TECHNICAL SUBMITTAL

PRE-ACTION SYSTEM

G+5P+15 @ Sharjah

BSIOKMPS-310319
INDEX
PREACTION SYSTEM 

I. Technical Datasheets and Catalogue 
A. PREACTION VALVE, PNEUMATIC/ ELECTRIC PILOT TRIM (SERIES 769)…………..…..……  1 
B. AIR COMPRESSOR ASSEMBLY (SERIES 7C7)….…………………………………………………………  2 
C. STANDARD UPRIGHT SPRINKLER (V2703)………….………………………………….……….…….  3 
D. Extinguishant Control Panel (BF‐ECP3DCSM)…………….……………………………..……….……..  4
E. Smoke Detector (B61‐1001)…………………………………………………………………….…….………  5 
F. Sounder Strobe (B61‐6301)………….………………………………………………………….…….……..  6 
G. Fire Alarm bell (BF‐AB‐0418)….…………………………………………………………..…………..……..  6

II. CD Certificates……………………………………………………………………………………………………….  7
III. Approval Certificates..……………………………………………………………………………………….….  7
IV. Method of Statement…………..………………………………………………………………………..…….  8
V. Company Profile……………………..…………………………………………………………………………….  9 
VI. Trade License……………….……………………………………………………………………………………….  9
I. Technical Data Sheets and Catalogue
A. PREACTION VALVE (SERIES 769)
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™ MEA: 248-98-E
VNIIPO
CSFM: 7770-0531-117

Actuated Valve with Preaction Trim


SERIES 769
With Preaction Trim
Grooved x Grooved

The patent-pending Victaulic Series 769 FireLock NXT™ Preaction Valve controls the
water supply entry into the Preaction system piping and sprinklers. The Preaction System
is ­normally supervised with pressurized air or nitrogen in order to detect any leaks in the
system. The Series 769 is a low differential, latched clapper valve that uses a unique direct
acting ­diaphragm to separate system water supplies from Preaction pipe sprinkler systems. PATENT PENDING
The ­positive latching mechanism uses the supply water pressure from upstream (city side) of
the main control valve to hold the clapper shut. When the water pressure in the diaphragm
chamber is released the latch retracts from the clapper and the valve actuates. The low dif-
ferential and unique latch and actuator design of the valve allows the valve to be self-resetting;
therefore it is not necessary to remove the cover. The low differential design is not subject to
water columns.

FEATURES The valve allows the water to operate a water motor alarm and/or electric pressure alarms, which
continue until the flow of water stops.

Latch
The valve is rated to 300 psi/2065 kPa water working pressure and is factory tested hydrostatically to
Clapper
600 psi/4135 kPa for sizes 1 1/2 – 8"/40 – 200 mm. Required air pressure is 13 psi/90 kPa. The Series
769 is available grooved x grooved. Standard grooved dimensions conform to ANSI/AWWA C606.
Victaulic Series 769 Preaction valves do NOT require a separate check valve in the preaction system
and feature a straight-through valve body design that provides superior flow and low-pressure drop.
The valve body is tapped with a special drain for a complete system. The valve has simple access to
all internal parts for easy maintenance. All internal parts are replaceable.
Diaphragm
Assembly Maintenance and service can be performed from the installed position. The rubber clapper seal is
replaced easily without removing the clapper from the valve. The body is tapped for main drain and
Seat Clapper all available trim configurations. The valve is painted inside and out to increase corrosion resistance.
Seal
The Victaulic Series 769 FireLock NXT Preaction valve trim includes an alarm test valve, which
allows testing of the alarm system without reducing the system pressure.
Exaggerated
NOTE: VALVE IS SHOWN for“SET”
ABOVE IN THE Clarity
POSITION
NOTE: The bare value carries the LPCB and VdS approvals for deluge applications only. There is no
Exaggerated for Clarity
NOTE: Valve is shown in the “set” position LPCB or VdS recognition of the preaction configurations.

JOB/OWNER CONTRACTOR ENGINEER


System No.___________________________ Submitted By_________________________ Spec Sect_____________ Para___________
Location_ ____________________________ Date ________________________________ Approved_ ___________________________
Date ________________________________

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_1
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

INSTALLATION OPTIONS Pre-trimmed


The pre-trimmed valve comes completely assembled with all necessary trim components.
Vic-Quick Riser
The Vic-Quick Riser comes completely pre-trimmed and includes a shut off valve (uses a Series
705W FireLock Butterfly valve – request publication 10.18; for 1 1/2 and 2"/40 and 50 mm sizes, the
Vic-Quick Riser comes with a Series 728 Ball Valve – request publication 10.17) for system shut off,
pre-set pressure switches, and a drain kit for ease of installation. For complete Vic-Quick Riser infor-
mation request publication 30.20.
Series 745 FireLock Fire-Pac
The Fire-Pac is a completely pre-assembled fire protection valve that provides maximum service in
a minimal enclosed space. The unit includes a water supply shutoff valve, the sprinkler system fire
protection valve, alarm line pressure switches, air supervisory pressure switches, supervisory pump
switches, and digital pressure gauges that are easily viewed through a window in the cabinet door.
For complete Fire-Pac information request publication 30.23.
Optional accessories ship separately.

RELEASE MECHANISM OPTIONS Non-Interlocked


Non-interlocked systems are designed so that either an event detection by the release mechanism or
loss of supervisory air in the sprinkler system will cause the valve to operate. When the valve oper-
ates, water will enter the sprinkler system and flow from any open sprinklers or other openings in the
system.
The pneumatic release system uses a supervisory pilot line to detect a release
event. When EITHER a pilot sprinkler or a system sprinkler operates, the water in the diaphragm
chamber is released and the valve operates. If the pilot sprinkler activates and a system sprinkler
does not operate, water will fill the sprinkler system, alarms will be activated and the Victaulic Series
769 Actuated Valve will act as an Alarm Check Valve. If the valve is actuated by the activation or
damage of a sprinkler, water will enter the system and flow from any open sprinklers. Alarms will acti-
vate due to water entering the intermediate chamber of the valve.
The Victaulic Electric Release System uses an electric solenoid valve,
approved electric panel and a compatible detection system. When EITHER an electric detection or a
system sprinkler operates, the water in the diaphragm chamber is released and the valve operates. If
there is an electric detection and a system sprinkler does not operate, water will fill the sprinkler sys-
tem, alarms will be activated and the Victaulic Series 769 Actuated Valve will act as an Alarm Check
Valve. If the valve is actuated by the activation or damage of a sprinkler system sprinkler, water will
enter the system and flow from any open sprinklers. Alarms will activate due to water entering the
intermediate chamber of the valve.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_2 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

SYSTEM DESCRIPTION Single Interlocked


Single interlocked systems are designed so that only an event detection by the release mechanism
will cause the valve to operate. When the valve operates water will enter the sprinkler system and
flow from any open sprinklers or other openings in the system.
The pneumatic release system uses a supervisory pilot line to detect a release
event. Only when a pilot sprinkler operates will the water in the diaphragm chamber be released and
the valve operate. Pneumatic pressure is maintained in the sprinkler system only for supervisory
purposes and a low pressure alarm is installed in the sprinkler system in order to detect any leaks in
the system. If the pilot sprinkler activates and a system sprinkler does not operate, water will fill the
sprinkler system, alarms will be activated and the Victaulic Series 769 Actuated Valve will act as an
Alarm Check Valve. If a system sprinkler is damaged or activates and there is no release mechanism
detection the low pressure alarm in the system will activate but no water will flow until there is a
release detection.
The Victaulic Electric Release System uses an electric solenoid valve, approved
electric panel and a compatible detection system. Only when a release system event occurs, will the
water in the diaphragm chamber be released and the valve operate. Pneumatic pressure is main-
tained in the sprinkler system only for supervisory purposes and a low pressure alarm is installed in
the sprinkler system in order to detect any leaks in the system. If there is an electric release activa-
tion and a sprinkler system sprinkler does not operate, the valve will operate and water will fill the
sprinkler system, alarms will be activated and the Victaulic Series 769 Actuated Valve will act as an
Alarm Check Valve. If a system sprinkler is damaged or activates and there is no release mechanism
detection, the low pressure alarm in the system will activate but the valve will not operate and no
water will flow until there is a release detection.
Double Interlocked
Double interlocked systems are designed so that the valve will actuate only in the event of multiple
fire detections by the release mechanisms. If a single release event occurs alarms will sound but the
valve will not operate and water will not flow until a second release event is detected. Double inter-
locked systems are commonly used in refrigerated systems and in systems where water entering the
sprinkler system is critical as well as when accidental discharge of water is critical.
The electric/pneumatic preaction system uses both an electric release
system, (composed of an approved solenoid valve, electric panel and an appropriate sensor), and
pneumatically pressurized sprinkler system. The Victaulic Series 769 Actuated Valve will activate
ONLY when there is a pressure loss in the sprinkler system AND the electric detection of a release
event. In the event of a loss of pressure in the sprinkler system without an electric detection the valve
will not actuate until a second release event is detected. In this way if there is accidental damage to
the sprinkler system no water will flow. Additionally, if there is an electric detection and no pressure
loss in the sprinkler system the valve will not actuate. Alarms will activate in both cases alerting the
user of a detection condition.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_3
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

SYSTEM DESCRIPTION Electric (Electric-Pneumatic/Electric): The electric/pneumatic/electric release uses two electric
detection devices, a fire detection device and a low pressure switch installed in the sprinkler system.
Both electric detection devices are wired into an approved control panel in a “cross-zoned” configu-
ration. The electric control panel controls a solenoid valve piped to the Victaulic Series 769 Actuated
Valve piston. In the event of a fire detection device activation and no pressure loss in the sprinkler
system the control panel will not trigger the solenoid valve and the valve will not actuate. If there is a
loss of pressure in the sprinkler system due to damage or a sprinkler activating and no fire detection
the control panel will not trigger the solenoid and the valve will not actuate. The valve will actuate
ONLY when BOTH a fire detection event and loss of system pressure occurs. When BOTH signals are
received by the control panel the panel triggers the solenoid valve. This allows the water supply pres-
sure in the Series 769 diaphragm chamber to be released and the valve will actuate allowing water
into the system.
The pneumatic/pneumatic system uses one Series 798 Double
Pneumatic Actuator to control the Series 769 Actuated Valve. The system control valve will operate
only when there are sprinklers activated in both the pilot line and the sprinkler system. If a sprinkler
is activated in either the pilot line or the sprinkler system (without an accompanying open sprinkler in
the other system) the system control valve will not operate. Since the pneumatic/pneumatic system
uses two separate pneumatic detections, the need for an electric release panel is eliminated. In all
cases, an open sprinkler will cause low-pressure supervisory alarm. Note: All Series 769 valves are
approved and listed for double interlock pneumatic – electric with the Series 767. It is also approved
for double interlock and pneumatic/pneumatic double interlock configurations with the Series 798.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_4 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

DIMENSIONS FOR TRIM WITH


SERIES 776 LOW-PRESSURE ACTUATORS
THE 4 INCH/114.3 MM CONFIGURATION IS SHOWN BELOW
1 ½ – 2 INCH/48.3 – 60.3 MM CONFIGURATIONS CONTAIN ¾ INCH/19 MM DRAIN VALVES.
2 ½ – 3 INCH/73.0 – 88.9 MM CONFIGURATIONS CONTAIN 1 ¼ INCH/31 MM DRAIN VALVES.
4 – 8 INCH/114.3 – 219.1 MM CONFIGURATIONS CONTAIN 2 INCH/50 MM DRAIN VALVES.

E
F
D
*D1

*B1
A B

*A1

H
K
C *E1
Full Open

Aprx. Weight Ea.


Size Dimensions – inches/mm lbs/kg
Actual Outside
Nominal Size Diameter
Inches/ Inches/ Without With
mm mm A A1* B B1* C D D1* E E1* F G H J K Trim Trim
1½ 1.900 9.00 16.43 28.25 40.50 13.75 16.00 5.25 8.50 9.50 22.25 3.04 9.17 6.98 16.7 43.0

40 48.3 228.60 417.32 717 1028 349 406 133 215 241 565 77.21 232.91 177.29 7.6 19.5
2 2.375 9.00 16.43 28.25 40.50 13.75 16.00 5.25 8.50 9.50 22.25 3.04 9.17 6.98 17.0 43.0

50 60.3 228.60 417.32 717 1028 349 406 133 215 241 565 77.21 232.91 177.29 7.7 19.5
2½ 2.875 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0
65 73.0 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5
3.000 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0
76.1 mm
76.1 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5
3 3.500 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0
80 88.9 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5
4 4.500 15.03 19.78 33.25 45.50 15.00 15.75 20.50 5.50 9.00 10.75 20.75 6.25 9.62 8.46 59.0 95.0
100 114.3 381.76 502.41 844 1155 381 400 520 139 228 273 527 158.75 244.34 214.88 26.7 43.0
6.500 16.00 22.00 33.50 45.75 15.50 17.00 22.00 6.00 8.50 11.50 20.00 6.20 9.62 8.84 80.0 116.0
165.1 mm
165.1 406.40 558.80 850 1162 393 431 558 152 215 292 508 157.48 244.34 224.53 36.2 52.6
6 6.625 16.00 22.00 33.50 45.75 15.50 17.00 22.00 6.00 8.50 11.50 20.00 6.20 9.62 8.84 80.0 116.0
150 168.3 406.40 558.80 850 1162 393 431 558 152 215 292 508 157.48 244.34 224.53 36.2 52.6
8 8.625 17.50 22.94 33.50 45.50 16.75 20.00 25.25 7.00 8.75 12.75 18.50 6.05 9.40 10.21 122.0 158.0
200 219.1 444.50 582.67 850 1155 425 508 641 177 222 323 469 153.67 238.76 259.33 55.3 71.6

NOTES:
The drawings shown above reflect the single-interlocked, pneumatic release trim with Series 776 Low-Pressure Actuator. In addition, these dimensions can
be applied to single-interlocked, pneumatic release; non-interlocked, pneumatic/electric release; single-interlocked, electric release; and double-interlocked,
electric (electric-pneumatic/electric) release trim.
The “A” dimension coupling is not shown for clarity.
Components shown as dotted lines denote optional equipment
* Measurements denoted with an asterisk take optional equipment into account
Optional drain connection kit is shown for reference and takeout dimensions.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_5
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

DIMENSIONS FOR TRIM WITH SERIES 767


ELECTRIC/PNEUMATIC ACTUATORS
THE 4 INCH/114.3 MM CONFIGURATION IS SHOWN BELOW
1 ½ – 2 INCH/48.3 – 60.3 MM CONFIGURATIONS CONTAIN ¾ INCH/19 MM DRAIN VALVES.
2 ½ – 3 INCH/73.0 – 88.9 MM CONFIGURATIONS CONTAIN 1 ¼ INCH/31 MM DRAIN VALVES.
4 – 8 INCH/114.3 – 219.1 MM CONFIGURATIONS CONTAIN 2 INCH/50 MM DRAIN VALVES.

D
*D1
*B1

A
B
*A1

H K

C *E1
Full Open

Aprx. Weight Ea.


