Model Implementation Conformance Statement


for the IEC 61850 interface in ABB 670 Series, version 1.2

Template version 0.1


Date: April 24, 2008
UCA International Users Group
Testing Sub Committee

Type des. Part no.


No. of p.
Prep. TP/TA / Reijo Pajunen 2009-10-23 Doc. kind Declaration of Conformity
Appr. / Apell Gert 2010-08-27 Title ABB 670 Series, version 1.2 - IEC 138
Resp. dept TP/TA Approved 61850 MICS
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 1
FILE: IED_670_series_ver_1.2_IEC_61850_MICS.doc; SAVEDATE: 2010-04-12 08:04; TEMPLATE: Techn_Doc_Stand_P.dot C; SKELETON: 1MRK3-475 en
1 Introduction ................................................................................................... 6
1.1 Scope ................................................................................................ 6
1.2 Denominations .................................................................................. 6
1.3 Related documents............................................................................ 6
2 Logical Nodes List ........................................................................................ 7
3 Logical Node Extensions............................................................................ 11
3.1 New Logical Nodes.......................................................................... 11
3.1.1 ZCVPSOF Revision 3............................................................. 11
3.1.2 CCRPLD ................................................................................ 12
3.1.3 CCSRDIF Revision 2.............................................................. 12
3.1.4 SDDRFUF .............................................................................. 13
3.1.5 QCBAY Revision 1 ................................................................. 13
3.1.6 QCRSV .................................................................................. 14
3.1.7 ZCLCPLAL ............................................................................. 15
3.1.8 ZMRPSL Revision 2 ............................................................... 16
3.1.9 IB16FCVB .............................................................................. 16
3.1.10 B16IFCVI................................................................................ 17
3.2 Extended Logical Nodes.................................................................. 17
3.2.1 LLN0 ...................................................................................... 23
3.2.2 BBSPLLN0 ............................................................................. 23
3.2.3 BBTPLLN0 ............................................................................. 24
3.2.4 CBPLLN0 ............................................................................... 24
3.2.5 COUVLLN0 ............................................................................ 25
3.2.6 EF4LLN0 Revision 1 .............................................................. 26
3.2.7 GEN2LLN0............................................................................. 26
3.2.8 GF2LLN0................................................................................ 27
3.2.9 LAPPLLN0 ............................................................................. 27
3.2.10 NS2LLN0................................................................................ 28
3.2.11 OC4LLN0 ............................................................................... 28
3.2.12 OCNDLLN0 ............................................................................ 29
3.2.13 RSY1LLN0 Revision 2............................................................ 29
3.2.14 LPHD Revision 4 .................................................................... 30
3.2.15 TR1ATCC Revision 4 ............................................................. 31
3.2.16 TR8ATCC Revision 5 ............................................................. 33
3.2.17 SCILO .................................................................................... 38
3.2.18 SCSWI Revision 1.................................................................. 38
3.2.19 AEGGAPC ............................................................................. 39
3.2.20 ZSMGAPC ............................................................................. 40
3.2.21 BZITGGIO .............................................................................. 41
3.2.22 BZISGGIO.............................................................................. 41
3.2.23 CNTGGIO .............................................................................. 42
3.2.24 DPGGIO................................................................................. 43
3.2.25 MVGGIO ................................................................................ 43
3.2.26 PCGGIO................................................................................. 44
3.2.27 SLGGIO Revision 3................................................................ 44
3.2.28 SPGGIO ................................................................................. 45
3.2.29 SP16GGIO ............................................................................. 45
3.2.30 SPC8GGIO ............................................................................ 46
3.2.31 STSGGIO............................................................................... 47
3.2.32 SWSGGIO.............................................................................. 48
3.2.33 TMAGGIO .............................................................................. 49

