Combustible dust is a major safety concern An initial, or primary, deflagration in a dust collector
in many bulk solids manufacturing plants. will cause shockwaves that can reverberate through the
This article introduces the hazards of building and disturb any accumulated dust. This dust
may then become airborne and provide fuel for one or
handling combustible dust, discusses the more secondary explosions if the primary deflagration
relevant standards and guidelines, and breaks out of the dust collector or if another ignition
explains protection options available to source is present. Often a secondary explosion is much
reduce your plant’s risk for a catastrophic more destructive than the primary explosion and can
dust explosion. potentially level a building in less than a second, as
shown in Figure 2.
D
ust generated during bulk solids distributing air but can also allow a flame front from a
manufacturing operations can be separated deflagration to travel from one end of the system to the
into two categories: combustible and other. A piece of process equipment with an explosive
noncombustible. Under predictable conditions, a concentration of dust along with an ignition source
noncombustible dust won’t ignite, burn, release could trigger a primary explosion that could travel
flammable gases, or support combustion when through the ductwork to the dust collector, causing a
subjected to fire or heat. A combustible dust, on the secondary explosion in the collector. This is also true in
other hand, will pose a fire or deflagration hazard the opposite direction; if a deflagration occurs in the
when subjected to fire or heat in the presence of an dust collector, the resulting flame front could travel
oxidizing medium (such as air). through the ductwork back to the process equipment.
Figure 2
c. Shockwaves reflect off building surfaces d. Disturbed dust becomes suspended in air
g. Secondary deflagration propagates through suspended dust cloud h. Secondary deflagration bursts from building
• NFPA 664 Standard for the Prevention of Fires and dust’s hazard classification, defined in NFPA 70 as
Explosions in Wood Processing and Woodworking follows:
Facilities Class I: Gases, vapors, and liquids
Class II: Dusts
On September 7, 2015, the NFPA adopted NFPA 652 Group E: Metal dusts (conductive and explosive)
Standard on the Fundamentals of Combustible Dust
(2016 Edition). NFPA 652 binds all these NFPA Group F: Carbon dusts (some conductive, all
standards and guidelines together and is now the explosive)
overarching standard for the industry. Group G: Flour, starch, grain, combustible plastic,
or chemical dusts (explosive)
NFPA 652 contains many new requirements that place Division I: Ignitable concentrations of dust are in
more responsibility on the facility owner-operator and suspension under normal operating conditions (dust
the authority having jurisdiction (AHJ). The AHJ is the clouds present)
party responsible for enforcing the standards and for Division II: Ignitable concentrations of dust are not
approving equipment, installation, materials, or typically in suspension under normal operating
procedures covered within the standards. Depending conditions (dust layers present)
on the application’s scope, the AHJ may be a federal, Class III: Ignitable fibers and flyings
state, or local department or an individual such as a fire
marshal. For insurance purposes, however, the AHJ is
typically an insurance company inspection department While preventing a dust explosion with absolute
or representative. certainty is impossible, methods are available to reduce
the likelihood of an explosion or limit an explosion’s
potential to cause injury or damage. These methods
Under NFPA 652, the facility owner-operator is include explosion venting, which is detailed in NFPA
responsible for determining whether the materials being 68, and ignition prevention, explosion suppression, and
processed or generated in the facility are combustible or explosion isolation, which are explained in NFPA 69.
explosible. If so, a dust hazards analysis (DHA) shall be
completed in accordance with the guidelines of NFPA Explosion protection methods and devices can generally
652, Chapter 7. The purpose of the DHA is to identify be categorized as either passive or active. Passive
hazards within a facility or process and document how protection methods rely on mechanics and physics in
the hazards are being controlled. The DHA must be their design and tend to be less expensive than active
performed by a qualified individual or a team led by a methods. While some passive protection methods are
qualified individual, and the DHA results must be powered, they don’t require power to operate. Active
documented. The DHA will include a general overview protection methods tend to allow for greater flexibility
of the entire facility where an explosion hazard exists in design and application than passive methods, but they
followed by an evaluation of the materials handled and do require power to operate. As a result, safeguards and
all processes, buildings, and building compartments failsafe mechanisms must be incorporated into the
where combustible dust is present. system design in case power to the device is lost.
The DHA requirement applies not only to new Different protection methods often overlap, and
processes or facility upgrades, but retroactively to several methods are frequently used in combination to
existing processes as well. The standard states that “the provide a complete explosion protection system. The
owner-operator shall schedule and complete DHAs of dust’s explosivity characteristics along with your
existing processes and facility compartments within a process and preference will determine what method or
3-year period from the effective date of the standard.” combination of methods you should choose. Whatever
explosion protection options you use, it’s critical to also
establish good housekeeping practices and eliminate
This means that as of September 7, 2018, all facilities that dust accumulation on horizontal surfaces to limit the
process or generate combustible dust must have a fuel available for an explosion if one should occur.
documented DHA on file or risk penalties from the AHJ.
Explosion venting
Hazard prevention and protection An explosion vent is a panel or door on a dust collector
OSHA requires that companies dealing with or other enclosure that’s designed to burst or open to
combustible dust put in place all necessary safeguards vent the combustion gases and pressure generated by a
to collect and handle the dust. This includes ensuring dust deflagration, protecting the enclosure’s structural
that all electrically powered cleaning devices, such as integrity and ensuring the safety of the surrounding
sweepers or vacuum cleaners, are approved for the area. Explosion vents must be located and oriented to
Copyright CSC Publishing
direct the pressure and flames safely away from and the dust being collected. Variables associated with
workers, equipment, and the building structure. determining explosion vent size are shown in Table I.
