DATA SHEET FOR CONTROL / REGULATOR VALVES


Project Code Package Company code Scope Disc Code Doc. Code Sequence Rev. Code
Contract No: No. Page 1 Of 145
RR-OI-PT-9808-PM-CN-0015
RR 02 PT 100 IN DT 0060 D00

28 Reservoirs Development Program

Ramshir Oil and Gas Processing Complex


[DATA SHEET FOR CONTROL / REGULATOR VALVES]

Rev Status Date Prepared by: Checked by: Approved by:


D00 IFC 11.03.2020 M.Khazanbaik A.Eisazadeh A.Hojatpanah

Class : 2
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Code Package Company Scope Disc Code Doc. Code Sequence No. Rev. Code
Contract No: code
RR-OI-PT-9808-PM-CN-0015 Page 2 Of 145
RR 02 PT 100 IN DT 0060 D00

Tabulation Of Revised Pages


Page D00 D01 D02 D03 D04 Page D00 D01 D02 D03 D04
1 × 101 ×
2 × 102 ×
3 × 103 ×
4 × 104 ×
5 × 105 ×
6 × 106 ×
7 × 107 ×
8 × 108 ×
9 × 109 ×
10 × 110 ×
11 × 111 ×
12 × 112 ×
13 × 113 ×
14 × 114 ×
15 × 115 ×
16 × 116 ×
17 × 117 ×
18 × 118 ×
19 × 119 ×
20 × 120 ×
21 × 121 ×
22 × 122 ×
23 × 123 ×
24 × 124 ×
25 × 125 ×
26 × 126 ×
27 × 127 ×
28 × 128 ×
29 × 129 ×
30 × 130 ×
31 × 131 ×
32 × 132 ×
33 × 133 ×
34 × 134 ×
35 × 135 ×
36 × 136 ×
37 × 137 ×
38 × 138 ×
39 × 139 ×
40 × 140 ×
41 × 141 ×
42 × 142 ×
43 × 143 ×
44 × 144 ×
45 × 145 ×
46 × 146
47 × 147
48 × 148
49 × 149
50 × 150
51 × 151
52 × 152
53 × 153
54 × 154
55 × 155
56 × 156
57 × 157
58 × 158
59 × 159
60 × 160
61 × 161
62 × 162
63 × 163
64 × 164
65 × 165
66 × 166
67 × 167
68 × 168
69 × 169
70 × 170
71 × 171
72 × 172
73 × 173
74 × 174
75 × 175
76 × 176
77 × 177
78 × 178
79 × 179
80 × 180
81 × 181
82 × 182
83 × 183
84 × 184
85 × 185
86 × 186
87 × 187
88 × 188
89 × 189
90 × 190
91 × 191
92 × 192
93 × 193
94 × 194
95 × 195
96 × 196
97 × 197
98 × 198
98 × 199
100 × 200
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Contract No: Project Code Package Company code Scope Disc Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN- Page 3 Of 145
0015 RR 02 PT 100 IN DT 0060 D00

REFERENCE DOCUMENTS :

General Specification for Instrumentation RR-02-PT-100-IN-SP-0003

P&ID-Inlet Flowline & Headers (Unit-100) RR-02-PT-120-PR-PI-0022

P&ID-Bangestan Separation Facilities and Pumps (Unit-200) RR-02-PT-120-PR-PI-0026

P&ID-Crude Oil Stripper Column (Unit-200) RR-02-PT-120-PR-PI-0027

P&ID-Test Separation Facilities (Unit-300) RR-02-PT-120-PR-PI-0029

P&ID-Glycol Storage Tank & Drain System (Unit-500) RR-02-PT-170-PR-PI-0064

P&ID-Air Generation System (Unit-500) RR-02-PT-130-PR-PI-0049

P&ID-Fuel Gas System (Unit-500) RR-02-PT-130-PR-PI-0054

P&ID-Fuel Gas Distribution Diagram (Unit-500) RR-02-PT-130-PR-PI-0055

P&ID-Dilution Water Tank and Pumps (Unit-500) RR-02-PT-170-PR-PI-0060

P&ID-Sour Water Stripper Package (Unit 600) RR-02-PT-120-PR-PI-0075

P&ID-4th Stage Inlet Scrubber (Unit-700) RR-00-PT-120-PR-PI-0076

P&ID-4th Stage Compressors (Unit-700) RR-00-PT-120-PR-PI-0077

P&ID-3rd Stage Gas K.O. Drum (Unit-700) RR-00-PT-120-PR-PI-0078

P&ID-3rd Stage Suction Scrubbers & Air Coolers (Unit-700) RR-00-PT-120-PR-PI-0079

P&ID-2nd Stage Gas K.O. Drum (Unit-700) RR-00-PT-120-PR-PI-0081

P&ID-2nd Stage Suction Scrubbers & Air Coolers (Unit-700) RR-00-PT-120-PR-PI-0082

P&ID-Composite Gas K.O. Drum (Unit-700) RR-00-PT-120-PR-PI-0084

P&ID-1st Stage Gas K.O. Drum (Unit-700) RR-00-PT-120-PR-PI-0085

P&ID-1st Stage Suction Scrubbers & Air Coolers (Unit-700) RR-00-PT-120-PR-PI-0086

P&ID-1st Stage Gas Outlet K.O. Drum (Unit-700) RR-00-PT-120-PR-PI-0088

P&ID-Production Tank and Pumps (Unit-100) RR-02-PT-170-PR-PI-0025

P&ID-Test Tank (Unit-300) RR-02-PT-170-PR-PI-0030

P&ID-Off-Spec Tank & Pumps (Unit 400) RR-02-PT-170-PR-PI-0036

P&ID-Dilution Water Tank and Pumps (Unit-500) RR-02-PT-170-PR-PI-0060

P&ID-Glycol Storage Tank & Drain System (Unit-500) RR-02-PT-170-PR-PI-0064

P&ID-Asmari Skimmer Tank (Unit 600) RR-02-PT-170-PR-PI-0065

P&ID-Asmari Disposal Water Tank and Pumps(Unit 600) RR-02-PT-170-PR-PI-0068

P&ID-Asmari Dirty Oil Tank and Pumps (Unit 600) RR-02-PT-170-PR-PI-0069

P&ID-Bangestan Skimmer Tank (Unit 600) RR-02-PT-170-PR-PI-0070

P&ID-Bangestan Disposal Water Tank and Pumps (Unit 600) RR-02-PT-170-PR-PI-0073

P&ID-Bangestan Dirty Oil Tank and Pumps (Unit 600) RR-02-PT-170-PR-PI-0074

P&ID-Asmari Salty/Desalted Crude Heat Exchanger (Unit 400) RR-02-PT-120-PR-PI-0032

P&ID-Multi Phase Flowmeter (Unit-300) RR-02-PT-120-PR-PI-0031

P&ID-Asmari Water / Water Heat Exchanger (Unit 400) RR-02-PT-120-PR-PI-0035

P&ID-Bangestan Salty/Desalted Crude Heat Exchanger (Unit 400) RR-02-PT-120-PR-PI-0037

P&ID-Bangestan Water / Water Heat Exchanger (Unit 400) RR-02-PT-120-PR-PI-0039

Instrument & Control/Safety System Basis of Design & Design Criteria RR-02-PT-100-IN-DB-0001

Piping Material Specification RR-02-PT-100-PI-SP-0002

Specification For Control valves RR-02-PT-100-IN-SP-0012


Control Valve Sizing Calculation Report RR-02-PT-120-PR-CN-0096
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
:‫شماره صفحه‬5‫ از‬172
DATA SHEET FOR CONTROL / REGULATOR VALVES
Contract No: Project Code Package
Company Scope Disc Code Doc. Code Sequence Rev. Code
RR-OI-PT-9808-PM-CN- code No. Page 4 Of 145
0015 RR 02 PT 100 IN DT 0060 D00

GENERAL NOTES:

1) The control valves will be installed in an open area and the electrical equipment shall be suitable for use in a hazardous
area Zone 1, Gas group IIB, Temperature class T4.

2) All control valve and accessories shall be weather proof to IP65 as minimum and suitable for tropicalized installation.

3) Electric and electronic parts shall also be provided for tropical services in order to prevent corrosion.

4) The control valves sizing shall be calculated on the basis of the process operating conditions and in compliance with the
ISA S75.01 Code.

5) Control valve body size shall never be less than half of nominal pipe line size.

6)
Vendor shall verify the following characteristics for each control valve as a minimum:
- CV coefficients at minimum, normal and maximum flows
- Percent lift at minimum, normal and maximum flows as indicated in data sheets
- Flow velocity in control valve at maximum specified conditions
- Noise level
- Vibrations
- Actuator sizing calculations. Actuation torque shall be 50% higher than maximum torque value with maximum upstream
pressure and downstream pressure
- Valve construction and material (body, trim, plug, stem, guide, top works, packing, lubrication, accessories etc.)

7) The Vendor shall guarantee that cavitation is eliminated to such a point that the valve may operate stable without repair
for a period of 12 months by proper selection of pressure drop and metallurgy.

8) Special type valves (e.g. angle valves, multi-step type, with labyrinth, cage type, etc.) will be used for very high-pressure
drops, for high fluid velocity, to reduce the noise level, etc.

9) Following body sizes shall be used: 1" -1 1/2" -2"-3"- 4"- 6"- 8" - 10" - 12" and larger.

