Sei sulla pagina 1di 8

Data sheet

ON/OFF zone valve - PN 16


AMZ 112, AMZ 113
Description / Applications

AMZ 112 2 port valve AMZ 113 3 port diverting valve

The ON / OFF zone valves type AMZ 112 & The ON / OFF zone valves can be applied
AMZ 113 are typical used in connection with: together with Danfoss Room Thermostats
• HVAC applications type RET 230 (single poled switch) and
• Domestic and commercial central heating programmable Room Thermostats type
applications TP 5000 / 7000.
• Domestic hot water and chilled water
applications The actuator can be controlled by a SPST or
• Solar energy plants SPDT switch.
• Priority control of hot water supply and
heating (diverting function) The limit stop switch can be used for start /
• Priority control of boiler and solid fuel stop of a fan or a circulation pump in an
installations (diverting function). entirely open valve.

ON / OFF control of Radiator -, under floor heating and zone systems (night set back).

SIBC VD.HC.N1.02 © Danfoss 11/03 1


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

Applications (continued)

ON / OFF control of one or more heating / cooling surfaces.

Priority control of hot water supply and heating - diverting function.

Priority control of boiler and solid fuel installations - diverting function.

Ordering AMZ 112 2-port valve / actuator AMZ 113 3-port valve / actuator
DN Kvs Connection Max ∆p Code No. Max ∆p
Valve DN Kvs Connection Code No.
Valve
15 17 Rp 1/2 2 bar 082G5501 15 3.8 Rp 1/2 2 bar 082G5511
20 41 Rp 3/4 2 bar 082G5502 20 7.7 Rp 3/4 2 bar 082G5512
25 68 Rp 1 2 bar 082G5503 25 11.6 Rp 1 2 bar 082G5513

2 VD.HC.N1.02 © Danfoss 11/03 SIBC


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

Technical data Actuator


AMZ 112 AMZ 113
Supply voltage 230 V, 50 / 60 Hz 230 V, 50 / 60 Hz
Micro switch 5 (1) A, 250 V, 50 Hz 5 (1) A, 250 V, 50 Hz
Power consumption 7.5 VA By operation 7.5 VA By operation
3.VA By stand by
Electrical protection class Class II acc. EN-60335-1 Class 1 acc. EN 60335-1
Enclosure IP 44 acc. IEC 60529 IP 44 acc. IEC 60529
Rotation time 30 sec / 90° 60 sec / 180°
Ambient temperature 0° ... max 50°C 0° ... max 50°C
Humidity RH 0% ... 80% RH 0% ... 80%
Wire 4x0.5 mm2, L= 1.5 m 4x0.5 mm2 L=1.5 m

Valve
AMZ 112 AMZ 113
Operation temperature 0°... 130°C 0°... 130°C
Max operating pressure PN 16 PN 16
Max operating torque 8 Nm 8 Nm
Max ∆P valve 2 bar 2 bar

Material
Body - stem Hot stamped brass CuZn40Pb2 Ni plated
Ball Hot stamped brass CuZn40Pb2 Cr plated
Gaskets PTFE - FPM - EPDM
Connection Internal thread Rp ISO 7/1

Capacity

AMZ 112 AMZ 113

Wiring

SIBC VD.HC.N1.02 © Danfoss 11/03 3


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

Installation
AMZ 112

AMZ 113

Manual control

4 VD.HC.N1.02 © Danfoss 11/03 SIBC


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

Dimensions
AMZ 112

Connection A B C D Kvs Weight


DN G mm mm mm mm kg
15 1/ " 139 121.5 17.5 63 17 0.90
2

20 3/ " 144 124.5 19.5 57 41 0.83


4

25 1" 153 129.5 23.5 68 68 1.04

AMZ 113

Connection A B C D Kvs Weight


DN G mm mm mm mm kg
1
15 /2" 152 118 34 64 3.81 0.78
3
20 /4" 164 125 39 74 7.68 1.08
25 1" 175 130 45 87 11.6 1.38

SIBC VD.HC.N1.02 © Danfoss 11/03 5


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

6 VD.HC.N1.02 © Danfoss 11/03 SIBC


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

SIBC VD.HC.N1.02 © Danfoss 11/03 7


Data sheet ON / OFF Zone valves AMZ 112 & AMZ 113

8 VD.HC.N1.02 © Danfoss 11/03 SIBC