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 2
3.2.34 VSGGIO Revision 1 ............................................................... 49
3.2.35 ETPMMTR ............................................................................. 50
3.2.36 CVMMXN Revision 1.............................................................. 51
3.2.37 GF2MMXN Revision 3............................................................ 52
3.2.38 CBPMMXU............................................................................. 53
3.2.39 CMMXU.................................................................................. 54
3.2.40 VMMXU.................................................................................. 54
3.2.41 VNMMXU ............................................................................... 55
3.2.42 CMSQI Revision 1.................................................................. 55
3.2.43 VMSQI Revision 1 .................................................................. 56
3.2.44 BCZTPDIF.............................................................................. 56
3.2.45 BCZSPDIF ............................................................................. 57
3.2.46 BZNTPDIF.............................................................................. 58
3.2.47 BZNSPDIF Revision 1 ............................................................ 59
3.2.48 GENPDIF Revision 1.............................................................. 60
3.2.49 HZRPDIF................................................................................ 61
3.2.50 L3CPDIF Revision 1 ............................................................... 61
3.2.51 L6CPDIF Revision 1 ............................................................... 63
3.2.52 LDLPDIF ................................................................................ 64
3.2.53 LT3CPDIF Revision 1............................................................. 65
3.2.54 LT6CPDIF Revision 1............................................................. 67
3.2.55 REFPDIF................................................................................ 68
3.2.56 T2WPDIF Revision 1 .............................................................. 69
3.2.57 T3WPDIF Revision 1 .............................................................. 71
3.2.58 FDPSPDIS Revision 2............................................................ 73
3.2.59 FMPSPDIS............................................................................. 74
3.2.60 FPSRPDIS ............................................................................. 75
3.2.61 LEXPDIS ................................................................................ 77
3.2.62 ZMCPDIS ............................................................................... 77
3.2.63 ZMCAPDIS............................................................................. 78
3.2.64 ZMHPDIS ............................................................................... 79
3.2.65 ZMMPDIS............................................................................... 79
3.2.66 ZMMAPDIS ............................................................................ 80
3.2.67 ZMQPDIS............................................................................... 80
3.2.68 ZMQAPDIS ............................................................................ 81
3.2.69 ZMRPDIS ............................................................................... 82
3.2.70 ZMRAPDIS............................................................................. 82
3.2.71 GOPPDOP ............................................................................. 83
3.2.72 RP3PDOP .............................................................................. 84
3.2.73 GUPPDUP ............................................................................. 84
3.2.74 LAPPPDUP ............................................................................ 85
3.2.75 SAPFRC................................................................................. 85
3.2.76 GEN4PHAR Revision 1 .......................................................... 86
3.2.77 GF2PHAR .............................................................................. 87
3.2.78 ROTIPHIZ .............................................................................. 87
3.2.79 STEFPHIZ Revision 1 ............................................................ 88
3.2.80 STTIPHIZ ............................................................................... 89
3.2.81 EFPIOC.................................................................................. 90
3.2.82 PHPIOC ................................................................................. 90
3.2.83 PSPPPAM Revision 1 ............................................................ 91
3.2.84 ECPSCH ................................................................................ 92
3.2.85 ECRWPSCH Revision 1......................................................... 92
3.2.86 ZCPSCH ................................................................................ 93
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 3
3.2.87 ZCRWPSCH Revision 1 ......................................................... 94
3.2.88 ZPCPSCH .............................................................................. 95
3.2.89 ZPCWPSCH........................................................................... 96
3.2.90 SDEPSDE .............................................................................. 96
3.2.91 BRCPTOC Revision 2 ............................................................ 98
3.2.92 LCNSPTOC............................................................................ 98
3.2.93 LCP3PTOC ............................................................................ 99
3.2.94 LCZSPTOC ............................................................................ 99
3.2.95 NS2PTOC ............................................................................ 100
3.2.96 PH1BPTOC.......................................................................... 100
3.2.97 PH1PTOC Revision 1........................................................... 101
3.2.98 PH3PTOC ............................................................................ 101
3.2.99 SCCVPTOC ......................................................................... 102
3.2.100 STBPTOC ............................................................................ 102
3.2.101 SAPTOF............................................................................... 103
3.2.102 COUVPTOV ......................................................................... 104
3.2.103 GF2PTOV ............................................................................ 104
3.2.104 HOLPTOV ............................................................................ 105
3.2.105 HPH1PTOV.......................................................................... 105
3.2.106 LCNSPTOV.......................................................................... 106
3.2.107 LCZSPTOV .......................................................................... 106
3.2.108 OV2PTOV ............................................................................ 107
3.2.109 ROV2PTOV.......................................................................... 107
3.2.110 VDCPTOV............................................................................ 108
3.2.111 BUSPTRC ............................................................................ 108
3.2.112 BUTPTRC ............................................................................ 109
3.2.113 EF4PTRC Revision 1 ........................................................... 110
3.2.114 LCCRPTRC.......................................................................... 110
3.2.115 NS2PTRC ............................................................................ 111
3.2.116 PH1PTRC ............................................................................ 111
3.2.117 PH3PTRC ............................................................................ 112
3.2.118 SMPPTRC............................................................................ 113
3.2.119 LPTTR Revision 4 ................................................................ 113
3.2.120 TRPTTR Revision 3 ............................................................. 114
3.2.121 GF2PTUC ............................................................................ 115
3.2.122 LCP3PTUC .......................................................................... 116
3.2.123 PH3PTUC ............................................................................ 116
3.2.124 SAPTUF ............................................................................... 117
3.2.125 COUVPTUV ......................................................................... 118
3.2.126 GF2PTUV............................................................................. 118
3.2.127 LOVPTUV ............................................................................ 119
3.2.128 UV2PTUV............................................................................. 119
3.2.129 LAPPPUPF .......................................................................... 120
3.2.130 GF2PVOC ............................................................................ 120
3.2.131 OEXPVPH Revision 2 .......................................................... 121
3.2.132 EF4RDIR Revision 4 ............................................................ 122
3.2.133 DRPRDRE ........................................................................... 122
3.2.134 CCRBRF .............................................................................. 123
3.2.135 CCSRBRF............................................................................ 123
3.2.136 LMBRFLO ............................................................................ 124
3.2.137 ZMRPSB Revision 1............................................................. 124
3.2.138 SMBRREC Revision 1.......................................................... 125
3.2.139 AUT1RSYN Revision 2......................................................... 127
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 4
3.2.140 MAN1RSYN Revision 2........................................................ 128
3.2.141 SYNRSYN Revision 3 .......................................................... 129
3.2.142 SXCBR Revision 1 ............................................................... 130
3.2.143 SXSWI Revision 1 ................................................................ 130
3.2.144 TCLYLTC Revision 3............................................................ 131
3.2.145 TCMYLTC Revision 4........................................................... 132
4 Common Data Class Extensions ............................................................. 134
Redundancy supervision CDC (RSS) ................... 134
5 Enum types Extensions............................................................................ 136
6 Control Block Extensions......................................................................... 137

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 5
1 Introduction

This model implementation conformance statement is applicable for ABB 670 Series version 1.2.

This MICS document specifies the modelling extensions compared to IEC 61850 edition 1
Clause 2 contains the list of implemented logical nodes.
Clause 3 describes the new and extended logical nodes.
Clause 4 describes the new and extended common data classes (if any).
Clause 5 describes the new and extended enum types.
Clause 6 describes any other extensions.

1.1 Scope
The purpose of this document is to serve as the MICS, Modelling Implementation Conformance
Statement according to IEC 61850-10. It covers the content of the products within ABB 670 Series,
release 1.2 that is REB 670, REC 670, RED 670, REG 670, REL 670 and RET 670.
The document contains the description and layout of the Logical Node types, the vendor specific
Logical Nodes and the vendor specific additions to the standard Logical Nodes.
The details of the respective DATA types are described in the ICD file for the respective products,
mentioned above.
There is no vendor specific Common Data Classes defined in these products.

This document describes the layout of the Logical Nodes types used in the ABB 670 Series product
platform. Each Logical Node type represents a function or a part of a function. The descriptions of the
functions and their connection to the logical nodes are described in the Technical reference manuals.
From the products definitions, it is a strict relation between the version of a function and the version
of each Logical Node type and these are re-used in different products based upon ABB 670 Series
platform. Note that the type versions of the Logical Nodes and their attributes are only unique for
each ICD file. This means that during engineering, creating the SCD file(s) of the communication, the
tool may change or add content to the type names.

1.2 Denominations
Although not required nor defined in IEC 61850, the ABB 670 Series family supports version
handling of the Logical Node types. The reason is that it shall be easy to distinguish between the LN
types used in different version of the products based upon the same platform and the version of the
platform. The revisions of LN type higher than 0 have Revision<No> concatenated with the LN type
name.
DATA types are not version handled.