Size Dimensions – inches/mm lbs/kg
Actual Outside
Nominal Size Diameter
Inches/ Inches/ Without With
mm mm A A1* B B1* C D D1* E E1* F G H J K Trim Trim
1½ 1.900 9.00 16.43 28.00 42.75 13.75 16.00 15.00 5.25 8.50 9.50 24.50 3.04 9.17 6.98 16.7 43.0
40 48.3 228.60 417.32 711 1085 349 406 381 133 215 241 622 77.21 232.91 177.29 7.6 19.5
2 2.375 9.00 16.43 28.00 42.75 13.75 16.00 15.00 5.25 8.50 9.50 24.50 3.04 9.17 6.98 17.0 43.0
50 60.3 228.60 417.32 711 1085 349 406 381 133 215 241 622 77.21 232.91 177.29 7.7 19.5
2½ 2.875 12.61 16.50 31.25 45.75 13.50 16.25 18.00 5.25 9.00 9.75 22.75 3.90 10.50 6.93 41.0 65.0
65 73.0 320.29 419.10 793 1162 342 412 457 133 228 247 577 99.06 266.70 176.02 18.7 29.5
3.000 12.61 16.50 31.25 45.75 13.50 16.25 18.00 5.25 9.00 9.75 22.75 3.90 10.50 6.93 41.0 65.0
76.1 mm
76.1 320.29 419.10 793 162 342 412 457 133 228 247 577 99.06 266.70 176.02 18.7 29.5
3 3.500 12.61 16.50 31.25 45.75 13.50 16.25 18.00 5.25 9.00 9.75 22.75 3.90 10.50 6.93 41.0 65.0
80 88.9 320.29 419.10 793 1162 342 412 457 133 228 247 577 99.06 266.70 176.02 18.7 29.5
4 4.500 15.03 19.78 32.75 47.50 15.00 16.25 20.75 5.50 9.00 11.25 22.75 6.25 9.62 8.46 59.0 100.0
100 114.3 381.76 502.41 831 1206 381 412 527 139 228 285 577 158.75 244.34 214.88 26.7 43.3
6.500 16.00 22.00 32.75 47.50 15.50 17.25 22.25 6.00 8.50 11.50 21.75 6.20 9.62 8.84 80.0 121.0
165.1 mm
165.1 406.40 558.80 831 1206 393 438 565 152 215 292 552 157.48 244.34 224.53 36.2 54.8
6 6.625 16.00 22.00 32.75 47.50 15.50 17.25 22.25 6.00 8.50 11.50 21.75 6.20 9.62 8.84 80.0 121.0
150 168.3 406.40 558.80 831 1206 393 438 565 152 215 292 552 157.48 244.34 224.53 36.2 54.8
8 8.625 17.50 22.94 32.50 47.00 16.75 20.00 25.50 7.00 8.75 13.00 20.25 6.05 9.40 10.21 122.0 163.0
200 219.1 444.50 582.67 825 1193 425 508 647 177 222 330 514 153.67 238.76 259.33 55.3 73.9

The “A” dimension coupling is not shown for clarity.


Components shown as dotted lines denote optional equipment
* Measurements denoted with an asterisk take optional equipment into account
Optional drain connection kit is shown for reference and takeout dimensions.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_6 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

DIMENSIONS FOR TRIM WITH SERIES 798


DOUBLE-PNEUMATIC ACTUATORS
THE 4 INCH/114.3 MM CONFIGURATION IS SHOWN BELOW
1 ½ – 2 INCH/48.3 – 60.3 MM CONFIGURATIONS CONTAIN ¾ INCH/19 MM DRAIN VALVES.
2 ½ – 3 INCH/73.0 – 88.9 MM CONFIGURATIONS CONTAIN 1 ¼ INCH/31 MM DRAIN VALVES.
4 – 8 INCH/114.3 – 219.1 MM CONFIGURATIONS CONTAIN 2 INCH/50 MM DRAIN VALVES.

E *F1
F

D *D1
*B1

A
*A1

H K
C *E1

Aprx. Weight Ea.


Size Dimensions – inches/mm lbs/kg
Actual Outside
Nominal Size Diameter
Inches/ Inches/ Without With
mm mm A A1* B B1* C D D1* E E1* F F1* G H J K Trim Trim
1½ 1.900 9.00 16.43 36.00 42.50 15.75 19.00 21.00 5.25 8.50 10.75 12.75 24.25 3.04 9.17 6.98 16.7 43.0
40 48.3 228.60 417.32 914 1079 400 482 533 133 215 273 323 615 77.21 232.91 177.29 7.6 19.5
2 2.375 9.00 16.43 36.00 42.50 15.75 19.00 21.00 5.25 8.50 10.75 12.75 24.25 3.04 9.17 6.98 17.0 43.0
50 60.3 228.60 417.32 914 1079 400 482 533 133 215 273 323 615 77.21 232.91 177.29 7.7 19.5
2½ 2.875 12.61 16.50 39.25 45.75 15.75 19.00 21.00 5.25 9.00 10.75 12.75 22.50 3.90 10.50 6.93 41.0 65.0
65 73.0 320.29 419.10 996 1162 400 482 533 133 228 273 323 571 99.06 266.70 176.02 18.7 29.5
3.000 12.61 16.50 39.25 45.75 15.75 19.00 21.00 5.25 9.00 10.75 12.75 22.50 3.90 10.50 6.93 41.0 65.0
76.1 mm
76.1 320.29 419.10 996 1162 400 482 533 133 228 273 323 571 99.06 266.70 176.02 18.7 29.5
3 3.500 12.61 16.50 39.25 45.75 15.75 19.00 21.00 5.25 9.00 10.75 12.75 22.50 3.90 10.50 6.93 41.0 65.0
80 88.9 320.29 419.10 996 1162 400 482 533 133 228 273 323 571 99.06 266.70 176.02 18.7 29.5
4 4.500 15.03 19.78 40.50 47.00 16.75 19.00 24.00 5.50 9.00 12.25 14.25 22.25 6.25 9.62 8.46 59.0 111.0
100 114.3 381.76 502.41 1028 1193 425 482 609 139 228 311 361 565 158.75 244.34 214.88 26.7 50.3
6.500 16.00 22.00 40.75 47.25 17.00 19.00 25.25 6.00 8.50 12.75 14.75 21.50 6.20 9.62 8.84 80.0 132.0
165.1 mm
165.1 406.40 558.80 1035 1200 431 482 641 152 215 323 374 546 157.48 244.34 224.53 36.2 59.8
6 6.625 16.00 22.00 40.75 47.25 17.00 19.00 25.25 6.00 8.50 12.75 14.75 21.50 6.20 9.62 8.84 80.0 132.0
150 168.3 406.40 558.80 1035 1200 431 482 641 152 215 323 374 546 157.48 244.34 224.53 36.2 59.8
8 8.625 17.50 22.94 40.50 47.00 18.25 21.50 28.75 7.00 8.75 14.25 16.25 20.00 6.05 9.40 10.21 122.0 174.0
200 219.1 444.50 582.67 1028 1193 463 546 730 177 222 361 412 508 153.67 238.76 259.33 55.3 78.9

The “A” dimension coupling is not shown for clarity.


Components shown as dotted lines denote optional equipment
* Measurements denoted with an asterisk take optional equipment into account
Optional drain connection kit is shown for reference and takeout dimensions.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_7
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

PERFORMANCE Hydraulic Friction Loss


The chart below expresses the flow of water
at 65ºF/18ºC through a full open valve.

6.0
5.0
4.0
3.0

m
mm

m
mm

5.1
50

6.1

16
2"/

0mm
d7
2.0

and
PRESSURE DROP – PSI

an

8"/20
m

m
m

m
0m

mm
5m

0m
0m
"/4

"/6

15
80

10

6"/
3"/

4"/
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3

0.2

0.1
10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000
800 3,000 8,000
FLOW RATE – GPM

Frictional Resistance
The chart below expresses the frictional resistance of Victaulic Series 769 FireLock NXT
Preaction Valve in equivalent feet of straight pipe.

Equivalent Length
Size of Pipe

Nominal Actual
Size Outside Dia.
Inches/ Inches/ Feet
mm mm meters
1 1/2 1.900 3.00
40 48.3 0.914
2 2.375 9.00
50 60.3 2.743
2 1/2 2.875 8.00
65 73.0 2.438
3.000 8.00
76.1 mm
76.1 2.439
3 3.500 17.00
80 88.9 5.182
4 4.500 21.00
100 114.3 6.401
6.500 22.00
165.1 mm
165.1 6.706
6 6.625 22.00
150 168.3 6.706
8 8.625 50.00
200 219.1 15.240

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_8 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

Cv VALUES Cv values for flow of water at +60°F/+16°C through a fully open valve are shown in the
table below.
Formulas for Cv values:

∆P = Q2 Where:
Cv2 Q = Flow (GPM)
∆P = Pressure Drop (psi)
Q = Cv x ∆P Cv = Flow Coefficient

Size

Nominal Actual
Size Outside Dia.
Inches/ Inches/ Cv/Kv
mm mm (Fully Open Valve)
1 1/2 1.900 60
40 48.3 52.0
2 2.375 110
50 60.3 95.0
2 1/2 2.875 180
65 73.0 156.0
3.000 180
76.1 mm
76.1 156.0
3 3.500 200
80 88.9 173.0
4 4.500 350
100 114.3 302.8
6.500 1000
165.1 mm
165.1 865.0
6 6.625 1000
150 168.3 865.0
8 8.625 1500
200 219.1 1499.1

OPERATION The Victaulic Preaction System utilizes the Series 769 Preaction Valve to control the entry of the
water supply into the Preaction System piping and sprinklers. The Series 769 Preaction Valve is con-
structed with a clapper having a replaceable rubber face. The clapper makes contact with the valve
seat ring which has access holes to the intermediate chamber of the valve. The clapper is contacted
by the latch which is contacted by the diaphragm. In the set position, water supply pressure from
upstream of the water supply control valve is maintained in the diaphragm chamber which holds the
clapper in the closed/set position. The water is maintained in the diaphragm by one of the system
release mechanisms (pneumatic, hydraulic or electric). Upon the detection of an appropriate actuat-
ing event of the Preaction System (see system description above) the water supply pressure in the
diaphragm chamber is released. This release allows the latch to move to its open position, permitting
the clapper to pivot freely, thus allowing water into the system. Water will flow from all open sprinklers
in the piping. Also, water enters the intermediate chamber of the valve through the holes in the seat
ring. The water flows from the intermediate chamber to the alarm line thus activating the system
alarms. These alarms will continue to sound until the flow of water is stopped. When the flow of water
is stopped the spring assisted valve clapper returns to the closed position and the valve acts as an
alarm check valve until the system is put back into service as a Preaction System.
Manual Operation
Any time the manual release handle is pulled water will be released from the diaphragm chamber
and the valve will actuate, allowing water into the Preaction System. Water motor alarms and alarm
pressure switches will activate.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_9
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to
ASTM A‑395, grade 65-45-15, is available upon special request.
Clapper: Aluminum bronze UNS-C95500
Latch: Aluminum bronze UNS-C95500
Clapper Seal: Peroxide cured EPDM, ASTM D2000
Bushing and Seat O-rings: Nitrile
Springs: Stainless steel (300 Series)
Shafts: Stainless 17-4
Diaphragm: Peroxide cured EPDM with fabric reinforcement

Bill of Materials
1 Valve Body 12 Cover Plate
2 Clapper 13 Cover Plate Gasket
3 Clapper Seal 14 Cover Plate Bolts*
4 Seal Ring 15 Latch
5 Seal Washer 16 Latch Spring
6 Seal Retaining Ring 17 Latch Shaft Bushing and O-Ring (Qty. 2)
7 Seal Assembly Bolt 18 Diaphragm
8 Bolt Seal 19 Diaphragm Cover
9 Clapper Spring 20 Diaphragm Cover Cap Screws (Qty. 8)
10 Clapper Shaft 21 Latch Shaft
11 Clapper Shaft Bushing and O-Ring (Qty. 2)
20

19

18
17

11

15
21
17

16 1

2 10

3 11

9
13 4
12
5

6
8
14
7
Exaggerated for clarity

* NOTE: The 1½-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of
the cover plate bolts.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_10 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

TRIM PACKAGES Trim Packages Options:


1 Non-Interlocked, Penumatic
2 Non-Interlocked, Pneumatic/Electric
3 Single-Interlocked, Pneumatic
4 Single-Interlocked, Electric or Double-Interlocked, Electric (Electric-Pneumatic/Electric)
5 Double-Interlocked, Electric/Pneumatic
6 Double-Interlocked, Pneumatic/Pneumatic
Trim packages include all required galvanized pipe and fittings. For trim package details and optional
accessories, see pages 17-22
Actuators:
• Series 776 Low-Pressure Actuator – The Series 776 Low-Pressure Actuator is pneumati-
cally actuated and requires only 13 psi/90 kPa minimum air pressure, regardless of the system
supply pressure. This actuator allows the system to operate with a low air or gas pressure of
7 psi/48 kPa. Request submittal 30.46.
• Series 767 Electric/Pneumatic Actuator – The Series 767 Electric/Pneumatic Actuator
­provides a single trip point for the pneumatic event and an integral electric actuator. This
­actuator requires only 13 psi/90 kPa minimum air pressure, regardless of the system supply
pressure. This actuator allows the system to operate with a low air or gas pressure of 7 psi/
48 kPa. Request submittal 30.62.
• Series 798 Double-Pneumatic Actuator – The Series 798 Double-Pneumatic Actuator requires
two separate pneumatic activations in order to actuate the system. This actuator requires only
13 psi/90 kPa minimum air pressure, regardless of the system supply pressure. This actuator
allows the system to operate with a low air or gas pressure of 7 psi/48 kPa. Request submittal
10.49.
• Series 753-E Solenoid Valve – The Series 753-E Solenoid Valve is designed for use with
­systems that require electrical activation. Request submittal 30.32.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_11
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

TRIM PACKAGES Optional accessories:


• Series 746-LPA Dry Accelerator – The Series 746-LPA Dry Accelerator can be used on
­pneumatic release systems to improve response time. Request submittal 30.64.
• Series 760 Water Motor Alarm – The Series 760 Water Motor Alarm is a mechanical device
that sounds when a sustained flow of water occurs (such as with an open sprinkler). Request
submittal 30.32.
• Series 75B Supplemental Alarm Device – The Series 75B Supplemental Alarm Device is
designed to provide a continuous alarm for systems equipped with a mechanical device.
Request submittal 30.33.
• Series 75D Water Column Kit – The Series 75D Water Column Kit is designed to minimize
residual water in the riser from collecting above the clapper. Request submittal 30.34.
• Alarm Pressure Switch – Alarm Pressure Switches are designed to activate electrical alarms
and control panels when a sustained flow of water occurs (such as with an open sprinkler).
• Air Supervisory Pressure Switch – Air Pressure Supervisory Switches are used to monitor
­system air pressure and are available as low-pressure and high-pressure sensitivity.
• Air Supply System – The air supply system contains all components for establishing and
maintaining air in a pneumatic system. The compressor, low pressure alarms, ball valves, and
required trim are included in the air supply system.
• Air Compressor (See page 14 for more on the Victaulic Series 7C7 Compressor Package)
• Air Maintenance Trim Assembly
• Alarm Panels
• Drain Connection Kit

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_12 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

AIR SUPPLY REQUIREMENTS The required air pressure for Series 769 FireLock NXT Preaction Valves is 13 psi/90 kPa minimum,
regardless of the system supply pressure. Air pressures should be kept below 18 psi/124 kPa, unless
a Series 746-LPA Dry Accelerator is installed. Systems with air pressures higher than 18 psi/124 kPa
may require the addition of a Series 746-LPA Dry Accelerator.
If multiple Series 769 FireLock NXT Preaction Valves are installed with a common air supply, isolate
the systems with a spring-loaded, soft-seated ball check valve to ensure air integrity for each system.
Good practice is to include a ball valve for isolation and service of each individual system.
Set the air pressure to the required system air pressure. Air pressure differing from the required sys-
tem air pressure could reduce system operation response time.
The engineer/system designer is responsible for sizing the compressor so that the entire system is
charged to the required air pressure within 30 minutes. DO NOT oversize the compressor to provide
more airflow. An oversized compressor will slow down or possibly prevent valve operation.
If the compressor fills the system too fast, it may be necessary to restrict the air supply. Restricting
the air supply will ensure that air being exhausted from an open sprinkler or manual release valve is
not replaced by the air supply system as fast as it is being exhausted.

