Sheet No.

Resistance of Members without Shear Reinforcement

Slab Ref: Roof Over Second Floor - Long Span

Shear Force 103.00 kN/m

Breadth 1.00 m
Effective Depth 219 mm

Concrete Grade C35


Fck 35 N/mm2

Area of Steel Provided 1131 mm2/m


Area of Steel Required 1049 mm2/m

Shear Stress
𝑣_𝐸𝑑=𝑉_𝐸𝑑/((𝑏𝑑) )
0.47 N/mm2

Resistance of member without shear reinforcement 'v Rd,c'

𝑣_(𝑅𝐷,𝑐)=0.12𝑘(100𝑝_1 𝑓_𝑐𝑘 )^(1/3)≥0.035𝑘^1.5 〖𝑓 _𝑐𝑘 〗 ^0.5 2


0.62 N/mm
𝑘=1+√(200/𝑑)≤2

1.96
𝑝_1=𝐴_𝑠/((𝑏𝑑) )≤0.02
0.01

Shear Capacity Check: 0.76 No Shear Reinforcement is Required


Sheet No. 2

Span-Effective Depth Ratio

Actual Span 6.23 m

The basic Ratios are modified in particular cases as follows:


F3) Where more tension reinforcement is provided (As,prov) than that calculated (As,req) at ULS,
multiply the basic ratio by As,prov/As,req (Upper limit = 1.5)

Reduction Value (F1) 1.00


Reduction Value (F2) 1.00
Reduction Value (F3) 1.08

Determine Basic l/d

Percentage of tension reinforcement 0.48 %

Factor for structural system 'k' 1.30 End Span Condition


(How to Design Concrete Structures using EC2 (Chapter 3 Figure 5 ))
𝑙/𝑑=𝑘[11+(1.5√(𝑓_𝑐𝑘 ) 𝑝_𝑜)/𝑝+3.2√(𝑓_𝑐𝑘 ) (𝑝_𝑜/𝑝−1)^1.5 ] 𝑤ℎ𝑒𝑟𝑒 𝑝≤𝑝_𝑜

Equation A 31.35

=𝑘[11+(1.5√(𝑓_𝑐𝑘 ) 𝑝_𝑜)/((𝑝−𝑝^′ ) )+√(𝑓_𝑐𝑘 )/12 𝑝^′/𝑝_𝑜 ] 𝑤ℎ𝑒𝑟𝑒 𝑝>𝑝_𝑜


Equation B 28.55

Required tension
reinforcement at mid-span to
resist the moment due to the
design loads 'p'
0.004790
Reference reinforcement ratio 0.005916
'po'

Required compression
reinforcement at mid-span to
resist the moment due to the
design loads 'p''
0

Is p ≤ po Equation A l/d 31.35

Modified Basic l/d 33.81


Actual l/d 28.45 PASS
Sheet No. 3

Minimum Area of Secondary Reinforcement

Minimum Area of Principal Reinforcment


𝐴_(𝑠,𝑚𝑖𝑛)=(0.26𝑓_𝑐𝑡𝑚 𝑏_𝑡 𝑑)/𝑓_𝑦𝑘 ≥0.0013𝑏_𝑡 𝑑
364.42 mm2/m

fctm 3.2
fyk 500 N/mm2

Minimum Area of Secondary Reinforcement

20% As,min 72.88 mm2/m