allowance
should be made for pressure losses due to fric-
Table 12 Number of Foam Injection Points for tion at valves or bends.
Low Expansion Foams in Sub-surface Systems
20 SEMI SUB-SURFACE SYSTEMS
Tank Diameter Volatile Non-volatile
m Products Products 20.1 General
( Flash Point ( Flash Point
Below 40°C ) Above 40°C > This covers systems from which foam is applied
I to the surface of oil storage tanks via a flexible
Up 24to 36
Overto 24 :
Over 36 to 42 3 hose rising from the base of the tank. A special
z
2”
2
container within the tank houses the hose and
Over 4248 to 48
54 is connected at the base of the tank to an ex-
Over 54 to 60 6 3 ternal foam generator capable of working against
Above 60 m add one extra the maximum product head. This type of
inlet for each additional
area of 460 ma 700 ma protection is suitable for fixed roof tanks but is
not normally considered appropriate for float-
ing roof tanks with or without fixed roofs
19.7.2.1 Where more than one foam injection ( see Fig. 13 ).
point is required, these points should be design-
ed to deliver foam at approximately the same 20.2 Systems Design
rate and should be positioned to distribute foam
evenly over the free surface of the fuel in the The advantages and limitations given in 20.2.1
tank shell, terminating in a central manifold and 20.2.2 should be taken into account when
with separate outlets arranged radially. considering the selection of this type of system.
19.7.2.2 Injection point pipe diameters should
be sized so that the discharge velocity of expand- 20.2.1 Possible Advantages
ed foam into the tank is less than 3 m/s for
volatile products ( flash point below 40°C ) or a) The total foam output reaches the surface
6 m/s for non-volatile products (flash point of the burning liquid.
above 40°C )
b) With large tanks, the semi sub-surface
NOTE - Dissharge velocities arc calculated on the units can be arranged to produce an even
flow of expanded foam assuming an expansion of 4. distribution over the fuel surface.
c> Protein, fluoroprotein or AFFF cgncen-
19.7.3 Foam System Pipework trates may be used.
Pipework should be in accordance with 10. The d) Foam generating equipment and operating
high back pressure foam generators and foam personnel may be located at a safe dis-
solution supply may be fixed or portable for tance from the fire.
connection to foam inlet pipes or product line
connections outside the bunded area. e) Light fuels as gasoline/kerosene be used.
21
.
I I /FOAM 6L ANKET
HOSE CONTAINER
- -. -I /-BLOCK VALVE
d) The system may be difficult to check, test The number of semi sub-surface units for dis-
and maintain. The hose container be pensing low expansion foam should be as shown
replaced every 8 years. in Table 13.
20.3 Application Rates Table 13 Number of Semi Sub-surface Units
Systems should be designed to deliver not less
Tank Diameter Number of Semi Sub-
than the minimum foam solution application surface Units
rates as specified in Table 6. up to 2:
Over 24 to 36 :
20.4 Duration of Discharge Over 36 to 42
Over 42 to 48 :
The system should be designed to operate at the Over 48 to 54
delivery foam rates specified in Table 6 for the Over 54 to 60 :
minimum period specified in Table 7. Above 60 m add one extra inlet for
each additional area of 460 rnr
20.5 Supply of Foam Concentrate
The requirements are as given in 14.5. 20.7.2 Foam System Pipework
The requirements are given in 17.8.2.
20.6 Operation
20.7.3 Valves, ( Check )
The requirements are as given in 11. The requirements are given in 17.8.3.
20.7 Special Considerations 20.7.4 Friction Losses
20.7.1 Semi sub-surface units should be secured The provision is given in 19.75.
by straps for support and sited within the base 21 SUPPLEMENTARY PROTECTION FOR
of the tank away from tank level indicator de- STORAGE TANKS
vices and swing arm product pipes. Where
more than one unit is required, these should be 21.1 General
spaced equally around the tank periphery and This covers the provision of water and foam
should be designed to dispense foam at approxi- hydrants and portable foam branchpipes to sup-
mately the same rate. Arrangements should be plement the primary means of fire protection.
made to ensure that access to the units can be
undertaken at regular intervals for inspection. 21.2 Each foam branchpipe should be designed
Non-return valves should be fitted at the foam to give a solution flow rate of at least 500
entry points adjacent to the tank wall. l/min. Additional foam concentrate should
22
.
be provided to permit operation of all extra outlets discharging onto the inner wall of the
branchpipes simultaneously with the primary bund, or by fixed foam or oscillating or portable
means of fire protection and for the minimum monitors, or by foam spray systems discharging
discharge duration specified in Table 14. within the bunded area. Alternatively portable
equipment may be desirable for large bund areas
Table 14 Minimum Number of Supplementary where fixed equipment is not appropriate.
