MULTIPLES OF CURRENT SETTING (C) MULTIPLES OF BREAKER SHORT-TIME RATING (H)

100
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
1000 1000 2 2
900 900
800 800
700 RMS9C MicroVersa Trip Plus™ or 700 RMS9C MicroVersa Trip Plus™
MicroVersa Trip PM™ Digital RMS or MicroVersa Trip PM™
600 600
Trip Units (ANSI) Long/Short Time Digital RMS Trip Units (ANSI)
500 500 1 Fixed Hi-Range Instantaneous 1
Long-Time .9 50/60 Hz Operation Only .9
400 Delay Bands 400 .8 .8
.7 .7
300 300 .6 .6

.5 .5

200 200 .4 .4

.3 .3

100 100 .2 .2
90 90
4
80 80

TIME IN SECONDS
70 70
60 60

50 50 .1 .1
Maximum Trip .09 .09
TIME IN SECONDS

40 3 Unit Response 40 .08 .08


Time .07 .07
30 30 .06 .06

.05 .05
2
20 20 .04 .04
1.5
Minimum Trip .03 .03
Unit Response
Time Application
1
10 2.0 10 .02 Determines .02
9 Short 9 End of Curve
8 Time 8
7 7
6
2.5 6

5 5 .01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
4 3.0 4
MULTIPLES OF BREAKER SHORT-TIME RATING (H)
3 I2t In 3
MULTIPLES OF INSTANTANEOUS PICKUP SETTING
4.0 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
2 2 2 2

5.0 RMS9C MicroVersa Trip Plus™ or


MicroVersa Trip PM™ Digital RMS
I2t Out Trip Units (ANSI) Instantaneous
1 1 1 1
.9 .9 .9 .9
.8 .8 .8 .8
.7
7.0 .7 .7
Instantaneous Pickup Settings in Multiples of .7
Rating Plug Amps (X)
GES-9913

GES-9913
.6 .6 .6 .6
9.0 Pickup Settings on Trip Units without Short-Time Function:
.5 .5 .5 For (S) = 150 thru 3200 amps: 1.5 to 10.0, in increments of 0.5 .5
For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
.4 Max .4 .4 .4
Pickup Settings on Trip Units with Short-Time Function:
.3 .3 .3 For (S) = 150 thru 2000 amps: 1.5 to 15.0, in increments of 0.5 .3
Application For (S) = 3200 amps: 1.5 to 13.0, in increments of 0.5
Int Determines For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
End of Curve
.2 .2 .2 .2

TIME IN SECONDS
Min

.1 .1 .1 .1
.09 .09 .09 .09
.08 .08 .08 .08
.07 .07 .07 .07
.06 .06 .06 .06

.05 .05 .05 .05

.04 .04 .04 .04

.03 .03 .03 .03

Application
.02 .02 .02 Determines .02
End of Curve

.01 .01 .01 .01


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
100

MULTIPLES OF CURRENT SETTING (C) MULTIPLES OF INSTANTANEOUS PICKUP SETTING

(Note: Does not include breaker clearing time.)

GES-9913
GE Consumer & Industrial -
Electrical Distribution Low-Voltage Power Circuit Breakers
Available Ratings (Amperes) Conversion Kits with Adjustments
Long-Time Function:
Breaker Current
Sensor
Enhanced MicroVersaTrip PlusTM or Current settings (C): 0.5 to 1.1 in 0.05 increments,
multiples of rating plug amps (X)
Model Frame (S) Rating Plug (X) MicroVersaTrip PMTM Delay bands: 1, 2, 3, and 4
225A 150 60, 80, 100, 125, 150 Short-Time Function
GE,
I-T-E®,
Federal 600A
225
225
100, 150, 225
100, 150, 225
Digital RMS Trip Units Pickup settings: 1.5 to 9.0 in 0.5 increments,
Pacific, 600 300, 400, 450, 500, 600 multiples of current setting (C)
Delay bands: Min, Int, Max; I2t In, I2t Out
Allis
Chalmers,
or
800A 150
400
60, 80, 100, 125, 150
150, 200, 225, 250, 300, 400 Long-Time Delay, Short-Time Delay, Instantaneous Function:
Westing-
house 1600A
800
800
300, 400, 450, 500, 600, 700, 800
300, 400, 450, 500, 600, 700, 800
and Instantaneous Time-Current Curves See table and curve above
1600 600, 800, 1000, 1100, 1200, 1600 Settings Glossary
2000A 2000 800, 1000, 1200, 1500, 1600, 2000
3000A 3000 1200, 1600, 2000, 2500, 3000 Curves apply at 50 to 400 Hertz and S = Current Sensor Rating in amps
3200A 3200 1200, 1600, 2400, 3200 from -20°C to 55°C Breaker ambient. X = Rating Plug in amps
4000A 4000 1600, 2000, 2500, 3000, 3600, 4000 C = Current Setting in amps
H = Breaker Short-time Ampere Rating
Note: Operation above 60 Hertz requires thermal
Voltage Rating: 635 Vac, maximum and interrupting derating of the circuit breaker.

11.94 3M