Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
It is important to stop pulling current when a battery reaches its low voltage limit.
Continuing to draw current below the low current threshold damages the battery.
To illustrate battery testing using constant current mode, we will use an industrial Li-ion
18650 battery. Battery capacity (C) is measurable in mAh. The capacity is also necessary
to determine the charging and discharging current. The charging current is limited to 0.5 C
or 0.5 * 2500 mAh = 1250 mA. The charging process starts with a constant current (CC) of
1250 mA and needs to stop before the battery voltage reaches 4.2 V.
Discharging is similar a constant current is drawn until the 2.5 V cutoff is achieved. The
amount of current drawn can vary from 0 to 20 A, but high currents reduce the number
of times it charges and discharges — limiting the life of the battery. Also discharging the
battery below the cutoff voltage reduces the life of the battery. Run time is determined
using the discharge plots, see Figure 2.
A battery can support a 1 C discharge for an hour, or five hours at a (1 C)/(5 h) = 0.2 C
discharge rate. Li-ion batteries typically have slightly more capacity at a 0.2 C discharge
rate. Finally, temperature affects both battery capacity and discharge voltages.
Temperatures above 25 °C are ideal but in lower temperatures capacity and voltage
drop. A multimeter monitoring the voltage is used to ensure the battery is not
discharging below the 2.5 V cutoff.
+ +
_
Multimeter
Battery DC Electronic Load
_ _
N6791A/N6792A
A capacity test is the most common battery test as it directly affects a device’s run time.
Capacity tests are made using a variety of constant discharge rates or even a dynamic
current that simulates a device pulling current at different rates. Many devices save
energy by using very little power in an idle or sleep state but then pull large currents in
their active state.
To determine the run time of a device, a profile of how a battery responds to various
discharge rates is helpful. Figure 2 shows several constant discharge rates; 1.5 C, 1 C, .2 C.
18650 Discharge
4.5
4 500 mA
2500 mA
Voltage (V)
3.5 3750 mA
3
2.5
2
1 136 271 361 451 586 721 856 991 1171 1306 1441 1576
Time (seconds)
Li-on batteries undergo excessive internal stress when the charge is above 4.0 V. Figure 2
shows the battery voltage drops quickly as the battery return to a relaxed state. The voltage
drop remains linear until 3.2 to 3.1 V. At lower voltages, the battery voltage drops very
quickly. The battery capacity is calculated as the current discharges; 500 mA multiplied by
the run time, 4.5 h or 2250 mAh. Measured battery capacities are lower than the specified
capacity as they are measurable over a smaller operating range of 4.1 to 2.6 V.
Max current
50% Current
Time
V
Max voltage
Transients
Time
Figure 3. Maximum current drawing from a power supply suddenly changes causing
transients in voltage
As an example, the Keysight E36312A specifies less than 50 µs to recover within the
15 mV settling band. This follows a load change from 50% to 100%, and from 100% to
50% of the full load.
Voltage
Settling band
Time
Figure 4. Transient response time displays as the time required for a power supply to
recover within the settling bands Measuring Response Time
Response time is challenging to measure with load resistors and switches. Often, power
resistors have some inductance that reacts with the transients from the power supply.
Using a DC electronic load avoids introducing additional distortion.
The two most common methods to setup the electronic load are in the resistant
mode or constant current mode. In resistance mode, a calculation is made to select
a resistance that draws current at 50%. The second resistance sinks the maximum
current. The current priority mode is straightforward as the desired currents are directly
input to the load.
As an example, the E36312A power supply with 6 V and 5 A is setup for the test.
The two currents required are 2.5 A (50%) and 5 A (max). An N6792A load module is
configured for current priority as shown in Table 2.
With the load configured for current priority — the next step is to create the transient.
The Keysight N6700 Series has several built-in waveforms that simplify setting up a
dynamic output by describing just a few points.
A stepped waveform generates a single transient as the current changes levels. The
pulse waveform causes two transients as the current rises and then falls. A pulse
waveform is setup for this test; see Figure 5.
Table 3 shows the SCPI programming commands along with the Keysight N6705C front
panel instructions. With the waveform defined, you can start it at any time by using the
arb run command, or with the run/stop key on the N6705C front panel.
The waveform is easily viewed and captured with an oscilloscope set to level trigger with
a single-shot acquisition. Once the arb runs, the transients are captured as shown in
Figure 6. The oscilloscope input is AC coupled, with bandwidth limiting and 50 mV/div.
The sweep is set to 20 µs/div with some delay to center the waveform.
Markers locate where the transient is within the 15 mV setting band to view the time the
waveform crosses. In both transients, the power supply recovery is much faster than its
specified 50 µs specification.
Configure the trigger — from the front panel of the N6705C select trigger on run/stop key
Enable the arb function to respond to
19 “CURR:MODE ARB,(@1)”
triggers
Table 3. Configuring the load module at channel 1 to pull dynamic current — the first seven
steps are identical to the steps in Tip 1
Current limit measurements are made to determine the degree to which a constant
voltage power supply limits its maximum output current to a preset value. This preset
value is fixed or variable throughout a specified range.
2. Power supplies with the ability to transition from constant voltage (CV) to constant
current (CC)
Conventional current limiting power supplies and CV/CC mode power supplies are very
similar in function. These implementations vary only in the degree of regulation in the
constant current operating region (see Figure 7). You can adjust the CC operating point
for CV/CC power supplies.
A rounded crossover knee and sloping current limit characteristic denote a less precise
current regulation. In comparison, a sharp knee and vertical current limit characteristic
indicate better current regulation. The foldback current limiting power supply uses a
technique that enables both the output voltage and current to decrease simultaneously
for load resistances below the crossover value.
