Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
h i g h l i g h t s
a r t i c l e i n f o a b s t r a c t
Article history: External walls provide an important barrier between occupied building spaces and variable ambient con-
Received 9 March 2013 ditions. Building insulation is often optimized for static performance based on its R-Value rating, but a
Received in revised form 6 June 2013 growing body of literature has begun to assess the dynamic thermal performance of multi-layer walls.
Accepted 12 June 2013
The focus of this work is to provide fundamental insight into configuring wall layers for improved insu-
Available online 6 July 2013
lating performance. Thirty-three different walls are evaluated based on four primary configurations with
fixed volumes of insulation and thermal mass. Only the layer distribution is varied. Because the total vol-
Keywords:
ume of each material is fixed, the overall thermal resistance and capacitance are equivalent for all con-
Insulation
Thermal mass
figurations studied. An electrical analogy is used to model the one dimensional heat conduction through
Energy savings the wall and determine the magnitude ratio and phase of the frequency response evaluated at the fre-
Optimization quency corresponding to a period of 1 day. The two temperatures used to quantify the wall system trans-
Buildings fer function are the inside and outside surfaces of the wall (i.e., two surfaces exposed to the indoor and
outdoor environments, respectively). The best insulating performance is achieved when insulation layers
are positioned as close as possible to the inside and outside layers of the wall (i.e., near the indoor and
outdoor environments). In addition, optimal results occur when both the insulation and thermal mass
are distributed evenly throughout the wall. Using this optimized configuration, each material is then
divided into an increasing number of thinner layers. Results indicate that an optimum number of layers
exist such that the magnitude ratio is maximized.
Ó 2013 Elsevier Ltd. All rights reserved.
0306-2619/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.apenergy.2013.06.024
236 D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245
outside surfaces. Many studies compare performance when insula- insulation towards the outside. The highest energy demand results
tion is placed near the inside or outside wall surface. Others from a light weight wall configuration with no significant thermal
experiment with various multi-layer configurations. Some studies mass layers. The lack of thermal mass in this poorly performing
consider both insulation optimization and investigation of the ac- assembly illustrates its importance.
tual configuration (i.e., order and number of layers). Unlike other studies that consider different combinations and
For example, Al-Sanea and Zedan [2] compare two wall config- configurations of insulation and thermal mass layers in a wall,
urations using single layers of insulation and thermal mass. The Asan and Sancaktar [8] evaluate the thermal performance of vari-
decrement factor is analyzed for the two wall configurations and ous building materials independently. They develop a numerical
for different response time periods, including an initial transient solution to the one dimensional heat equation and investigate
or instantaneous response and a steady periodic response. Between the effects of wall thickness and material properties on time lag
the two configurations, insulation towards the inside yields a low- and decrement factor. Results demonstrate common conclusions,
er instantaneous load, but insulation towards the outside has a such as the time lag increases and decrement factor decreases with
much longer time lag (almost 10 times). The results are somewhat increasing heat capacity; time lag increases and decrement de-
conflicting, since insulation on the inside is better for reducing the creases with increasing thickness; and, low thermal conductivity
load while insulation at the outside is better for increasing time and high heat capacity yield longer time lags. In a subsequent
lag, both features of effective insulating walls. In a follow up study study, Asan [9] evaluates heat conduction in 26 building materials.
[3], the two configurations are studied while varying the amount The time lag and decrement factor for each building material are
and position of thermal mass under steady periodic conditions. calculated for 8 variations of a single layer wall thickness. For all
The total wall resistance is maintained by varying the mass and the materials, the decrement factor decreases with increased wall
insulation layer thicknesses. Results show that increasing the thickness, and for small thicknesses (roughly less than 0.050 m)
amount of thermal mass in the wall leads to lower transmission the decrement factor is nearly constant. The decrement factor
loads during swing seasons when temperatures are not extreme. tends to zero for wall thickness greater than 1 m, and for wall
They find that for any set amount of thermal mass, positioning thickness less than 1 cm, all materials exhibit zero time lag. In
the mass towards the inside surface and positioning the insulation the second part of the study, two multi-layer walls are analyzed:
near the outside surface yields better overall thermal performance. one with three layers and no insulation and one with five layers
Kossecka and Kosny [4] evaluate six wall configurations using a including insulation. For the same thickness wall, the wall with
simplified building model and a one story residential building insulation has a longer time lag and lower decrement factor. In
model simulated with six different US climates. The thermal per- these two works, Asan analyzes a large set of walls and provides
formance of the walls is evaluated in terms of annual building generalized conclusions relating material properties to thermal
heating and cooling demands and total annual energy demands performance, but suggests that future work will aim to optimize
as calculated by the building modeling program. Each wall has insulation thickness and position to achieve larger time lags and
internal layers of concrete and insulation with either one or two smaller decrement factors.