Branchpipes and Duration of Discharge
22.3 Application Rates
Diameter of Minimum Number Minimum The principles involved in the protection of
Largest Tank of Foam Branchpipes Discharge bunded areas will be governed by the size and
with Manifold with Time
shape of the bund, and the type of fire ptotec-
up to 10 Each
HyPrant ( %Yute
) tion used. Where a bunded area is small enough
Over 10 and up to 20 I for the use of fixed sprayers, monitors and
Over 20 and up to 30 i pourers then the design of the protection system
C$; jg and up fo 40 2”
3 30 should generally be such as to cover the whole
area of the bund. In these cases the application
rates should be selected from Tables 1, 3, 5, 7
21.3 Hydrants as applicable. Where appropriate, mobile
For fixed piping systems in addition to the monitors and branchpipes may be used to apply
primary means of protection, and the supple- foam to cover the bunded area progressively.
mentary protection specified in 21.2 supplemen- The area of immediate application should be
tary hydrants should be provided for use with provided with foam at the above rate and it is
portable foam monitors or portable foam towers essential that this area is secured before pro-
in the event that a fixed discharge outlet on the ceeding to farther areas.
primary protection system is damaged. In lieu
of a foam hydrant a water hydrant may be used 22.4 Duration of Discharge
in conjunction with suitable foam producing The system should be designed to operate at the
equipment. The minimum number of hydrants, delivery rates specified in 22.3 for a minimum
each having at least one outlets, should be as period of 1 hour.
shown in Table 15.
Each hydrant should be located between 15 m 22.5 Supply of Foam Concentrate
and 75 m from the shells of the tanks being pro-
tected by the associated primary system. The requirements are same as given in 14.5.
The flow from hydrants should be sufficient to 22.6 Operation
support portable equipment to be used,
23
IS 12835 ( Part 1 ) : 1989
ANNEX A
( Clause 9.4 )
INFORMATION ON FOAM CONCENTRATE PROPORTIONING SYSTEMS
A-0.1 All foam systems require a foam concen- A-2.1 In this method, the acceleration of a
trate to be mixed with water in a specified cor- water stream through an inductor produces a
rect proportion to provide a foam-making fall in water pressure which is utilized to induce
solution. Methods by which this may be foam concentrate into this stream in the required
achieved are listed as follows: proportions. There are several arrangements
available, and each has a particular application.
a) By premixing the concentrate in water. a>Self Induction ( see Fig. 14 )
b) By induction of the concentrate into the Self-inducing foam-making equipment in-
water stream. corporates a foam of inductor to draw in
foam concentrate via an induction or
c) By displacement of the concentrate in pick-up tube. This arrangement may be
the water stream. referred to as ‘end of lme’ induction.
This method may be used for fixed or
d) By injection of the concentrate into the portable branchpipes and monitors. The
water stream. following points should be considered:
A-l PREMIXED FOAM SOLUTION 1) The concentrate should be made avail-
able at the nozzle.
A-l.1 This method involves mixing appropriate 2) The bottom of the concentrate ‘container
quantities of water and foam concentrate for generally should be not more than 2 m
storage as a premixed foam solution ( premix ). below the induction point. The length
The foam system can then be supplied with and size of the induction hose or pipe
premix when required either by pumping if the should depend upon the design of
premix is stored in an atmospheric tank or by inductor.
pressurization if the premix is stored in a 3) It should have balance pressure propor-
pressure vessel. Different types of foam have tionater.
different shelf life as concentrate and premixed.
The following points should be considered: b) In-Line Induction ( see Fig. IS )
An inductor is arranged in the hose or
The foam concentrate should be suitable pipework between the fire pump and the
for storing for long periods as a premixed foam-making units, usually at some
solution. Higher concentrations may distance from the latter. Foam concen-
sometimes be employed to reduce pro- trate may therefore be introduced at a safe
blems of deterioration that is by using a distance from the iire. Variation of
6 percent concentrate at 10 percent solu- concentration may be achieved by use
tion strength. of a manually controlled metering
valve. The following points should be
High storage temperatures tend to accele- considered:
rate any deterioration due to ageing of the 1) The in-line inductor should be suitable
solution.