1.3 Related documents


Document Id Title
IEC 61850-5 (2003) Communication Networks and Systems in
Substations – Part 5: Communication
requirements for functions and device
models
IEC 61850-6 (2003) Communication Networks and Systems in

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 6
Substations Part 6: Configuration
description language for communication in
electrical substations related to IEDs
IEC 61850-7-1 (2003) Communication Networks and Systems in
Substations Part 7-1: Basic communication
structure for substation and feeder
equipment – Principles and models
IEC 61850-7-2 (2003) Communication Networks and Systems in
Substations Part 7-2: Basic communication
structure for substations and feeder
equipment – Abstract communication
service interface (ACSI)
IEC 61850-7-3 (2003) Communication Networks and Systems in
Substations Part 7-3: Basic communication
structure for substation and feeder
equipment – Common data classes
IEC 61850-7-4 (2003) Communication Networks and Systems in
Substations Part 7-4: Basic communication
structure for substation and feeder
equipment – Compatible logical node
classes and data classes
IEC 61850-8-1 (2003) Communication Networks and Systems in
Substations Part 8-1: Specific
communication service mapping (SCSM) –
Mapping to MMS(ISO/IEC 9506 Part 1 and
Part 2)
IEC 61850-10 (2005) Communication Networks and Systems in
Substations Part 10: Conformance testing
ABB 1MRG000707 ABB 670 Series 1.2 PIXIT - IEC 61850
Protocol Extra Information
ABB 1MRG000835 ABB 670 Series ver 1.2 - IEC 61850 PICS
Protocol Information Conformance
Statement
ABB 1MRG000706 ABB 670 Series ver 1.2 - IEC 61850 TICS
Tissue Information Conformance Statement

2 Logical Nodes List

The following table contains the list of logical nodes implemented in the device:

A: Logical Nodes for automatic control

ATCC (Automatic tap changer control)

C: Logical Nodes for control

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 7
CBAY (Bay control)

CILO (Interlocking)

CRSV (Bay reserve)

CSWI (Switch controller)

F: Logical Nodes for conversion functions

FCVB (Integer to Boolean converter)

FCVI (Boolean to integer converter)

L: System Logical Nodes

LLN0 (Logical node zero)

LPHD (Physical device information)

P: Logical Nodes for protection functions

PDIF (Differential protection)

PDIS (Distance protection)

PDOP (Directional overpower)

PDUP (Directional underpower)

PFRC (Rate of change of frequency)

PHAR (Harmonic distortion)

PHIZ (Ground detector)

PIOC (Instantaneous overcurrent)

PLAL (Local acceleration logic)

PPAM (Phase angle measuring)

PSCH (Protection scheme)

PSDE (Sensitive directional earthfault)

PSOF (Switch onto fault logic)

PTOC (Time overcurrent)

PTOF (Overfrequency)

PTOV (Overvoltage)

PTRC (Protection trip conditioning)

PTTR (Thermal overload)

PTUC (Time undercurrent)

PTUF (Underfrequency)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 8
PTUV (Undervoltage)

PUPF (Underpower factor)

PVOC (Voltage controlled time overcurrent)

PVPH (Volts per Hz)

R: Logical nodes for protection related functions

RBRF (Breaker failure protection)

RDIF (Differential supervision)

RDIR (Directional element)

RDRE (Disturbance recorder)

RFLO (Fault locator)

RFUF (Fuse failure supervision)

RPLD (Pole discordance protection)

RPSB (Power swing detection)

RPSL (Power Swing Logic)

RREC (Autoreclosing)

RSYN (Synchronising)

G: Logical Nodes for generic references

GAP00C (Generic automatic process control)

GGIO (Generic process I/O)

M: Logical Nodes for metering and measurement

MMTR (Metering)

MMXN (Non phased related measurement)

MMXU (Measurement)

MSQI (Sequence and imbalance)

S: Logical Nodes for sensors and monitoring

X: Logical Nodes for switchgear

XCBR (Circuit breaker)

XSWI (Switch)

Y: Logical Nodes for power transformers

YLTC (Tap changer)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 9
Z: Logical nodes for further power system equipment

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 10
3 Logical Node Extensions

The following table use


 M : Data is mandatory in the IEC-61850-7-4.
 O: Data is optional in the IEC-61850-7-4 and is used in the device.
 E: Data is an extension to the IEC-61850-7-4.
 C: Data is conditional in the IEC-61850-7-4.

3.1 New Logical Nodes

New logical nodes have the lnNs attribute in the Name plate. The value of lnNs is a reference to the
MICS document.
The ABB 670 Series platform contains the following new functions:
LN
Class Prefix LN Type Description
PSOF ZCV ZCVPSOF Automatic switch onto fault logic.
Pole-discordance protection, current and/or contact
RPLD CC CCRPLD based.
RDIF CCS CCSRDIF Current circuit supervision, current based.
Fuse failure supervision, Zero sequence and du/dt
RFUF SDD SDDRFUF and di/dt based.
CBAY Q QCBAY Bay function.
CRSV Q QCRSV Bay reserve function.
PLAL ZCLC ZCLCPLAL Local acceleration logic.
RPSL ZM ZMRPSL Power Swing Logic
FCVB IB16 IB16FCVB Integer to Boolean16 converter
FCVI B16I B16IFCVI Boolean16 to Integer converter

3.1.1 ZCVPSOF Revision 3

PSOF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PSOF Switch onto fault logic.

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 11
Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

Op ABB_bACT Trip output E

3.1.2 CCRPLD

RPLD class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RPLD Pole discordance.

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

Op ABB_bACT Trip signal M

Str ABB_v2ACD Started. Trip condition true, E


waiting for delay time to expire

3.1.3 CCSRDIF Revision 2

RDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RDIF Differential current supervision

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 12
Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

Op ABB_bACT Detection of current circuit E


failure

Alm ABB_v1SPS Alarm for current circuit failure E

3.1.4 SDDRFUF

RFUF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RFUF Fuse failure supervision

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

Str3Ph ABB_v2ACD Three-phase start of function E

Str ABB_v2ACD General start of function E

StrRst ABB_v2ACD Start of current and voltage E


controlled function

3.1.5 QCBAY Revision 1

CBAY class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

CBAY Bay function

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 13
Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_b_dLPL Name plate M

Status Information

LocSwPos ABB_v1_dINS The position of the local E


switch

SrcOpPrm ABB_v1_dINS Permitted Source To Operate E

BlkCmd ABB_v1_dSPC Block commands E Controllable

BlkMeas ABB_v1_dSPS Block measureand E

BlkUpd ABB_v1_dSPC Block update E Controllable

Loc ABB_v1_dSPS Local operation E

Rem ABB_v1_dSPS Remote operation E

3.1.6 QCRSV

CRSV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

CRSV Bay reserve function.