10) The minimum globe control valve body size to be used shall be 1 inch and the internal trim size shall be in accordance to
the requirements as specified in data sheet.

11) For lines that are 1" or less in diameter, the minimum valve body size will be 1" with reduced trim if necessary

12) Body sizes smaller than 1" may be used for special applications and pressure regulation services.

13) For flanged valves, the minimum flange rating shall be 300# ANSI. The flange rating and finish shall be as per the
Project Piping Material Specification.

14) The valve shall have quick change trim type using top entry.

15) No trim component shall be screwed or welded to the valve body. The valve shall have equal pressure distribution around the plug.

16) Reduced trims in oversized bodies shall be used for:


• Situations where the calculated flow co-efficiency would result in a standard valve two or more sizes smaller than the
line.
• Flashing or cavitating flow conditions
• Fluids containing solids
• When calculated valve size is below 1"
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex

DATA SHEET FOR CONTROL / REGULATOR VALVES :‫شماره صفحه‬6‫ از‬172


Contract No: Company Sequence
Project Code Package
code Scope Disc Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN- Page 5Of 145
0015 RR 02 PT 100 IN DT 0060 D00

17) For corrosive services, i.e. acid service, consideration to be given to other suitable materials, taking into account the full
process conditions in each case. In toxic services, consideration should be given to using "bellows seal" bonnets.

18)
Control valves shall have as a minimum 316 stainless steel or hardened stainless trim components depending on
service.
Hardened metal facing shall be provided if 316 stainless steel trim is used for:
• Pressure drops above 7 Barg
• Temperature exceeding 315ºC
• Fluids containing solids
• Flashing liquids
• Cavitation flow conditions

19) Bonnets and blind heads shall be of the same material as the valve body and of integral or bolted construction with fully
retained gaskets.

20) The material of bonnet shall be suitable to withstand the ambient temperatures and operating temperatures indicated in
the Technical Data Sheets.

21) Seat leakage of globe type control valves shall be class IV as defined in ANSI B-16-104.

22) For diaphragm type actuators, the casing shall be of steel construction, suitably protected against corrosion for the
environmental conditions.

23) Generally the stroking time of the valve shall be 5 seconds but no longer than 10 seconds with normal process conditions
unless otherwise specified. Manufacturer shall submit the stroking time calculation.

24) All positioner shall be equipped with 3 pressure gauges in AISI 316 SS (double dial PSI g and bar g) at inlet signal,
output signal and supply.

25) For control valves with accessories i.e. positioners, air sets, air locks etc., the valve is to be supplied completely
assembled including all necessary tubing.

26) Tubing to be stainless steel with double ferrule compression fittings.

27) All air connections shall be 1/4" NPT and electrical entries shall be ISO M20 X 1.5.

28) All control valves shall be equipted with Eexia, IP 65 , HART supported position transmitter.

29) Environmental Condition For Field Instrumentation Of Ramshir Complex Shall Be Considered As Per The Following:
Max Recorded Temperature 55°C
Min Recorded Temperature -5 °C
Max Steel Surface Temperature Exposed To 85 °C
Max Relative Humidity 100%
Min Relative Humidity 11%
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 6 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-7001 P&ID NO : RR-00-PT-120-PR-PI-0076 SERVICE: FROM 4th STAGE COMP. TO AC-701
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 0.81
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 13739 -
2 INLET PRESSURE bar(g) - 1.3 - -
3 OUTLET PRESSURE bar(g) - 0.1 -
4 DIFFERENTIAL PRESSURE bar - 1.2 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 80 -
6 DENSITY kg/m³ - 4.5 -
7 SPEC.GRAVITY *
- 1.857 -
8 MOLECULAR WEIGHT *
- 53.84 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 281 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.96 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.1 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 GR. WCB, 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 7 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-7031 P&ID NO : RR-00-PT-120-PR-PI-0078 SERVICE: 3rd STAGE COMP. SPILL BACK
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 2.61
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 31705 -
2 INLET PRESSURE bar(g) - 6.17 - -
3 OUTLET PRESSURE bar(g) - 1 -
4 DIFFERENTIAL PRESSURE bar - 5.17 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 80 -
6 DENSITY kg/m³ - 20.7 -
7 SPEC.GRAVITY *
- 1.725 -
8 MOLECULAR WEIGHT *
- 50.03 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 202 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.89 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.09 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8 & SCH 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16 & SCH.20 57 * MFR. & MODEL VTA


19 PIPE LINE INSULATION/SPEC PP / AN07/AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 8 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-7032 P&ID NO : RR-00-PT-120-PR-PI-0078 SERVICE: TO LLP FLARE HEADER
FLUID : VENT GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 0.81
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 13739 -
2 INLET PRESSURE bar(g) - 1.3 - -
3 OUTLET PRESSURE bar(g) - 0.1 -
4 DIFFERENTIAL PRESSURE bar - 1.2 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 80 -
6 DENSITY kg/m³ - 4.38 -
7 SPEC.GRAVITY *
- 1.857 -
8 MOLECULAR WEIGHT *
- 53.84 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 281 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.96 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.1 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10 & SCH.20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16 & SCH.20 57 * MFR. & MODEL VTA


19 PIPE LINE INSULATION/SPEC PP/PT / AN04/AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 9 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-7062 P&ID NO : RR-00-PT-120-PR-PI-0081 SERVICE: FROM C-702-A/B TO LP FLARE HEADER
FLUID : FLARE GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 2.61
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 31705 -
2 INLET PRESSURE bar(g) - 6.22 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 6.14 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 60 -
6 DENSITY kg/m³ - 20.7 -
7 SPEC.GRAVITY *
- 1.725 -
8 MOLECULAR WEIGHT *
- 50.03 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 582 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.09 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 12" & SCH.40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH.40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP/PT / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 12" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 12" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 12" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 10 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-7061 P&ID NO : RR-00-PT-120-PR-PI-0081 SERVICE: FROM 2nd STAGE COMP. SPILL BACK
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 10.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 47629 -
2 INLET PRESSURE bar(g) - 27.2 - -
3 OUTLET PRESSURE bar(g) - 5.9 -
4 DIFFERENTIAL PRESSURE bar - 21.3 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 73.9 -
6 DENSITY kg/m³ - 94.18 -
7 SPEC.GRAVITY *
- 1.51 -
8 MOLECULAR WEIGHT *
- 43.83 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 100 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.75 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.13 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH.80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH 10S 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC pp / CN07/AS03 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 GR. WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 11 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-7060 P&ID NO : RR-00-PT-120-PR-PI-0081 SERVICE: FROM V-702
FLUID : Hydro Carbon FLUID TYPE : LIQUID Critical Press. Pc (bar(a)) (Gas/Liq) 42.5
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 5492 -
2 INLET PRESSURE bar(g) - 5.9 - -
3 OUTLET PRESSURE bar(g) - 1.1 -
4 DIFFERENTIAL PRESSURE bar - 4.8 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 52.6 -
6 DENSITY kg/m³ - 582 -
7 SPEC.GRAVITY *
- 0.582 -
8 MOLECULAR WEIGHT *
- 69 -
9 VISCOSITY (Gas/Liquid) cp - 0.17 -
10 VAPOR PRESSURE Pv bar(g) - 5.9 -
11 * REQUIRED Cv - 9.7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.03 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.05 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH.40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH.40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 GR 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS LINEAR 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 12 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
FROM 2nd STAGE COMPRESSOR SPILL BACK
TAG NO : PCV-7090 P&ID NO : RR-00-PT-120-PR-PI-0084 SERVICE: TO HP FLARE HEADER
FLUID : FLARE GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 10.21
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 31706 -
2 INLET PRESSURE bar(g) - 6.2 - -
3 OUTLET PRESSURE bar(g) - 0.1 -
4 DIFFERENTIAL PRESSURE bar - 6.12 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 73.9 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- -
8 MOLECULAR WEIGHT *
- 50.1 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 202 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.88 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH.80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH.80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS V 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 13 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-7093 P&ID NO : RR-00-PT-120-PR-PI-0084 SERVICE: FROM V-101 TO V-703
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 9.96
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 13843 -
2 INLET PRESSURE bar(g) - 26.6 - -
3 OUTLET PRESSURE bar(g) - 25.9 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 59.4 -
6 DENSITY kg/m³ - 29.06 -
7 SPEC.GRAVITY *
- 0.911 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 105 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.9 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.29 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH.80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH.80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06/CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 14 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-7090 P&ID NO : RR-00-PT-120-PR-PI-0084 SERVICE: FROM V-703
FLUID : Hydro Carbon FLUID TYPE : LIQUID Critical Press. Pc (bar(a)) (Gas/Liq) 52.6
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 17114 -
2 INLET PRESSURE bar(g) - 29.6 - -
3 OUTLET PRESSURE bar(g) - 9.5 -
4 DIFFERENTIAL PRESSURE bar - 17.1 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 59.5 -
6 DENSITY kg/m³ - 504.8 -
7 SPEC.GRAVITY *
- 0.497 -
8 MOLECULAR WEIGHT *
- 54 -
9 VISCOSITY (Gas/Liquid) cp - 0.11 -
10 VAPOR PRESSURE Pv bar(g) - 26.7 -
11 * REQUIRED Cv - 14.5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.11 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.06 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH.80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH.80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS LINEAR 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 15 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
M.KH:
TAG NO : PCV P&ID NO : RR-00-PT-120-PR-PI-0084 SERVICE: FROM V-703
THERE ISNT TAG NO. IN
FLUID : FLUID
PID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 4" & SCH.80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH.80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 GR 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN / 300# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes (NOTE1) 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 16 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
M.KH:
TAG NO : PCV P&ID NO : RR-00-PT-120-PR-PI-0084 SERVICE: FROM V-703
THERE ISNT TAG NO. IN
FLUID : FLUID
PID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 10" & SCH.XS 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH.XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN / 300# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 17 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-7131 P&ID NO : RR-00-PT-120-PR-PI-0085 SERVICE: FROM V-704 TO HP HEADER
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 9.68
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 68108 -
2 INLET PRESSURE bar(g) - 25.8 - -
3 OUTLET PRESSURE bar(g) - 25.1 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 67.7 -
6 DENSITY kg/m³ - 27.65 -
7 SPEC.GRAVITY *
- 0.911 -
8 MOLECULAR WEIGHT *
- 26.45 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 525 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.9 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.28 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 12" & SCH.60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH.60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06/AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 18 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-7150 P&ID NO : RR-00-PT-120-PR-PI-0086(1/3) SERVICE: 1st STAGE GAS COMP. SPILL BACK
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) 33.37
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 68108 -
2 INLET PRESSURE bar(g) - 91.4 - -
3 OUTLET PRESSURE bar(g) - 25.8 -
4 DIFFERENTIAL PRESSURE bar - 65.6 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 67.7 -
6 DENSITY kg/m³ - 27.65 -
7 SPEC.GRAVITY *
- 0.911 -
8 MOLECULAR WEIGHT *
- 26.45 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 41 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.68 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.28 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH.XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN05/CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)- IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO - 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA : Vendor to Advise PMS : PIPING MATERIAL SPECIFICATION VTC : Vendor to Confirm
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPOSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 19 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1001 P&ID NO : RR-02-PT-120-PR-PI-0022(1/8) SERVICE: FROM WELL NO. 1
FLUID : LIQUID FLUID TYPE :
CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.700000000000003 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
VALVE BODY/BONNET

