Sei sulla pagina 1di 4

Engine and Main Components Troubleshooting Record

Plant Code: GC00023 Plant Name: Palembang 50 mw


Maint Date: August 15, 2015 Job Done By: Daus, Ryan
Maint Methods: Repair / Replace Parts Replace: Original Parts/Vpower Parts
Product No. - Product Model: -
Product S/N: 19117097 1312 Engine S/N: 604924-9/33
Fault Time: 02:25 AM Running hours: 1802 Hours
Fault Reason:

①Fault Description:
MSP failure

②Fault code:
SM 135 Connection PLC ↔ MSP Failure

Solution:

①Inspection Process:
1. Checking Engine Alarm Status
2. Checking MMC MCB panel.
3. Checking MSP status and Alarm

②Cause found and solution:


1. MSP found not turned on
2. Unplug all cables from MSP.
3. Exchange MSP G33 from G28
4. Checking MSP status.

Operation status:
After exchanging MSP from G28, Engine running normally.
MSP taken from G28.
Need new MSP unit immediately.
Pic1 for engine and main components fault:
Alarm Fault in MMC.

Pic2 for engine and main components fault:


MSP fail, MSP screen doesn’t turn on.
Pic1 for engine and main components fault solution:
MSP from G28 Installed in G31
Parametrieden

Datum :26.03.2012 Zeit:13:39:11 Benutzer :System Seite:5


Great :-8440_1546_H_1 Dateiname :8440_MTU_E222xx_Vpower_China_480V_50

Name Wert
Frequency Monitoring Ja ON
Overfrequency f>threshold f>51.00 Hz
Overfrequency delay time 0.10s
Overfrequency on relay no. 0034
Underfrequency f< threshold f<49.60 Hz
Underfrequency delay time 0.10s
Underfrequency on relay no 0034

Voltage Monitoring Ja ON
Overvoltage v>threshold V>440V
Overvoltage delay time 0.10s
Overvoltage on relay no. 0034
Undervoltage v< threshold V<360V
Undervoltage delay time 0.10s
Undervoltage on relay no 0034

Central alarm on relay no 0000

Monitoring on after 15s


monitoring on at generator frequency f>15Hz
I Gen > xx Hz on relay no 0000

Battery undervoltage
threshold 25.0V
Battery undervoltage on relay no 0000