COMPRESSOR SIZING
COMPRESSOR REQUIREMENTS
12

20 psi/138 kPa
13 psi/90 kPa
10
REQUIRED FLOW RATE (CFM)

0
1050

1300

1550

1800
300

550

800
50

SYSTEM CAPACITY (in gallons)

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_13
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

BASE OR RISER-MOUNTED For base or riser-mounted compressors, the recommended air pressure of 13 psi/90 kPa is the
COMPRESSORS “on” or “low” pressure setting for the compressor. The “off” or “high” pressure setting should
be 18 psi/124 kPa. Victaulic offers the Series 7C7 Compressor package for FireLock NXT devices
which is riser-mounted and pre-set for the FireLock NXT pressure requirements as stated above.
For information on the Series 7C7 package, consult publication 30.22. The Series 7C7 Compressor
package is only available in North America.
When a base or riser-mounted air compressor supplies air to a Series 768 FireLock NXT Dry Valve,
it is not necessary to install the Victaulic Series 757 Regulated Air Maintenance Trim Assembly
(AMTA). In this case, the airline of the compressor connects to the trim at the fitting where the Series
757 Regulated AMTA is normally installed (refer to the applicable trim drawing). If the compres-
sor is not equipped with a pressure switch, the Series 757P Air Maintenance Trim Assembly with
Pressure Switch should be installed. For information on the Series 757 Regulated Air Maintenance
Trim Assembly, see publication 30.35. For information on the Series 757P Air Maintenance Trim
Assembly, see publication 30.36.

SHOP AIR OR TANK-MOUNTED In the event a compressor becomes inoperative, a properly sized tank-mounted air compressor
AIR COMPRESSORS p­rovides the the greatest protection for systems.
When shop air or a tank-mounted air compressor is used, the Series 757 Regulated AMTA must be
installed. The Series 757 Regulated AMTA provides proper air regulation from the air reservoir to the
sprinkler system.
For tank-mounted air compressors, the recommended air pressure of 13 psi/90 kPa should be used
as the set point for the air regulator. The “on” pressure of the compressor should be at least 5 psi/
34 kPa above the set point of the air regulator.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_14 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

SERIES 757 REGULATED AIR


MAINTENANCE TRIM ASSEMBLY NOTICE
• Victaulic recommends a maximum of two Series 769 FireLock NXT Preaction Valves
per Series 757 Regulated AMTA

Bill of Materials
1 1⁄8"/3.2 mm Restrictor
2 Slow Fill Ball Valve (Normally Open)
3 Air Regulator
4 Strainer (100 Mesh)
5 Spring-Loaded, Soft-Seated
Ball Check Valve 1
6
6 Fast Fill Ball Valve (Normally Closed)
2

4
5

Exaggerated for clarity

SERIES 757P AIR MAINTENANCE TRIM


ASSEMBLY WITH PRESSURE SWITCH NOTICE
• Victaulic recommends a maximum of two Series 769 FireLock NXT Preacttion Valves
per Series 757P AMTA with Pressure Switch.

Bill of Materials 8
Item Qty. Description
1 1 Restrictor (½-inch NPT) 14
2 1 Strainer (½-inch NPT) 7
3 1 Swing Check (½-inch NPT)
4 1 Slow-Fill Ball Valve 16
(Normally Open)
5 1 Spring-Loaded, Soft-Seated 1
Check Valve 9
6 1 Pressure Switch
7 2 Compression Fitting, Straight 12
(¼-inch NPT x ¼-inch Tube) 5 4
8 1 Copper Tubing (¼-inch OD)
9 11 Close Nipple 13
(½-inch NPT x 1.13) 11
10 1 Nipple (½-inch NPT x 4.00)
11 1 90° Female Elbow (½-inch NPT)
12 4 Female Tee (½-inch NPT)
13 3 Union (½-inch NPT)
14 2 Reducing Bushing
(½-inch NPT x ¼-inch NPT)
15 1 Fast-Fill Ball Valve
(Normally Closed) 3
2
16 1 Pressure Switch Isolation Ball 10
Valve (Normally Open -
Lockable) FROM
COMPRESSOR 15

Exaggerated for clarity TO


SYSTEM

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_15
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

COMPRESSOR REQUIREMENTS Compressor Requirements and Settings for Series 769 FireLock NXT Preaction Valves Installed
with Series 746-LPA Dry Accelerators
Set the air regulator of the Series 757 Regulated AMTA to 13 psi/90 kPa.
THE SERIES 757P AIR MAINTENANCE TRIM ASSEMBLY WITH PRESSURE SWITCH MUST NOT
BE USED ON A SERIES 769 FIRELOCK NXT PREACTION VALVE INSTALLED WITH A SERIES
746-LPA DRY ACCELERATOR.
When a Series 769 FireLock NXT Preaction Valve is installed with a Series 746-LPA Dry Accelerator,
the Series 757 Regulated AMTA must be used. NOTE: The use of an air regulator with a base or
riser-mounted compressor could cause short cycling, resulting in premature wear of the compressor.
In the event a compressor becomes inoperative, a properly sized tank-mounted air compressor
­provides the greatest protection for systems installed with a Series 746-LPA Dry Accelerator. In
this situation, air can be supplied continuously to the sprinkler system for an extended time period.
NOTE: The Series 757 Regulated AMTA must be used with a tank-mounted air compressor that
supplies air to a Series 769 FireLock NXT Preaction Valve installed with a Series 746-LPA Dry
Accelerator.
The air regulator of the Series 757 Regulated AMTA is a relief-type design. Any pressure in the
­system that is above the set point of the air regulator will be released. Therefore, charging the air reg-
ulator above the set point could cause premature operation of a valve installed with a Series 746‑LPA
Dry Accelerator. NOTE: The Series 746-LPA should not be used above 30 psi/207kPa. If higher pres-
sures are required, the Series 746 should be used.
Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches
Air supervisory pressure switches are required for preaction systems and must be set according to
the following instructions. NOTE: Switches for Vic-Quick Risers are pre-set at the factory.
Wire the air supervisory pressure switches to activate a low-pressure alarm signal. NOTE: In addition,
the local authority having jurisdiction may require a high-pressure alarm. Contact the local authority
having jurisdiction for this requirement.
Set the air supervisory pressure switches to activate at 2 – 4 psi/14 – 28 kPa below the minimum air
pressure required, but not lower than 10 psi/69 kPa.
Wire the alarm pressure switch to activate a water flow alarm.
Set the alarm pressure switch to activate on a pressure rise of 4 – 8 psi/28 – 55 kPa.
Remote System Test Valve Requirements
The remote system test valve (inspector’s test connection) should contain a UL Listed and/or FM
Approved valve (normally closed), which can be opened to simulate the operation of a sprinkler.
The remote system test valve (inspector’s test connection) should be located at the most hydrauli-
cally demanding location in the release system. NOTE: Multiple restrictions on the remote system
test valve (inspector’s test connection) may slow the air decay rate and cause the system to respond
slower than required.
The remote system test valve (inspector’s test connection) should terminate with an orifice equal to
the smallest orifice in the releasing system.
The remote system test valve (inspector’s test connection) is used to ensure that water reaches the
most remote part of the system within 60 seconds.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_16 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

NON-INTERLOCKED,
PNEUMATIC RELEASE TRIM
Series 769 FireLock NXT Preaction Valve –
Non-Interlocked, Pneumatic Release Trim
(Optional Accessories Also Shown)

Bill of Materials From System


Air Feed
1 Series 769 FireLock NXT Preaction Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR 15
Assembly is Ordered)
3 Water Supply Main Control Valve (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered)
4 Drain Swing Check Valve To Pilot
Line
5 Drip Cup with Cap 20
Location
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR
16
A
Assembly is Ordered) 14
7 Series 729 Drip Check Valve
8 Diaphragm-Charge-Line Ball Valve 24
(Normally Open) 5
9 3-in-1 Strainer/Check/Restrictor Assembly 17 22

10 Series 760 Water Motor Alarm To Drip 13 To Drip


Cup Cup
(Optional/Sold Separately) 4
Location Location
21
11 Alarm Test Ball Valve A A 12
12 Diaphragm-Charge-Line Pressure 23
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 Auto Drain
Note 1
14 Series 776 Low-Pressure Actuator To System
18
15 Air Manifold
19 21 9
16 Air Supervisory Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered) 21
17 System Pressure Gauge
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard) 11
18 Water Supply Main Drain Valve - Flow Test
19 Water Supply Pressure Gauge 1 10
(0-300 psi/0-2068 kPa/0-20.7 Bar)
20 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered)
7
21 Gauge Valve To Drip
6
22 System Main Drain Valve Cup
2 Location
23 Series 755 Manual Pull Station
24 Series 748 Ball Check Valve
A
8

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_17
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

NON-INTERLOCKED, PNEUMATIC/
ELECTRIC RELEASE TRIM
Series 769 FireLock NXT Preaction Valve –
Non-Interlocked, Pneumatic/Electric Release
Trim (Optional Accessories Also Shown)

Bill of Materials
26a
1 Series 769 FireLock NXT Preaction Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR 26
Assembly is Ordered)
3 Water Supply Main Control Valve (Optional/Sold From System
Separately – Comes Standard when VQR Air Feed 26b

Assembly is Ordered)
4 Drain Swing Check Valve
15
5 Drip Cup with Cap
6 Alarm Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR Location

Assembly is Ordered)
16 20
A
7 Series 729 Drip Check Valve
8 Diaphragm-Charge-Line Ball Valve 14

(Normally Open) 24
9 3-in-1 Strainer/Check/Restrictor 5
22
Assembly 17
10 Series 760 Water Motor Alarm 13
4 To Drip
(Optional/Sold Separately) 21
To Drip Cup
Cup
Location
11 Alarm Test Ball Valve Location 12
12 Diaphragm-Charge-Line Pressure
A A 25

Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)


13 Series 749 Auto Drain Note 1
To System
14 Series 776 Low-Pressure Actuator 18
15 Air Manifold 19
21 9 23
16 Air Supervisory Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR 21
Assembly is Ordered) To Drip Cup
11 Location
17 System Pressure Gauge
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard) A
18 Water Supply Main Drain Valve - Flow Test 1 10
19 Water Supply Pressure Gauge
(0-300 psi/0-2068 kPa/0-20.7 Bar)
20 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR 7 6

Assembly is Ordered) To Drip Cup


21 Gauge Valve 2 Location
22 System Main Drain Valve A 8
23 Series 755 Manual Pull Station
24 Series 748 Ball Check Valve
25 Series 753-E Solenoid Valve
26 Series 746-LPA Dry Accelerator 3
(Optional/Sold Separately)

From Water
Supply

Exaggerated for clarity


NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_18 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

SINGLE-INTERLOCKED,
PNEUMATIC RELEASE TRIM
Series 769 FireLock NXT Preaction Valve –
Single-Interlocked, Pneumatic Release Trim
(Optional Accessories Also Shown)

Bill of Materials
1 Series 769 FireLock NXT Preaction Valve 25a
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR
Assembly is Ordered) 25

3 Water Supply Main Control Valve (Optional/Sold


Separately – Comes Standard when VQR To Pilot 25b
Assembly is Ordered) Line
4 Drain Swing Check Valve
5 Drip Cup with Cap
15
6 Alarm Pressure Switch (Optional/Sold
From System
Separately – Comes Standard when VQR Air Feed
Assembly is Ordered)
7 Series 729 Drip Check Valve 20
16 Location
8 Diaphragm-Charge-Line Ball Valve A
(Normally Open)
14
9 3-in-1 Strainer/Check/Restrictor Assembly
10 Series 760 Water Motor Alarm
(Optional/Sold Separately) 24
11 Alarm Test Ball Valve 22 5
17
12 Diaphragm-Charge-Line Pressure To Drip To Drip
Cup 13 Cup
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar) Location
Location
13 Series 749 Auto Drain 4
21 A A 12
14 Series 776 Low-Pressure Actuator
23
15 Air Manifold
16 Air Supervisory Pressure Switch (Optional/Sold
Separately – Comes Standard when VQR Note 1 To System
Assembly is Ordered)
18
17 System Pressure Gauge 21 9
19
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard)
18 Water Supply Main Drain Valve - Flow Test
19 Water Supply Pressure Gauge 21

(0-300 psi/0-2068 kPa/0-20.7 Bar)


11
20 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR 10
1
Assembly is Ordered)
21 Gauge Valve
22 System Main Drain Valve
23 Series 755 Manual Pull Station
24 Series 748 Ball Check Valve 7
25 Series 746-LPA Dry Accelerator
To Drip Cup 6
(Optional/Sold Separately) 2 Location
A 8

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_19
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

SINGLE-INTERLOCKED,
OR DOUBLE-INTERLOCKED,
ELECTRIC RELEASE TRIM
Series 769 FireLock NXT Preaction
Valve – Single-Interlocked, Electric Release
Trim or Double-Interlocked, Electric
Release (Electric-Pneumatic/Electric) Trim
(Optional Accessories Also Shown)

Bill of Materials
1 Series 769 FireLock NXT Preaction Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR
From System
Assembly is Ordered) 15
Air Feed Location
19
3 Water Supply Main Control Valve (Optional/Sold
Separately – Comes Standard when VQR
A
Assembly is Ordered) 14
4 Drain Swing Check Valve
5 Drip Cup with Cap 23
6 Alarm Pressure Switch (Optional/Sold 5
21
Separately – Comes Standard when VQR 16
To Drip
Assembly is Ordered) 13 Cup
To Drip
7 Series 729 Drip Check Valve 4 Cup Location
8 Diaphragm-Charge-Line Ball Valve
20 Location A 12
(Normally Open) A
22
9 3-in-1 Strainer/Check/Restrictor Assembly
10 Series 760 Water Motor Alarm
Note 1
(Optional/Sold Separately) To System
17
11 Alarm Test Ball Valve 20 9
18
12 Diaphragm-Charge-Line Pressure
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 Auto Drain 20
14 Series 753-E Solenoid Valve
15 Air Supervisory Pressure Switch** 11
10
16 System Pressure Gauge
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard) 1
17 Water Supply Main Drain Valve - Flow Test
18 Water Supply Pressure Gauge
(0-300 psi/0-2068 kPa/0-20.7 Bar)
19 Drain Connection Kit (Optional/Sold
7 6
Separately – Comes Standard when VQR
Assembly is Ordered) To Drip Cup
2
20 Gauge Valve Location
21 System Main Drain Valve A 8
22 Series 755 Manual Pull Station
23 Series 748 Ball Check Valve
**Item #15 is optional/sold separately (or standard when VQR 3
assembly is ordered) for single-interlocked, electric release trim.
**Item #15 is standard for double-interlocked, electric release
(electric-pneumatic/electric) trim.