24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3


25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9
26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
POSITIONER

32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD


33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA
* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 19 Of 145

Control Valve
FROM WELL NO. 1

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 20 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1002 P&ID NO : RR-02-PT-120-PR-PI-0022(1/8) SERVICE: FROM WELL NO. 2
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 20 Of 145

Control Valve
FROM WELL NO. 2

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 21 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1003 P&ID NO : RR-02-PT-120-PR-PI-0022(1/8) SERVICE: FROM WELL NO. 4
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET
Com FOR CONTROL / REGULATOR VALVES
pan
Project Disc
Contract No: Code Package y Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
cod Page 22 Of 145
RR 02 e
PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1004 P&ID NO : RR-02-PT-120-PR-PI-0022(1/8) SERVICE: FROM WELL NO. 5
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 23 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1005 P&ID NO : RR-02-PT-120-PR-PI-0022(1/8) SERVICE: FROM WELL NO. 22
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT
THE RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 24 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1006 P&ID NO : RR-02-PT-120-PR-PI-0022(2/8) SERVICE: FROM WELL NO. 7
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 24 Of 145

Control Valve
FROM WELL NO. 7

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 25 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1007 P&ID NO : RR-02-PT-120-PR-PI-0022(2/8) SERVICE: FROM WELL NO. 9
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 26 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1008 P&ID NO : RR-02-PT-120-PR-PI-0022(2/8) SERVICE: FROM WELL NO. 10
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 27 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1009 P&ID NO : RR-02-PT-120-PR-PI-0022(2/8) SERVICE: FROM WELL NO. 11
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 28 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1010 P&ID NO : RR-02-PT-120-PR-PI-0022(2/8) SERVICE: FROM WELL NO. 12
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 28 Of 145

Control Valve
FROM WELL NO. 12

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 29 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1011 P&ID NO : RR-02-PT-120-PR-PI-0022(3/8) SERVICE: FROM WELL NO. 14
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 29 Of 145

Control Valve
FROM WELL NO. 14

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 30 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1012 P&ID NO : RR-02-PT-120-PR-PI-0022(3/8) SERVICE: FROM WELL NO. 16
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 31 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1013 P&ID NO : RR-02-PT-120-PR-PI-0022(3/8) SERVICE: FROM WELL NO. 17
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 32 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1014 P&ID NO : RR-02-PT-120-PR-PI-0022(3/8) SERVICE: FROM WELL NO. 18
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 32 Of 145

Control Valve
FROM WELL NO. 18

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 33 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1015 P&ID NO : RR-02-PT-120-PR-PI-0022(3/8) SERVICE: FROM WELL NO. 19
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 33 Of 145

Control Valve
FROM WELL NO. 19

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 34 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1016 P&ID NO : RR-02-PT-120-PR-PI-0022(4/8) SERVICE: FROM WELL NO. 20
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 - -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSUREVTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 35 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1017 P&ID NO : RR-02-PT-120-PR-PI-0022(4/8) SERVICE: FROM WELL NO. 21
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 35 Of 145

Control Valve
FROM WELL NO. 21

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 36 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1018 P&ID NO : RR-02-PT-120-PR-PI-0022(4/8) SERVICE: FROM WELL NO. **
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 36 Of 145

Control Valve
FROM WELL NO. **

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 37 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1019 P&ID NO : RR-02-PT-120-PR-PI-0022(4/8) SERVICE: FROM WELL NO. **
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSUREVTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 38 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1020 P&ID NO : RR-02-PT-120-PR-PI-0022(4/8) SERVICE: FROM WELL NO. **
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 38 Of 145

Control Valve
FROM WELL NO. **

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 39 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1021 P&ID NO : RR-02-PT-120-PR-PI-0022(5/8) SERVICE: FROM WELL NO. **
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 40 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1022 P&ID NO : RR-02-PT-120-PR-PI-0022(5/8) SERVICE: FROM WELL NO. W015
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 41 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1023 P&ID NO : RR-02-PT-120-PR-PI-0022(5/8) SERVICE: FROM WELL NO. W105S
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 41 Of 145

Control Valve
FROM WELL NO. W105S

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 42 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1024 P&ID NO : RR-02-PT-120-PR-PI-0022(5/8) SERVICE: FROM WELL NO.W012N
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 42 Of 145

Control Valve
FROM WELL NO.W012N

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 43 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1025 P&ID NO : RR-02-PT-120-PR-PI-0022(5/8) SERVICE: FROM WELL NO. E015
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSUREVTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 44 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1026 P&ID NO : RR-02-PT-120-PR-PI-0022(6/8) SERVICE: FROM WELL NO. E060N
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 44 Of 145

Control Valve
FROM WELL NO. E060N

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 45 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1027 P&ID NO : RR-02-PT-120-PR-PI-0022(6/8) SERVICE: FROM WELL NO. E056S
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 45 Of 145

Control Valve
FROM WELL NO. E056S

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 46 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1028 P&ID NO : RR-02-PT-120-PR-PI-0022(6/8) SERVICE: FROM WELL NO. W005N
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 46 Of 145

Control Valve
FROM WELL NO. W005N

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 47 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1029 P&ID NO : RR-02-PT-120-PR-PI-0022(6/8) SERVICE: FROM WELL NO. 23
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 47 Of 145

Control Valve
FROM WELL NO. 23

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 48 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1030 P&ID NO : RR-02-PT-120-PR-PI-0022(6/8) SERVICE: FROM WELL NO. 24
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 44.47
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 33085 -
2 INLET PRESSURE bar(g) - 28.1 -
3 OUTLET PRESSURE bar(g) - 27.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 63.9 -
6 DENSITY kg/m³ - 87.72 -
7 SPEC.GRAVITY *
- 0.08 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.86 -
10 VAPOR PRESSURE Pv bar(g) - 28.1 -
11 * REQUIRED Cv - 162.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 48 Of 145

Control Valve
FROM WELL NO. 24

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 49 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1031 P&ID NO : RR-02-PT-120-PR-PI-0022(7/8) SERVICE: FROM WELL NO. 23
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 49 Of 145

Control Valve
FROM WELL NO. 23

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 50 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1032 P&ID NO : RR-02-PT-120-PR-PI-0022(7/8) SERVICE: FROM WELL NO. 24
FLUID : FLUID TYPE : Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h
2 INLET PRESSURE bar(g)
3 OUTLET PRESSURE bar(g)
4 DIFFERENTIAL PRESSURE bar
SERVICE CONDITION

5 INLET TEMPERATURE OC

6 DENSITY kg/m³
7 SPEC.GRAVITY *

8 MOLECULAR WEIGHT *

9 VISCOSITY (Gas/Liquid) cp
10 VAPOR PRESSURE Pv bar(g)
11 * REQUIRED Cv
12 * TRAVEL %
13 ALLOWABLE / *PREDICTED SPL dBA
14 COMPRESSIBILITY Z
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid)
16 CRITICAL TEMP. (Gas/Liquid) OC

17 PIPE LINE SIZE In 6" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / GN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 4" / 900# 65 PRESSURE
*BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 900# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RTJ 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 50 Of 145

Control Valve
FROM WELL NO. 24

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 51 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1301A P&ID NO : RR-02-PT-170-PR-PI-0024(1/3) SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 610 -
2 INLET PRESSURE bar(g) - 1 -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 91 -
6 DENSITY kg/m³ - 2.03 -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 20 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 4" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 51 Of 145