layers of each such that all of the walls have the same total resis- In a more recent study, Asan [10] evaluates six wall configura-
tance and capacitance values. The study agrees with previous find- tions for time lag and decrement factor based on a Crank Nicolson
ings that walls with concrete layers at the inside and insulation numerical solution to the one-dimensional heat equation with
layers at the outside show the best building energy savings. In periodic convection boundary conditions. Fewer than six configu-
terms of dynamic performance criteria, part of the study indicates rations are actually studied due to overlap between the different
that a concrete/insulation/concrete configuration has a lower dec- configuration ‘families’. Two different thermal mass and insulation
rement factor than a configuration of insulation/concrete/insula- materials are selected each, so that a total of four thermal mass-
tion, which has a longer time lag. The authors describe an even insulation combinations are studied. The minimum decrement fac-
distribution of insulation on either side of the mass, but they do tor is achieved with half the insulation at the inner and outer walls,
not consider other wall configurations with unevenly distributed while the maximum time lag is achieved with two layers of insu-
layers. Furthermore, because these results seem to conflict, the lation located within the wall, equidistant from the inner and outer
need for clear and unambiguous guidelines for assembling multi- surfaces. While practical guidelines for renovating building walls
layer walls remains. for improved insulating performance are provided from the results,
Two other studies consider different mass/insulation configura- the number of layers studied was limited and different weighting
tions. Bojić and Loveday [5] find an alternating insulation/mass/ configurations were not considered.
insulation configuration is better under intermittent heating con- Another such study that addresses insulation thickness and po-
ditions and an alternating mass/insulation/mass configuration is sition is Al-Sanea and Zedan [11]. They evaluate the number and
better under intermittent cooling conditions. In a separate study distribution of insulation layers in a wall with fixed amounts of
from Bojic et al. [6], six wall configurations are analyzed within a insulation and thermal mass. The wall width is fixed and the total
full building model of two high-rise residences comprised of vari- amount of insulation is optimized for cost and energy performance.
ous flats facing different directions on each floor. Results show that Different wall configurations are arranged and thermal perfor-
thicker insulation reduces the cooling load and insulation at the in- mance evaluated. The study concludes that the best configurations
side position yields the lowest annual cooling load. Cooling de- for insulating performance have either two layers of insulation di-
mand results are varied, however. It is lower for insulation at the vided between the outside and middle layers or three layers of insu-
outside position for some flats and at the inside positions for other lation split evenly among the outside, middle, and inside layers. The
flats. The authors suggest this is due to the different orientation of study only considers evenly distributing insulation layers, and the
the flats within the building. The mixed results suggest that whole analysis is limited to using one, two, and three layers of insulation.
building simulation may not be the best tool for analyzing thermal The effects of increasing the number of insulation layers further is
dynamic wall performance. not explored nor is the concept of using unevenly distributed layers.
In a slightly different study, Aste et al. [7] analyzes six represen- In a supporting study, Mavromatidis et al. [12] investigate the ef-
tative wall configurations as a Southern facing wall within a whole fects of wall composition and orientation on time lag and decrement
building analysis. All of the walls have the same R-value but differ- factor. The authors conclude that their multi-layer insulation (MTI)
ent values of thermal capacity and mass per unit area. The wall has the best overall thermal performance and increases time lag
system with the lowest energy demand is a two layer wall with compared to insulation alone, citing similar results from Al-Sanea.
D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245 237
lation results from different fundamental wall configurations A block diagram in Fig. 2c shows the system frequency response
which ultimately provides insight into optimizing designs for mul- function G(jx) with an ambient sinusoidal input and the output
ti-layered walls. as a modified amplitude and peak time shifted by /.
