Sei sulla pagina 1di 20

Visiting Engineer name

From
Visiting date
To
State TELANGANA
Name
Address
I/D or O/D type
Substation details Busbar arrangement
Latitude 16.60214
GPS coordinate
Longitude 78.19839
Substation voltage level(kV) 220 KV
Owner Name TSTRANSCO
Visiting Substation details
Substation Incharge Name DE/O&M/wanaparthy
Contact 9491491647
Signature
Date
Generator details
Values (Specify the units of the values) either ohms or p.u.
Sl. No. Particulars
Unit-1 Unit-2 Unit-3 Unit-4 Unit-5 Unit-6
1 MW Rating
2 MVA Rating
3 Rated Power Factor
4 kV Rating
5 Armature Resistance (Ra)
6 Direct Axis Synchronous Reactance (Xd)
7 Direct Axis Transient Reactance (Xd')
8 Direct Axis Sub Transient Reactance (Xd”))
9 Quadrature Axis Synchronous Reactance (Xq)
10 Quadrature Axis Transient Reactance (Xq')
11 Quadrature Axis Sub Transient Reactance (Xq”)
12 Negative Sequence Reactance (Xn)
13 Zero Sequence Reactance (Xo)
14 Potier Reactance (Xp)
15 Direct Axis Transient Open Circuit Time Constant (T’do)
16 Direct Axis Sub – Transient Open Circuit Time Constant (T”do)
17 Quadrature Axis Transient Open Circuit Time Constant (T’qo)
18 Quadrature Axis Sub – Transient Open Circuit Time Constant (T”qo)
19 Generator Inertia Constant (H)
20 NGT Voltage rating
21 NGR in ohms
22 Continuous I2 current in %
23 Max. (I22 * t) [I2 in p.u. & t in sec]
**Provide AVR and Governor data seperately
I2 = Negative sequence current of generator

24 AVR model (block diagram, time constant values, output graphs of AVR)
25 Governor model (block diagram, time constant values, output graphs of governor)
Transformer Details
Particulars Interconnecting Transformer
Sl. No.
Name of the transformer ICT1 ICT2
1 MVA Rating 315 315
2 HV (kV) 400 400
3 IV (kV) 220 220
4 LV (kV) 33 33
5 % impedance At Max Tap 13.01 12.93
6 % impedance At Normal Tap 13.01 12.94
7 % impedance At Minimum Tap 13.48 13.45
8 Tap Maximum Number 17 17
9 Tap Minimum Number 1 1
10 Nominal Tap 9B 9B
11 Minimum Voltage (kV) 360 360
12 Maximum Voltage (kV) 440 440
13 Winding Configuration YNa0d11 YNa0d11
14 From Breaker Rating (kA)
15 To Breaker Rating (kA)
16 Loading (MVAR)
17 Loading (MW)
Line Details Positive sequence impedance Zero sequence impedance 65 deg C 75 deg C

Thermal rating based on allowable


Bay No. From Substation To Substation Voltage level (kV) No. of Ckts Length (km) Conductor Type R (ohm/km) X (ohm/km) B/2 (mho/km) R (ohm/km) X (ohm/km) B/2 (mho/km) conductor temperature at ambient Breaker rating Remarks
temperature

401 Dindi Boothpur-I 220 1 73.02 Twin Moose 420KV, 3150 A

404 Dindi Boothpur-II 220 1 73.02 Twin Moose 420KV, 3150 A

403 Dindi Kalwakurthy-I 220 1 74.9 Twin Moose 420KV, 3150 A

406 Dindi Kalwakurthy-II 220 1 74.9 Twin Moose 420KV, 3150 A

Veltoor-I 220 1

201 Dindi Veltoor-II 220 1 82.33 Single Zebra 245KV, 3150 A

202 Dindi 245KV, 3150 A

204 Dindi 245KV, 3150 A

205 Dindi 245KV, 3150 A

213 Dindi 245KV, 3150 A

214 Dindi 245KV, 3150 A


Bus Reactor data Line reactor details

Bay No Voltage rating Neutral Grounding


Sl No. Connecting S/S bus MVAr rating Remarks if any Sl No. Connected line voltage rating in kV MVAr rating Reactor (if available)
(kV)
sample data= 1 NA

1 NA
Series Capacitor Shunt Capacitor data
Connecting line
Voltage rating Voltage rating
Sl No MVAr rating Switching or Fixed SL NO. Connecting S/S bus MVAr rating Switching or Fixed
From S/S To S/S (kV) (kV)