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_20 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

DOUBLE-INTERLOCKED,
ELECTRIC/PNEUMATIC RELEASE TRIM
Series 769 FireLock NXT Preaction Valve  –
Double-Interlocked, Electric/Pneumatic
Release Trim
(Optional Accessories Also Shown)

Bill of Materials
1 Series 769 FireLock NXT Preaction Valve 25a
2 FireLock Rigid Coupling (Optional/Sold NOTE: When installing the optional Series 746-LPA Dry Accelerator,
relocate the auto vent to the location of the indicated plug.
Separately – Comes Standard when VQR
Assembly is Ordered) From System 25
3 Water Supply Main Control Valve Air Feed
25b
(Optional/Sold Separately – Comes
Standard when VQR Assembly is Ordered)
15
4 Drain Swing Check Valve 28
5 Drip Cup with Cap
6 Alarm Pressure Switch (Optional/Sold
20
Separately – Comes Standard when VQR 16 Location 27
Assembly is Ordered) A
7 Series 729 Drip Check Valve
8 Diaphragm-Charge-Line Ball Valve 14 29
(Normally Open) 30

9 3-in-1 Strainer/Check/Restrictor 24
26
Assembly 17 22 5
10 Series 760 Water Motor Alarm
(Optional/Sold Separately) 13
To Drip
Cup
11 Alarm Test Ball Valve 21 4
To Drip Cup Location
Location
12 Diaphragm-Charge-Line Pressure B 12
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar) B 23
13 Series 749 Auto Drain
14 Series 767 Electric/Pneumatic Actuator Note 1
15 Air Manifold To System
18
16 Air Supervisory Pressure Switch
19 21
(Optional/Sold Separately – Comes 9
Standard when VQR Assembly is Ordered)
17 System Pressure Gauge 21
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard)
18 Water Supply Main Drain Valve - Flow Test 11

19 Water Supply Pressure Gauge


10
(0-300 psi/0-2068 kPa/0-20.7 Bar)
20 Drain Connection Kit (Optional/Sold 1
Separately – Comes Standard when VQR
Assembly is Ordered)
21 Gauge Valve
22 System Main Drain Valve 7 6
23 Series 755 Manual Pull Station To Drip
24 Series 748 Ball Check Valve Cup
2 Location
25 Series 746-LPA Dry Accelerator
(Optional/Sold Separately) B
8
26 Upper Chamber Strainer (100 Mesh)
27 Upper Chamber Pressure Gauge for
Series 767 Electric/Pneumatic Actuator 3
28 Auto Vent for Series 767 Electric/
Pneumatic Actuator
29 Upper Chamber Inlet Restrictor
.032-inch) for Series 767 Electric/
Pneumatic Actuator From Water
Supply
30 Upper Chamber Check Valve (¼-inch)
for Series 767 Electric/Pneumatic Actuator

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_21
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

DOUBLE-INTERLOCKED, PNEUMATIC/
PNEUMATIC RELEASE TRIM
Series 769 FireLock NXT Preaction Valve –
Double-Interlocked, Pneumatic/Pneumatic
Release Trim
(Optional Accessories Also Shown)

Bill of Materials
29
1 Series 769 FireLock NXT Preaction Valve
2 FireLock Rigid Coupling (Optional/Sold
21
Separately – Comes Standard when VQR 25a

Assembly is Ordered)
3 Water Supply Main Control Valve (Optional/Sold 25
30 25
Separately – Comes Standard when VQR 26a Pilot
26 Line
Assembly is Ordered) 25b

4 Drain Swing Check Valve To Pilot NOTE: When installing the


Line optional Series 746-LPA Dry
5 Drip Cup with Cap 28
Accelerator(s), relocate the
6 Alarm Pressure Switch (Optional/Sold 26 auto vent to the location of
Separately – Comes Standard when From System 26b System the indicated plug.
Air Feed Line 16
15
VQR Assembly is Ordered) 27
7 Series 729 Drip Check Valve 15
8 Diaphragm-Charge-Line Ball Valve
(Normally Open)
9 3-in-1 Strainer/Check/Restrictor Assembly
10 Series 760 Water Motor Alarm
Location
(Optional/Sold Separately)
11 Alarm Test Ball Valve 16 A
12 Diaphragm-Charge-Line Pressure
Gauge (0-300 psi/0-2068 kPa/0-20.7 Bar)
13 Series 749 Auto Drain 24
14
14 Series 798 Pneumatic/Pneumatic Actuator 5
17 22 20
15 Air Manifold
16 Air Supervisory Pressure Switch (Optional/Sold 13 To Drip Cup
To Drip Cup Location
Separately – Comes Standard when VQR 4
Assembly is Ordered) 21
Location A 12

17 System Pressure Gauge


A
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard)
18 Water Supply Main Drain Valve - Flow Test Note 1 To System
19 Water Supply Pressure Gauge
18
(0-300 psi/0-2068 kPa/0-20.7 Bar) 19
21
9
20 Drain Connection Kit (Optional/Sold
Separately – Comes Standard when VQR 21 23
Assembly is Ordered)
21 Gauge Valve 11
10
22 System Main Drain Valve
23 Series 755 Manual Pull Station 1
24 Series 748 Ball Check Valve
25 Series 746-LPA Dry Accelerator
(Optional/Sold Separately)
26 Air Feed Valve Assembly 7 6
26a Pilot Line Fill Valve and Shutoff Valve
(Shutoff Valve has Yellow Handle) To Drip Cup
2 Location
26b System Line Fill Valve and Shutoff Valve
(Shutoff Valve has Yellow Handle) A 8

27 System Air Line Strainer (100 Mesh)


28 Pilot Line Strainer (100 Mesh)
29 Pilot Line Pressure Gauge 3
(0-80 psi/0-552 kPa/0-5.5 Bar with Retard)
30 Auto Vent for Series 798 Pneumatic/
Pneumatic Actuators

From Water
Supply

Exaggerated for clarity

NOTE 1: Connection point for the Series 75D Water Column Device Kit.
For installation of the Series 75B Supplemental Alarm Device, refer to the instructions supplied with
the product.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.82_22 REV_E
FIRE PROTECTION PRODUCTS – DEVICES 30.82
FireLock NXT™
Actuated Valve with Preaction Trim
SERIES 769
With Preaction Trim
Grooved x Grooved

WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.

WARNING
WARNING
• This product must be installed by an experienced, trained installer,
in accordance with the instructions provided with each valve. These
­instructions contain important information.
Failure to follow these instructions may result in serious personal injury,
property damage, or valve leakage.
If you need additional copies of this product literature or the valve
­installation instructions, or if you have any questions about the safe
installation and use of this device, contact Victaulic Company, P.O.
Box 31, Easton, PA 18044-0031 USA, Telephone: 001-610-559-3300.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_E 30.82_23
INSTALLATION, MAINTENANCE, AND TESTING MANUAL I-769P-EPA
FireLock NXT™ Preaction Valve
with Series 767 Electric/Pneumatic Actuator
SERIES 769
(DOUBLE-INTERLOCKED, ELECTRIC/PNEUMATIC RELEASE)

IMPORTANT INSTALLATION INFORMATION


1. For proper operation and approval, the Series 769 FireLock NXT
CAUTION
Preaction Valve must be installed in accordance with the spe- • Make sure no foreign material gets into the valve body, pipe
cific trim diagrams included with the shipment. NOTE: Victaulic nipples, or valve openings.
­provides specific trim diagrams for installations involving a Series
• If using any material other than Teflon tape, use extra caution
746-LPA Dry Accelerator.
so that no material gets into the trim.
2. Before installing the Series 769 FireLock NXT Preaction Valve,
Failure to follow these instructions could cause improper valve
flush the water supply piping thoroughly to remove all foreign
operation, resulting in personal injury and/or property damage.
material.
3. Series 769 FireLock NXT Preaction Valves MUST NOT be located 4. Install the valve, trim, and accessories per the trim drawing.
in an area where the valve can be exposed to freezing tempera-
tures. In addition, the Series 769 FireLock NXT Preaction Valve
MUST NOT be located in an area where physical damage may
occur.
4. It is the system designer’s responsibility to confirm material com-
patibility of the Series 769 FireLock NXT Preaction Valve, trim, and
­associated accessories when a corrosive environment or contami-
nated water is present.
5. SERIES 769 FIRELOCK NXT PREACTION VALVES MUST BE
INSTALLED ONLY IN THE VERTICAL POSITION WITH THE
ARROW ON THE BODY POINTING UPWARD.
6. Air or nitrogen supply to the dry piping system must be clean, dry,
and oil-free.
7. Air supplies must be regulated, restricted, and continuous.
8. When an uninterruptible water flow alarm is required, Victaulic
RE-LOCATE THE ACTUATOR’S
recommends the use of a low-pressure alarm installed on the AUTO VENT ASSEMBLY TO
THE LOCATION OF THIS PLUG
diaphragm charge line downstream of the strainer/check restric-
tor. Another option is to install a Series 75B Supplemental Alarm
Device.
9. Per NFPA 13 requirements, piping must be pitched so that TO ACTUATOR
­systems can drain properly. For areas that are subject to high TRIM

levels of condensation, or where piping is not properly pitched, an


5. FOR VALVES INSTALLED WITH A SERIES 746-LPA DRY
optional Series 75D Water Column Device kit is available to assist
ACCELERATOR: Make sure the Series 746-LPA Dry Accelerator is
in automatically draining water out of the riser.
installed in accordance with the trim drawing provided. The end
VALVE/TRIM INSTALLATION with the vent seal “button” must be installed facing down (toward
the trim, as shown above).
1. Make sure the trim drawing matches the system’s requirements.
6. Supply pressure to the diaphragm charge line by providing an
uninterrupted source of water from upstream of the main control
CAUTION valve.
• Make sure the foam spacer is removed from
inside the valve body before attempting to
install the valve.
Failure to follow this instruction could cause
improper valve operation, resulting in personal
injury and/or property damage.

2. Remove all plastic caps and foam spacers from the valve.
3. Apply a small amount of pipe joint compound or Teflon* tape to
the external threads of all threaded pipe connections. DO NOT get
any tape, compound, or other foreign material into the valve body,
pipe nipples, or valve openings.

* Teflon is a registered trademark of the DuPont Company

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

I-769P-EPA_10 REV_D
...Technical Data Sheets and Catalogue
B. Air Compressor Assembly (Series 7C7)
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7
For FireLock NXT™ Series 768 Dry Valves, Series 769 Deluge and Preaction Valves,
Series 764 Alternate Valves.
Note: The Series 7C7 Air Maintenance/Compressor Assembly is designed for systems that do
not require an accelerator to achieve the required system pressure performance. If an
accelerator is required, a tank-mounted compressor with a regulated air maintenance device
should be used.

SERIES 7C7

PRODUCT DESCRIPTION The Series 7C7 Air Maintenance/Compressor assembly consists of a riser-mounted compressor,
Series 757P Air Maintenance Device and flexible hoses for installation. It is designed to ensure the
valve system can achieve operational air pressure within 30 minutes of discharge, in accordance with
NFPA 13 requirements (7.2.6.2.2).
The Series 757P Air Maintenance Device is UL Listed and FM Approved.
The Series 7C7 Assembly is available with 1/6, 1/3 and 1/2 horsepower compressors depending upon the
system requirements.
COMPRESSOR CAPACITIES
The engineer/system designer is responsible for sizing the compressor so that the entire
system is charged to the required air pressure within NFPA guidelines (30 minutes). DO
NOT oversize the compressor to provide more airflow. An oversized compressor will slow
down or possibly prevent valve operation.

Nominal Capacity Capacity


AC WITH WITHOUT
Voltage/Hz Pressure Time AutoVent AutoVent Amp
Hp (+/- 10%) psi/Bar Minutes gallons/m3 gallons/m3 Draw
18 175 275
1/6 110/60 30 2.1 Amps
1.2 0.7 1.1
18 375 525
1/3 110/60 30
1.2 1.4 2.0
18 160 235
1/3 220/50 30
1.2 0.6 0.9
4.4 Amps
18 450 660
1/3 220/50 60
1.2 1.7 2.5
18 370 400
1/3 220/60 30
1.2 1.4 1.5
18 660 670
1/2 110/50 30
1.2 2.5 2.5
6.6 Amps
18 780 830
1/2 110/60 30
1.2 3.0 3.1

NOTE: Refer to the charts on the following pages for minimum required
fill capacities to 13 psi/0.9 Bar. Low air alarms will clear at 13 psi/0.9 Bar. In
addition, these charts contain higher capacities to 18 psi/1.2 Bar that are not
shown in the table above.

JOB/OWNER CONTRACTOR ENGINEER


System No._______________________________ Submitted By_____________________________ Spec Sect________________ Para____________
Location_ ________________________________ Date ____________________________________ Approved_ _______________________________
Date ____________________________________

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_F 30.22_1
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

ASSEMBLY DIMENSIONS

A A
A

B B B

C C C

D D D

Series 7C7 - 1/2HP Compressor Series 7C7 - 1/3HP Compressor Series 7C7 - 1/6HP Compressor

Series 7C7 - 1/2HP Compressor

Pipe Size A B C D
1 1/2” 14.5 4.8 6.55 15.54
2” 14.77 4.8 6.55 15.54
2 1/2” & 76.1 15.03 4.8 6.55 15.54
3” 15.36 4.8 6.55 15.54
4” 15.94 4.8 6.55 15.54
6” & 165.5 16.98 4.8 6.55 15.54
8” 18.01 4.8 6.55 15.54

Series 7C7 - 1/3HP Compressor

Pipe Size A B C D
1 1/2” 14.53 5.00 6.55 15.38
2” 14.78 5.00 6.55 15.38
2 1/2” & 76.1 15.04 5.00 6.55 15.38
3” 15.36 5.00 6.55 15.38
4” 15.88 5.00 6.55 15.38
6” & 165.5 16.98 5.00 6.55 15.38
8” 18.02 5.00 6.55 15.38

Series 7C7 - 1/6HP Compressor

Pipe Size A B C D
1 1/2” 14.53 4.60 6.55 15.38
2” 14.78 4.60 6.55 15.38
2 1/2” & 76.1 15.04 4.60 6.55 15.38
3” 15.36 4.60 6.55 15.38
4” 15.88 4.60 6.55 15.38
6” & 165.5 16.98 4.60 6.55 15.38
8” 18.02 4.60 6.55 15.38

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.22_2 REV_F
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

ASSEMBLY PERFORMANCE (1/2 HP Compressor)


- For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

Estimated Time to Reach Various Pressures - Estimated Time to Reach Various Pressures -
Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and Auto Vent Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and No Auto Vent
50 50 18 psi

45
18 psi

40 40

35 13 psi
13 psi
30

Time (minutes)
Time (minutes)

30

25

20 20

15

10
10

0
0
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
System Size (gallons) System Size (gallons)

Estimated Time to Reach Various Pressures - Estimated Time to Reach Various Pressures -
Series 7C7 with 1/2-hp (110 VAC, 60-Hz) Compressor and Auto Vent Series 7C7 with 1/2-hp (110 VAC, 60 Hz) Compressor and No Auto Vent
18 psi 50
40

18 psi
35
13 psi 40
30

25 13 psi
30
Time (minutes)
Time (minutes)

20

15 20

10
10
5

0
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 0
25 75 125 175 225 275 325 375 425 475 525 575 625 675 725 775 825 875 925 975 1025 1075 1125 1175 1225

System Size (gallons)


System Size (gallons)

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_F 30.22_3
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

ASSEMBLY PERFORMANCE (1/3 HP Compressor)


- For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

Estimated Time to Reach Various Pressures - Estimated Time to Reach Various Pressures -
Series 7C7 with 1/3-hp (110 VAC) Compressor and Auto Vent Series 7C7 with 1/3-hp (110 VAC) Compressor and No Auto Vent

60 18 psi 13 psi
30

18 psi
50

13 psi 20
40

Time (minutes)
Time (Minutes)

30

10
20

10

0
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750
0
50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 System Size (gallons)
System Size (Gallons)

Estimated Time to Reach Various Pressures - 220-volt Option Estimated Time to Reach Various Pressures - 220-volt Option
Series 7C7 with 1/3-hp (220-240 VAC, 50-Hz) Compressor and Auto Vent Series 7C7 with 1/3-hp (220 - 240 VAC, 50 Hz) Compressor and No AutoVent
1.2 Bar 0.9 Bar 70
60
1.2
Bar
60
50

50
0.9
40 Bar
Time (minutes)

Time (minutes)

40

30
30

20
20

10
10

0 0
0.2 0.6 1.0 1.4 1.8 2.2 2.6 3.0 0 0.5 1.0 1.5 2.0 2.5 3.0

System Size (cubic meters) System Size/Volume (cubic meters)

Estimated Time to Reach Various Pressures - 220-volt Option Estimated Time to Reach Various Pressures - 220-volt Option
Series 7C7 with 1/3-hp (220-240 VAC, 60-Hz) Compressor and Auto Vent Series 7C7 with 1/3-hp (220 - 240 VAC, 60 Hz) Compressor and No Auto Vent

60 60

1.2
1.2 Bar Bar
50
50

0.9 Bar 40 0.9


40 Bar
Time (minutes)
Time (minutes)

30
30

20
20

10
10

0
0 0.5 1.0 1.5 2.0 2.5 3.0
0
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 System Size/Volume (cubic meters)

System Size (cubic meters)

NOTE: Refer to the following page for charts reflecting the 220-volt 1/3-hp option.

