Sei sulla pagina 1di 1

Stationary Ni-Cd battery sizing

Battery calculation worksheet IEEE 1115-2014


Range KPH
No. of cells 82
Final voltage/cell 1.14 V
Nominal temperature 20 °C
Minimum temperature 10 °C
Maximum temperature 50 °C

(7) (8)
(3) (4) (6)
(2) (5) Temp Required
(1) Changes in Duration of Kt Factor
Load End of Section Derating Section Size
Period Load Period *
(Amperes) (minutes) Factor (3)x(6)x(7)
(Amperes) (minutes) **
** =Rated Ah
Section 1 - First 1 Periods Only - If A2>A1, go to Section 2-No
A1-0=
1 A1=608.73 M1=1.00 t=M1=1.00 0.3986 1.1025 267.51
608.73
Total 267.51
Section 2 - First 2 Periods Only - If A3>A2, go to Section 3-Yes

Section 3 - First 3 Periods Only - If A4>A3, go to Section 4-No


A1-0= t=M1+...
1 A1=608.73 M1=1.00 0.7872 1.0934 523.95
608.73 +M3=15.00
A2-A1=
2 A2=284.62 M2=13.00 t=M2+M3=14.00 0.7739 1.0941 -274.43
-324.11
A3-A2=
3 A3=608.90 M3=1.00 t=M3=1.00 0.3986 1.1025 142.51
324.28
Total 392.03
Section 4 - First 4 Periods Only - If A5>A4, go to Section 5-Yes

Section 5 - First 5 Periods Only - If A6>A5, go to Section 6-No


A1-0= t=M1+...
1 A1=608.73 M1=1.00 1.3313 1.0487 849.87
608.73 +M5=60.00
A2-A1= t=M2+...
2 A2=284.62 M2=13.00 1.3169 1.0494 -447.91
-324.11 +M5=59.00
A3-A2= t=M3+...
3 A3=608.90 M3=1.00 1.1308 1.0580 387.96
324.28 +M5=46.00
A4-A3=
4 A4=441.36 M4=44.00 t=M4+M5=45.00 1.1165 1.0587 -198.04
-167.54
A5-A4=
5 A5=470.85 M5=1.00 t=M5=1.00 0.3986 1.1025 12.96
29.49
Total 604.84

Visit our website at www.amcosaft.in


(376241) Version: 2.6, Last updated on 12/2018 P 4/5