Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Instructor’s Signature:
Handout #2
Two-Way Slabs
By
You are not allowed to write anything in this handout, otherwise you will not be
allowed to carry it during the exam.
4 Ecb I b / l
f
4 Ecs I s / l
Because the lengths, l, of the beam and slab are equal, this quantity is simplified and expressed in
code as
Ecb I b
f
Ecs I s
Where Ecb and Ecs are the moduli of elasticity of the beam concrete and slab concrete respectively,
and Ib and Is are the moments of inertia of the uncracked beams and slabs (about centroidal axis).
If there is no beam αf =0
αf for the edge beams shall not be less than 0.8.
1. For fm 0.2, the minimum thicknesses are obtained as they were for slabs
without interior beams spanning between their supports.
2. For 0.2 fm 2.0, the thickness shall not be less than 120 mm or
fy
ln 0.8
h 1500
36 5 ( fm 0.2)
3. For fm 2.0, the thickness shall not be less than 90 mm or
fy
ln 0.8 ln and fy are in mm and
h 1500
MPa, respectively.
36 9
CE 470 (RC - II) : Dr. Nadeem A. Siddiqui November 27, 2014
Note
8
For panels with discontinuous edges, the Code requires that edge
beams be used, which have a minimum stiffness ratio αf = 0.8, or
else that the minimum slab thicknesses must be increased by 10%.
If the various rules for minimum thickness is followed but the
resulting slab be insufficient to provide the shear capacity required
for the particular column size, column capitals will probably be
required.
Beams running between the columns may be used for some slabs
where partitions or heavy equipment loads are placed near column
lines. A very common case of this type occurs where exterior beams
are used when the exterior walls are supported directly by the slab.
Another situation where beams may be used occurs where there is
concern about the magnitude of slab vibrations.
The direct-design method is easier to use than the equivalent-frame method, but can be
applied only to fairly regular multi panel slabs. The limitations, given in ACI/SBC code
include the following:
There must be a minimum of three continuous spans in each direction.
Thus, a nine panel structure (3 by 3) is the smallest that can be
considered. If there are fewer than three panels, the interior negative
moments from the direct-design method tend to be too small.
The panels should be rectangular, and the ratio of the longer span to the shorter span
within a panel should not be greater than 2.0
The successive span lengths in each direction should not differ by more than one-third
of the longer span.
This limit is imposed so that certain standard reinforcement cut off details can be
used.
Columns may be offset from the basic rectangular grid of the building by up to 0.1
times the span (i.e. 10%) parallel to the offset.
All loads must be due to gravity only and uniformly distributed over an entire panel.
The direct-design method cannot be used for unbraced, laterally loaded frames,
foundation mats, or prestressed slabs.
For a panel with beams between supports on all sides, the relative stiffness of the
beams in the two perpendicular directions given by (αf1l22/ αf2l12) shall not be less than
0.2 or greater than 5. l1 and l2 are spans in the two directions.
For the purpose of computing ln , the circular supports (circular columns or column
capitals of diameter d c ) are replaced by equivalent square columns having a side length c1 :
d c2 c12 c1 d c 0.886d c c1 0.886d c
4 4
Note: If the computed negative moments on two sides of an interior support are different, the
negative-moment section of the slab is designed for the larger of the two.
“Exterior edge unrestrained” refers to a slab whose exterior edge rests on, but is not attached to, for example, a
masonry wall.
Exterior edge full restrained” refers to a slab whose exterior edge is supported by, and is continuous with, a
concrete wall with a flexural stiffness as large or larger than that of the slab.
For economic reasons, designers prefer to avoid the use of shear reinforcement,
and thus, Vs is usually zero.
The tributary areas for one - way shear in a slab are illustrated in figure for columns 4 and 5.
The shear strength on the critical section is computed as was done for beams by using the
following expression.
f '
Vc c
bd
6
Punching shear strength : Smallest of the following expressions First equation governs in
f ' most cases. For normal
Vc 2 c
bd size column where β
6 0
exceeds 2.0, second
2 f c equation governs, and for
'
Vc 1 b0 d (not applicable unless 2)
6 very large columns, last
equation governs.
sd f c'
Vc 2 b0 d
0 b
12
ratio of the long side of the column to the short side of the column.
For non - rectangular columns, this is defined as shown in the figure.
l a
Vu1 qu bw d
2 2
f '
Beam shear strength : Vc c
bd
6
b0 2(a d ) 2(a' d )
α1 is the ratio of the stiffness of a beam section to the stiffness of a width of slab
bounded laterally by the center line of the adjacent panel, if any, on each side of the
beam and equals EcbIb/EcsIs.
Ecb I b
1
Ecs I s
For floor system without interior beams, α1l2/l1 is taken to be equal to zero, because α1 =0.
In this case, 75% of the negative moment is distributed to the column strip, and the
remaining 25% is divided equally between the two adjacent half-middle strips.
For floor systems without interior beams, 60% of the positive moment is
assigned to the column strip and the remaining 40% is divided equally
between the adjacent half-middle strips.
0.85 f c' b
a a
Nominal strength : M n T d M n As f y d As f y jd
2 2
Step 1 : Calculate trial value of As assuming jd 0.95d for slabs of normal proportions.
Mu
As
f y jd