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.22_4 REV_F
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

ASSEMBLY PERFORMANCE (1/6 HP Compressor)


- For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

Estimated Time to Reach Various Pressures - Estimated Time to Reach Various Pressures -
Series 7C7 with 1/6-hp (110 VAC) Compressor and Auto Vent Series 7C7 with 1/6-hp (110 VAC) Compressor and No AutoVent
70 18 psi 13 psi
30
18 psi
60

13 psi
50 20

Time (minutes)
Time (Minutes)

40

10
30

20

0
10 50 100 150 200 250 300 350 400

System Size (gallons)

0
50 100 150 200 250 300 350 400

System Size (Gallons)

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_F 30.22_5
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

exploded view drawing -


series 7c7 air maintenance compressor assembly with 1/2-hp compressor

15
24
Bill of Materials
14 Item Qty. Description
1 1 Compressor
2 1 Mounting Bracket
1
3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch
25 19 4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female)
5 2 Split Hanger for ½-inch Pipe
To Actuator
Trim 6 2 Hose Clamp
4 7 1 Close Nipple (¼-inch NPT)
8 3 Close Nipple (½-inch NPT)
26 23
14 9 3 90° Female Elbow (½-inch NPT)
2 10
17 10 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long)
7 11 4 Lock Washer (5⁄16 inch)
5 18
12 12 2 Lock Washer (3⁄8 inch)
16 13 4 Hex Nut (¼ - 20 UNC)
6 14 2 Straight Conduit Connector (½-inch)
15 1 Liquid-Tight Conduit (½ inch x 9½ inches Long)
11 16 1 14 AWG, 3-Strand Cable (25 inches Long)
3
17 3 #8 U-Style Wire Connector
13 18 1 Identification Tag
19 1 Compressor Air Intake Filter
8 20 1 Nipple (½-inch NPT x 10 inches Long)
22 21 1 Nipple (½-inch NPT x 4½ inches Long)
22 1 Union (½-inch NPT)
23 1 Reducing Bell (½-inch NPT x ¼-inch NPT)
24 1 14 AWG Grounded Cord with Plug (5½ feet Long)*
9 25 1 Strain Relief Connector*
21 26 1 Identification Label*

* NOTE: Items 24 - 26 apply only to the CSA version


20
Exaggerated for Clarity

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.22_6 REV_F
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

exploded view drawing -


series 7c7 air maintenance compressor assembly with 1/3-hp compressor

Bill of Materials
16
Item Qty. Description
1 1 Compressor
15 10 2 1 Mounting Bracket
25
3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch
4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female)
1
5 2 Split Hanger for ½-inch Pipe
To Actuator 6 2 Hose Clamp
Trim 7 1 Close Nipple (¼-inch NPT)
26
4 8 2 Close Nipple (½-inch NPT)
9 3 90° Female Elbow (½-inch NPT)
10 4 Hex-Head Bolt (5⁄16 - 18 x ¾-inch Long)
11 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long)
18 7
19 27 20 21 12 4 Lock Washer (5⁄16 inch)
13 2 Lock Washer (3⁄8 inch)
2 14 4 Hex Nut (5⁄16 - 18)
5 11
17 15 2 Straight Conduit Connector (½ inch)
13
6 16 1 Liquid-Tight Conduit (½ inch x 9½ inches Long)
24 17 2 14 AWG, 3-Strand Cable (25 inches Long)
18 3 #8 U-Style Wire Connector
3
19 1 Identification Tag
8 12 20 1 Reducing Bell (½-inch NPT x ¼-inch NPT)
21 1 Nipple (½-inch NPT x 1½ inches Long)
14
22 1 Nipple (½-inch NPT x 5½ inches Long)
22
23 1 Nipple (½-inch NPT x 9½ inches Long)
24 1 Union (½-inch NPT)
23 25 1 14 AWG Grounded Cord with Plug (5½ feet Long)*
26 1 Strain Relief Connector*
27 1 Identification Label*
9
* NOTE: Items 25 - 27 apply only to the CSA version
Exaggerated for Clarity

exploded view drawing -


series 7c7 air maintenance compressor assembly with 1/6-hp compressor
Bill of Materials
Item Qty. Description
1 1 Compressor
26 15 2 1 Mounting Bracket
17 18 1 3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch
4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female)
8 5 2 Split Hanger for ½-inch Pipe
To Actuator 6 2 Hose Clamp
Trim
4 7 3 90° Female Elbow (½-inch NPT)
25 24 19 8 1 Close Nipple (¼-inch NPT)
16 9 2 Close Nipple (½-inch NPT)
2 10 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long)
5 10 7 11 3 Hex-Head Bolt (#10 - 32 x ½-inch Long)
12 20
12 2 Lock Washer (3⁄8 inch)
6 13 3 Lock Washer (#10)
22 14 1 Identification Tag
3 14 15 1 Straight Connector, Flexible Cord
13 16 1 Connector, Flexible Cord
17 1 Liquid-Tight Conduit (½ inch x 11½ inches Long)
11
18 3 #8 U-Style Wire Connector
9
19 1 Reducing Bell (½-inch NPT x ¼-inch NPT)
20 1 Nipple (½-inch NPT x 1½ inches Long)
23 21 1 Nipple (½-inch NPT x 9 inches Long)
22 1 Union (½-inch NPT)
23 1 Nipple (½-inch NPT x 5 inches Long)
24 1 Identification Label*
21 25 1 Strain Relief Connector*
5 26 1 14 AWG Grounded Cord with Plug (5½ feet Long)*

Exaggerated for Clarity * NOTE: Items 24 - 26 apply only to the CSA version

www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_F 30.22_7
FIRE PROTECTION PRODUCTS – DEVICES 30.22
Air Maintenance/
Compressor Assembly
SERIES 7C7

electrical information
INCOMING POWER SUPPLY
DANGER (REFERENCE COMPRESSOR
DATA PLATE)
• Only qualified electricians should connect L1 L2
incoming power to the Series 7C7 Air
Maintenance/Compressor Assembly.
• To reduce the risk of electric shock, check
the electrical source for proper grounding.
Failure to follow these instructions could result in LINE LOAD LOAD LINE
death or serious personal injury.

L1 T1 T2 L2

T1 T2

Ground MOTOR
Connection

ELECTRICAL CONNECTION
NOTE: NEMA 1 Enclosure - intended only for indoor use
Only qualified electricians should make the connection to the
incoming power supply. All wiring shall be completed in accordance
with requirements of the local authority having jurisdiction and any
applicable electrical codes.

WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.

WARNING
WARNING
• This product must be installed by an experienced, trained installer,
in accordance with the instructions provided with each valve. These
­instructions contain important information.
Failure to follow these instructions may result in serious personal injury,
property damage, or valve leakage.
If you need additional copies of this product literature or the valve
i­nstallation instructions, or if you have any questions about the safe
installation and use of this device, contact Victaulic Company, P.O.
Box 31, Easton, PA 18044-0031 USA, Telephone: 001-610-559-3300.

For complete contact information, visit www.victaulic.com


30.22 4847 REV F UPDATED 08/2010
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

30.22
...Technical Data Sheets and Catalogue
C. Standard Upright Sprinkler
FireLock® V27, K5.6
Models V2703, V2707, V2704, V2708 40.10
Standard Spray Technical Specifications:
Upright, Pendent and Recessed Pendent
Standard and Quick Response Models: V2703, V2704, V2707, V2708
Style: Pendent, Upright or Recessed Pendent
Nominal Orifice Size: 1/2"/13 mm
K Factor: 5.6 Imp./8.1 S.I.1
Nominal Thread Size: 1/2" NPT/15 mm
Max. Working Pressure:
• 175 psi/1200 kPa (FM)
V2703/V2704 V2707/V2708 V2707/V2708 • 250 psi/1725 kPa (UL)
Upright Pendent Recessed Pendent
Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa
Approvals/Listings: Min. Operating Pressure:
• 7 psi/48 kPa
0786 • 0.35 bar/5 psi (VdS for upright only)
See Victaulic Publication 10.01 for more details. Temperature Rating: See chart
1 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0.

Product Description:
These Model V27 standard spray sprinklers are
designed to produce a hemispherical spray pattern for
standard commercial applications. They are available
with either standard or quick response bulbs. It is cast
with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This
sprinkler is available in various temperature ratings (see
chart on page 3) and finishes to meet many design
requirements. The recessed pendent should be utilized
with a Model V27 recessed escutcheon which provides
up to 3 /4"/19 mm of adjustments.

Coverage
For coverage area and sprinkler placement, refer to
NFPA 13 or applicable standard.

Exaggerated for clarity


Exaggerated for clarity

Job/Owner Engineer
System No. Spec Section

Location Paragraph

Contractor Approved

Submitted By Date

Date

victaulic.com | Sprinklers | FireLock® | K5.6, V27 | Publication 40.10


40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
1
victaulic.com | Sprinklers | FireLock® | K5.6, V27 | Publication 40.10

Material Specifications: Accessories


Upright Deflector: Bronze per UNS C11000
Pendent Deflector: Bronze per UNS C51000 Installation Wrench:

Bulb: Glass with glycerin solution Open End: V27

Bulb Nominal Diameter: Recessed: V27-2

Standard: 5.0 mm Sprinkler Finishes:


Quick Response: 3.0 mm Plain Brass
Load Screw: Bronze per UNS C65100 Chrome plated
Pip Cap: Bronze per UNS C65100 White painted3
Spring: Beryllium nickel Black painted3
Seal: Teflon2 tape Custom painted3
Frame: Die cast brass 65-30 Proprietary Nickel Teflon2 coating3
Lodgement Spring: Stainless steel per UNS S30200 VC-250 4

155, 200, 286 SR Only:


Wax3
For cabinets and other accessories refer to
separate sheet.
2 Teflon is a registered trademark of Dupont Co.
3 UL Listed for corrosion resistance.
4 UL Listed and FM Approved for corrosion resistance.

40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com | Sprinklers | FireLock® | K5.6, V27 | Publication 40.10

Approvals/Listings:

Model
APPROVALS/LISTINGS
V2703 V2707 V2707 V2704 V2708 V2708 7
1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
Orifice Size (inches)
Orifice Size (mm) 13 13 13 13 13 13
Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 5.6
Nominal K Factor S.I.5 8.1 8.1 8.1 8.1 8.1 8.1
Response Standard Standard Standard Quick Quick Quick
Recessed Recessed
Deflector Type Upright Pendent Upright Pendent
Pendent Pendent
Approved Temperature Ratings F°/C°
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
155°F/68°C 155°F/68°C 155°F/68°C
175°F/79°C 175°F/79°C 155°F/68°C
cULus 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C
200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C
175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C
FM 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
155°F/68°C 155°F/68°C 155°F/68°C
175°F/79°C 175°F/79°C 155°F/68°C
NYC/MEA 62-99-E 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C
200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
155°F/68°C 155°F/68°C 155°F/68°C
175°F/79°C 175°F/79°C 155°F/68°C
CSFM 7690-0531:112 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C
200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C
155°F/68°C 135°F/57°C
175°F/79°C 155°F/68°C
LPCB None None None None
200°F/93°C 175°F/79°C
286°F/141°C 200°F/93°C
360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C
175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C
VNIIPO 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C

ZSTZ ZSTX K-ZSTZ K-ZSTZ


CCC 155°F/68°C 155°F/68°C None 155°F/68°C 155°F/68°C None
200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C

135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
175°F/79°C
VdS None None 175°F/79°C None None
200°F/93°C
200°F/93°C
286°F/141°C
286°F/141°C
360°F/182°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
175°F/79°C
CE None None 175°F/79°C None None
200°F/93°C
200°F/93°C
286°F/141°C
286°F/141°C
360°F/182°C
5 For K Factor when pressure is measured in Bar, multiply S.I. units by 10.0
7 FM Approved with 1/ 2” adjustment escutcheon only - quick response

Note: Listings and Approvals as of printing. All are approved open.