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

AckRsvBay ABB_v1SPS Acknowledge to other bays E


that this bay is reserved

PrmOp1 ABB_v1SPS Reservation is made and the E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 14
app. 1 is allowed to operate

PrmOp2 ABB_v1SPS Reservation is made and the E


app. 2 is allowed to operate

PrmOp3 ABB_v1SPS Reservation is made and the E


app. 3 is allowed to operate

PrmOp4 ABB_v1SPS Reservation is made and the E


app. 4 is allowed to operate

PrmOp5 ABB_v1SPS Reservation is made and the E


app. 5 is allowed to operate

PrmOp6 ABB_v1SPS Reservation is made and the E


app. 6 is allowed to operate

PrmOp7 ABB_v1SPS Reservation is made and the E


app. 7 is allowed to operate

PrmOp8 ABB_v1SPS Reservation is made and the E


app. 8 is allowed to operate

RqRsvBay ABB_v1SPS Request for reservation of E


other bays

Rsv ABB_v1SPS Indicates that the bay is E


reserved

3.1.7 ZCLCPLAL

PLAL class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PLAL Local acceleration logic

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

OpLosLod ABB_v2ACT Trip by loss of load E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 15
OpZnExd ABB_v2ACT Trip by zone extension E

3.1.8 ZMRPSL Revision 2

RPSL class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RPSL Power Swing Logic

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_bLPL Name plate M

Status Information

Op ABB_bACT Operate (TRIP) E

OpUnRchZn ABB_v2ACT underReachZoneOperate E

BlkLoSetZn ABB_v1SPS blockLowSetProtZone E

BlkHiSetZn ABB_v1SPS blockHighSetProtZone E

CarSend ABB_v2ACT carrierSend E

3.1.9 IB16FCVB

FCVB class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Integer to Boolean16
FCVB
converter

Data

Common Logical Node Information


Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 16
NamPlt ABB_b_dLPL Name plate M

Status Information
ISCSO ABB_b_dINC Integer status controllable M Controllable
status output

3.1.10 B16IFCVI

FCVI class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Boolean16 to Integer
FCVI
converter

Data

Common Logical Node Information


Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M

Status Information

OutInt ABB_b_dINS Integer output M

3.2 Extended Logical Nodes

The following logical nodes are included in the product. All extra data that has been added, is marked as
“E” (Extended), these data contains the “dataNs” attribute.

LN Class Prefix LN Type Description


(default)
LLN0 General LN0 for LD0
BBSP BBSPLLN0 LN0 for Busbar protection, 1 phases
BBTP BBTPLLN0 LN0 for Busbar protection, 3 phases

LLN0 CBP CBPLLN0 LN0 for Capacitor Bank Protection


LN0 for Compensated overvoltage and
COUV COUVLLN0 undervoltage protection function for DTT
scheme

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 17
LN0 for Four-step time-delayed non-
EF4 EF4LLN0 directional/directional residual overcurrent
protection
GEN2 GEN2LLN0 LN0 for 2 step protection functions
LN0 for general multipurpose protection
GF2 GF2LLN0
function
LN0 for Low active power and power
LAPP LAPPLLN0
factor detection function for DTT scheme
LN0 for Negativ phase sequence
NS2 NS2LLN0
overcurrent protection, 2 Steps
LN0 for Four-step time-delayed non-
OC4 OC4LLN0 directional / directional phase overcurrent
protection
LN0 for Over current single phase non
OCND OCNDLLN0
direction
RSY1 RSY1LLN0 LN0 for synchrocheck function
LPHD LPHD Physical device information
TR1 TR1ATCC Automatic Tap Changer Control
ATCC
TR8 TR8ATCC Automatic Tap Changer Control
Interlocking modules for three single or
two double CB bays or one 1½ CB
CILO S SCILO
diameter incl. single and multiple
command function blocks
CSWI S SCSWI Switch controller
Accidental energisation protection for
AEG AEGGAPC
generator
GAPC
Impedance supervision logic for Mho
ZSM ZSMGAPC
Distance function
Busbar differential protection zone
BZIT BZITGGIO
interconnection, 3 Phases
Busbar differential protection zone
BZIS BZISGGIO
interconnection, 1 Phase
CNT CNTGGIO Generic counters
DP DPGGIO Generic double point status
MV MVGGIO Generic measured value

GGIO PC PCGGIO Pulse counter for energy metering


SL SLGGIO Selector/rotary switch
SP SPGGIO Generic single point status
SP16 SP16GGIO Generic single point status, 16 outputs
SPC8 SPC8GGIO Single point command, 8 SPC’s
Startupscheme function for Differential
STS STSGGIO
protection
SWS SWSGGIO Switch status used for Busbar protection