for the particular foam-maker with
The premix method usually employs a which it is to be used. The device is
pressurized tank for the smaller risk where very sensitive to downstream pressures
a quick acting automatic system is requir- and is accordingly designed for use with
ed. Nitrogen or carbondioxide is gene- specified length of hose or pipe between
rally used for expellmg the tank contents. it and the foam-maker. Location of
FOAM ENTRY
VALVE
25
IS 12835 ( Part 1 ) : 1989
PLATFORM :EvEp /
RISER PIPE
r
BY PASS INOUCTOR
t
NON RETURN VALVE
r
FOAM CONCENTRATE
CONTROL VALVE
CONCENTRATE
FIG. 16 BYPASSINDUCTION
FIRE PUMP
METERING VALVE
(IF FITTED)
FOAM CONCENTRAT
PICK- UP -
. t t
FOAM
CONCENTRATE
CONTAINER
A-3 DIS CLACEMENT PROPORTIONER ducing a moderate pressure drop when the fire
( BLADDER PRESSURE PROPORTIONING fighting system is operating, has its high and low
TANK ) ( see Fig. 18 ) pressure sides connected to the pressure vessel
A-3.1 Foam concentrate is stored in a flexible in such a way that a feed from the high pressure
bag within a pressure vessel. A device for pro- side of the water supply flows into the vessel to
26
IS 12835 ( Part 1) : 1989
FILTER CAP
/
FOAM CONCENTRATE-
FLEXIBLE MEMBRANE
/ FOAM CONCENTRATE STORED
PERFORATED IN FLEXIBLE MEMBRANE
/ I
fjYPW0r.l TUBE-
RRESSURE
5 ToRAGE TANK
FIG. 18 DISPLACEMENTPROPORTIONER
displace the foam concentrate by applying pres- concentrate pressure vary. The following
sure to the bag. The concentrate then flows to points should be considered:
the low pressure side of the device where it 1) The system is suitable only for a fixed
mixes with the main water flow. A variety of water flow rate.
arrangement may be used ranging from a single
pressure vessel to a battery of vessels connected
by a manifold. Twin vessels are often used so
that when one is exhausted, the other may be
operated. The first vessel is then recharged,
thus securing continuous operation of the
system. This arrangement is suitable for both
large and small systems. The following points
should be considered:
a) Units are able to cater for a variation in
water flow rates.
b) The pressure drop across the proportioner FIG. 19 CONSTANTFLOW VALVE
varies from 0’1 bar to 1’0 bar, depending
upon the range of water flows. 2) A separate pump is required to deliver
the concentrate.
c) Multiple units permit recharging with
foam concentrate during operation, if this
is required. b) Variable Flow Injection ( see Fig. 20 )
This unit is situated in the fire water main
A-4 INJECTION and is fed with foam concentrate at pres-
sures higher than or equal to the water
A-4.1 Foam concentrate is supplied to a meter- pressure. Regulation of the concentra-
ing device under a pressure greater than that of tion is effected automatically whether
the water supply, by means of a foam pump. water or foam concentrate pressure vary
Several arrangements are available and each is or whether the water main flow varies.
suited to a particular application.
c>Balanced Pressure Proportioning ( see
Fig. 21 )
a) Metering OrijicelConstant Flow Valve ( see
Fig. 19) By means of an auxiliary pump, foam
compound is injected into the water stream
An orifice is used to provide a fixed flow passing through an inductor. The result-
of foam concentrate into the water stream. ing foam solution is then delivered to a
Alternatively a constant flow valve may foam-maker or playpipe. The inductor
be used to maintain accurate proportion- may be inserted in the line at any point
ing in the system when the water or foam between the water source and foam-maker
27
12835( Part 1) : 1989
rFOAt4A(fM4ECENTRATE
-&I-
PRESSURE RELIEF
TO SYSTEM (S)
I
FIG. 20 VARIABLE FLOW INJECTION
CONNECTION
EXPANSION DOME ANn I-
WITH FUNNEL
l FOAM CONCENT~T~
PUMP AND MOTOR
ASSEMBLY
or branchpipe. The following points 2) Units are able to cater for flow ratios
should be considered: up to 10 to 1.
28
IS 12835 ( Part 1 ) : 1989
ANNEX B
( CZause 13.1 )
b) Monthly
3) Strainers
Check that all operators are familiar with
the equipment or system and that new Strainers should be inspected and clean-
employees have been instructed about ed. This should always be accomplish-
its use. ed after any flow test.
29
IS I2835 ( Part 1 ) : 1989
30
I I
Standard Mark
I
The use of the Standard Mark is governed by the provisions of the Bureau of Indian
StandardsAct, 1986 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been produced
to comply with the requirements of that standard under a well defined system of inspection,
testing and quality control which is devised and supervised by BlS and operated by the pro-
ducer. Standard marked products are also continuously checked by BIS for conformity to
that standard as a further safeguard. Details of conditions under which a licence for the use
of the Standard Mark may be granted to manufacturers or producers may be obtained from
the Bureau of Indian Standards.
, I