The studies referenced in this work use either simplified analyt- Based on the RC wall system model described above, the system
ical calculations, numerical analysis, or whole building simulation transfer function is determined for frequency analysis. Fig. 3a shows
to evaluate the performance of different wall configurations. In this the RC circuit model for a wall with N layers, where Tamb is the input
study, each wall layer is modeled as a T-shaped RC circuit with the and Ts,rm is the system output. The outside and inside surface heat
resistance divided evenly on each side of the capacitance, as shown transfer coefficients (hamb and hrm) are approximated using the ASH-
in Fig. 2a. This analysis is in accordance with multiple studies [16– RAE [19] procedure for estimating surface conductance. The inner
18] that determine the time lag and decrement factor for heat con- and outer layer material is cement plaster with a summer time wind
duction in external walls using an electrical analogy. The RC sys- speed of 7.5 mp h and building material emissivity of 0.90 used in
tem is formed by connecting each layer in series with resistance the calculation to obtain hamb = 16.74 W/m2 K and hrm = 8.23 W/
added at each end to capture the convective heat transfer at both m2 K. However, only the inside convection coefficient is applicable
interior (Rh,rm) and exterior (Rh,amb) sides of the wall. The wall tem- to this model, because the decrement factor and time lag relate in-
perature at the outside surface is denoted as Ts,amb, while the wall side and outside surface temperatures. The outside convection coef-
temperature at the inside surface of the wall is denoted Ts,rm. The ficient affects outside surface temperature, but the outside surface
inside room and surface temperature will oscillate as a result of temperature is considered the input to the wall system modeled
the outside temperature fluctuation. The outside temperature is here. In other words, the transfer functions compared for various
modeled as a sinusoidal input with a 24 h period. The wall acts wall configurations are from Ts,amb to Ts,rm, and do not include Rh,amb,
as a filter to reduce the amplitude of the transmitted signal and which is there simply to complete the circuit analogy that includes
to shift the signal in time, as in Fig. 2b. The amplitude ratio of an ideal ambient temperature source. As described previously, this
the outside surface temperature Ts,amb to the inside surface temper- model is decoupled from any specific weather signal.
ature Ts,rm is known as the decrement factor (df), and defined The resistance (R) and capacitance (C) of each layer are based on
equivalently to the magnitude ratio (M): three material properties: thermal conductivity (k), density (q),
and heat capacity (Cp). They also depend on the layer thickness
Amplitude of T s;rm Arm (L) according to the following equations:
df ¼ ¼ ¼j GðjxÞ j¼ M ð1Þ
Amplitude of T s;amb Aamb
L
The magnitude ratio (magnitude of the transfer function G(jx), a R¼ ð3Þ
k
term more familiar with traditional frequency response), is evalu-
ated at x = xday. The phase angle (/) can likewise be evaluated at C ¼ Cp q L ð4Þ
x = xday in order to find the time lag (tlag) in hours according to
the following equation: The wall system transfer function is determined using an imped-
ance method and voltage divider calculation. The impedance value
24 h for the resistance of layer ‘‘i’’ is:
t lag ¼ /ðxday Þ ¼ ð2Þ
2p
1
Z Ri ¼ Ri ð5Þ
2
where the division by two is included to account for the fact that
the thickness of each layer is divided into two as previously dis-
cussed. The corresponding impedance for the capacitance of layer
‘‘i’’ is:
1
Z Ci ¼ ð6Þ
sC i
The RC circuit can be simplified by recognizing that the transfer
function of primary interest, G(jx) = Ts,rm/Ts,amb, can be expressed
as the product of intermediate transfer functions, shown in the fol-
lowing equation:
T s;rm T n T n1 T 1 T s;rm
¼ ð7Þ
T s;amb T s;amb T n T2 T1
To determine the intermediate transfer functions, the circuit is col-
lapsed from right to left by combining individual impedances in ser-
ies or in parallel. The transfer function relating each layer is
calculated as the circuit is reduced. The transfer function for the
innermost layer, including convective resistance (Rh,rm), is calcu-
lated first. In Eq. (8), T1 represents the temperature in the first layer,
measured as the voltage across the first capacitor C1.
T s;rm Rh;rm
¼ ð8Þ
T1 Rh;rm þ Z R1
Fig. 2. RC system analysis: (a) RC network diagram, (b) ambient temperature (left)
and inside wall temperature after filtering (right), and (c) frequency response The circuit can then be reduced as shown in Fig. 3b using an equiv-
representation of wall. alent impedance Z eq1 defined in Eq. (9) as:
D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245 239
Fig. 3. N-layer RC network diagram: (a) full circuit, (b) collapsed circuit to first equivalent impedance, and (c) collapsed circuit to second equivalent impedance.
1
1 1 Then taking the product of each intermediate transfer function, as
Z eq1 ¼ þ ð9Þ shown in Eq. (7), gives the final relationship of interest G(jx) = Ts,-
Z R1 þ Rh;rm Z C 1
rm/Ts,amb, which is easily evaluated for any value of x. The magni-
The transfer function relating T1 to T2 is also calculated as a voltage tude ratio and phase at a period of 24 h (xday = 7.27e5 rad/s) are
divider: extracted from the frequency analysis for each wall assembly sys-
T1 Z eq1 tem. This procedure is used to develop transfer functions for each
¼ ð10Þ wall assembly considered, thereby enabling a quick and simple fre-
T 2 Z eq1 þ Z R1 þ Z R2
quency analysis procedure.