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 18
TMA TMAGGIO Trip Matrix
E VSGGIO Versatile Switch
MMTR ETP ETPMMTR Energy Three Phase Measurement
CV CVMMXN Service value reading of power
MMXN Non phase related measurements for
GF2 GF2MMXN
General Multipurpose protection
CBP CBPMMXU Current monitoring
C CMMXU Current monitoring
MMXU
V VMMXU Voltage monitoring
VN VNMMXU Voltage monitoring Ph-Gnd
C CMSQI Current monitoring, sequence values
MSQI
V VMSQI Voltage monitoring, sequence values
Busbar differential protection check zone,
BCZT BCZTPDIF
3 Phases
Busbar differential protection check zone,
BCZS BCZSPDIF 1 Phases
Busbar differential protection zone, 3
BZNT BZNTPDIF Phases
Busbar differential protection zone, 1
BZNS BZNSPDIF
Phases
GEN GENPDIF Generator Differential Protection
Classic restricted earth fault with
HZR HZRPDIF harmonic filtered overcurrent, high
impedance measuring, external VDR
Line differential protection, phase
L3C L3CPDIF
segregated
PDIF Line differential protection, phase
L6C L6CPDIF
segregated
Logical element for line differential
LDL LDLPDIF
function
Line differential protection, phase
LT3C LT3CPDIF segregated including add-on for
transformer in protected zone
Line differential protection, phase
LT6C LT6CPDIF segregated including add-on for
transformer in protected zone
REF REFPDIF Restricted earth fault protection
Transformer Differential protection, two
T2W T2WPDIF
winding
Transformer Differential protection, three
T3W T3WPDIF
winding
Combined phase selection and general
FDPS FDPSPDIS fault-criteria, impedance and current
based
PDIS
FMPS FMPSPDIS Phase selection logic
FPSR FPSRPDIS
Combined phase selection and general
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 19
fault-criteria, impedance and current
based
LEX LEXPDIS Under and Loss of Excitation
Full-scheme distance measuring zone for
ZMC ZMCPDIS series compensation, quadrilateral
characteristic, Zone 1
Full-scheme distance measuring zone for
ZMCA ZMCAPDIS
series compensation, additional zones
ZMH ZMHPDIS Mho Distance function
Full-scheme distance measuring zone,
ZMM ZMMPDIS
quadrilateral characteristic
Full-scheme distance measuring zone,
ZMMA ZMMAPDIS
additional
Full-scheme distance measuring zone,
ZMQ ZMQPDIS
quadrilateral characteristic, Zone 1
Full-scheme distance measuring zone,
ZMQA ZMQAPDIS
additional zones
ZMR ZMRPDIS Full-scheme distance measuring
zone,Quadilateral
ZMRA ZMRAPDIS Full-scheme distance measuring
zone,Quadilateral
GOP GOPPDOP Reverse Power Protection
PDOP
RP3 RP3PDOP Reactive Power Protection
GUP GUPPDUP Low Forward Power Protection
PDUP Low Active power and power factor
LAPP LAPPPDUP
protection for under power

PFRC Selectable over-and under-frequency


SA SAPFRC
function
GEN4 GEN4PHAR Harmonic restraint for 4-stage protection
PHAR function
Harmonic restraint used in General
GF2 GF2PHAR
MultiPurpose protection function
100% Rotor earthfault protection by using
ROTI ROTIPHIZ
injection
PHIZ STEF STEFPHIZ 100% Stator Earth Fault Protection
100% Stator earthfault protection by using
STTI STTIPHIZ
injection
Instantaneous non-directional residual
EF EFPIOC
overcurrent protection
PIOC
Instantaneous non-directional phase
PH PHPIOC
overcurrent protection,
PPAM PSP PSPPPAM Pole slip generator protection
Scheme communication logic for residual
EC ECPSCH
overcurrent protection
Current reversal and weak-end infeed
PSCH ECRW ECRWPSCH
logic for residual over-current protection
Scheme communication logic for residual
ZC ZCPSCH
overcurrent protection

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 20
Current reversal and weak-end infeed
ZCRW ZCRWPSCH
logic for distance protection

ZPC ZPCPSCH Phase segregated communication logic


function
Phase Segregated Current reversal and
ZPCW ZPCWPSCH weak-end infeed logic for distance
protection
Sensitive Directional earth Fault
PSDE SDE SDEPSDE
Protection WEF
BRC BRCPTOC Broken conductor monitoring
Negative Sequence over current for local
LCNS LCNSPTOC
criteria
Three phase over current LN for Local
LCP3 LCP3PTOC
Criterion Check
Zero sequence over current for local
LCZS LCZSPTOC
criteria
Negativ phase sequence overcurrent
NS2 NS2PTOC
protection, 2 Steps
PTOC
Single phase over-current protection 4
PH1B PH1BPTOC
stages for Busbar
Over-current protection used in four-stage
PH1 PH1PTOC
protection function, one phase
Over-current protection used in four-stage
PH3 PH3PTOC
protection functions, three phase
SCCV SCCVPTOC Sudden change in current variation
STB STBPTOC Stub protection
Selectable over-and under-frequency
PTOF SA SAPTOF
function
Over voltage for MAF of Compensated
COUV COUVPTOV
over and under voltage
Over-voltage function for General
GF2 GF2PTOV
Multipurpose protection
PTOV for Harmonic over load in IDMT
HOL HOLPTOV
stage capbankprot
PTOV for Harmonic over load in DT stage
HPH1 HPH1PTOV
capbankprot

PTOV Negatavie sequence over voltage for


LCNS LCNSPTOV
Local criteria
Zero sequence over voltage for local
LCZS LCZSPTOV
criteria
Over-voltage for 2 step over-volt
OV2 OV2PTOV
protection
Over-voltage function for 2 step over-volt
ROV2 ROV2PTOV
protection
VDC VDCPTOV Voltage differential function (for US)
Busbar differential protection bay unit, 1
BUS BUSPTRC
PTRC Phases
Busbar differential protection bay unit, 3
BUT BUTPTRC
Phases
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 21
EF4 EF4PTRC Trip logic for 4-stage earth fault protection
LCCR LCCRPTRC Carrier receive logic for DTT
Trip logic for aggregated functions, one
PH1 PH1PTRC
phase
Trip logic for aggregated functions, three
PH3 PH3PTRC
phase
SMP SMPPTRC Single, two or three pole tripping logic
L LPTTR Thermal overload 1 time constants
PTTR Thermal overload 2 time constants for
TR TRPTTR
transformers
Undercurrent for General Multipurpose
GF2 GF2PTUC
protection
PTUC Under Current Protection LN for Local
LCP3 LCP3PTUC
criterion check in DTT
PH3 PH3PTUC Undercurrent protection, three phase
Selectable over-and under-frequency
PTUF SA SAPTUF
function
Under voltage for MAF of Compensated
COUV COUVPTUF
over and under voltage
Undervoltage function for General
GF2 GF2PTUV
PTUV Multipurpose protection
LOV LOVPTUV Loss of Voltage Check Function
Undervoltage function for 2 step undervolt
UV2 UV2PTUV
protection
Under power factor protection LN for
PUPF LAPP LAPPPUPF
LAPP
Overcurrent function for General
PVOC GF2 GF2PVOC
Multipurpose protection
PVPH OEX OEXPVPH Overexcitation protection
CC CCRBRF Breaker failure protection
RBRF
Breaker failure protection single phase
CCS CCSRBRF
function
Directional element used for 4-stage earth
RDIR EF4 EF4RDIR
fault protection
RDRE DRP DRPRDRE Disturbance recorder
RFLO LMB LMBRFLO Fault locator
RPSB ZM ZMRPSB Power-swing detection
Autorecloser - 1-, 2-, and/or 3-phase,
RREC SMB SMBRREC single circuit breaker, 1 1/2 or double
circuit breaker
Auto control of synchrocheck and
energizing check, single circuit breaker,
RSYN AUT1 AUT1RSYN
11/2 or double circuit breaker, for
automatic purpose

