MULTIPLES OF CURRENT SETTING, C

100
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .2 .2
1000 1000
900 900
800 800
700 700

TIME IN SECONDS
600 Long-time 600
.1 .1
500 Delay Bands 500 .09 .09
.08 .08
400 400 .07 .07
.06 .06
300 300
.05 .05

.04 Application
.04
200 200
Determines
.03 End of Curve .03

.02 .02
100 100
90 90
80 80
70 70
60 60
.01 .01
TIME IN SECONDS

50 50 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
40 Maximum Total
Clearing Time
40 MULTIPLES OF BREAKER SHORT-TIME RATING, H
30 30
Breaker Short-time Rating (H)
Frame Amps (Amps. rms symmetrical)

20 20 800 25,000
1.5 Minimum Total 1600, 2000 40,000
Clearing Time
2500, 3000, 4000 42,000

10 10
9 2.0 9
8 8
Short-
7 time 7
6 6
2.5
5 5
12 t In MULTIPLES OF INSTANTANEOUS PICKUP
4 3.0 4 4 4

3 3 3 3

Instantaneous Pickup Setting in multiples of rating plug amps (X):


4.0 Pickup Settings on trip units with Short-time function:
2 2 2 2
12 t Out For (S) = 200 to 2000 amps: 1.5 to 15.0, in increments of 0.5
For (S) = 2500 and 3000 amps: 1.5 to 13.0, in increments of 0.5
5.0 For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
Pickup Settings on trip units without Short-time function:
For (S) = 200 to 3000 amps: 1.5 to 10.0, in increments of 0.5
For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
1 1 1
.9 .9 .9 .9
.8 .8 .8 .8
.7 7.0 .7 .7 .7
GES-9889H

GES-9889H
.6 .6 .6 .6
9.0
.5 .5 .5 .5
Max
.4 .4 .4 .4

.3 Application .3 .3 .3
Int Determines
End of Curve

.2 .2 .2 .2

Min

.1 .1 .1 For rating plugs noted below in bold-face type


.1
.09 .09 .09 .09
with instantaneous setting 3.0X and below,
.08 .08 .08 .08

TIME IN SECONDS
use dotted line for total clearing time.
.07 .07 .07 .07
.06 .06 .06 .06
.05 .05 .05 .05

.04 .04 .04 .04

.03 .03 .03 .03

.02 .02 .02 .02


Application
Determines
End of Curve

.01 .01 .01 .01


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
100

MULTIPLES OF CURRENT SETTING, C MULTIPLES OF INSTANTANEOUS PICKUP

PowerBreak™ II
GES-9889H
GE Consumer & Industrial -
Electrical Distribution Insulated Case Circuit Breakers
Available Ratings (Amperes) Types SS, SH Programmer Adjustments
Current
Frame Sensor (S) Rating Plug (X) with Power+™ MicroVersaTrip PlusTM Long-time Function Current Settings (C):
0.50 to 1.0 multiples of rating plug amps (X).
800 200
400
100, 150, 200
150*, 200, 225, 250, 300, 400
or MicroVersaTrip PMTM Delay Bands: 1, 2, 3 and 4.

1600
800
800
300*, 400, 450, 500, 600, 700, 800
300*, 400, 450, 500, 600, 700, 800
Digital RMS Trip Units Short-time Function Pickup Settings:
1.5 to 9.0 multiples of current setting (C).
1000 400*, 600, 800, 1000
1600 600*, 800, 1000, 1100, 1200, 1600 Long-time Delay, Short-time Delay, and Delay Bands: MIN, INT, MAX; I2t In/Out
2000 2000 750*, 800*, 1000, 1200, 1500, 1600, 2000
Instantaneous Time-Current Curves Instantaneous Function:
2500 1000 400*, 600, 800, 1000 See Table with Curves above.
2000 800*, 1000, 1200, 1600, 2000
(High-Range not available with Power+™
2500 1600, 2000, 2500 Curves apply at 50 to 60 Hertz
3000 3000 2000, 2500, 3000
and from -20°C to 70°C breaker ambient S: Current Sensor Amps
4000 4000 1600, 2000, 2500, 3000, 4000
* Not available with Power+™ Trip Unit.
X: Rating Plug Amps
C: Current Setting Amps
Voltage Rating: 600 Vac, maximum H: Breaker Short-time Rating Amps

05.00