PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
Assumptions:
Building data
No of frames: No_frames := 3
Basic values
110
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
Season factor
cseason := 1.0
(EN1991-1-4, NA 2.4/cl. 4.2(2)):
Directional factor
cdir := 1.0
(EN1991-1-4, NA 2.4/cl. 4.2(2)):
Orography
Orography factor
co := 1.0
(EN1991-1-4,cl.4.3.3(2):
Obstruction height
have := 15m
(EN1991-1-4,Annex A.5):
0 if x 6 have
210
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
310
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
0.07
Terrain factor zo
kr := 0.19 = 0.17
(EN1991-1-4,cl.4.3.2(1)):
z0.II
Roughness factor zmin
cr := kr ln = 0.782
(EN1991-1-4,cl.4.3.2(1)): zo
Mean wind velocity -1
vm := cr co vb = 23.453 m s
(EN1991-1-4,cl.4.3.1(1)):
Turbulence factor
kI := 1.0
EN1991-1-4,cl.4.4(1)):
kI
Turbulence intensity Iv := = 0.217
EN1991-1-4,cl.4.4(1)): zmin
co ln
zo
Peak velocity pressure 2 -2
EN1991-1-4,cl.4.5(1)):: ( )
q p := 1 + 7 Iv 0.5 vm = 0.866 kN m
There is no blockage beneath the canopy, however the values of cp.net and c f have been taken
using the ϕ=0 for m inim um values and ϕ=all for m aximum values.
The overall force coefficient represent the resulting force. The net pressure coefficient represents
the m aximum local pressure for all wind directions and have been used in the design of roofing
elements and fixing.
410
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
510
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
-2
Wind pressure for zone A we.A.do.30 := qp cp.net.A.do.30 = 1.906 kN m
(EN1991-1-4,Eq.5.1)
Figure 2: Location of the centre of force for monopitch canopies (EN1991-1-4,Figure 7.16)
610
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
No. 4 Load cases for wind force on structure for inclination of 30deg (edge members)
b
= 0.672 m
4 Fw.ed.do.30 = 4.055 kN Fw.ed.do.30 = 4.055 kNb
= 0.672 m
4
b
= 0.672 m
4 b
= 0.672 m
4
710
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
No. 4 Load cases for wind force on structure for inclination of 30deg (middle members)
b
= 0.672 m
4 Fw.mid.do.30 = 8.11 kN Fw.mid.do.30 = 8.11 kNb
= 0.672 m
4
b
= 0.672 m
4 b
= 0.672 m
4
Frictional force should be considered to the roof canopy structures - see EN1991-1-4,cl.7.3.(7)
Surface type
Surface_type := "Very rough"
(EN1991-1-4,Table 7. 10):
Frictional coefficient
cfr := 0.01 if Surface_type = "Smooth" = 0.04
(EN1991-1-4,Table 7. 10):
0.02 if Surface_type = "Rough"
0.04 if Surface_type = "Very rough"
2
Reference area: Afr := 2 ss b = 15.602 m
810
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
910
WIND LOAD CALCULATION BASE ON EN1991-4
PV SYSTEM REV.A
Calculated by:V.N.
Reviewed by: V.N.
1010