Test Pit No:

AJK ENGINEERS (PVT.) LTD. TP-01


Testpit Started on:
TEST PIT LOG
27-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-1, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 27-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14238 Test Pit Size:
Elevation (m): East: 73.26812 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

15 Brown, Medium to Highly Plasticity, trace Grass roots, Moist,

1.0 30

45

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0.8m to 1.0m.

105 Brown, Medium to Highly Plasticity, Moist,

4.0 120

135
Field Density Test
performed at 5.0ft
depth.
5.0 150 FDT-1
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-02
Testpit Started on:
TEST PIT LOG
27-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-1, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 27-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.1415 Test Pit Size:
Elevation (m): East: 73.26781 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, trace


15 concretions, Moist,

1.0 30

45

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105 Brown, Medium to Highly Plasticity, Moist,

4.0 120

135
Field Density Test
performed at 5.0ft
depth.
5.0 150 FDT-1
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-02
Testpit Started on:
TEST PIT LOG
29-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-3, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 29-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14058 Test Pit Size:
Elevation (m): East: 73.26847 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, trace


15 concretions, Moist,

1.0 30

45 FDT-1 Field Density Test


performed at 1.5ft
depth.

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-04
Testpit Started on:
TEST PIT LOG
29-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-4, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 29-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.13952 Test Pit Size:
Elevation (m): East: 73.26978 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, trace


15 concretions, Moist,

1.0 30

45

2.0 60 Field Density Test


performed at 2.3ft
depth.
FDT-1

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-05
Testpit Started on:
TEST PIT LOG
30-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-5, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 30-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.13985 Test Pit Size:
Elevation (m): East: 73.26717 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

15 Brown, Medium to Highly Plasticity, trace Grass roots, Moist,

1.0 30

45

2.0 60

Composite Bulk
Samples collected
75 from 0ft to 5.0ft.

3.0 90

105 Field Density Test


performed at 3.7ft
FDT-1 depth.

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-06
Testpit Started on:
TEST PIT LOG
30-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-5, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 30-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.13919 Test Pit Size:
Elevation (m): East: 73.26636 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

2.0 60

Composite Bulk
Samples collected
75 from 0ft to 5.0ft.

Field Density Test


performed at 3.0ft
3.0 90 FDT-1 depth.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-07
Testpit Started on:
TEST PIT LOG
02-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-7, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 02-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14013 Test Pit Size:
Elevation (m): East: 73.26556 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

15 Brown, Medium to Highly Plasticity, trace Grass roots, Moist,

1.0 30

45

2.0 60

Composite Bulk
Samples collected
75 from 0ft to 5.0ft.

Field Density Test


performed at 3.0ft
3.0 90 depth.

105

4.0 120

135
FDT-1 Field Density Test
performed at 4.7ft
depth.
5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-08
Testpit Started on:
TEST PIT LOG
01-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-7, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 02-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14122 Test Pit Size:
Elevation (m): East: 73.26531 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

Field Density Test


4.0 120 FDT-1 performed at 4.0ft
depth.

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-09
Testpit Started on:
TEST PIT LOG
30-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-8, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 30-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14060 Test Pit Size:
Elevation (m): East: 73.26746 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

Field Density Test


4.0 120 FDT-1 performed at 4.0ft
depth.

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-10
Testpit Started on:
TEST PIT LOG
03-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-8A, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 03-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14120 Test Pit Size:
Elevation (m): East: 73.26665 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

Field Density Test


4.0 120 performed at 4.2ft
FDT-1 depth.

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-11
Testpit Started on:
TEST PIT LOG
02-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-10, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 02-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14215 Test Pit Size:
Elevation (m): East: 73.26550 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

Field Density Test


performed at 2.2ft
2.0 60 depth.
FDT-1

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-12
Testpit Started on:
TEST PIT LOG
03-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-11, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 03-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14285 Test Pit Size:
Elevation (m): East: 73.26681 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

15 Brown, Medium to Highly Plasticity, trace Grass roots, Moist,

1.0 30

45

Field Density Test


performed at 2.2ft
2.0 60 depth.
FDT-1

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-13
Testpit Started on:
TEST PIT LOG
27-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-12, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 27-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14420 Test Pit Size:
Elevation (m): East: 73.26811 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, trace


15 concretions, Medium to Highly Moist,

1.0 30

45

Field Density Test


performed at 2.0ft
2.0 60 FDT-1 depth.

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-14
Testpit Started on:
TEST PIT LOG
03-07-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-14, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 03-07-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14301 Test Pit Size:
Elevation (m): East: 73.26625 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

45

Field Density Test


performed at 2.3ft
2.0 60 depth.

FDT-1

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends
Test Pit No:
AJK ENGINEERS (PVT.) LTD. TP-15
Testpit Started on:
TEST PIT LOG
29-06-2019
PROJ.: GEOTECHNICAL SITE INVESTIGATION - COMSATS UNIVERSITY CAMPUS Testpit Completed on:

LOCATION: ZONE-13, COMSATS UNIVERSITY, DHAMTORE, ABBOTABAD. 29-06-2019


CLIENT: COMSATS UNIVERSITY, ISLAMABAD. Geologist:

METHOD OF EXCAVATION: Manual CO-ORDINATES: Farhan Ali


Water Table. Not Encountered. North: 34.14417 Test Pit Size:
Elevation (m): East: 73.26656 4.0ft x 6.0ft x 5.0ft
Field Density Lab Density
Test Test

In place % Compaction
Depth in Centimeters

Classification Symbol

Optimum Moisture
Density (gm/cm3)
Natural Moisture

Maximum Dry
Sample Type No.

Content (%)

Content (%)
Dry Density
DESCRIPTION OF MATERIAL REMARKS

(gm/cm3)
Depth in feet

Profile

SILTY CLAY

Brown, Medium to Highly Plasticity, trace Grass roots, traces


15 concretions, traces Gravels, Moist,

1.0 30

Field Density Test


45 FDT-1 performed at 1.5ft
depth.

2.0 60

75

Composite Bulk
Samples collected
3.0 90 from 0ft to 5.0ft.

105

4.0 120

135

5.0 150
BOTTOM OF TESTPIT
Legends