40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com | Sprinklers | FireLock® | K5.6, V27 | Publication 40.10

Dimensions:
17⁄16"/
37 mm

15⁄8"/
23⁄8"/ 41 mm
60 mm 23⁄8"/
15⁄8"/ 60 mm
41 mm

Standard Pendent1"/
– Standard Upright –
25 mm
V2707, V2708 V2703, V2704

23⁄8"/60 mm
Max. Hole
2"/51 mm
Min. Hole

13⁄16"/
11⁄16"/
Typical Ceiling Tile 30 mm
17 mm

13⁄16"/
111⁄16"/ Finished Surface 30 mm
43 mm

MAXIMUM RECESS

215⁄16"/
75 mm

MAXIMUM EXTENSION

½" Adjustment Recessed – V2707, V2708 (drawing not to scale)

23⁄8"/60 mm
Max. Hole
2"/51 mm
Min. Hole

17⁄16"/
15⁄16"/
11⁄16"/ 37 mm
24 mm Typical Ceiling Tile
18 mm

15⁄16"/
24 mm
Finished Surface

MAXIMUM RECESS

215⁄16"/
75 mm

MAXIMUM EXTENSION

¾" Adjustment Recessed – V2707, V2708 (drawing not to scale)

40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 4
10'
3,0 m 8'
2,4 m
10'
victaulic.com | Sprinklers 3,0
| FireLock
m
®
| K5.6, V27 | Publication
8' 40.10
2,4 m 6'
Distribution Patterns: 1,8 m
8'
2,4 m 6'
Models V2707, V2708 1,8 m 4'
K5.6 Standard Pendent and Recessed Pendent 1,2 m
6' Patterns – Trajectory
Distribution
1,8 m 4'
10'
1,2 m 2'
3.0m
0,6 m
4'
1,2 m 2'
8' 0,6 m 0
2.4m
2' 4' 6' 8' 10' 12'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m 3,7 m
0,6 m 0
6' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
1.8m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
4'
1.2m 10'
7 psi 15 psi 30 psi 3,0 m
48 kPa 103 kPa 207 kPa
10'
2'
3,0 m 8'
0.6m
2,4 m
10'
3,0 m 8'
0 2,4 m 6'
2' 4' 6' 8' 10' 12' 14' 1,8 m
0.6m 1.2m 8'1.8m 2.4m 3.0m 3.7m 4.3m
2,4 m 6'
7 psi 15 psi 30 psi 1,8 m 4'
48 kPa 103 kPa 207 kPa
Models V2703, V2704 1,2 m
6'
K5.6
1,8 m Standard Upright 4'
Distribution Patterns – Trajectory 1,2 m 2'
10' 0,6 m
3.0m 4'
1,2 m 2'
0,6 m 0
8' 2' 4' 6' 8' 10' 12'
2.4m 2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m 3,7 m
0,6 m 0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
6' 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
1.8m 0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
4'
1.2m 7 psi 15 psi 30 psi
48 kPa 103 kPa 207 kPa

2'
0.6m

0
2' 4' 6' 8' 10' 12' 14' 16'
0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m

7 psi 15 psi 30 psi


NOTES: 48 kPa 103 kPa 207 kPa

A. Data shown is approximate and can vary due to differences in installation.

B. These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as
information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA
National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of coverage requirements. Failure to
follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties.

C. All patterns are symmetrical to the centerline of the waterway.

40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com | Sprinklers | FireLock® | K5.6, V27 | Publication 40.10

Ratings: Available Wrenches:


All glass bulbs are rated for temperatures from -67°F
(-55°C) to those shown in the table below. V27-2 V27
Recessed Open End

Temperature – ºF/ºC V2707, V2708 Pendent 3 3

Maximum V2707, V2708 Recessed Pendent 3 –


Sprinkler Victaulic Nominal Ambient Glass
Temperature Part Temperature Temperature Bulb V2703, V2704 Upright – 3
Classification Identification Rating Allowed Color
Ordinary A  135ºF/57ºC 100ºF/38ºC Orange

Ordinary C  155ºF/68ºC 100ºF/38ºC Red

Intermediate E  175ºF/79ºC 150ºF/65ºC Yellow

Intermediate F  200ºF/93ºC 150ºF/65ºC Green

High J  286ºF/141ºC 225ºF 8/107ºC Blue

Extra High 7 K  360ºF/182ºC 300ºF/149ºC Purple

– M  Open – No Bulb

7 Standard response only.


8 150/65 if wax coated.

WARNING
• Always read and understand installation, care, and maintenance instructions, supplied with each box of sprin-
klers, before proceeding with installation of any sprinklers.
• Always wear safety glasses and foot protection.
• Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping
products.
• Installation rules, especially those governing obstruction, must be strictly followed.
• Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For
minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam-
phlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may
have additional maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this
product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone:
001-610-559-3300.

Installation Note
Reference should always be made to the I-40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Installation and Maintenance Sheet for the product you are installing. This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions.
is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications, designs and standard
data, and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations.
Warranty Trademarks
Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company.

40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 6
...Technical Data Sheets and Catalogue
D. Extinguishant Control Panel
EXTINGUISHANT CONTROL PANEL

FEATURES:

 Three detection zones as standard


KM 598387  Any single zone or any combination of zones can be configured
to release

 Configurable first stage sounder delays

 Configurable detection delays

 Zero time delay upon manual release option

 Compatible with I.S. barriers

 Non-latching zone input option to receive signals from other


systems such as aspirating equipment

 Configurable extinguishant duration up to 5 minutes in 5


seconds steps

 Countdown timer shows time remaining until release


BF-ECP3DCSM
 Supports up to seven, four wire status indicators

 Built-in Extract Fan Control

Designed and manufactured to the highest standards in a quality controlled environment and with European EN-12094-1
approvals, the BF-ECP Series extinguishant releasing panel offers outstanding value and performance for small to medium
fixed firefighting installations.

With three detection zones as standard, extinguishant release can be configured to activate from any combination of
detection zone inputs to allow (among other combinations) any two from three type activations such as would be required
for detection in ceiling void, room and floor void applications.

The extensive configuration options of the BRISTOL allow the functionality of the system to be extensively modified while
still complying with the requirements of the controlling standard for the equipment (EN 12094-1, EN54-2 and EN54-4).

The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until
extinguishant release for added user safety.

The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system
status.

With all the electronics mounted on a single easy removable, steel plate BRISTOL panels are both robust and easy to install.
EXTINGUISHANT CONTROL PANEL

Technical Information
Construction 1.2 mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Color-lid and box Red
Color-controls plate and labels RAL 7047 light gray satin
Mains supply 230V AC, 50Hz +10% - 15% (100 Watts maximum)
Mains supply fuse 1.6 Amp ( F1.6A L250V)
Power supply rating 3 Amps total including battery charge 28V +/- 2V
Maximum ripple current 200 millivolts

Battery type Two 12 Volt 7Ah sealed lead acid in series


Battery charge voltage 27.6VDC nominal (temperature compensated)
Battery charge current 0.7A maximum
Battery fuse 20mm, 3.15A glass
Maximum current draw from batteries 3 Amps
Quiescent current of panel in mains fail 0.095A
R0V output Fused at 500mA with electronic fuse
DATA & SPECIFICATIONS

Sounder outputs 21 to 28V DC Fused at 500mA with electronic fuse


Fault relay contact rating 30VDC 1A Amp maximum
Fire relay contact rating 30VDC 1A Amp maximum
Local fire relay contact rating 30VDC 1A Amp maximum
First stage contact rating 30VDC 1A Amp maximum
Second stage contact rating 30VDC 1A Amp maximum
Extract contact rating 30VDC 1A Amp maximum
Zone quiescent current 2mA maximum
Terminal capacity 0.5mm to 2.5mm2 solid or stranded wire
2

Number of detectors per zone Dependent on type


Number of sounders per circuit Dependent on type and current consumption
Detection circuit end of line 6K8 +/- 5% ½ Watt resistor
Monitored input end of line 6K8 +/- 5% ½ Watt resistor
Sounder circuit end of line 10K +/- 5% ¼ Watt resistor
Extinguishant output end of line 1N4004 Diode
No. of detection circuits 3
No. of sounder circuits 2 x 1st Stage, 1 x 2nd Stage
Extinguishant release output Fused at 1 Amp
Extinguishant release delay Adjustable 0 to 60 seconds (in 5 seconds steps)
Extinguishant release duration Adjustable 60 to 300 seconds (in 5 seconds steps)
SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
Zone normal threshold 8K Ohms to 1K Ohms
EXTINGUISHANT CONTROL PANEL

Technical Information
Detector alarm threshold 999 Ohms to 400 Ohms
Call point alarm threshold 399 Ohms to 100 Ohms
DATA & SPECIFICATIONS

Short circuit threshold 99 Ohms to 0 Ohms


Head removal condition 15.5 to 17.5 volts
Cabling FP200 or equivalent
Monitored inputs normal threshold 8K Ohms to 1K Ohms
Monitored inputs alarm threshold 999 Ohms to 100 Ohms
Monitored inputs Short circuit threshold 99 Ohms to 0 Ohms
Status unit/Ancillary board connection Two wire RS485 connection
Status unit power output Fused at 500mA with electronic fuse

Programmable Functions Access Level 3


Access Level 2  Sounder Delay
 Test Zone 1 – 3  Coincidence Detection
 Disable Zone 1 – 3  Disable Panel Features
 Disable 1st Stage sounders  Zone Alarm Delays (Detectors)
 Disable Preactivated (1st stage) relay  Zone Alarm Delays (Call Points)
 Disable Activated (2nd stage) relay  Configure Zone for I.S. Barrier use
 Disable Extract Fan output  Zone Short Circuit Alarm
 Disable Manual Release inputs  Zone Non-Latching
 Disable Extinguishant sub-system  Zone Inputs Delay
 Activate sounder Delays  Extinguishant Release Time Delay
 Activate extract output  Extinghuishant Release Duration Timer
...Technical Data Sheets and Catalogue
E. Smoke Detector
DETECTORS
C ONVE NT IONAL OPT IC A L S MOK E D ETE CTOR
LPCB Approved, EN 54-7

Optical Smoke Detector are activated when smoke particles enter


the light path, and some of the light is scattered by reflection and
refraction onto the sensor. The light signal is processed and used to 1174a-(cl-3)
convey an alarm condition when it meets the preset criteria.

FEATURES

 Intelligent drift compensation to the variation of external


environment (temperature, humidity, dust, static)

 Can accurately detect the chronic fire happened in 24 hours

 Intelligent algorithm and judgment, warning reminder for dirty


and cleaning

 Filter designed in both software and hardware, enhance the


ability of anti-interference

 PCB board inside is sealed with full protection

 Unique chamber design for protection against dust, insects and


other external interferences

 Talented design of structure without a single screw

 Compatible with a wide range of conventional panel or interface

Conventional Optical Smoke Detector — B61-1001


Operating Voltage 9VDC ~ 28VDC
Quiescent Current ≤60uA
Alarm Current 10mA ≤I ≤ 50mA
LED indicator Red, flashing every 2s ~ 4s when standby; Illuminating when alarm fire
SPECIFICATIONS

Remote indicator output 10kΩ resistor is required


Power-Up Time ≤ 10s
Wiring Method Polarized two-wire
Ingress Protection Rating IP32
Temperature -10⁰C ~+ 55⁰C

Humidity ≤95%, non-condensing


Dimension Diameter: 100mm, Height: 43mm (w/out base)
Weight About 120g
...Technical Data Sheets and Catalogue
F. Sounder Strobe
G. Fire Alarm Bell
ALARM DEVICES
C ONVE NT IONAL S OU ND ER STROB E
LPCB Approved, EN54-3

FEATURES

 Alert Sound and flash combined in one unit


1174c-(cl-3)
 A select of 16 different tones

 Using ultra bright LEDs as source for light indication

 Fully synchronized operating frequencies and LED beacon

 Low power consumption

 Plug-in structure design for easy installation

 Compatible with a wide range of conventional panel or interface

Conventional Sounder Strobe — B61-6301


Operating Voltage 20VDC ~ 28VDC
Alarm Current ≤35mA
SPECIFICATIONS

Flashing Frequency 1.4 x (1± 20%) Hz


Ingress Protection Rating IP21C
Temperature -10⁰C ~ + 50⁰C
Humidity ≤95%, non-condensing
Dimensions (LxWxH): 152mm x 91mm x 49.5mm
Weight About 210g
ALARM DEVICES
F IRE A LA R M BE LL
EN54, LPCB Approved

Bristol Fire Alarm Bells have low power consumption and long
operating life.

FEATURES

 Electricity insulating base

 Can accept 2.5mm terminal cables

 Fitted with 2 series diodes for fault monitoring

EN54 AE 50203154 0001


506e-(cl-2)

MODEL BF-AB-0418
Voltage 24VDC
Current 25mA
Sound Output 93dB @ 1m
SPECIFICATIONS

Movement Motor, Pinion and Striker


Movement Feature DC Motor, Acetral Gear Wheel,
Steel Striker
Material Steel Plate
Base Plate Molded Black Polycarbonate
Dimensions Ø6‖ (152mm) x 58mm (H)
Weight ≈850g
II. CD Certificates
• -
;._ . , , , , ,

Ill <.· .
i
~~~~~~~~~~~
K36 =~-' ill ~.)
2018 • • . -:11 ~
-~J---

19 - 19 :~l~I~~

~.:i · t?i.Jll tUW.U <a.oL::.tt O.Jl.:i)'I - -• -• -- -


United Arab Em irates
88869 529724 . , . t .-: ....
ea~~->: ___ ~..)>-_ _.=-_
.:J\ ~\

- - - - -- - - - -
Ministry of I nterior - _ft......:31 u~ ~I ~ .1ll:.. ~_>ill ~\...a ~I
DCD General Directorate
~->---11 u l.,.>--l=i

12282 :'-;-1.~ 04-3414748 04-3472900 Uri~\ ~f--..-.9..;


Tel .: 009714 261 1111 -- · -- - - -- -
Fax : 009714 26 12449 L....s~1w1.J 1¥

P.O. Box 11377 Dubai


United Arab Emirates
ameed@c~r~dex.com ~.J_jiS.l'Jl J.J~I/ c9yJI

f2018/11_
/2_6_~ f2012/04/12 t~...J~ ~L___:i
k 1t
t;_;l. j 31 o~I o~'il.J~IJLJI JJ£:.
Emergency • ~, .•... ~::t\J$ 3 LJ:!' ll ~~I J~
U:! ~
0 0
-,.

997
www.dcd.gov. ae
'"