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 22
Manual control of synchrocheck and
energizing check, single circuit breaker,
MAN1 MAN1RSYN
11/2 or double circuit breaker, for manual
purpose
Auto control of synchrocheck and
SYN SYNRSYN energizing check, single circuit breaker,
11/2 or double circuit breaker
XCBR S SXCBR Circuit breaker
XSWI S SXSWI Circuit switch
(large) Load Tap Changer, 32 Binary
TCL TCLYLTC
Input for tap
YLTC
(mini) Load Tap Changer, 6 Binary Input
TCM TCMYLTC
for tap

3.2.1 LLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

LLN0 Logical node 0

Data

Common Logical Node Information


Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M

Status Information

3.2.2 BBSPLLN0

LLN0 class

Attribute DATA Explanation M/O/E Remarks

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 23
/C
Name Type

LLN0 Logical node 0 (for BBSP)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

3.2.3 BBTPLLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

LLN0 Logical node 0 (for BBTP)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

3.2.4 CBPLLN0

LLN0 class

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 24
Attribute DATA M/O/E
Explanation Remarks
Name Type /C

LLN0 Logical node 0 (for CBP)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

CapDisc ABB_v1SPS Signal indicating the E


capacitor bank status

Inh ABB_v1SPS Capacitor bank inhibit E


signal

Op ABB_bACT General operate signal E

Str ABB_bACD General start signal E

3.2.5 COUVLLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

LLN0 Logical node 0 (for COUV)

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_ln0_dLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 25
3.2.6 EF4LLN0 Revision 1

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

LLN0 Logical node 0 (for EF4)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

IvdCrv ABB_v1SPS Invalid coefficients for user E


programmable curve

3.2.7 GEN2LLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0
aggregated function GEN2)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 26
3.2.8 GF2LLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0
aggregated function GF2)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

IvdCrv ABB_v1SPS Invalid coefficients for user E


programmable curves in
PVOC1 and PVOC2

UnVBehMem ABB_v1SPS Low voltage for directional E


polarization

3.2.9 LAPPLLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0 aggregated function
LAPP)

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 27
NamPlt ABB_ln0_dLPL Name plate M

Status Information

3.2.10 NS2LLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0
aggregated function NS2)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

IvdCrv ABB_v1SPS Invalid curve E

NSCurr ABB_v2MV Negative sequence current E


in primary amps

3.2.11 OC4LLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0
aggregated function OC4)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 28
Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

IvdCrv ABB_v1SPS Invalid coefficients for user E


programmable curve

3.2.12 OCNDLLN0

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0
aggregated function OCND)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_ln0LPL Name plate M

Status Information

IvdCrv ABB_v1SPS Invalid coefficients for user E


programmable curve

3.2.13 RSY1LLN0 Revision 2

LLN0 class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Logical node 0 (for


LLN0 aggregated function
RSY1)

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 29
Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_ln0_dLPL Name plate M

Status Information

Bus1Sel ABB_v1_dSPS Bus1 selected E

Bus2Sel ABB_v1_dSPS Bus2 selected E

Lin1Sel ABB_v1_dSPS Line1 selected E

Lin2Sel ABB_v1_dSPS Line2 selected E

SelFuFail ABB_v1_dSPS Selected voltage E


transformer fuse failed

TestEnOK ABB_v1_dSPS Energizing check OK test E


output

VInd ABB_v1_dSPS Voltage difference out of E


limit

VHiAlm ABB_v1_dSPS Voltage amplitudes above E


set limits

InadCBCls ABB_v1_dSPS Inadvertent circuit breaker E


closing

3.2.14 LPHD Revision 4

LPHD class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Physical device
LPHD
information

Data

Common Logical Node Information

PhyNam ABB_a_dDPL Physical device name M


plate

PhyHealth ABB_c_dINS Physical device health M

Status Information

Proxy ABB_b_dSPS Indicates if this LN ia a M


proxy

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 30
SrcSt ABB_v1_dRSS Redundancy port E
supervision

3.2.15 TR1ATCC Revision 4

ATCC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Automatic Tap Changer


ATCC
Control

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Loc ABB_a_dSPS Local operation M

TapChg ABB_a_dBSC Change tap position stop, C Controllable


higher, lower

ParOp ABB_c_dSPC Parallel/Independent M Controllable


operation

LTCBlk ABB_a_dSPC Block (B Inhibit ) Automatic O Controllable


control of LTC

CtlV ABB_b_dMV Control voltage M

LodA ABB_b_dMV Load current O

HiTapPos ABB_b_dINS High tap position O

LoTapPos ABB_b_dINS Low tap position O

VCTRStatus ABB_v2_dINS VCTR Control word (horiz E


com)

LodARe ABB_v4_dMV Real part of load current E


(horiz com)

LodAIm ABB_v3_dMV Imaginary part of load current E


(horiz com)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 31
AutoCtl ABB_v1_dSPC Automatic/Manual control E Controllable

SetV ABB_v6_dMV Voltage setpoint (horiz com) E

AutoRedV ABB_v2_dMV Load dependent automatic E


reduction voltage

PosRel ABB_v7_dMV Relative tap position (horiz E


com)

BusV ABB_v5_dMV Busbar voltage (horiz com) E

AverA ABB_v2_dMV Average of three phase E


current

BndCtrSet ABB_v2_dMV Voltage setpoint set by user E

BndCtrSng ABB_v2_dMV Voltage setpoint single E

DayHuntAlm ABB_v1_dSPS Alarm for to many commands E


within the latest day

ExLowerBlk ABB_v1_dSPS External block of lower E


command activated

ExRaiseBlk ABB_v1_dSPS External block of raise E


command activated

ForceMast ABB_v1_dSPC Force transformer to master E Controllable

HiABlk ABB_v1_dSPS One phase current is above E


the settable limit

HiV ABB_v1_dSPS Voltage above max limit E

HiVArFwd ABB_v1_dSPS Reactive power forward E


alarm

HiVArRv ABB_v1_dSPS Reactive power reverse E


alarm

HiWFwd ABB_v1_dSPS Active power forward alarm E

HiWRv ABB_v1_dSPS Active power reverse alarm E

HrHuntAlm ABB_v1_dSPS Alarm for to many commands E


within the latest hour

HuntAlm ABB_v1_dSPS Alarm from to many E


commands in opposite
direction

LodV ABB_v2_dMV Load voltage E

LoV ABB_v1_dSPS Voltage below min limit E

LVA1On ABB_v1_dSPC Activation of load voltage E Controllable

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 32
adjust. factor 1

LVA1V ABB_v2_dMV Value 1 for load voltage E


adjustment

LVA2On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 2

LVA2V ABB_v2_dMV Value 2 for load voltage E


adjustment

LVA3On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 3

LVA3V ABB_v2_dMV Value 3 for load voltage E


adjustment

LVA4On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 4

LVA4V ABB_v2_dMV Value 4 for load voltage E


adjustment

LVAReset ABB_v1_dSPC Deactivation of load voltage E Controllable


adjust.

