ISOLATED CONVERTER OF DC CURRENT OR VOLTAGE

- PX24 loop powered 4- 20mA


- PXN auxiliary power supply

- measures and separates input DC current and voltage


- allows bipolar input and output signal
- input, output and supply circuits are isolated (4000VRMS tested)
- designed for DIN 35 rail mounting
- conversion accuracy < 0.1%
- time constant typ.1ms, for order up to 300ms

The module has been designed to convert DC current (±50uA…±10A) or voltage


(±10mV…±1000V) from shunt resistors and sensors into a series of unified ranges (0..10V, 0..20mA,
4..20mA, 0..± 20mA, 0..±10V ). The converter output-to-input response is linear. The converter is
particularly well-suited for heavy electromagnetic interference environment operation and features input-to-
output isolation.

Electrical specifications: Converter dimensions:

- operating temperature range: -25...+ 70°C


- storage temperature:: -40...+ 80°C
- supply voltage: PX24: 12..30V DC
PXN: 19-300VDC 90-250VAC
for order: 20 – 60VAC
- consumption: max. 1,5VA
- input signal: voltage from ±10mV to ±1000V
current from ±50uA to ±10A
- output signal: PX24: 4..20mA
PXN: 0..20mA, 4..20mA, 0..10V
0..±20mA, 0..±10V
- output voltage amplitude: min. 15V
- voltage output load: max. 10mA
- input resistance of voltage input: typ. 100kohm / V, max.13Mohm
- voltage drop of current input:: < 0,54V for 20mA, 5mV for 10A
- output current limit: typ. 30mA (electronic fuse)
- measurement error: < 0,1%
- linearity error: < 0,1%
- temperature induced error: < 50ppm /°C
- time constant: 1ms , for order up to 300ms Terminal designation:
- enclosure (casing / terminal board): IP40 / IP20 1,3…input signal (3 is +)
- weight: 90g 4,5..output signal ( 5 is + )
- working environment: pollution level 2 6,7.. auxiliary power supply without polarity
- max.working voltage across isolation isolation level:
overvoltage category instalation basic reinforced
I up 1000V up 1000V
II up 1000V up 600V
III up 600V up 300V

Type tests: Application variants:


Standard type test: to ČSN EN 60770-1
EMC: to ČSN EN 61326-1
Safety: assessed acc. to ČSN EN 61010-1

Connections: The terminals accept wires with 2,5mm2. We


recommend using a cable with a minimal cross 0,5mm2. In the
interfering environments use shielded or twisted cable.

Ordering instructions:
Your order should include:
- module type
- quantity
- input and output signal
- time response ( if it is different from 1ms )
Likvidaci po ukončení životnosti provést odděleným sběrem.
Rawet s.r.o. je členem sdružení RETELA www.retela.cz

Rawet s.r.o. IČO: 47901411 tel.: 516 419995, 516 416942


Čapkova 22 DIČ: CZ47901411 fax: 516 416963
Blansko ČSOB Blansko E-mail: rawet@rawet.cz
678 01 č. ú. 106093786/0300 Internet: www.rawet.cz

Potrebbero piacerti anche