~~~~~~.:~~21~
_ 6__.I =~Y1' ~_)
.__K3
.__2_0_1s__.I =~Y1' ~

.;. ..... -::w., • ~·;:; -


(19 - 7) I =~'Y1' ~~
- ..
,.- <?~·t-'!l
~-- -

l~~~~~~~~L
~---~---~-~
~~~~~~~~-'j,~~
Special Svstem Water Control Valves. Deluge Type
10378 VLFI.
2018/10/12 UL-USA VICTAULIC Models: ·769,
EX5197
<,r.~ -~..i.t1 t~.JJS a..w1 ;.J1~~1 Sizes: 1-112, 2, Z-112, 76.1 mm, 3, 4, 6, 165.1 mm and 8 in,
Rated Pressure: 300 psi, ~
United Arab Emirates Installation: Vertical
Ministry of Interior
DCD General Directorate Special System Water Control Valves. Deluge Type .. '
...;

1. Models: 869E,
Sizes: 1-112, 2, 2-112, 3, 4, 6 and 8 in,
Tel.: 009714 2611111 Rated Pressure: 250 psi, ..· -
VLFI. Installation: Vertical and Horizontal.
Fax : 009714 2 61 2449 2018/10112 10378 UL-USA VICTAULIC 2. Models: 869Y, ~
EX5197
Sizes: 3, 4, 6, 8 and 10 in,
P.O. Box 11377 Dubai Rated Pressw:e: 365 psi, 1 ~.-
United Arab Emi r ates Installation: Vertical and Horizo ntal. li .•
3. Models: 869, I!
Sizes: 1-112, 2,2-112, 3, 4, 6, ~ and 10 in, :... ,_
Rated Pressure: 300 psi,
Installation: Verticaland Horizontal.
ts.) 'J't--....b._._.
tt
Emergency :~

997
www.dcd.gov.ae
~

~f\4,~~~~~~~~~~
...
K36 I =~yi1 ~..)
201s I =~yi1 4-i.u.
I (19 - I
12) :~1yi1 .)~

Sprinklers. Automatic and Open


4..,_..,_;-
· __._ _ _,,..;.1~1 o.Jlj.9
B. Unrioht and PcndentSr.:1nd:ird Spr.:tv Sprinklers:
er.~ -~..Ill t.lll...1.1! :a..ow1 ;;.J1~~1 15. Model: V2708, V2706, vz.404, V3406,
Quick Response Type & Pendent Type ,
16. Model: V2704, V2756, V2702, V2402, V-.>402,
United Arab Emirat es Quick Response Type & Upright Type,
17. Model: V2707, V2403, V3405,
Mini st ry of Interi or Sbndard Response Type & Pendent Type ,
18. Model: V2703, V2755, V3401, V2701, V240l,
DCD General Directorate Sbnd.ard Rcspoasc Type & Upright Type,
19. Model: V2706,
Quick Response Type & Recessed Pendent Type ,
20. Model: V270S,
VNIV. Sbadard Respoasc T:ype & Recessed Pend cat Type,
2018/10/12 10378 UL - USA VICTAULIC
EX5170 C. Sbndud Sidew:>ll Spr:iv Sprinklers:
Te l.: 009714 26111 11 2L Model: V2710, V3410,
Quick Responsc Type & HSW and Rec. BSW Type,
22.. Model: V2709, V3409,
Fax: 0097 14 2612449 Sbadard Rcspoasc Type & HSW aad Rec. HSW Type,
D. Flush. Recessed znd Concealed Sprinklers:
P.O . Box 11377 Dubai 23. Model: V3S02, Y-.>808,
Quick Response Type & Cone. Pendent Type ,
United Arab Emirates 24. Model: V380l, V-.>807,
St:mdard Response Type & Cone. Pendent Type,
2S. Model: V2904, --
Qaick Respoasc Type & Flush Type ,
E. Conventional {Old Stvle) Sprinkler<:
t)_; t_, t, t r 26. Model: V27U, V2754,
Qaick Rcspoasc Type,
27. Model: V2725, V27S3,
Emergency St:mdard Response Type,

997 :~

www. dcd . gov.ae


III. Approval Certificate
2/16/2015 VLFT.EX5197 ­ Special System Water Control Valves, Deluge Type

VLFT.EX5197
Special System Water Control Valves, Deluge Type

Page Bottom

Special System Water Control Valves, Deluge Type

See General Information for Special System Water Control Valves, Deluge Type

VICTAULIC CO EX5197
4901 KESSLERSVILLE RD
EASTON, PA 18040­6714 USA

Model 769, 1­1/2, 2, 2­1/2, 76.1 mm, 3, 4, 6, 165.1 mm and 8 in. sizes are rated 300 psig for vertical installation only. For operation by dry
pilot, wet pilot, electric or manual activation. For operation by wet pilot sprinklers, the height of the pilot line above the valve is limited as
shown in the manufacturer's installation instructions.

Model 769, 1­1/2, 2, 2­1/2, 76.1 mm 3, 4, 6, 165.1 mm and 8 in. sizes are rated 300 psig when provided with the FireLock NXT preaction
system, Non­Interlock Preaction w/ pneumatic release , Non­Interlocked Preaction w/ pneumatic/electric release, Single­Interlock Preaction w/
pneumatic release, Single­Interlock Preaction w/ electric release, Double­Interlock w/electric/electric­pneumatic release, installed in accordance
with the manufacturer's installation instructions. For accessories used with these valves, see "Accessories for Special Systems". For vertical
installation only.

Model 769, 1­1/2, 2, 2­1/2, 76.1 mm, 3, 4, 6, 165.1 mm and 8 in. sizes are rated 300 psig when provided with the FireLock NXT preaction
system with Series 767 Electric/Pneumatic Actuator, Double­Interlock w/ electric/pneumatic release, installed in accordance with the
manufacturer's installation instructions. For accessories used with these valves, see "Accessories for Special Systems". For vertical installation
only.

Model 769, 1­1/2, 2, 2­1/2, 76.1 mm, 3, 4, 6, 165.1 mm and 8 in. sizes are rated 300 psig when provided with the FireLock NXT preaction
system with Series 798 Double Pneumatic Actuator, Double­Interlock w/ pneumatic/pneumatic release, installed in accordance with the
manufacturer's installation instructions. For accessories used with these valves, see "Accessories for Special Systems". For vertical installation
only.

Authorities having jurisdiction to be consulted before installation.

Last Updated on 2013­01­03

Questions? Print this page Terms of Use Page Top

© 2015 UL LLC

When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2015 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VLFT.EX5197&ccnshorttitle=Special+System+Water+Control+Valves,+… 1/1
Preaction Sprinkler Systems
Preaction sprinkler systems are equipped with automatic sprinklers and are used where it is important to prevent the accidental
discharge of water. These systems may also be used where an alarm is desired in advance of sprinkler operation or where it is
desired to minimize the water delivery delay inherent in a standard dry-pipe system. For this reason, the following factors shall be
carefully assessed: detector spacing and sensitivity, sprinkler piping arrangement and ceiling construction.
Supervisory pressure is maintained in the sprinkler piping of a preaction sprinkler system. A trouble alarm sounds if the
supervisory pressure is not maintained; however, such a condition will not cause the automatic water control valve to operate.
Generally, a single check valve is installed downstream of the automatic water control valve to contain the supervisory pressure.
Except for the addition of a single check valve and the use of automatic sprinklers, components of preaction sprinkler systems are
identical or similar to those of deluge sprinkler systems.
The water supply is held back by a water control valve which is operated manually or automatically by the actuation of a fire detection
system. The fire detection system is required to be one of the following types: hydraulic rate-of-rise, pneumatic rate-of-rise or electric.
Compatible FM Approved Release Control Panels for use with electric release preaction sprinkler system(s) are listed under
RELEASE CONTROL PANEL COMPATIBILITY.

Electrically operated preaction sprinkler systems are FM Approved on a component basis. Only the major, compatible
components noted in the sprinkler system listing shall be used in designing an FM Approved system. FM Global installation
acceptance may stipulate that only heat-actuated fire detection devices be used. Acceptance criteria by other jurisdictional authorities
may vary.
Preaction sprinkler systems are FM Approved as complete systems. Only the listed components for a specific manufacturer shall be
used in an FM Approved system.

Series 758, 769


Series 758-LPA FireLock Automatic Water Control Valve, electric release, available in sizes 1 1⁄2, 2, 2 1⁄2, 3, 4, 6, and 8 in. NPS,
grooved inlet and grooved outlet, and flanged inlet and grooved outlet in sizes 4, 6, and 8 in. NPS, vertical or horizontal orientation;
sizes 76.1 and 165.1 mm NPS, grooved inlet and grooved outlet, vertical or horizontal orientation. The 758-LPA includes the Series
776 pneumatic actuator for low pressure, nominally 10 psi, supervised system pressure. Series 749 Auto Drain (pressure operated
relief valve); the Series 755 manual pull station; the Series 748 Ball Check; the Series 729 Ball Drip; the optional Series 757 or
Series 757-P air maintenance devices for a dry pilot sprinkler line. Rated working pressure is 300 psi (2069 kPa) except: for electric
activation it is 175 psi (1207 kPa) with the ASCO Model No. 8210G207 solenoid valve; 300 psi (2069 kPa) with the Victaulic Series
753-E solenoid valve, except the 8 in. valves, which have a rated working pressure of 225 psi (1551 kPa). The Series 75-D Water
Column Drain Kit is an option, which automatically drains water from the sprinkler system and subsequently reseals to maintain air
pressure in the system piping.
Series 769 Firelock NXT Single-Interlocked Valve with Electric Release. Sizes 1 1⁄2, 2, 2 1⁄2, 3, 4, 6 and 8 in. and 76.1 and 165.1
mm NPS. The system rated working pressure is 300 psi (2070 kPa). Grooved inlet and grooved outlet, installed vertically. Major trim
components consist of the following:
• Series 753-E normally closed solenoid valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 748 anti-flood Ball Check Valve
• Series 729 alarm line Drip Check Valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly.
Optional system components include:
• System Sensor EPS10-2 alarm line pressure switch
• System Sensor EPS40-2 system air pressure supervisory switch
• Series 755 Manual Pull Station
• Series 760 Water Motor Alarm
• Series 705W water supply butterfly shutoff valve.

Series 769 Firelock NXT Single-Interlocked Preaction System with Electric AutoConvert Dry Trim. Sizes 1-1⁄2, 2, 2-1⁄2, 3, 4, 6 and
8 inch and 76.1 and 165.1 mm NPS. The system rated working pressure is 300 psi (2070 kPa). Grooved inlet and grooved outlet,
installed vertically. The AutoConvert Trim Assembly consists of a latching solenoid valve and a Series 776 Low-Pressure Actuator.
The AutoConvert Trim Assembly monitors incoming power to the Fire Alarm Control Panel (FACP) and allows for continuous fire
protection in the event of an AC power loss, without draining battery backup. In the event of AC power loss, the latching solenoid
module receives a quick electrical pulse from the FACP to latch open. The latching solenoid module stays in the open position
without requiring additional current draw. This allows the FACP to continuously monitor the system and provide alarms in the event
of a fire condition for the normal life of the battery backup or until power is restored. In the open position, air is allowed to flow
through the latching solenoid module to the Series 776 Low Pressure Actuator, which operates as a dry actuator and converts the
system to a non-interlocked condition. An air loss in the system piping or an electrical release from the FACP would allow the
Series 769 automatic water control valve to open and fill the sprinkler system piping with water. The system continues to act as a
dry pipe valve until AC power is restored. When AC power is restored, the latching solenoid module receives another quick
electrical pulse from the FACP to latch closed. The preaction system then returns to its standard release method. Manual resetting
of the system is not required.

Major trim components consist of the following:

• Series 753-E normally closed solenoid valve

© 2007-2015 FM Approvals. All rights reserved. 1 of 2


• Series 753-E normally closed solenoid valve
• Series 749 Auto Drain pressure operated piston charge line water relief valve
• Series 748 anti-flood Ball Check Valve
• Series 729 alarm line Drip Check Valve
• Water Supply Main Drain/Flow Test Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• System Main Drain Valve, size 2 in. with three 1⁄2 in. NPT outlets for gage and drain connections
• Series 752 piston charge line Strainer/Check Valve/Restrictor assembly
• IMI Norgren Buschjost GmbH & Co. KG Model 8241250.9100 latching solenoid valve

Optional system components include:

• System Sensor EPS10-2 alarm line pressure switch


• System Sensor EPS40-2 system air pressure supervisory switch
• Series 755 Manual Pull Station
• Series 760 Water Motor Alarm
• Series 705W water supply butterfly shutoff valve.
All preaction sprinkler systems discussed above offer the Series 75-B supplemental alarm valve as an option recommended for
systems where continuous flow to the alarm port, which supplies flow to the water motor alarm, must be positively maintained.
The 1-1⁄2, 2, 2-1⁄2, 3, 4 and 6 inch and 76.1 and 165.1 mm NPS Preaction Sprinkler Systems are available factory assembled in the
Victaulic Series 745 Fire-Pac enclosure, a cabinet containing all system components and accessories, and requires only the
connection to the water supply inlet, water outlet (to system), main drain, the alarm and detection connections, and the electrical
power supply. The Series 745 Fire-Pacs may be connected to to a System Sensor PDRP-2001 fire alarm control panel.

Company Name: Victaulic Company


Company Address: 4901 Kesslersville Rd, Easton, Pennsylvania 18040, USA
Company Website: http://www.victaulic.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved

© 2007-2015 FM Approvals. All rights reserved. 2 of 2


9/6/2015 VNIV7.EX5170 ­ Sprinklers, Automatic and Open Certified for Canada

VNIV7.EX5170
Sprinklers, Automatic and Open Certified for Canada

Page Bottom

Sprinklers, Automatic and Open Certified for Canada

See General Information for Sprinklers, Automatic and Open Certified for Canada

VICTAULIC CO EX5170
4901 KESSLERSVILLE RD
EASTON, PA 18040­6714 USA

Sprinkler Identification Numbers (SIN) V24XX, V27XX, V2904 and V36XX Series Glass Bulb Type. Painted or plated sprinklers are identified by
an unpainted or unplated compression screw.

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS

NOMINAL 8.1 k­FACTOR

Response  Nom  System Working 


SIN Type Type k­Factor Pressure, kPa Temp Rating, °C

V2708 QR Pendent 8.1 1725 57, 68, 79, 93, 141

V2708 QR Recessed Pendent 8.1 1725 57, 68, 79, 93

V2704 QR Upright 8.1 1725 57, 68, 79, 93, 141

V2756 QR Upright 8.1 1725 57, 68, 79, 93, 141

V2707 SR Pendent 8.1 1725 57, 68, 79, 93, 141, 182

V2707 SR Recessed Pendent 8.1 1725 57, 68, 79, 93, 141

V2703 SR Upright 8.1 1725 57, 68, 79, 93, 141, 182

V2755 SR Upright 8.1 1725 57, 68, 79, 93, 141, 182

NOMINAL 2 TO 6 k­FACTOR

Response  Nom  System Working 


SIN Type Type k­Factor Pressure, kPa Temp Rating, °C

*V2401 SR Upright 4.2 1200 57, 68, 79, 93, 141, 182

*V2403 SR Pendent 4.2 1200 57, 68, 79, 93, 141, 182

*V2402 QR Upright 4.2 1200 57, 68, 79, 93, 141, 182

*V2404 QR Pendent 4.2 1200 57, 68, 79, 93, 141, 182

V2701 SR Upright 4.0 1200 57, 68, 79, 93, 141, 182

V2705 SR Recessed/Pendent 4.0 1200 57, 68, 79, 93, 141, 182

V2702 SR Upright 4.0 1200 57, 68, 79, 93, 141

V2706 QR Pendent 4.0 1200 57, 68, 79, 93, 141

V2706 QR Recessed Pendent 4.0 1200 57, 68, 79, 93

* 10mm NPT will be utilized.

NOMINAL 11.5 K­FACTOR

Response Inlet System Working 


SIN Type Type Thread NPT Pressure, kPa Temp Rating, °C

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VNIV7.EX5170&ccnshorttitle=Sprinklers,+Automatic+and+Open+Certifi… 1/7
Certificate of Compliance
This certificate is issued for the following equipment:

Model K Type Resp. Element NPT Finishes Temperature Ratings


(in.) °F (°C)
V2701 2.8 Upright SR 5 mm* 1/2 Nickel 135, 155, 175, 200 (57, 68,
Plated 79, 93)
V2702 2.8 Upright QR 3 mm* 1/2 Nickel 135, 155, 175, 200, 286 (57,
Plated 68, 79, 93, 141)
V2703 5.6 Upright SR 5 mm* 1/2 Nickel 135, 155, 175, 200, 286, 360
Plated (57, 68, 79, 93, 141, 182)
V2704 5.6 Upright QR 3 mm* 1/2 Nickel 135, 155, 175, 200, 286 (57,
Plated 68, 79, 93, 141)
*Job and Norbulb
Prepared for: Victaulic Company, 4901 Kesslersville Road, Easton, PA 18040

Manufacturing Location: Victaulic Company, Leland Facility, 2010 Enterprise Drive NE,
Leland, NC 28451

FM Approvals Class: 2042, 2002, 2016


FM Approval Standard: Class Series 2000 (March 2006)

Approval Identification: 3045488 Approval Granted: October 22, 2013

To verify the availability of the Approved product, please refer to www.approvalguide.com

Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.

Richard B. Dunne
Group Manager – Fire Protection
FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062
USA
IV. Method Of Statement
INSTALLER SAFETY INSTRUCTIONS

WARNING

• A
 nexperienced,trainedinstallermustinstallthisproductinaccordancewithall instructions.These
instructionscontainimportantinformation.

• Depressurizeanddrainthepipingsystembeforeattemptingtoinstall,remove,adjust,ormaintainany
Victaulicpipingproducts.

Failuretofollowtheseinstructionscancauseproductfailure,resultinginseriouspersonalinjuryand/or
propertydamage.

GENERAL MAINTENANCEANDTESTING
1. Readandunderstandallinstructionsandrefertothetrim 1. Notifytheauthorityhavingjurisdiction. Always notify the author-
diagramsbeforeproceedingwiththeinstallation,maintenance, ity having jurisdiction before performing any maintenance that
andtestingofthisVictaulicSeries769FireLockNXTPreaction eliminates the fire protection provided by the system.