Control Valve
FROM FUEL GAS HEADER

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 52 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : P&ID NO : RR-02-PT-170-PR-PI-0024(1/3) SERVICE: TO 4th STAGE INLET SCRUBBER (SK-701)
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6306 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 51 -
6 DENSITY kg/m³ - 2.23 -
7 SPEC.GRAVITY *
- 1.88 -
8 MOLECULAR WEIGHT *
- 54.5 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 1029 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 16" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 53 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : P&ID NO : RR-02-PT-170-PR-PI-0024(1/3) SERVICE: TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6306 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 51 -
6 DENSITY kg/m³ - 2.23 -
7 SPEC.GRAVITY *
- 1.88 -
8 MOLECULAR WEIGHT *
- 54.5 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 1029 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 20" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 20" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 16" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 16" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 16" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 54 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1401 P&ID NO : RR-02-PT-170-PR-PI-0024(2/3) SERVICE: TO ASMARI DESALTING UNIT (E-401)
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 187.9
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 290561.7 -
2 INLET PRESSURE bar(g) - 12.08 -
3 OUTLET PRESSURE bar(g) - 11.38 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 51.6 -
6 DENSITY kg/m³ - 887.5 -
7 SPEC.GRAVITY *
- 0.887 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 12.13 -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 427.7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 16" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 54 Of 145

Control Valve
TO ASMARI DESALTING UNIT (E-401)

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 55 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1402 P&ID NO : RR-02-PT-170-PR-PI-0024(2/3) SERVICE: TO DEGASSING TANK (TK-102)
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 187.9
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 96853.9 -
2 INLET PRESSURE bar(g) - 12.08 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 12 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 51.6 -
6 DENSITY kg/m³ - 887.5 -
7 SPEC.GRAVITY *
- 0.887 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 12.13 -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 36.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 56 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1501C P&ID NO : RR-02-PT-170-PR-PI-0025(1/3) SERVICE: TO 4th STAGE INLET SCRUBBER (SK-701)
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2039 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 53 -
6 DENSITY kg/m³ - 2.31 -
7 SPEC.GRAVITY *
- 1.96 -
8 MOLECULAR WEIGHT *
- 56.89 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 319 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 20" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 20" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 16" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 16" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 16" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 57 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-1501B P&ID NO : RR-02-PT-170-PR-PI-0025(1/3) SERVICE: FROM TK-101 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2039 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.06 -
4 DIFFERENTIAL PRESSURE bar - 0.04 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 53 -
6 DENSITY kg/m³ - 2.31 -
7 SPEC.GRAVITY *
- 1.96 -
8 MOLECULAR WEIGHT *
- 56.89 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 231 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 12" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 58 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1501A P&ID NO : RR-02-PT-170-PR-PI-0025(1/3) SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 651 -
2 INLET PRESSURE bar(g) - 1 -
3 OUTLET PRESSURE bar(g) - 0.06 -
4 DIFFERENTIAL PRESSURE bar - 0.94 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 2.03 -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 22 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 58 Of 145

Control Valve
FROM FUEL GAS HEADER

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 59 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1601 P&ID NO : RR-02-PT-170-PR-PI-0025(3/3) SERVICE: TO PIG LAUNCHER (PL-101)
FLUID : LIQUID FLUID TYPE : NON SALTY CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 41.8
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 327389.7 -
2 INLET PRESSURE bar(g) - 32 - -
3 OUTLET PRESSURE bar(g) - 31.3 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 53 -
6 DENSITY kg/m³ - 849.08 -
7 SPEC.GRAVITY *
- 0.847 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 6.9 -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 493.21 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 12" & SCH. XS 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 60 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-1603 P&ID NO : RR-02-PT-170-PR-PI-0025(3/3) SERVICE: TO (TK-101) & (TK-301)
FLUID : LIQUID FLUID TYPE : NON SALTY CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 41.8
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 109129.9 -
2 INLET PRESSURE bar(g) - 32 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 31.92 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 53 -
6 DENSITY kg/m³ - 849.08 -
7 SPEC.GRAVITY *
- 0.847 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 6.9 -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 26.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 6" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 61 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-2101 P&ID NO : RR-02-PT-120-PR-PI-0026(1/4) SERVICE: FROM V-201 TO V-202
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 261.4
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 89925 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 26.9 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 61 -
6 DENSITY kg/m³ - 815.46 -
7 SPEC.GRAVITY *
- 0.863 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.26 -
10 VAPOR PRESSURE Pv bar(g) - 27.6 -
11 * REQUIRED Cv - 134.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 62 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-2102 P&ID NO : RR-02-PT-120-PR-PI-0026(1/4) SERVICE: V-201 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.7
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2151.6 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 25.5 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 61 -
6 DENSITY kg/m³ - 1149.91 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.52 -
10 VAPOR PRESSURE Pv bar(g) - ATM -
11 * REQUIRED Cv - 0.5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 3" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 63 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : LCV-2103 P&ID NO : RR-02-PT-120-PR-PI-0026(2/4) SERVICE: FROM V-202 TO V-203
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 219
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 98604 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 6.2 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 55 -
6 DENSITY kg/m³ - 823.23 -
7 SPEC.GRAVITY *
- 0.83 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.79 -
10 VAPOR PRESSURE Pv bar(g) - 6.9 -
11 * REQUIRED Cv - 161.4 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 10" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 64 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-2104 P&ID NO : RR-02-PT-120-PR-PI-0026(2/4) SERVICE: V-202 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.4
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 1076 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 4.8 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 55 -
6 DENSITY kg/m³ - 1155.03 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.5 -
10 VAPOR PRESSURE Pv bar(g) - 2.32 -
11 * REQUIRED Cv - 0.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 2" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS
82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 65 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2101A P&ID NO : RR-02-PT-120-PR-PI-0026(1/4) SERVICE: V-201 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7336 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 25.9 -
4 DIFFERENTIAL PRESSURE bar - 1.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 34.02 -
7 SPEC.GRAVITY *
- 0.998 -
8 MOLECULAR WEIGHT *
- 26.4 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 35 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.87 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Compa Scope Disc Doc. Code Sequence Rev. Code
Contract No: Code ny code Code No.
RR-OI-PT-9808-PM-CN-0015 Page 66 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2101B P&ID NO : RR-02-PT-120-PR-PI-0026(1/4) SERVICE: V-201 GAS TO HP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7336 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 3.99 -
4 DIFFERENTIAL PRESSURE bar - 23.61 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 34.02 -
7 SPEC.GRAVITY *
- 0.998 -
8 MOLECULAR WEIGHT *
- 26.4 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 16 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.87 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 67 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2104B P&ID NO : RR-02-PT-120-PR-PI-0026(2/4) SERVICE: V-202 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6830 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 6.2 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 55 -
6 DENSITY kg/m³ - 12.22 -
7 SPEC.GRAVITY *
- 1.35 -
8 MOLECULAR WEIGHT *
- 37.7 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 84 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.93 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 10S 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 10S 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AS03 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 351 CF3M 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL AISI 316L 80 ACTUATION POINT N/A


42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
THERE ISNT IN PMS
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 68 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2104A P&ID NO : RR-02-PT-120-PR-PI-0026(2/4) SERVICE: V-202 GAS TO LP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6830 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 6.82 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 55 -
6 DENSITY kg/m³ - 12.22 -
7 SPEC.GRAVITY *
- 1.35 -
8 MOLECULAR WEIGHT *
- 37.7 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 47 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.93 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 10S 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 10S 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AS03 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 351 CF3M 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL AISI 316L 80 ACTUATION POINT N/A


42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
THERE ISNT IN PMS
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 69 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2201A P&ID NO : RR-02-PT-120-PR-PI-0026(3/4) SERVICE: V-203 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 4758 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 5.85 -
7 SPEC.GRAVITY *
- 1.67 -
8 MOLECULAR WEIGHT *
- 48.46 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 86 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 70 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2201B P&ID NO : RR-02-PT-120-PR-PI-0026(3/4) SERVICE: V-203 GAS TO LP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 4758 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 5.85 -
7 SPEC.GRAVITY *
- 1.67 -
8 MOLECULAR WEIGHT *
- 48.46 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 74 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.13 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 71 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-2201 P&ID NO : RR-02-PT-120-PR-PI-0026(3/4) SERVICE: V-203 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.3
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 1076 -
2 INLET PRESSURE bar(g) - 2.1 -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 1160.57 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.55 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 2.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC N / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS
82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 71 Of 145