Defining a new nested impedance, Z eq2 , the circuit can be further
collapsed as shown in Fig. 3c, where equivalent impedance Z eq2 is
calculated in a similar manner. The general expression for equiva- 2.2. RC model validation
lent impedance for the ith layer Z eqi is simply:
To validate the model used in this study, the seven wall config-
1
1 1 urations from Al-Sanea and Zedan [11] are modeled using this RC
Z eqi ¼ þ ð11Þ
Z eqi1 þ Z Ri1 þ Z Ri Z C i circuit methodology and results are compared with those pub-
lished. The seven wall configurations are shown in Fig. 11 in the
Subsequent transfer functions relating T2 to T3, T3 to T4, and eventu- Appendix. Each wall contains 200 mm concrete and 78 mm insula-
ally Ti1 to Ti, are calculated as: tion distributed in varying configurations between two 15 mm lay-
T i1 Z eqi1 ers of cement plaster on both inner and outer surfaces. The same
¼ ð12Þ overall wall thickness (308 mm) and total volume of each material
Ti Z eqi1 þ ðZ Ri1 þ Z Ri Þ
is fixed, so the total resistance and capacitance values do not
Table 1
Model validation results.
Wall system Decrement factora (%) Magnitude ratio (%) Time laga (h) Phase (h)
Wall 1a 1.35 1.51 6.13 5.92
Wall 1b 1.34 1.55 7.33 7.53
Wall 1c 0.74 0.90 6.71 6.10
Wall 2a 0.42 0.51 9.33 8.97
Wall 2b 0.24 0.33 8.19 6.76
Wall 2c 0.26 0.31 10.44 10.07
Wall 3 0.13 0.16 12.13 11.27
a
Decrement factor and time lag results from Al-Sanea et al. [15] compared with magnitude ratio and phase results from frequency analysis. Al-Sanea wall configurations
are reproduced for visual reference in the Appendix Fig. 11.
240 D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245
Table 2
Weighting variations for each of three wall configurations and extended Wall 0 configurations (8, 9, and 10). Layer lengths are displayed as percentages of total wall insulation or
thermal mass.
3 family is reversed with insulation at the middle and outside. thickness, or distribution, and material position. Wall 0.0, with
Variations of these four primary or base configurations are ex- evenly distributed layers, is extended to investigate the effect of
tended to investigate different weighting scenarios for the insula- increasing the total number of layer divisions. As with the other
tion and concrete layers. wall variations, Walls 0.8, 0.9, and 0.10 have the same total volume
Any weighting distribution might be selected for study with of insulation and concrete, thus maintaining the same overall resis-
infinitely many scenarios possible. For this paper, scenarios are tance and capacitance. However, each wall configuration divides
studied in which each base configuration, 0.0, 1.0, 2.0, and 3.0, is the two materials into a greater number of thinner layers. One
extended using different volumetric weightings. Specifically, con- might expect further divisions to continually improve perfor-
figurations are constructed to investigate alternatively weighting mance, but results will be discussed that suggest otherwise.
insulation, concrete, or both insulation and concrete by 80% of each
material volume towards the outside, middle, or inside of the wall.
Table 2 shows the configurations for all walls studied. For example, 3. Results and discussion
Wall 0.1 weights 80% of the insulation towards the outside with
the remaining 20% divided evenly between the middle and inside. Figs. 5–8 illustrate the (a) magnitude ratio and (b) phase results
Similarly, Wall 1.1 weights 80% of the concrete towards the out- for each material weighting configuration of the four wall families.
side. Wall 1.2 weights 80% of the concrete towards the middle, Fig. 5a, for example, shows the magnitude ratio results for Wall 0.0
and Wall 1.3 shifts it to the inside. Walls 1.4 and 1.5 alternate through 0.7 from the RC model frequency analysis, and Fig. 5b
weighting the two insulation layers towards the outside or inside, shows the respective phase results. Each bar is shaded and labeled
while Walls 1.6 and 1.7 alternate weighting concrete and insula- to indicate which material is weighted (no weighting or evenly dis-
tion layers towards the outside or inside together. tributed, insulation weighting, concrete weighting, or both in a
The four base configurations and the various weighting scenar- combined weighting) and in what direction the weighting is ap-
ios are designed to clarify wall assembly guidelines regarding layer plied (outside, middle, or inside). Refer to Fig. 4 and Table 2 for
242 D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245
Fig. 5. (a) Magnitude ratio and (b) phase results for Wall 0 weighting Fig. 6. (a) Magnitude ratio and (b) phase results for Wall 1 weighting
configurations. configurations.