Valve.
2. FollowNFPArequirementsforsystemtestingandinspection
2. Inspecttheshipment. Make sure all components are included in schedules. The building owner or their representative is responsi-
the shipment and that all necessary tools are available for installa- ble for inspecting the system in accordance with current NFPA-25
tion. requirements or in accordance with the requirements of the local
3. Useonlyrecommendedaccessories. Accessories and equipment authority having jurisdiction (whichever is more stringent).
that are not approved for use with this valve may cause improper 3. Depressurizeanddrainthesystemcompletelybeforeperforming
system operation. anymaintenance. Water under pressure can cause the cover plate
4. Wearsafetyglasses,hardhat,footprotection,andhearing to blow off during removal if the system is not depressurized and
protection. Wear hearing protection if you are exposed to long drained completely.
periods of noisy job-site operations. 4. Protectthevalvefromfreezingtemperatures,foreignmatter,
5. Preventbackinjury. Larger and pre-trimmed valves are heavy and andcorrosiveatmospheres. Any condition that might degrade the
require more than one person or mechanical lifting equipment to system or affect system performance must be avoided.
position and install the assembly. Always practice proper lifting
techniques.
6. Avoidusingelectricallypoweredtoolsindangerousenviron-
ments. When using electrically powered tools for installation, make
sure the area is moisture-free. Keep the work area well lit, and
allow enough space to accommodate proper installation of the
valve, trim, and accessories.
7. Watchforpinchpoints. Do not place fingers under the valve
body where they could be pinched by the weight of the valve. Use
caution around spring-loaded components (i.e. clapper assembly).
8. Keepworkareasclean. Cluttered areas, benches, and slippery
floors can create hazardous working conditions.
9. PROTECTTHESYSTEMFROMFREEZINGCONDITIONS.THE
VALVEANDSUPPLYPIPINGMUSTBEPROTECTEDFROM
FREEZINGTEMPERATURESANDMECHANICALDAMAGE.
10. IFTHEINLETWATERSUPPLYISINTERRUPTEDFORANY
REASON,ANDSYSTEMSUPPLYPRESSURETOTHEVALVE
DECREASES,MAKESURETHEDIAPHRAGMCHARGELINEIS
FULLYPRESSURIZEDBEFOREPLACINGTHESYSTEMBACK
INSERVICE.
...Method Of Statement
IMPORTANTINSTALLATIONINFORMATION
1. For proper operation and approval, the Series 769 FireLock NXT
CAUTION
Preaction Valve must be installed in accordance with the specific • Makesurenoforeignmaterialgetsintothevalvebody,pipe
trim diagrams included with the shipment. NOTE: Victaulic pro- nipples,orvalveopenings.
vides specific trim diagrams for installations involving a Series 746-
• IfusinganymaterialotherthanTeflontape,useextracaution
LPA Dry Accelerator.
sothatnomaterialgetsintothetrim.
2. Before installing the Series 769 FireLock NXT Preaction Valve,
Failuretofollowtheseinstructionscouldcauseimpropervalve
flush the water supply piping thoroughly to remove all foreign
operation,resultinginpersonalinjuryand/orpropertydamage.
material.
3. Series 769 FireLock NXT Preaction Valves MUST NOT be located 4. Install the valve, trim, and accessories per the trim drawing.
in an area where the valve can be exposed to freezing tempera-
tures. In addition, the Series 769 FireLock NXT Preaction Valve
MUST NOT be located in an area where physical damage may
occur.
4. It is the system designer’s responsibility to confirm material com-
patibility of the Series 769 FireLock NXT Preaction Valve, trim, and
associated accessories when a corrosive environment or contami-
nated water is present.
5. SERIES769FIRELOCKNXTPREACTIONVALVESMUSTBE
INSTALLEDONLYINTHEVERTICALPOSITIONWITHTHE
ARROWONTHEBODYPOINTINGUPWARD.
6. Air or nitrogen supply to the dry piping system must be clean, dry,
and oil-free.
7. Air supplies must be regulated, restricted, and continuous.
8. When an uninterruptible water flow alarm is required, Victaulic
recommends the use of a low-pressure alarm installed on the
TO ACTUATOR
diaphragm charge line downstream of the strainer/check restric- TRIM
tor. Another option is to install a Series 75B Supplemental Alarm
Device. 5. FORVALVESINSTALLEDWITHASERIES746-LPADRY
ACCELERATOR:Make sure the Series 746-LPA Dry Accelerator is
9. Per NFPA 13 requirements, piping must be pitched so that
installed in accordance with the trim drawing provided. The end
systems can drain properly. For areas that are subject to high
with the vent seal “button” must be installed facing down (toward
levels of condensation, or where piping is not properly pitched, an
the trim).
optional Series 75D Water Column Device kit is available to assist
in automatically draining water out of the riser. 6. Supply pressure to the diaphragm charge line by providing an
uninterrupted source of water from upstream of the main control
VALVE/TRIMINSTALLATION valve.
1. Make sure the trim drawing matches the system’s requirements.

CAUTION

• Makesurethefoamspacerisremovedfrom
insidethevalvebodybeforeattemptingto
installthevalve.
Failuretofollowthisinstructioncouldcause
impropervalveoperation,resultinginpersonal
injuryand/orpropertydamage.

2. Remove all plastic caps and foam spacers from the valve.
3. Apply a small amount of pipe joint compound or Teflon* tape to
the external threads of all threaded pipe connections. DO NOT get
any tape, compound, or other foreign material into the valve body,
pipe nipples, or valve openings.

* Teflon is a registered trademark of the DuPont Company


V. Company Profile
Firefighting Solutions Provider
www.bristol-fire.com

BRISTOL Fire Engineering, part of the Concorde – Corodex Group (CCG), was
established in 1974 as a leading manufacturer of high quality Fire Fighting
Systems and Equipments. BRISTOL was one of the first fire fighting companies
to receive an ISO 9001 certification in the Middle East, placing a great emphasis
on achieving international and Third party approvals in all our product range
such as (Kite Mark, LPBC, UL listing and FM Approval). In addition, all our
products carry Civil Defense approvals in the market we operate in.

We are continuously working on adding new technologies to our product range


so we can meet the ever changing customer needs.

Our range of experience expands to all category projects from residential,


commercial, healthcare, Industrial and educational.

Integrity and Quality are ingrained in BRISTOL name. For over three decades,
Bristol related companies have consistently performed complex projects on
time and within the budget while never compromising quality.

BRISTOL’s complete in house staff consists of fire fighting specialist engineers,


project executive staff, professional services & maintenance teams and it
ensures that end users receive a total solution rather than merely a product.

Product range

• Fire Alarm & Detection System


• Fire Suppression systems (Novec 1230, FM200,CO2,Water Mist, Kitchen
Hood & Inert gas)
• FOAM System /FOAM Concentrate
• Fire Sprinkler systems
• Fire Pumps
• Fire and Rescue trucks
• Hydrant valves /Nozzles and accessories
• Wet / Dry riser components (Fire Hose reel ,Landing Valves ,PRV etc.. )
• Fire Extinguishers ( Wet Chemical, Dry Chemical Powder
/CO2/Foam/Water Harleton)
• Fire Doors
Concorde-Corodex Group

Group Profile

The Concorde- Corodex Group, a part of M.H Al Mana Group of Companies, is


one of the Middle East region’s pioneering providers of fire protection, water
purification, wastewater treatment and environmental services. Established in
1974, the company has evolved to become the largest group to offer a diverse
portfolio of products and services like a complete kit of water treatment services,
fire fighting equipment and marine & industrial chemical cleaning to name a few.

Looking to meet the continuously changing demands and requirements from


customers across various industry verticals, the Concorde – Corodex Group has
diversified itself into 17 individual companies--each excelling in their respective
field of expertise and operating as an independent entity. Collectively, all
subsidiary companies continue to consolidate the Concorde – Corodex Group
market leadership in the Middle East region, with assets worth over USD 90
million.

CCG’s core values have been the cornerstone of what define us and what we
stand for. They are excellence, innovation, environment stewardship, and health
& safety.

All business units of Concorde-Corodex Group are registered companies with


Quality, Environment, Occupational Health and Safety Management Systems
(QHSEMS) in compliant to international standards such as ISO 9001:2008, ISO
14001:2004 and OHSAS 18001:2007.

Our Team
From relatively small team, Concorde-Corodex Group has vastly grown in size.
Presently, we have 920 total employees, amongst which are 322 Engineers,
Specialists, Chemists and other Technical Professionals.
Mission Statement

We, the Concorde-Corodex Group, are committed to provide quality products


and services.

In pursuit of this commitment in serving the consumers, we shall adopt sound


trade and industrial policies as well as regulations provided by the government.

We shall provide timely and world class services that answer our clients'
business needs for Design, Manufacturing, Servicing and Trading.

In the same way we relate with our clients, so shall we relate with each other as
we promote an internal environment that foster professional growth.

In the attainment of this mission and for love of this country, we bind ourselves to
be the highest standards of competence, integrity and dedication.

Vision Statement
We are committed to deliver world class products in various business activities in
the fields of Designing, Manufacturing, Servicing and Trading.

We shall actively provide innovative and effective services to the consumers, with
customers' delight as our measure of success.

As we move toward this direction, we shall endeavor to become leader in


providing total quality service in the field.

We are group of highly capable, skilled and dedicated people with creative and
noble ideas committed to build an organization we can be proud of.

We shall triumph in a work environment that upholds the highest distinction in


excellence professionalism, integrity and harmony.

In essence, we shall always strive to be a provider of true service worthy of


consumer’s trust as we meet the challenges of the ever changing consumer
needs.

International Operating offices:

• U.A.E. (Head corporate office and manufacturing facility)


• Winnipeg, Canada
• London, UK
• Khartoum, Sudan
• Doha, Qatar
• Muscat, Oman
• Jeddah, K.S.A
• Amman, Jordan

UAE Operating Offices:

• Abu Dhabi
• ICAD Mussafa
• Khalidiya
• Dubai
• Al Quoz
• Al Awir
• Sheikh Zayed
• Sharjah
• Al Ain
• Ras Al Khayma

Core Activities
ƒ Water Purification / Treatment Systems
ƒ Sewage Treatment Plants
ƒ Vacuum Sewer Systems
ƒ Operation & Maintenance
ƒ Electromechanical Services
ƒ Marine and Industrial Chemical Cleaning
ƒ Fire Fighting Equipments and Systems
ƒ Fire Protection and Safety
ƒ Machine Tools and Engineering Equipment
ƒ Scientific & Laboratory Equipment
ƒ Oilfield Equipment
ƒ Industrial Gases
ƒ Welding Equipment
ƒ Vehicle Manufacturing Division

Quality Policy

Concorde-Corodex Group is a professional company devoted to build a strong


customer relation base to deliver a wide range of quality products. With a history
of service excellence that has evolved through the decades, our organization
leads a Group of Companies/ Business Operating Units, incorporating a variety
of business activities in the fields of Designing, Manufacturing, Servicing and
Trading.
We at CCG have committed ourselves to provide and exceed our customers’
expectations and contractual requirements through:

Employee: We recognize our employees as the most valuable asset of the


organization. On the basis of merit hiring the right incumbent for the right
position, we value their skills and knowledge and we lead, motivate and empower
them through a working environment that advances our business objectives.

Products/Services: Our objective is to provide products or services that meets


or exceeds customer’s satisfaction. We deliver to customer the right product or
service at the right time at the right quantity, quality and price.

Processes: We have implemented ISO 9001:2008 to define and control our


processes and ensure that they are conforming with the set policies. Our aim is
to reach to the most efficient way of carrying out the tasks to enhance our
business relations with customers.

Customers: Customer Satisfaction is recognized as the number one priority in


our organization as our success is directly linked to the satisfaction of the
customer towards his final output of the quality of our product and services.

CCG is an enterprise that retains a tradition of integrity and is on the path to


expand and continually improve in line with the market trends.

Environmental Policy
We, at Concorde-Corodex Group, are committed to provide quality products and
services in a manner that ensures a safe and healthy workplace for our
employees and minimizes our potential impact on the environment. We will
operate in compliance with ISO 14001: 2004 and all relevant environmental
legislations and will strive to use pollution prevention and environmental best
practices in all we do.
We are committed to continually improving our environmental performance
using the following measures:

1. The control of emissions and discharges consequential upon our


Operations to ensure these has minimal detrimental effect upon the
environment.
2. The control of odour, noise and litter to eliminate or minimize the
effects on surrounding areas.
3. To optimize raw materials usage and conversion efficiencies including
the rework and/or recycling of scrap.
4. To seek to reduce the consumption of materials, fuel & energy used in our
operations.
5. Compliance with environmental legislation and regulations.
6. To take into account the concerns of interested parties such
as regulators, shareholders, suppliers, employees and the public.
7. To communicate this policy to all members of the organization and
ensure all are trained in their respective environmental responsibilities.
8. To make this Environmental Policy available to customers and the public
on demand.
The introduction and implementation of this Policy is a commitment of
CCG Management and a shared responsibility of all our employees.

This policy will be reviewed annually as part of the company’s overall


Environmental Management review system.

Occupational Health and Safety (OHS) Policy


Concorde-Corodex Group is committed to prevent injury and ill health by
providing safe and healthy working conditions for all its employees and to ensure
that work done does not affect adversely the health and safety of others.

CCG strives for continual improvement in Occupational Health and Safety


(OH&S) management and performance through consultation and participation of
employees.

To achieve this, the following work policy is hereby issued:

ƒ Provide adequate control of the Health and Safety risks arising from our
work activities.
ƒ Consult with our workers and volunteers on matters affecting their Health
and Safety, including work related stress.
ƒ Provide and maintain safe plant and equipment.
ƒ Ensure safe handling and use of substances.
ƒ Provide training, information, instruction and supervision for workers to
ensure that they are aware of their individual OH&S obligations.

All works will be carried out in accordance with the requirements of OHSAS
18001:2007 and other relevant Health & Safety laws, Acts, Regulations, Codes
of Practice and Guidance Notes and ensure compliance to applicable laws where
the company subscribes to.

Management and supervisory staff have the responsibility for implementing this
policy throughout the company and must ensure that health and safety are
always given priority in planning day-to-day supervision of work.

This policy will be reviewed periodically and will be available to interested parties.
Group Members
• Concorde Trading Co, Abu Dhabi
For everything water related
• Concorde Agencies Est, Abu Dhabi
Fire protection and automation system
• Concorde Technical Est, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• Corodex Trading Co, Dubai
For everything water related
• Corodex Agencies Est, Dubai
Fire protection and automation system
• Corodex Industries, Dubai
Water Purification and Wastewater Treatment Specialists
• Corodex Marine, Dubai
Step ahead in chemical cleaning
• Corodex Electromechanic, Dubai
Bringing Engineering Solutions to Life Vacuum Sewerage System Water
and Wastewater
Treatment Systems
• Bristol Fire Engineering, Dubai
Everything Fire Related
• Al Jaddaf Electromechanical, Abu Dhabi