RvActBlk ABB_v1_dSPS Block caused by reversed E


action

X2 ABB_v8_dMV Transformer reactance E


secondary side (horiz com)

TotBlock ABB_v1_dSPS Auto and man commands are E


blocked

AutoBlock ABB_v1_dSPS Auto commands are blocked E

TotW ABB_c_dMV Calculated active power E

TotVAr ABB_c_dMV Calculated reactive power E

BlkV ABB_a_dSPS Voltage below block limit E

BndCtrAct ABB_v2_dMV Actual voltage setpoint E

3.2.16 TR8ATCC Revision 5

ATCC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Automatic Tap Changer


ATCC
Control

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 33
Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Loc ABB_a_dSPS Local operation M

TapChg ABB_a_dBSC Change tap position stop, C Controllable


higher, lower

ParOp ABB_c_dSPC Parallel/Independent M Controllable


operation

LTCBlk ABB_a_dSPC Block (B Inhibit ) Automatic O Controllable


control of LTC

CtlV ABB_b_dMV Control voltage M

LodA ABB_b_dMV Load current O

CircA ABB_b_dMV Circulating current O

HiTapPos ABB_b_dINS High tap position O

LoTapPos ABB_b_dINS Low tap position O

VCTRStatus ABB_v2_dINS VCTR Control word (horiz E


com)

Adapt ABB_v1_dSPS The transformer is adapting E

LodARe ABB_v4_dMV Real part of load current E


(horiz com)

LodAIm ABB_v3_dMV Imaginary part of load current E


(horiz com)

AutoCtl ABB_v1_dSPC Automatic/Manual control E Controllable

SetV ABB_v6_dMV Voltage setpoint (horiz com) E

AutoRedV ABB_v2_dMV Load dependent automatic E


reduction voltage

PosRel ABB_v7_dMV Relative tap position (horiz E


com)

AutoSlave ABB_v1_dSPS Auto slave activated E

BusV ABB_v5_dMV Busbar voltage (horiz com) E


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 34
AvBusV ABB_v2_dMV Average of measured busbar E
voltage

AverA ABB_v2_dMV Average of three phase E


current

BndCtrAct ABB_v2_dMV Actual voltage setpoint E

BndCtrPar ABB_v2_dMV Voltage setpoint parallel E

BndCtrSet ABB_v2_dMV Voltage setpoint set by user E

BndCtrSng ABB_v2_dMV Voltage setpoint single E

CCAV ABB_v2_dMV Circulating Current Adjusted E


Voltage

CircABlk ABB_v1_dSPS Block from high circulating E


current

CircALim ABB_v2_dMV Alarm level for high E


circulating current

CircV ABB_v2_dMV Calculated circulating voltage E

CommFlt ABB_v1_dSPS Bay to bay communication E


error

DayHuntAlm ABB_v1_dSPS Alarm for to many commands E


within the latest day

ExLowerBlk ABB_v1_dSPS External block of lower E


command activated

ExRaiseBlk ABB_v1_dSPS External block of raise E


command activated

ForceMast ABB_v1_dSPC Force transformer to master E Controllable

HiABlk ABB_v1_dSPS One phase current is above E


the settable limit

HiPosDif ABB_v1_dSPS To high difference in tap E


positions

HiV ABB_v1_dSPS Voltage above max limit E

HiVArFwd ABB_v1_dSPS Reactive power forward E


alarm

HiVArRv ABB_v1_dSPS Reactive power reverse E


alarm

HiWFwd ABB_v1_dSPS Active power forward alarm E

HiWRv ABB_v1_dSPS Active power reverse alarm E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 35
Homing ABB_v1_dSPS Homing activated E

HrHuntAlm ABB_v1_dSPS Alarm for to many commands E


within the latest hour

HuntAlm ABB_v1_dSPS Alarm from to many E


commands in opposite
direction

LodV ABB_v2_dMV Load voltage E

LoV ABB_v1_dSPS Voltage below min limit E

LTCId ABB_v1_dINS Identity of transformer E

LVA1On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 1

LVA1V ABB_v2_dMV Value 1 for load voltage E


adjustment

LVA2On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 2

LVA2V ABB_v2_dMV Value 2 for load voltage E


adjustment

LVA3On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 3

LVA3V ABB_v2_dMV Value 3 for load voltage E


adjustment

LVA4On ABB_v1_dSPC Activation of load voltage E Controllable


adjust. factor 4

LVA4V ABB_v2_dMV Value 4 for load voltage E


adjustment

LVAReset ABB_v1_dSPC Deactivation of load voltage E Controllable


adjust.