Control Valve
V-203 WASTE WATER

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 72 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2301 P&ID NO : RR-02-PT-120-PR-PI-0027(1/2) SERVICE: T-201 INLET FROM DE-404
FLUID : OIL FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) 64.93
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 82610 -
2 INLET PRESSURE bar(g) - 7.9 - -
3 OUTLET PRESSURE bar(g) - 2.6 -
4 DIFFERENTIAL PRESSURE bar - 5.3 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 67 -
6 DENSITY kg/m³ - 301.31 -
7 SPEC.GRAVITY *
- 0.79 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.27 -
10 VAPOR PRESSURE Pv bar(g) - 3.48 -
11 * REQUIRED Cv - 54.8 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 73 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2303B P&ID NO : RR-02-PT-120-PR-PI-0027(1/2) SERVICE: T-201 TOLP FLARE HEADER
FLUID : GAS FLUID TYPE : VENT GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 5267 -
2 INLET PRESSURE bar(g) - 2.4 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2.32 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 66.6 -
6 DENSITY kg/m³ - 6.77 -
7 SPEC.GRAVITY *
- 1.82 -
8 MOLECULAR WEIGHT *
- 52.79 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 72 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 74 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-2303A P&ID NO : RR-02-PT-120-PR-PI-0027(1/2) SERVICE: T-201 GAS TOV-701
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 5267 -
2 INLET PRESSURE bar(g) - 2.4 - -
3 OUTLET PRESSURE bar(g) - 1.7 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 135 -
6 DENSITY kg/m³ - 6.77 -
7 SPEC.GRAVITY *
- 1.793 -
8 MOLECULAR WEIGHT *
- 52.79 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 87 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 75 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-2401 P&ID NO : RR-02-PT-120-PR-PI-0027(1/2) SERVICE: FROM P-201 TO T-201
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 64.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 27618 -
2 INLET PRESSURE bar(g) - 6.1 - -
3 OUTLET PRESSURE bar(g) - 2.6 -
4 DIFFERENTIAL PRESSURE bar - 3.5 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 71.6 -
6 DENSITY kg/m³ - 788.95 -
7 SPEC.GRAVITY *
- 0.79 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1.96 -
10 VAPOR PRESSURE Pv bar(g) - 2.57 -
11 * REQUIRED Cv - 20.4 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4'' & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 76 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-2501 P&ID NO : RR-02-PT-120-PR-PI-0028 SERVICE: FROM P-201 TO H-201
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 64.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 83061 -
2 INLET PRESSURE bar(g) - 6.1 - -
3 OUTLET PRESSURE bar(g) - 5.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 71.6 -
6 DENSITY kg/m³ - 788.95 -
7 SPEC.GRAVITY . *
- 0.79 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1.96 -
10 VAPOR PRESSURE Pv bar(g) - 2.57 -
11 * REQUIRED Cv - 129.25 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence
Contract No: Code Package any Scope Code Doc. Code No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 77 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-2701 P&ID NO : RR-02-PT-120-PR-PI-0026(4/4) SERVICE: FROM P-202 TO V-203
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 199
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 31733 -
2 INLET PRESSURE bar(g) - 11.6 -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 9.5 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 49.5 -
6 DENSITY kg/m³ - 841.96 -
7 SPEC.GRAVITY *
- 0.842 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 4.16 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 13.9 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 77 Of 145

Control Valve
FROM P-202 TO V-203

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 78 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-2702 P&ID NO : RR-02-PT-120-PR-PI-0026(4/4) SERVICE: FROM P-202 TO E-403 & TK-401
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 199
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 95920 -
2 INLET PRESSURE bar(g) - 11.6 - -
3 OUTLET PRESSURE bar(g) - 10.9 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 49.5 -
6 DENSITY kg/m³ - 841.96 -
7 SPEC.GRAVITY *
- 0.84 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 4.16 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 145.1 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc Sequence No.
Contract No: Code Package any Scope Code Doc. Code Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 79 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3101 P&ID NO : RR-02-PT-120-PR-PI-0029(1/3) SERVICE: FROM V-301 TO V-302
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 261.4
UNITS Min. Flow Norm. Flow Max Flow
1 FLOW RATE (Gas/Liquid) kg/h - 89925 -
2 INLET PRESSURE bar(g) - 27.6 -
3 OUTLET PRESSURE bar(g) - 26.9 -
4 DIFFERENTIAL PRESSURE bar - 0.700000000000003 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 61 -
6 DENSITY kg/m³ - 815.46 -
7 SPEC.GRAVITY *
- 0.863 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.26 -
10 VAPOR PRESSURE Pv bar(g) - 27.6 -
11 * REQUIRED Cv - 134.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Page 79 Of 145

Control Valve
FROM V-301 TO V-302

Shut-Off

Spring Return Diaphragm

Yes

barg
barg

Electro-Pneumatic / with LCD

Increase
Required

Eex (ia)-Zone1 IIB T4 / IP65


N/A

N/A

TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 80 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3102 P&ID NO : RR-02-PT-120-PR-PI-0029(1/3) SERVICE: V-301 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.7
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2151 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 25.5 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 61 -
6 DENSITY kg/m³ - 1149.91 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.52 -
10 VAPOR PRESSURE Pv bar(g) - ATM -
11 * REQUIRED Cv - 0.5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 3" & SCH.160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH.160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC pp / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 81 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3103 P&ID NO : RR-02-PT-120-PR-PI-0029(2/3) SERVICE: FROM V-302 TO V-303
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 219
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 98604 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 6.2 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 55 -
6 DENSITY kg/m³ - 823.23 -
7 SPEC.GRAVITY *
- 0.83 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.79 -
10 VAPOR PRESSURE Pv bar(g) - 6.9 -
11 * REQUIRED Cv - 161.4 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 10" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 82 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3104 P&ID NO : RR-02-PT-120-PR-PI-0029(2/3) SERVICE: V-302 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.4
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 1076 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 4.8 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 55 -
6 DENSITY kg/m³ - 1155.03 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.5 -
10 VAPOR PRESSURE Pv bar(g) - 2.32 -
11 * REQUIRED Cv - 0.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 2" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 83 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3101A P&ID NO : RR-02-PT-120-PR-PI-0029(1/3) SERVICE: V-301 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7336 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 25.9 -
4 DIFFERENTIAL PRESSURE bar - 1.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 34.02 -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- 26.4 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 35 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.87 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 84 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3101B P&ID NO : RR-02-PT-120-PR-PI-0029(1/3) SERVICE: FROM V-301 TO HP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7336 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 3.99 -
4 DIFFERENTIAL PRESSURE bar - 23.61 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 34.02 -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- 26.4 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 16 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.87 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 85 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3102A P&ID NO : RR-02-PT-120-PR-PI-0029(2/3) SERVICE: V-302 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6830 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 6.2 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 55 -
6 DENSITY kg/m³ - 12.22 -
7 SPEC.GRAVITY *
- 1.35 -
8 MOLECULAR WEIGHT *
- 37.7 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 84 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.93 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 10S 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 10S 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AS03 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 351 CF3M 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL AISI 316L 80 ACTUATION POINT N/A


42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
THERE ISNT IN PMS
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 86 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-3102B P&ID NO : RR-02-PT-120-PR-PI-0029(2/3) SERVICE: V-302 GAS TO LP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6830 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 6.82 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 55 -
6 DENSITY kg/m³ - 12.22 -
7 SPEC.GRAVITY *
- 1.35 -
8 MOLECULAR WEIGHT *
- 37.7 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 47 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.93 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 10S 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 10S 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AS03 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 351 CF3M 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL AISI 316L 80 ACTUATION POINT N/A