VOUT
ce
an
ist
es
rr
ve
so
os
Cr
=
AD
LO
R
Load
effect
band
k
CV/Current limit
bac
fold
ent
urr
CV/CC
/C
CV
IOUT
(50%)IMAX (100%)IMAX (105%)IMAX
Figure 7. Voltage vs. current shows three types of current limiting designs
_
Multimeter
Power Supply DUT DC Electronic Load
_ _
N6791A/N6792A
The test begins with the power supply set to its highest voltage and the load set to high
resistance. High-resistance draws minimal current, and the power supply is in its normal
constant voltage mode.
During the test, the power supplies’ output voltage and current are recording. A
program begins decrementing the electronic load resistance in steps. The output
voltage remains constant as the current increases due to load. Once the output current
reaches the current limit, the voltage drops.
Figure 9 shows the drop known as the crossover region. The power supply no longer
maintains a constant voltage. As the resistance continues to decrease, the power
supply operates in its current limiting mode. A quality power supply with CV/CC has a
sharp transition to the constant current mode. As the resistance continues to increase,
the current should remain constant.
VOUT
RL = Open circuit
C
R
RL = Load resistance
R>
C
R
L =
L
RC = Crossover resistance
R
RC
R L< RL = Short circuit
3 String variable reset is used to lower the resistance "RES " & resSet & ", (@1)"
7 "RES:SLEW:NEG INF,(@1)"
Results
The test power supply has its current limit set at 2 A. The electronic load provides a three-
ohm resistance — both voltage and current are measurable. Resistance is reduced by
0.1 ohms and the power supply is allowed to settle before the next set of measurements.
The process continues until the resistance reaches 0.1 ohms. See Figure 10 for the
voltage-current measurements. The test power supply gives you a very sharp transition
from constant voltage mode to the constant current model. An abrupt transition is a sign of
a high-quality power supply.
CV to CC
3.5
2.5
2
Voltage
1.5
0.5
0
1 1.2 1.4 1.6 1.8 2.0
Current
Figure 10. Plot depicts voltage versus current with a current limit of 2 A
Electronics in automobiles use a nominal 12 VDC and are designed to run off 9 VDC — from
a low battery or up to 14 VDC generated by a running engine. A DC-DC converter is used to
accept voltages from 9 to 14 VDC on the input and output a consistent 12 VDC.
A DC-DC converter input draws constant power when it has a steady load. To consume
a constant amount of power the converter pulls less current as the voltage increases.
Figure 11 is a graph of constant power. Over a broad voltage range, it is easy to see the
relationship between voltage and currents is a curve.
V 70
60
50
40
30
20
10
0
0 5 10 15 20 25
I
Figure 11. A constant power curve over an extensive range of voltage and current
Figure 12. A single current limit only protects the DC-DC converter at a single voltage (green line)
A DC-DC converter has a limited voltage-to-current range relative to the curve shown
in Figure 11. A data sheet for a 19 V / 6 A converter has an input voltage range of 9 V
to 18 V. To test the entire range of the converter’s input, a DC power supply capable of
producing 9V / 13 A and 18 V / 6.5 A is necessary.
20
15
10
0
0 2 4 6 8 10 12 14 I
Figure 13. Illustration of a power limit (green) slightly larger than the operating power (red)
Another issue with the standard current protection is with the current limit the power
supply transitioning to a constant current mode. In the constant current mode, the
power supply’s output voltage is allowed to fall and could drop below the operating
voltage of the converter. A low voltage causes the converter to go into an unregulated
state which requires resetting the converter.
Overcurrent protection (OCP) prevents the power supply from supplying a low voltage.
Instead of transitioning to the constant current mode, OCP shuts off the power supply
output.
The load also protects the converter by only drawing current when the converter is
operating at its expected 19 V. An under-voltage inhibit function turns the load off until
the voltage is above the 19 V limit. Once the converter is supplying the correct voltage;
the load will again draw current.
A calculation of efficiency occurs at each voltage. The efficiency of the converter is the
output power divided by input power. The power supply produces and measures the
1 Output 9 to 18 V using a string variable voltSet "VOLT " & voltSet & ",(@3)"
Table 5. Configuring the power supply module at Channel 3 to drive the inverter
Load configuration
“VOLT:INH:VON 19,(@1)”
4 Under voltage inhibit is set to 19 V and enabled
“VOLT:INH:VON:MODE LIVE,(@1)”
Results
To begin the test, 18 V is applied to the converter along with an 85 W load. Voltage
and current measurements calculate at the converter’s input and output. Efficiency
is calculated using the voltage and current measurements. Next, after lowering the
converts input voltage 500 mV, a three-second pause allows the converter to settle.
Once settled, all voltages and currents are measured and recorded. A program continues
to reduce the voltage and make the measurements until the input voltage reaches the
9 V lower limit. Figure 14 shows the input voltages and currents. Efficiency results range
from 97% to 98%.
12
10
8
6
4
2
0
1 2 3 4 5 6 7 8 9 10 11
Current
Figure 14. Input voltage and current graphed for an 85 W inverter
Plus, the N6790 series loads perform both dynamic and static tests.
Bench
The N6705C 600W modular power supply offers four slots for modules, a large
display, view settings, and measurements for all channels simultaneously. Setups are
easy with configuration panels for each module.
ATE system
Choose from three 1 U high mainframes N6700C 400 W, N6701C 600 W, or N6702C
1200 W — all mainframes give you four slots for modules. Create dynamic power
waveforms and load profiles easily with several built-in arbitrary waveforms definable
with just a few points.
Download the N6700 Modular Power System Family - Data Sheet 5992-1857EN