1 NA
NA
CT Details
Ba Output (VA) Accuracy class
y CT Name Make Serial no. Type Location of CT Ratio Primary Secondary No of
current (A) current (A) Cores Core-1 Core-2 Core-3 Core-4 Core-5 Core-1 Core-2 Core-3 Core-4 Core-5
No
R-ph:510583
1 Boothpur-I Toshibha Y-ph:510589 DT245 Line 800-600-400/1 800 1 5 - - - - 20 PS PS PS PS 0.2
B-ph:510588
R-ph:510579
2 Boothpur-II Toshibha Y-ph: 510589 DT245 LINE 800-600-400/1 800 1 5 - - - - 20 PS PS PS PS 0.2
B-ph: 510578
R-ph: 510582
3 Kalwakurthy-I Toshibha Y-ph: 510580 DT245 Line 800-600-400/1 800 1 5 - - - 20 PS PS PS PS 0.2
B-ph: 510586
R-ph: 510585
4 Kalwakurthy-II Toshibha Y-ph:510584 DT245 Line 800-600-400/1 800 1 5 - - - - 20 PS PS PS PS 0.2
B-ph: 510587
R-ph: 510599
5 Veltoor-I Toshibha Y-ph: 510594 DT245 Line 1600-1200-800/1 1600 1 5 - - 20 - - PS PS 0.2 PS PS
B-ph: 510593
R-ph: 510590
6 Veltoor-II Toshibha Y-ph: 510592 DT245 Line 1600-1200-800/1 1600 1 5 - - 20 - - PS PS 0.2 PS PS
B-ph:510597
Remarks
ISF/ALF RCT at 75deg centi in ohm KPV (in V) knee point voltage Iexc at Vk/4 (in mA) magnetising current

Core-1 Core-2 Core-3 Core-4 Core-5 Core-1 Core-2 Core-3 Core-4 Core-5 Core-1 Core-2 Core-3 Core-4 Core-5 Core-1 Core-2 Core-3 Core-4 Core-5

100l(rct 100l(rct 80l(rct+ 80l(rct+


- - - - <5 <5at800/1A <5at800/1A <5at80 <5at800/1A - +20)at +20)at 3)at 3)at - <30 <30 <30 <30 -
0/1A
800/1 800/1 800/1 800/1

100l(rct 100l(rct 80l(rct+ 80l(rct+


- - - - <5 <5at800/1A <5at800/1A <5at80 <5at800/1A - +20)at +20)at 3)at 3)at - <30 <30 <30 <30 -
0/1A
800/1 800/1 800/1 800/1

<5at80 100l(rct 100l(rct 80l(rct+ 80l(rct+


- - <5 <5at800/1A <5at800/1A <5at800/1A - +20)at +20)at 3)at 3)at - <30 <30 <30 <30
0/1A 800/1 800/1 800/1 800/1

100l(rct 100l(rct 80l(rct+ 80l(rct+


- - - - <5 <5at800/1A <5at800/1A <5at80 <5at800/1A - +20)at +20)at 3)at 3)at - <30 <30 <30 <30 -
0/1A
800/1 800/1 800/1 800/1
1200at <30 <30 <30
<6 1200at1 1200at1 1200at1
<6 at1200/1A& <6 <6 at1200/1 1200/1 200/1A 200/1A 200/1A <30 at1200/1A& at1200/ at1200/ at1200/
- - <5 - - at1200/1A& - at1200/1A& A&800a - 1A& - 1A& 1A&
<4at 800/1A <4at 800/1A <4at 800/1A A& <4at t &800at &800at &800at <45at 800/1A <45at <45at <45at
800/1A 800/1A 800/1A 800/1A
800/1A
1200at 800/1A
<30 800/1A
<30 800/1A
<30
<6 <6 <6 1200/1 1200at1 1200at1 1200at1 at1200/ at1200/ at1200/
<6 at1200/1A& at1200/1 200/1A 200/1A 200/1A <30 at1200/1A&
- - <5 - - <4at 800/1A at1200/1A& - at1200/1A& A& <4at A&800a &800at - &800at &800at <45at 800/1A 1A& - 1A& 1A&
<4at 800/1A <4at 800/1A t <45at <45at <45at
800/1A 800/1A 800/1A 800/1A
800/1A 800/1A 800/1A 800/1A
PT Details

SECONDARY WINDING
Primary PRIMARY WINDING
HIGHEST
Voltage WINDING-I WINDING-II WINDING-III SYSTEM
level Bay NO PT Name Manufacturer Name YEAR VOLTAGE FACTOR
A-N 1a-1n 2a-2n 3a-3n VOLTAGE
connected in
(in kV)
kV ACCURACY ACCURACY ACCURACY
VOLTS VOLTS BURDEN (VA) VOLTS BURDEN (VA) VOLTS BURDEN (VA)
CLASS CLASS CLASS

220 - BUS-1 Toshiba 2014 220000/√3 110/√3 30VA 3P 110/√3 150/50 3P - - - 245 1.2 CONT./1.5-30 SEC

220 - BUS-2 Toshiba 2014 220000/√3 110/√3 30VA 3P 110/√3 150/50 3P - - - 245 1.2 CONT./1.5-30 SEC
CVT Details

Total burden Thermal Highest HF Capacitance Primary Secondary Burden


Bay No. Maker Year location of CVT simultaneously(VA) burden (VA) Rated voltage system Voltage factor (pF) Capacitance C1 Capacitance C2 Connection Ratio Accuracy Class
voltage (pF) (pF)