42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
THERE ISNT IN PMS
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 87 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3105 P&ID NO : RR-02-PT-120-PR-PI-0029(3/3) SERVICE: V-303 OIL OUTLET
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 199
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 95200 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 842 -
7 SPEC.GRAVITY *
- 0.842 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 2.78 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 272.3 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH N/A 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 88 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-3106 P&ID NO : RR-02-PT-120-PR-PI-0029(3/3) SERVICE: V-303 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.3
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 1076 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 1160.57 -
7 SPEC.GRAVITY *
- 1.16 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.55 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 2.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS
82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 89 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3103B P&ID NO : RR-02-PT-120-PR-PI-0029(3/3) SERVICE: V-303 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 4758 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.6 -
4 DIFFERENTIAL PRESSURE bar - 0.5 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 5.85 -
7 SPEC.GRAVITY *
- 1.67 -
8 MOLECULAR WEIGHT *
- 48.46 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 100 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 90 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3103A P&ID NO : RR-02-PT-120-PR-PI-0029(3/3) SERVICE: V-303 GAS TO LP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 4758 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 48.8 -
6 DENSITY kg/m³ - 5.85 -
7 SPEC.GRAVITY *
- 1.67 -
8 MOLECULAR WEIGHT *
- 48.46 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 74 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.95 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.13 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 91 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3201A P&ID NO : RR-02-PT-170-PR-PI-0030 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 651 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 22 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 4" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 92 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3201C P&ID NO : RR-02-PT-170-PR-PI-0030 SERVICE: FROM TK-301 TO SK-701
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2039 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 1.96 -
8 MOLECULAR WEIGHT *
- 56.89 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 326 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.13 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 20" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 20" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 16" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 16" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 16" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 93 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-3201B P&ID NO : RR-02-PT-170-PR-PI-0030 SERVICE: FROM TK-301 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 2039 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 1.96 -
8 MOLECULAR WEIGHT *
- 56.89 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 326 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 16" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10'' (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 10'' / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10'' / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH N/A 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 94 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-5602 P&ID NO : RR-02-PT-130-PR-PI-0049 SERVICE: TO PLANT AIR USERS
FLUID : GAS FLUID TYPE : INSTRUMENT AIR Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 520 -
2 INLET PRESSURE bar(g) - 8 - -
3 OUTLET PRESSURE bar(g) - 7.2 -
4 DIFFERENTIAL PRESSURE bar - 0.8 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 54.9 -
6 DENSITY kg/m³ - 8.4 -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- 29 -
9 VISCOSITY (Gas/Liquid) cp - - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 1 1/2'' & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 1 1/2'' & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3/4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 105 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3/4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3/4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM A 182 F6A 80 ACTUATION POINT N/A
42 *SEAT MATERIAL Seat: Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm N:NOT ISULATED/PAINTED PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 95 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-5701 P&ID NO : RR-02-PT-130-PR-PI-0054 SERVICE: FROM V-101 & V-301
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7233.6 -
2 INLET PRESSURE bar(g) - 26.6 - -
3 OUTLET PRESSURE bar(g) - 7 -
4 DIFFERENTIAL PRESSURE bar - 19.6 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 60 -
6 DENSITY kg/m³ - 30.15 -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 17 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.89 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Shut-Off
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 96 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-5401 P&ID NO : RR-02-PT-130-PR-PI-0055 SERVICE: FROM K.O DRUM V-506
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7233.6 -
2 INLET PRESSURE bar(g) - 7 - -
3 OUTLET PRESSURE bar(g) - 1 -
4 DIFFERENTIAL PRESSURE bar - 6 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 59 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.93 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 97 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-5203 P&ID NO : RR-02-PT-170-PR-PI-0057 SERVICE: TO TK-502
FLUID : LIQUID FLUID TYPE : RAW WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 50000 -
2 INLET PRESSURE bar(g) - 2 - -
3 OUTLET PRESSURE bar(g) - 1 -
4 DIFFERENTIAL PRESSURE bar - 1 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 58 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 98 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-5201 P&ID NO : RR-02-PT-170-PR-PI-0057 SERVICE: TO TK-502
FLUID : LIQUID FLUID TYPE : RAW WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 16666.67 -
2 INLET PRESSURE bar(g) - 2 - -
3 OUTLET PRESSURE bar(g) - ATM. -
4 DIFFERENTIAL PRESSURE bar - 2 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 986.8 -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.52 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 6.5 -
12 * TRAVEL % - 13.7 -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 99 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : LCV-5021 P&ID NO : RR-02-PT-170-PR-PI-0060(1/2) SERVICE: FROM PK-518 TO TK-503
FLUID : LIQUID FLUID TYPE : PROCESS WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 30000 -
2 INLET PRESSURE bar(g) - 2 - -
3 OUTLET PRESSURE bar(g) - 1 -
4 DIFFERENTIAL PRESSURE bar - 1 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- AMB. -
6 DENSITY kg/m³ - - -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.5-1 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 34.8 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 100 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-5021A P&ID NO : RR-02-PT-170-PR-PI-0060(1/2) SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 145 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 85 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 101 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-5021B P&ID NO : RR-02-PT-170-PR-PI-0060(1/2) SERVICE: FROM TK-503 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 145 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 85 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 33 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 102 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-5501 P&ID NO : RR-02-PT-170-PR-PI-0060(1/2) SERVICE: TO TK-503
FLUID : LIQUID FLUID TYPE : PROCESS WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 20000 -
2 INLET PRESSURE bar(g) - 13.8 - -
3 OUTLET PRESSURE bar(g) - 1 -
4 DIFFERENTIAL PRESSURE bar - 12.8 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- AMB. -
6 DENSITY kg/m³ - - -
7 SPEC.GRAVITY *
- 1 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 6.5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 103 Of 145
RR 02 PT 100 IN DT 0060 D00

Self Actuated Valve


TAG NO : SAV-5080 P&ID NO : RR-02-PT-170-PR-PI-0064 SERVICE: FROM FUEL GAS DISTRIBUTION HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 15 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - -
11 * REQUIRED Cv - 0.5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 1" & SCH. 80 56 * TYPE Self-actuated regulators
LINE

18 & SCHEDULE Out 1" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3/4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE VTA
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A 105 63 AVAILABLE MIN: N.A N.A
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: N.A N.A


26 END IN 3/4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3/4" / 300# 66 ACT. ORIENTATION VTA
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL N.A
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL N.A


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 N.A
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS N.A N.A
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification N.A
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM A 182 F6A 80 ACTUATION POINT N/A
42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE 0.07 PSIG


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm N:NOT ISULATED /PAINTED PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 104 Of 145
RR 02 PT 100 IN DT 0060 D00

Self Actuated Valve


TAG NO : SAV-5081 P&ID NO : RR-02-PT-170-PR-PI-0064 SERVICE: TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 15 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - -
11 * REQUIRED Cv - 3 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Self-actuated regulators
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3/4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE VTA
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: N.A N.A
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: N.A N.A


26 END IN 3/4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3/4" / 300# 66 ACT. ORIENTATION VTA
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL N.A
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL N.A


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 N.A
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS N.A N.A
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification N.A
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE 0.1 PSIG


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm N:NOT ISULATED /PAINTED PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 105 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-4001 P&ID NO : RR-02-PT-120-PR-PI-0032 SERVICE: TO TK-101 & TK-301
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 40.7
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 251350 -
2 INLET PRESSURE bar(g) - 6.7 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 6.62 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 62.7 -
6 DENSITY kg/m³ - 878.6 -
7 SPEC.GRAVITY *
- 0.853 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 13.7 -
10 VAPOR PRESSURE Pv bar(g) - 0.192 -
11 * REQUIRED Cv - 134.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 12" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 106 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-4401A P&ID NO : RR-02-PT-170-PR-PI-0036 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 940 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 85 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 31 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 107 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-4401B P&ID NO : RR-02-PT-170-PR-PI-0036 SERVICE: FROM TK-401 TO FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 1692 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 85 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 1.88 -
8 MOLECULAR WEIGHT *
- 54.5 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 276 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.98 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 12" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH.20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 108 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-4501 P&ID NO : RR-02-PT-120-PR-PI-0037 SERVICE: E-403-A TO TK-101 & TK-301
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 53.4
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 79530 -
2 INLET PRESSURE bar(g) - 2.6 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2.52 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 70 -
6 DENSITY kg/m³ - 824 -
7 SPEC.GRAVITY *
- 0.813 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 8.4 -
10 VAPOR PRESSURE Pv bar(g) - 2.6 -
11 * REQUIRED Cv - 181 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 109 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : TCV-4501 P&ID NO : RR-02-PT-120-PR-PI-0037 SERVICE: FROM E-403-A
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 53.4
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 79530 -
2 INLET PRESSURE bar(g) - 2.6 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2.52 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 70 -
6 DENSITY kg/m³ - 824 -
7 SPEC.GRAVITY *
- 0.813 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 8.4 -
10 VAPOR PRESSURE Pv bar(g) - 2.6 -
11 * REQUIRED Cv - 181 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 8" & SCH. 20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 110 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-6001A P&ID NO : RR-02-PT-170-PR-PI-0065 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 173.8 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 91 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 111 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6001B P&ID NO : RR-02-PT-170-PR-PI-0065 SERVICE: TK-601 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 173.8 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 91 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 41 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 112 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6401A P&ID NO : RR-02-PT-170-PR-PI-0068(1/2) SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 216.7 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 113 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6401B P&ID NO : RR-02-PT-170-PR-PI-0068(1/2) SERVICE: TK-603 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 216.7 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 51 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 114 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-6401 P&ID NO : RR-02-PT-170-PR-PI-0068(2/2) SERVICE: TO DISPOSAL TANK (TK-603)
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.1
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 22911.9 -
2 INLET PRESSURE bar(g) - 14 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 13.92 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 62.9 -
6 DENSITY kg/m³ - 1150.7 -
7 SPEC.GRAVITY *
- 1.15 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.8 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 4" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / FN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 600# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 600# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 115 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-6402 P&ID NO : RR-02-PT-170-PR-PI-0068(2/2) SERVICE: DISPOSAL WATER TO INJECTION WELL
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 76373 -
2 INLET PRESSURE bar(g) - 69 - -
3 OUTLET PRESSURE bar(g) - 68.3 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 62.9 -
6 DENSITY kg/m³ - 1150.7 -
7 SPEC.GRAVITY *
- 1.15 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.8 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 98.7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 6" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 6" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / FN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 10 barg