Fig. 7. (a) Magnitude ratio and (b) phase results for Wall 2 weighting Fig. 8. (a) Magnitude ratio and (b) phase results for Wall 3 weighting
configurations. configurations.
4. Conclusions
Appendix A
Fig. 11. Al-Sanea [11] Wall configurations: Wall 3 has insulation at inside, middle,
and outside.
See Fig. 11.
model, dividing each thermal mass layer into a greater number of References
layers increases the number of poles in the transfer function of the
model, since the impedance of each capacitance layer adds an inte- [1] Chen A. Closing in on zero-energy buildings. Environ Energy Technol Division
News 2008;8(2).
grator. The increased number of poles increases the negative slope
[2] Al-Sanea SA, Zedan MF. Effect of insulation location on initial transient thermal
of the phase response, resulting in a longer phase lag at the same response of building walls. J Therm Envelope Build Sci 2001;24:275–300.
D.E.M. Bond et al. / Applied Energy 112 (2013) 235–245 245
[3] Al-Sanea SA, Zedan MF, Al-Ajlan SA, Hadi ASA. Heat transfer characteristics and [16] Fraisse G, Viardot C, Lafabrie O, Achard G. Development of a simplified and
optimum insulation thickness for cavity walls. J Build Phys accurate building model based on electrical analogy. Energy Build
2003;26(3):285–307. 2002;34:1017–31.
[4] Kossecka E, Kosny J. Influence of insulation configuration on heating and [17] Peng C, Wu Z. Thermoelectricity analogy method for computing the periodic
cooling loads in a continuously used building. Energy Build 2002;34:321–31. heat transfer in external building envelopes. Appl Energy 2008;85:735–54.
[5] Bojić ML, Loveday DL. The influence on building thermal behavior of the [18] Davies MG. Optimum design of resistance and capacitance elements in
insulation/masonry distribution in a three-layered construction. Energy Build modelling a sinusoidally excited building wall. Build Environ 1983;18:19–37.
1997;26(2):153–7. [19] ASHRAE Handbook. Fundamentals. American society of heating. Refrigerating
[6] Bojic M, Yik F, Sat P. Influence of thermal insulation position in building and Air-Conditioning Engineers, Inc., Atlanta, GA; 2009.
envelope on the space cooling of high-rise residential buildings in Hong Kong.
Energy Build 2001;33:569–81.
[7] Aste N, Angelotti A, Buzzetti M. The influence of the external walls thermal
Glossary
inertia on the energy performance of well insulated buildings. Energy Build
2009;41:1181–7. xday: frequency whose period is one day
[8] Asan H, Sancaktar YS. Effects of wall’s thermophysical properties on time lag k: thermal conductivity
and decrement factor. Energy Build 1998;28:159–66. q: density
[9] Asan H. Numerical computation of time lags and decrement factors for Cp: heat capacity
different building materials. Build Environ 2006;41:615–20. df: decrement factor
[10] Asan H. Investigation of wall’s optimum insulation position from maximum M: magnitude ratio
time lag and minimum decrement factor point of view. Energy Build G(jx): system transfer function
2000;32(2):197–203. /: phase angle
[11] Al-Sanea SA, Zedan MF. Improving thermal performance of building walls by
tlag: time lag
optimizing insulation layer distribution and thickness for same thermal mass.
hout: outside surface heat transfer coefficients
Appl Energy 2011;88:3113–24.
[12] Mavromatidis LE, Mankibi MEL, Michel P, Santamouris M. Numerical hin: inside surface heat transfer coefficients
estimation of time lags and decrement factors for wall complexes including R: resistance
multilayer thermal Insulation, in two different climatic zones. Appl Energy C: capacitance
2012;92:480–91. L: length
[13] Kaynakli O. A review of the economical and optimum thermal insulation Z Ri : impedance value for the resistance of layer ‘‘i’’
thickness for building applications. Renew Sustain Energy Rev 2012;16:415–25. Z C i : impedance for the capacitance of layer ‘‘i’’
[14] Masoso OT, Grobler LJ. A new and innovative look at anti-insulation behaviour Zeq: equivalent impedance
in building energy consumption. Energy Build 2008;40:1889–94.
[15] Al-Sanea SA, Zedan MF, Al-Hussain SN. Effect of thermal mass on performance
of insulated building walls and the concept of energy savings potential. Appl
Energy 2012;89:430–42.