Application Note

Universal Relay General Electric T60


Differential Relay 87 module
TDMS software

Differential Relay 87 Module


with TDMS software and DRTS 66
A completely new way of testing for
transformer differential protections
is now possible. In few steps the user
can easily set up a complete network
model for the best fault simulation:
. Power Transformer vector group
. Earthing transformers
. Current Transformers connections
(wye, delta)
. YDY Interposing transformers for a
proper phase and zero-sequence
compensation.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
This application note will guide you step by step to perform tests on
Differential Relay, using TDMS software.

Set the Power Transformer vector group, the nominal primary and
secondary voltage and the rated power.

The magnitude compensation


factor must be calculated
according to the GE T60
formulas

Phase and zero sequence can be compensated internally by the


relay or externally with a proper CTs connection, in this example the
compensation is internal:

For General Electric relays the reference


winding for the phase shift compensation
is the first delta, in this case the reference
winding is the primary.
TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
In case of external compensation, the user must disable the internal
Phase and Zero Sequence compensation and select the proper delta
connected CT group.

The number inside the relay picture


represents the phase shift between
the primary and secondary currents,
it is zero when the phase shift is well
compensated.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
The trip characteristic can be set by copying directly the relay
parameters, the special GE T60 curve will be plotted automatically.

Decide the fault side and the


faulty phase and perform an
automatic verify of the trip
characteristic. The results are
stored in the results table and they are
displayed graphically for a quick and
easy analysis.

TDMS
Application Note
Universal Relay General Electric T60
Differential Relay 87 module
TDMS software
Possibility to perform Harmonic Restraint characteristic test from the
second to the seventh harmonic of the fundamental frequency.

Bibliography
ISA - TDMS user manual - MSE 10015
ISA - DIFF 87 user manual - MSE 20029
ISA - DRTS 66 user manual rev. 1.33 - MIE 10170
General Electric - GE Multilin - T60 Transformer Protection System - UR Series instruction manual

TDMS

December 2015