26 END IN 6" / 600# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 600# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 116 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6501A P&ID NO : RR-02-PT-170-PR-PI-0069 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 8.8 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 0 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A105 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# SW PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# SW 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH N.A 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 117 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6501B P&ID NO : RR-02-PT-170-PR-PI-0069 SERVICE: TK-602 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 21.7 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 118 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6601A P&ID NO : RR-02-PT-170-PR-PI-0070 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 101.2 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 3 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04/AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 119 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-6602B P&ID NO : RR-02-PT-170-PR-PI-0070 SERVICE: TK-604 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 101.2 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 24 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 120 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : LCV-6601 P&ID NO : RR-02-PT-170-PR-PI-0070 SERVICE: TK-604 SALTY WASTE WATER OUTLET
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 22684.2 -
2 INLET PRESSURE bar(g) - 0.18 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.1 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 1148.5 -
7 SPEC.GRAVITY *
- 1.19 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1.2 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 76.3 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC N / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
42 *SEAT MATERIAL M.KH: 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 121 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-6701A P&ID NO : RR-02-PT-170-PR-PI-0073(1/2) SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 42.9 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 91 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 1 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 122 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6701B P&ID NO : RR-02-PT-170-PR-PI-0073(1/2) SERVICE: TK-606 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 42.9 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 91 -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 10 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 123 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-6801 P&ID NO : RR-02-PT-170-PR-PI-0073(2/2) SERVICE: TO DISPOSAL TANK (TK-606)
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6789.42 -
2 INLET PRESSURE bar(g) - 68.96 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 68.88 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 1151.7 -
7 SPEC.GRAVITY *
- 1.15 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1.26 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 0.9 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / FN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 GR. WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 600# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 600# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 124 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-6802 P&ID NO : RR-02-PT-170-PR-PI-0073(2/2) SERVICE: DISPOSAL WATER TO INJECTION WELL
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 22631.4 -
2 INLET PRESSURE bar(g) - 68.96 - -
3 OUTLET PRESSURE bar(g) - 68.26 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- 61 -
6 DENSITY kg/m³ - 1151.7 -
7 SPEC.GRAVITY *
- 1.15 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 1.26 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 29.3 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / FN07 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 600# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 600# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 125 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-6801A P&ID NO : RR-02-PT-170-PR-PI-0074 SERVICE: FROM FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 8.8 -
2 INLET PRESSURE bar(g) - 1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.92 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 0 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 80 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A105 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 126 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-6801B P&ID NO : RR-02-PT-170-PR-PI-0074 SERVICE: TK-605 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 21.7 -
2 INLET PRESSURE bar(g) - 0.1 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 0.02 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 5 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 80 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 127 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-6312 P&ID NO : RR-02-PT-120-PR-PI-0075 SERVICE: FUEL GAS HEADER
FLUID : GAS FLUID TYPE : FUEL GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 722.7 -
2 INLET PRESSURE bar(g) - 3.5 - -
3 OUTLET PRESSURE bar(g) - 1.5 -
4 DIFFERENTIAL PRESSURE bar - 2 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 8.14 -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 11 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & SCH. 160 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & SCH. 160 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 128 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-6311 P&ID NO : RR-02-PT-120-PR-PI-0075 SERVICE: TO SOUR WATER STRIPPER TOWER (T-606)
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 6801.96 -
2 INLET PRESSURE bar(g) - 4.5 - -
3 OUTLET PRESSURE bar(g) - 0.5 -
4 DIFFERENTIAL PRESSURE bar - 4 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 1150 -
7 SPEC.GRAVITY *
- 1.19 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.52 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 3.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 2" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 2" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC N / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3/4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3/4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3/4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS YES 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
M.KH:
42 *SEAT MATERIAL 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS
82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 129 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : FCV-6310 P&ID NO : RR-02-PT-120-PR-PI-0075 SERVICE: TO DISPOSAL TANK (TK-606)
FLUID : LIQUID FLUID TYPE : SALTY WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 22673.2 -
2 INLET PRESSURE bar(g) - 4.5 - -
3 OUTLET PRESSURE bar(g) - 3.5 -
4 DIFFERENTIAL PRESSURE bar - 1 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 1150 -
7 SPEC.GRAVITY *
- 1.19 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.52 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 24.1 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 4" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC N / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 3" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL Alu-Br 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 3" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 3" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS YES 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM B 148 Gr. C 95800 80 ACTUATION POINT N/A
M.KH:
42 *SEAT MATERIAL 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA THERE ISNT IN PMS
82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 130 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-6310 P&ID NO : RR-02-PT-120-PR-PI-0075 SERVICE: T-606 TO LLP FLARE HEADER
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 722.7 -
2 INLET PRESSURE bar(g) - 1.5 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 1.42 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - 2.13 -
7 SPEC.GRAVITY *
- 0.91 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 19 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.99 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 3" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / AN05 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE OPEN
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS Yes 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 131 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV 1602A P&ID NO : RR-02-PT-170-PR-PI-0025(2/3) SERVICE: To Discharge Oil Transfer Pump
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 40.8
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 327662.8 -
2 INLET PRESSURE bar(g) - 33 - -
3 OUTLET PRESSURE bar(g) - 32.7 -
4 DIFFERENTIAL PRESSURE bar - 0.3 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.847 -
8 MOLECULAR WEIGHT *
- -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 754 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10" & SCH. XS 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8'' (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8'' / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8'' / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic/with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 132 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1602B P&ID NO : RR-02-PT-170-PR-PI-0025(2/3) SERVICE: To Discharge Oil Transfer Pump
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 40.8
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 327662.8 -
2 INLET PRESSURE bar(g) - 33 - -
3 OUTLET PRESSURE bar(g) - 32.7 -
4 DIFFERENTIAL PRESSURE bar - 0.3 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.847 -
8 MOLECULAR WEIGHT *
- -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 754 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10" & SCH. XS 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8'' (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8'' / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8'' / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic/with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 133 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : FCV-1602C P&ID NO : RR-02-PT-170-PR-PI-0025(3/3) SERVICE: To Discharge Oil Transfer Pump
FLUID : LIQUID FLUID TYPE : OIL Critical Press. Pc (bar(a)) (Gas/Liq) 40.8
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 327662.8 -
2 INLET PRESSURE bar(g) - 33 - -
3 OUTLET PRESSURE bar(g) - 32.7 -
4 DIFFERENTIAL PRESSURE bar - 0.3 -
SERVICE CONDITION

5 INLET TEMPERATURE OC
- -
6 DENSITY kg/m³ - -
7 SPEC.GRAVITY *
- 0.847 -
8 MOLECULAR WEIGHT *
- -
9 VISCOSITY (Gas/Liquid) cp - -
10 VAPOR PRESSURE Pv bar(g) - 0.08 -
11 * REQUIRED Cv - 754 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) OC
- - -
17 PIPE LINE SIZE In 10" & SCH. XS 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 10" & SCH. XS 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PT / CN04 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8'' (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8'' / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8'' / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic/with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS NO 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 134 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1101 P&ID NO : RR-02-PT-120-PR-PI-0023(1/3) SERVICE: FROM V-101 TO 2nd STAGE SEPARATOR
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 264.3
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 329595.2 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 6.9 -
4 DIFFERENTIAL PRESSURE bar - 20.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 844.12 -
7 SPEC.GRAVITY *
- 0.844 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 4.36 -
10 VAPOR PRESSURE Pv bar(g) - 27.6 -
11 * REQUIRED Cv - 246.7 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 16" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 135 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1102 P&ID NO : RR-02-PT-120-PR-PI-0023(1/3) SERVICE: V-101 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.3
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 8070 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 25.5 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 1148.04 -
7 SPEC.GRAVITY *
- 1.148 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.44 -
10 VAPOR PRESSURE Pv bar(g) - 2.32 -
11 * REQUIRED Cv - 1.9 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 4" & SCH. 120 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 4" & SCH. 120 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL 13Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™ 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 136 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1103 P&ID NO : RR-02-PT-120-PR-PI-0023(2/3) SERVICE: FROM V-102 TO V-103
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 218.3
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 312167.9 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 5.8 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 857.51 -
7 SPEC.GRAVITY *
- 0.857 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 6.37 -
10 VAPOR PRESSURE Pv bar(g) - 6.9 -
11 * REQUIRED Cv - 502.6 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 12" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 10" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 10" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 10" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 137 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1104 P&ID NO : RR-02-PT-120-PR-PI-0023(2/3) SERVICE: V-102 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 8070 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 2.1 -
4 DIFFERENTIAL PRESSURE bar - 4.8 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 1149.97 -
7 SPEC.GRAVITY *
- 1.148 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 0.46 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 4 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 3" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1 1/2" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1 1/2" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1 1/2" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS YES 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM A182 80 ACTUATION POINT N/A


42 *SEAT MATERIAL AISI 316 + Stellite 6 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 138 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1103B P&ID NO : RR-02-PT-120-PR-PI-0023(1/3) SERVICE: V-101 GAS OUTLET
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 158608 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 3.99 -
4 DIFFERENTIAL PRESSURE bar - 23.61 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 11.06 -
7 SPEC.GRAVITY *
- 0.911 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 353 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.9 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 16" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 139 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1103A P&ID NO : RR-02-PT-120-PR-PI-0023(1/3) SERVICE: FROM V-101
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 158608 -
2 INLET PRESSURE bar(g) - 27.6 - -
3 OUTLET PRESSURE bar(g) - 25.9 -
4 DIFFERENTIAL PRESSURE bar - 1.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 11.06 -
7 SPEC.GRAVITY *
- 0.911 -
8 MOLECULAR WEIGHT *
- 26.41 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 766 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.9 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 16" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 16" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / CN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 12" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 12" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 12" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 140 Of 145
RR 02 PT 100 IN DT 0060 D00
Control Valve
TAG NO : PCV-1104B P&ID NO : RR-02-PT-120-PR-PI-0023(2/3) SERVICE: V-102 TO LP FLARE
FLUID : GAS FLUID TYPE : GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 9356 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 0.2 -
4 DIFFERENTIAL PRESSURE bar - 6.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 5.53 -
7 SPEC.GRAVITY *
- 1.25 -
8 MOLECULAR WEIGHT *
- 36.37 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 66 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 4" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE CLOSE
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 4" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 4" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Open
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 141 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1104A P&ID NO : RR-02-PT-120-PR-PI-0023(2/3) SERVICE: V-102 GAS TO V-702
FLUID : GAS FLUID TYPE : FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq) -
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 9356 -
2 INLET PRESSURE bar(g) - 6.9 - -
3 OUTLET PRESSURE bar(g) - 6.2 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 63.9 -
6 DENSITY kg/m³ - 5.53 -
7 SPEC.GRAVITY *
- 1.25 -
8 MOLECULAR WEIGHT *
- 36.37 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 118 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.94 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE OPEN
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE Close
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 142 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1305 P&ID NO : RR-02-PT-120-PR-PI-0023(3/3) SERVICE: FROM V-103 OIL OUTLET
FLUID : LIQUID FLUID TYPE : CRUDE OIL Critical Press. Pc (bar(a)) (Gas/Liq) 196
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 300707 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 57.2 -
6 DENSITY kg/m³ - 868.48 -
7 SPEC.GRAVITY *
- 0.869 -
8 MOLECULAR WEIGHT *
- - -
9 VISCOSITY (Gas/Liquid) cp - 8.46 -
10 VAPOR PRESSURE Pv bar(g) - 2.1 -
11 * REQUIRED Cv - 838 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 12" & SCH. 40 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 12" & SCH. 40 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Butterfly 59 ON / OFF MODULATING N.A Yes
21 * SIZE 8" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 8" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 8" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH N/A 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Wafer Type 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 143 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : LCV-1303 P&ID NO : RR-02-PT-120-PR-PI-0023(3/3) SERVICE: V-103 WASTE WATER
FLUID : LIQUID FLUID TYPE : WASTE WATER Critical Press. Pc (bar(a)) (Gas/Liq) 221.2
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 4034 -
2 INLET PRESSURE bar(g) - 2.1 - -
3 OUTLET PRESSURE bar(g) - 1.4 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 57.2 -
6 DENSITY kg/m³ - 1153.09 -
7 SPEC.GRAVITY *
- 1.148 -
8 MOLECULAR WEIGHT *
- 53.84 -
9 VISCOSITY (Gas/Liquid) cp - 0.48 -
10 VAPOR PRESSURE Pv bar(g) - ATM. -
11 * REQUIRED Cv - 5.2 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - - -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - - -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 3" & PN=20 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 3" & PN=20 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AX01 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 1" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE VTA
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 1" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 1" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE CLOSE
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS YES 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Linear 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL ASTM A182 80 ACTUATION POINT N/A