The three options for orienting and locating dust As the table shows, most of the variables focus on
collectors and vessels with explosion vents are shown attributes of the dust collection system, but two
in Figure 3. The best option will depend on the local additional critical variables, P max and K St , are
environment around the dust collector and the determined by the dust’s characteristics. Pmax is the
collector’s proximity to the building exterior. A maximum pressure (in bar), developed in a contained
standard explosion vent is suitable for collectors that deflagration at the dust’s optimum concentration. KSt is
are located outdoors (Figure 3a) or indoors near an the dust’s deflagration index, or the rate of pressure rise
exterior wall (Figure 3b) and where sufficient space is (in bar-m/s) during a deflagration. Dusts are placed into
available for the fireball to vent safely. A flameless or hazard classes based on KSt value, as shown in Table II,
flame-quenching explosion vent (Figure 3c) is more with the least explosive dusts classified as St-1, and the
expensive than a standard explosion vent but is a safe most explosive dusts classified as St-3.
option for situations where venting outside the
building isn’t practical or desired. NFPA 68 provides a list of some common dusts and
their respective KSt and Pmax values. However, these
The explosion vent size required for a given dust values are intended as reference only. The best way to
collection system can be calculated according to determine a dust’s explosivity is to have it tested in a lab.
NFPA 68 and is a function of both the system design The test uses a spherical test chamber outfitted with
Figure 3
a. Dust collector outside with b. Dust collector inside with standard c. Dust collector inside with
standard explosion vent explosion vent ducted to outside flameless explosion vent
Table l
The infrared sensors are designed to operate in the Sensors can be used to detect these pressure waves and
worst possible environments, with heavy dust loads, trigger a suppressant agent to quench the developing
high static pressures, and high airstream temperatures. fireball before it reaches a destructive magnitude. A
Typically, the system will have a response time of 300 typical suppression system consists of a pressure
to 400 milliseconds between sensing the spark and sensor, a monitoring control panel, a power supply
activating the solenoid valve. This means that the with battery backup, and a suppressant-delivery
distance between the sensor and suppression valve is device, as shown in Figure 7.
very critical. For example, if the airstream is moving at
3,000 fpm (50 ft/s), a spark can travel 15 feet in 300 The location, quantity, and size of the sensors and
milliseconds and 20 feet in 400 milliseconds. suppression devices are determined for each
application based on the characteristics of both the
dust (KSt and Pmax) and the vessel (size and strength).
Explosion suppression Pressure sensors are available that can sense a pressure
At the onset of a dust explosion, pressure waves increase in less than a millisecond. Once the pressure
expand out at the speed of sound ahead of the fireball.
Figure 5
Airflow
Airflow without
with sparks sparks
Air bubble
Turbulent
Spark airflow
arrestor
Figure 6
Hot sparks
Pressure
Passive isolation. A back-blast damper is essentially a waves
one-way flap valve that remains open during normal
operation but is forced shut by pressure waves
traveling upstream from the dust collector, preventing
a deflagration from spreading through the ductwork.
A back-blast damper sometimes comes equipped with
a pressure relief panel (explosion vent) on the
downstream side of the flap. This panel is designed to Chemical Battery
burst once the flap shuts to alleviate the deflagration suppressant backup
pressure and requires that the damper be installed
outdoors in a safe area.
Using a material choke valve or rotary airlock on the Devices are also available that chemically isolate a
dust collector’s hopper prevents a deflagration from deflagration. The chemical isolation is triggered in the
escaping through the collector’s material discharge. A same way as a high-speed abort gate. Frequently,
rotary airlock must meet three main requirements to chemical isolation is part of a complete chemical
adequately provide explosion isolation. First, the body, suppression system, as shown in Figure 8, and the same
rotor, and vanes must be strong enough to withstand pressure sensor that triggers the chemical suppression
the maximum anticipated explosion pressure (Pred). device in the dust collector will also trigger the inlet and
Second, to prevent flames from escaping, the clearance outlet chemical isolation devices. PBE
between the valve body and the tip of the rotating vanes
must be less than 0.2 millimeters (0.0079 inches). The
vanes must be monitored for wear during normal
preventative maintenance activities to ensure that the Reference
clearance doesn’t exceed this limit. Finally, each side of 1. All NFPA standards and guidelines discussed in this article are
the valve (upward rotating and downward rotating) available at www.nfpa.org.
must have two vanes in contact with the housing at all
times. To accomplish this, the airlock must have a For further reading
minimum of eight vanes.
Find more information on this topic in articles listed
under “Dust collection and dust control” and
Active isolation. Similar to active prevention methods, “Explosion protection” in Powder and Bulk
active isolation methods require sensing devices to Engineering’s comprehensive article index in the
detect a deflagration along with controls to activate the December 2016 issue or the Article Archive on PBE’s
protection device. A high-speed abort gate isolates the website, www.powderbulk.com. (All articles listed in
airflow from the dust collector inlet or outlet and the archive are available for free download to
diverts the deflagration pressure and flames into the registered users.)
open atmosphere. The gate is triggered by a control
panel that receives an explosion confirmation from a
pressure monitor on the dust collector.
Copyright CSC Publishing
Figure 8
Dust
collector
Chemical
isolation
on outlet
Chemical
isolation
on inlet
Chemical
suppression
in dust
collector