LOCATION: NHQ, ISLAMABAD
DATED: 27TH JANUARY, 2020
SUBJECT PLUMBING SYSTEM METHODOLOGY
(DWSP‐01A/01B) DEEP WELL SUBMERSIBLE PUMP CALCULATIONS
TANK SPECIFICS AND REQUIRED THROUGHPUT FLOW CALCULATIONS
TOTAL WATER HOLDING CAPACITY OF U.G.W.T (EXCLUDES 1 FEET
= 225,176 GALLONS
OF CLEAR BOARD HEIGHT)
TOTAL WATER DEMAND CAPACITY REQUIED FOR FIRE FIGHTING
= 60,000 GALLONS
SYSTEM (1000 GPM FOR A DURATION OF 30 MINUTES)
TOTAL WATER DEMAND CAPACITY FOR 1 DAY REQUIED FOR NON‐
= 165,176 GALLONS
POTABLE WATER SUPPLY TO THE BUILDING
TANK WATER LEVEL RELATIVE TO SITE'S GROUND LEVEL = ‐12.0 FEET
PUMPING LEVEL (DEPTH OF WATER LEVEL IN THE WELL BELOW
= 500 FEET
GRADE)
SUBMERGENCE LEVEL OF PUMP AND ITS PIPING (VERTICAL DEPTH
= 700 FEET
BELOW GRADE)
HORIZONTAL LENGTH OF PIPING RUN = 350 FEET
TOTAL TIME REQUIRED TO REPLENISH 1 COMPLETE DAYS NON‐
= 4 HOURS
POTABLE WATER SUPPLY FLOW DRAW
CYCLING TIME OF THE DEEP WELL SUBMERSIBLE PUMP = 20 MINUTES
STOP TIME OF THE DEEP WELL SUBMERSIBLE PUMP = 5 MINUTES
STARTS PER HOUR = 3
TRANSFER PUMP'S ‐ DISCHARGE PIPE SIZE (AS PER HAZEN WILLIAMS)
RECOMMENDED PIPE MATERIAL = uPVC CLASS‐E
PUMP TOTAL DYNAMIC HEAD CALCULATIONS
NUMBER OF ACTIVE PUMPS = 2
NUMBER OF STANDBY PUMPS = 1
EACH PUMP WITH A
FLOW = 459 GPM
HEAD = 243 PSI
POWER = 74.5 kW