42 *SEAT MATERIAL AISI 316 + Stellite 6 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Project Package Comp Scope Disc Doc. Code Sequence No. Rev. Code
Contract No: Code any Code
RR-OI-PT-9808-PM-CN-0015
code Page 144 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1306A P&ID NO : RR-02-PT-120-PR-PI-0023(3/3) SERVICE: V-103 TO V701
FLUID : GAS FLUID TYPE : VENT GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7427 -
2 INLET PRESSURE bar(g) - 2.08 - -
3 OUTLET PRESSURE bar(g) - 1.38 -
4 DIFFERENTIAL PRESSURE bar - 0.7 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 51 -
6 DENSITY kg/m³ - 2.23 -
7 SPEC.GRAVITY *
- 1.63 -
8 MOLECULAR WEIGHT *
- 47.2 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 138 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.96 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Open
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE CLOSE
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
Ramshir Oil Field Development
Ramshir Oil and Gas Processing Complex
DATA SHEET FOR CONTROL / REGULATOR VALVES
Comp
Project Disc
Contract No: Code Package any Scope Code Doc. Code Sequence No. Rev. Code
RR-OI-PT-9808-PM-CN-0015
code Page 145 Of 145
RR 02 PT 100 IN DT 0060 D00

Control Valve
TAG NO : PCV-1306B P&ID NO : RR-02-PT-120-PR-PI-0023(31/3) SERVICE: V-103 GAS TO FLARE
FLUID : GAS FLUID TYPE : LP FLARE GAS Critical Press. Pc (bar(a)) (Gas/Liq)
UNITS Min. Flow Norm. Flow Max Flow Shut-Off
1 FLOW RATE (Gas/Liquid) kg/h - 7427 -
2 INLET PRESSURE bar(g) - 2.08 - -
3 OUTLET PRESSURE bar(g) - 0.08 -
4 DIFFERENTIAL PRESSURE bar - 2 -
SERVICE CONDITION

5 INLET TEMPERATURE °C
- 51 -
6 DENSITY kg/m³ - 2.23 -
7 SPEC.GRAVITY *
- 1.63 -
8 MOLECULAR WEIGHT *
- 47.2 -
9 VISCOSITY (Gas/Liquid) cp - 0.01 -
10 VAPOR PRESSURE Pv bar(g) - - -
11 * REQUIRED Cv - 119 -
12 * TRAVEL % - - -
13 ALLOWABLE / *PREDICTED SPL dBA - Max 85 dBA (VTC) -
14 COMPRESSIBILITY Z - 0.96 -
15 SPEC. HEAT RATIO(K=Cp/Cv) (Gas/Liquid) - 1.3 -
16 CRITICAL TEMP. (Gas/Liquid) °C
- - -
17 PIPE LINE SIZE In 8" & SCH. 60 56 * TYPE Spring Return Diaphragm
LINE

18 & SCHEDULE Out 8" & SCH. 60 57 * MFR. & MODEL VTA
19 PIPE LINE INSULATION/SPEC PP / AN06 58 *SIZE VTA
20 * TYPE Globe 59 ON / OFF MODULATING N.A Yes
21 * SIZE 6" (Vendor to Verify) 60 SPRING ACTION OPEN /CLOSE Close
ACTUATOR

22 DESIGN PRESS./TEMP AS PER PMS 61 *MAX ALLOWABLE PRESSURE VTA


23 * MFR. & MODEL VTA 62 *MIN REQUIRES PRESSURE OPEN
24 * BODY / BONNET MATL ASTM A216 WCB 63 AVAILABLE MIN: 3 barg
VALVE BODY/BONNET

25 *LINER MATERIAL / ID 64 AIR SUPPLY MAX: 9 barg


26 END IN 6" / 300# PRESSURE
65 *BENCH RANGE 3~15 psi
27 CONNECTION OUT 6" / 300# 66 ACT. ORIENTATION VERTICAL UP
28 FLG FACE FINISH RF 67 HAND WHEEL N.A
29 END EXT./MATL. VTA 68 AIR FAILURE VALVE N.A
30 *FLOW DIRECTION VTA 69 ADJSTABLE LIMIT STOP
31 * TYPE OF BONNET Standard 70 INPUT SIGNAL 4-20 mA/HART
32 LUBE & ISO VALVE NO 71 * TYPE Electro-Pneumatic / with LCD
POSITIONER

33 *PACKING MATERIAL PTFE based 72 * MFR. & MODEL VTA


* ON INCR SIGNAL OUTPUT
34 *PACKING TYPE V-Ring(VTA) 73 Increase
INCR / DECR
35 NACE REQUIREMENTS No 74 GAUGES BYPASS Yes Required
36 * TYPE Single Seat 75 *CAM CHARACTERISTIC N.A
37 * SIZE RATED TRAVEL VTA VTA 76 Electrical Certification Eex (ia)-Zone1 IIB T4 / IP65
38 *CHARACTERISTICS Equal % 77 * TYPE QUANTITY N/A N/A
SWITCHES

39 *BALANCED / UNBALANCED VTA 78 * MFR. & MODEL N/A


LIMT

40 * RATED Cv: *FL: *XT: VTA VTA VTA 79 CONTACTS / RATING N/A
TRIM

41 *PLUG / BALL / DISK MATERIAL Cr 80 ACTUATION POINT N/A


42 *SEAT MATERIAL Stellite 6™, 81 TAG NO. : N/A
43 *CAGE / GUIDE MATERIAL VTA 82 * MFR. & MODEL VTA
AIR SET

44 * STEM / MATERIAL 316 S.S. 83 * SET PRESSURE VTA


45 LEAKAGE CLASS IV 84 FILTER Yes
46 85 GAUGES Yes
47 SOLENOID VALVE N.A 86
SPECIAL/ACCESS.

48 MANUAL RESET N.A 87 * HYDRO PRESSURE Yes


TEST

49 TAG NO Required 88 ANSI/FCI LEAKAGE CLASS Yes


50 FUSIBLE LEAKAGE N.A 89 FUNCTIONAL TEST Yes
51 BLOCK RELAY N.A 90
52 BOOSTER N.A 91
53 CARTRIDGE N.A 92
54 POSITION TRANSMITTER 4-20 mA/HART-Loop Powered 93
55 VOLUME TANK N.A 94
* INFORMATION SUPPLIED BY MANUFACTURER UNLESS ALREADY SPECIFIED
Notes: VTA:Vendor to Advise PMS:PIPING MATERIAL SPECIFICATION VTC:Vendor to Confirm PP:PERSONNAL PROTECTION PT:PAINTING
* ALL INFORMATION SHOULD BE COMPLETED BY VENDOR.
* VENDOR IS RESPONSIBLE TO PROPOSE HIS BEST TO MEET THE SERVICE CONDITIONS AND PROJECT REQUIREMENTS AND SUBMIT THE
RELEVANT CALCULATION SHEETS.
1) WETTED PARTS MATERIAL SHALL BE SUITABLE FOR SOUR SERVICES ACCORDING TO NACE MR-0175
THESE ITEM HAVE GATE LEGEND IN THESE ITEM HAVE BUTTERFLY LEGEND
PID IN PID

PCV-4001 5021B

LCV-4501 PCV-6401B

TCV-4501 PCV-6001B

PCV-4401A PCV-6501B

PCV-4401B PCV-6602B

PCV-6801A PCV-6701B

FCV-6801 PCV-6801B

PCV-6701A

FCV-6802

PCV-6601A

LCV-6601

PCV-6501A

PCV-6401A

FCV-6401

FCV-6402

PCV-6001A

PCV-6310

FCV-6311

FCV-6310

FCV-6312

Potrebbero piacerti anche