1 Crompton Geaves ltd 2014 Boothpur-I 50 220000/√3/110 245 1.2 CONT./1.5-30 SEC 4400 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/ 0.2,0.5,3p,3p
300
/√3 3n,3a2-3n 110/√3 110/√3)

220000/√3/110 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/


2 Crompton Geaves ltd 2014 Boothpur-I 50 300 /√3 420 1.2 CONT./1.5-30 SEC 4400 3n,3a2-3n 110/√3 110/√3) 0.2,0.5,3p,3p

3 Crompton Geaves ltd 2014 Kalwakurthy-I 50 300 220000/√3/110 420 1.2 CONT./1.5-30 SEC 4400 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/ 0.2,0.5,3p,3p
/√3 3n,3a2-3n 110/√3 110/√3)

220000/√3/110 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/


4 Crompton Geaves ltd 2014 Kalwakurthy-II 50 300 /√3 420 1.2 CONT./1.5-30 SEC 4400 3n,3a2-3n 110/√3 110/√3) 0.2,0.5,3p,3p

220000/√3/110 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/


5 Crompton Geaves ltd 2014 Veltoor-I 50 300 /√3 420 1.2 CONT./1.5-30 SEC 4400 3n,3a2-3n 110/√3 110/√3) 0.2,0.5,3p,3p

6 Crompton Geaves ltd 2014 Veltoor-II 50 300 220000/√3/110 420 1.2 CONT./1.5-30 SEC 4400 1a-1n, 2a-2n, 3a1- 220000/√3/(110/√3/ 0.2,0.5,3p,3p
/√3 3n,3a2-3n 110/√3 110/√3)
Substation Relay data
Connected
Panel no. Panel name Element Protection(Main/Backup) Protective Relay Manufacture's name Relay type Model no.
CT ratio

1 Boothpur-I Transmission Line 800/1 Main Distance Schinder Numerical P442

800/1 Backup Distance Siemens Numerical 7sa52

2 Boothpur-I Transmission Line 800/1 Main Distance Schinder Numerical P442

800/1 Backup Distance Siemens Numerical 7sa52

3 Kalwakurthy-II Transmission Line 800/1 Main Distance Schinder Numerical P442

800/1 Backup Distance Siemens Numerical 7sa52

4 kalwakurthy-II Transmission Line 800/1 Main Distance Schinder Numerical P442

800/1 Backup Distance Siemens Numerical 7sa52

5 Veltoor-I Transmission Line 800/1 Main Distance Schinder Numerical P442

800/1 Backup Distance Siemens Numerical 7sa52

6 veltoor-II Transmission Line 800/1 Main Distance ALSTOM Numerical P442

800/1 Backup Distance ALSTOM Numerical 7sa52


bstation Relay data
Electromechanical
Model Description Version no. Static Numerical Others Image No. Remarks
PSM TSM

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes

NA Yes
Generating Station Relay data
Connected Electromechanical
Panel no. Panel name Element Protection Protective Relay Manufacture's name Relay type Model no. Model Description Version no. Static Numerical Others Image no. Remarks
CT ratio PSM TSM
CB Details

Number Tag Number Sub Station Medium Make Feeder Number Switch board Name Serial Number Type Rated voltage (KV) Breaking Current (kA)

220KV SS Crompton R-44538C Y-44538C


1
Thimajjipet SF6 Greaves Ltd 1 Boothpur-I B-44538C, 200-SFM-50A 245 50

R-44539C
220KV SS Crompton
2
Thimajjipet SF6 Greaves Ltd 2 Boothpur-II Y- 200-SFM-50A 245 50
44539C B-44539C,

220KV SS Crompton R-44537C Y-


3 SF6 3 Kalwakurthy-I 200-SFM-50A 245 50
Thimajjipet Greaves Ltd 44537C B-44537C,

220KV SS Crompton R-44536C Y-


4
Thimajjipet
SF6
Greaves Ltd
4 Kalwakurthy-II 200-SFM-50A 245 50
44536C B-44536C,

220KV SS Crompton R-44534C Y-


5
Thimajjipet
SF6
Greaves Ltd
5 Veltoor-I 200-SFM-50A 245 50
44534C B-44534C,

220KV SS Crompton R-44533C Y-


6
Thimajjipet
SF6
Greaves Ltd
6 Veltoor-II 200-SFM-50A 245 50
44533C B-44533C,

220KV SS Crompton R-44535c Y-44535c


7
Thimajjipet
SF6
Greaves Ltd Busc0upler 200-SFM-50A 245 50
B-44535c
tails
Auxilary Volts
Making Current (kA Peak) Weight (Kgs) Rated Current (A) Rated Frequency (Hz) STC (kA/1sec) Standard Year
Closing (VDC) Trippin (VDC) Spring Charge (VAC) DOC Remarks

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -


07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -

07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -

07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -

07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -


07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -


07.06.2017

125 3750 3150 50 50 KA/3 IEC-62271-100 2015 220 220 240 -


07.06.2017
Bus Coupler
Bay No. From bus To bus Voltage level (kV) Breaker Rating (kA)

1 1 2 220 50