MSMode ABB_v1_dSPS Master Slave mode activated E

Q1Conn ABB_v1_dSPS Reactive bank1 connected E

Q1VAr ABB_v2_dMV Size of reactive bank1 E

Q2Conn ABB_v1_dSPS Reactive bank2 connected E

Q2VAr ABB_v2_dMV Size of reactive bank2 E

Q3Conn ABB_v1_dSPS Reactive bank3 connected E

Q3VAr ABB_v2_dMV Size of reactive bank3 E

RvActBlk ABB_v1_dSPS Block caused by reversed E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 36
action

SimTap ABB_v1_dSPS Simultaneous tapping E


activated

T1Master ABB_v1_dSPS Transformer 1 is master E

T1ParGr ABB_v1_dSPS Transformer 1 included in E


parallel group

T2Master ABB_v1_dSPS Transformer 2 is master E

T2ParGr ABB_v1_dSPS Transformer 2 included in E


parallel group

T3Master ABB_v1_dSPS Transformer 3 is master E

T3ParGr ABB_v1_dSPS Transformer 3 included in E


parallel group

T4Master ABB_v1_dSPS Transformer 4 is master E

T4ParGr ABB_v1_dSPS Transformer 4 included in E


parallel group

T5Master ABB_v1_dSPS Transformer 5 is master E

T5ParGr ABB_v1_dSPS Transformer 5 included in E


parallel group

T6Master ABB_v1_dSPS Transformer 6 is master E

T6ParGr ABB_v1_dSPS Transformer 6 included in E


parallel group

T7Master ABB_v1_dSPS Transformer 7 is master E

T7ParGr ABB_v1_dSPS Transformer 7 included in E


parallel group

T8Master ABB_v1_dSPS Transformer 8 is master E

T8ParGr ABB_v1_dSPS Transformer 8 included in E


parallel group

TotVAr ABB_c_dMV Reactive power E

TotW ABB_c_dMV Active power E

VDif ABB_v1_dSPS VT supervision alarm E

X2 ABB_v8_dMV Transformer reactance E


secondary side (horiz com)

Disc ABB_v1_dSPS Transformer is disconnected E

TotBlock ABB_v1_dSPS Auto and man commands are E


blocked

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 37
AutoBlock ABB_v1_dSPS Auto commands are blocked E

DiffPosMF ABB_v1_dSPS To high difference in tap E


positions

MFFlt ABB_v1_dSPS The number of masters is E


different from one

ParSet ABB_v1_dINS Setting value for transformer E


in parallel mode

BlkV ABB_a_dSPS Voltage below block limit E

3.2.17 SCILO

CILO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

CILO Interlocking

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

EnaOpn ABB_aSPS Enable Open M

EnaCls ABB_aSPS Enable Close M

3.2.18 SCSWI Revision 1

CSWI class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

CSWI Switch control

Data

Common Logical Node Information


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 38
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M

Status Information
Pos ABB_a_dDPC Switch, general M Controllable
OpCls ABB_b_dACT Operation “Close Switch” O
OpOpn ABB_b_dACT Operation “Open Switch” O
BlkCmd ABB_v1_dSPC Block of commands E Controllable

3.2.19 AEGGAPC

GAPC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Accidental energisation
GAPC
protection for generator

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Armed ABB_v1SPS undervoltage activated E

Op ABB_bACT Accidental energization E


generator protection
operate

Str ABB_bACD accidental energization E


generator protection start

StopCarTx ABB_v1SPS Stops the blocking signal to E


remote end

BLkTDmnImp ABB_v1SPS Block signal for blocking of E


time domained mho

CarTcBlk ABB_v1SPS Blocking signal to remote E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 39
en to block overreaching
zone

FLtIncp ABB_v1SPS Fault inception detected for E


any phase voltage

IndHiSIR ABB_v1SPS Indication of source E


impledance ratio above set
limit

3.2.20 ZSMGAPC

GAPC class

Attribute DATA M/O/


Explanation Remarks
Name Type E/C

Impedance supervision logic


GAPC
for Mho Distance function

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

StopCarTx ABB_v1SPS Stops the blocking signal to E


remote end

BLkTDmnImp ABB_v1SPS Block signal for blocking of E


time domained mho

CarTcBlk ABB_v1SPS Blocking signal to remote en E


to block overreaching zone

FLtIncp ABB_v1SPS Fualt inception detected for E


any phase voltage

IndHiSIR ABB_v1SPS Indication of source E


impledance ratio above set
limit

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 40
3.2.21 BZITGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential
GGIO protection zone
interconnection, 3 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Alm ABB_bSPS General single alarm O

Act ABB_v1SPS Load Transfer/Zone E


Interconnection active

3.2.22 BZISGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential
GGIO protection zone
interconnection, 1 Phase

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 41
Alm ABB_bSPS General single alarm O

Act ABB_v1SPS Load Transfer/Zone E


Interconnection active

3.2.23 CNTGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Event counters

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Cnt1 ABB_v1BCR Output of counter 1 E Data type for counter


value is INT32 (INT128 is
not supported)

Cnt2 ABB_v1BCR Output of counter 2 E Data type for counter


value is INT32 (INT128 is
not supported)

Cnt3 ABB_v1BCR Output of counter 3 E Data type for counter


value is INT32 (INT128 is
not supported)

Cnt4 ABB_v1BCR Output of counter 4 E Data type for counter


value is INT32 (INT128 is
not supported)

Cnt5 ABB_v1BCR Output of counter 5 E Data type for counter


value is INT32 (INT128 is
not supported)

Cnt6 ABB_v1BCR Output of counter 6 E Data type for counter


value is INT32 (INT128 is
not supported)

RsCnt ABB_v1SPC Reset counters E Controllable

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 42
3.2.24 DPGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Generic double point status

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

DPCSO ABB_bDPC General position indication O Controllable

3.2.25 MVGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Generic measured value

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 43
AnIn ABB_aMV Measured value O

3.2.26 PCGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Pulse counter

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

AnIn ABB_bMV Scaled measured value O


since the last reset

TotVal ABB_v1BCR Measured value since last E Data type for counter
reset value is INT32 (INT128 is
not supported)

ValUpd ABB_v1SPS A new pulse counter value E


is generated

IcpCyc ABB_v1SPS The reported value does E


not compromise a
complete cycle

3.2.27 SLGGIO Revision 3

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 44
GGIO Selector switch

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

IntIn ABB_b_dINS Integer status input O

SwPosC1 ABB_v2_dISC Integer step controllable E Controllable


output

SPCCO ABB_v2_dSPC Raise/Lower Commands E Controllable

3.2.28 SPGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Generic single point status

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Ind ABB_cSPS Output status O

3.2.29 SP16GGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 45
Generic single point status,
GGIO
16 outputs

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Ind ABB_cSPS General indication (binary O


input)

GrInd ABB_v1SPS OR of all indications 1-16 E

Ind2 ABB_v1SPS General indication no 2 E

Ind3 ABB_v1SPS General indication no 3 E

Ind4 ABB_v1SPS General indication no 4 E

Ind5 ABB_v1SPS General indication no 5 E

Ind6 ABB_v1SPS General indication no 6 E

Ind7 ABB_v1SPS General indication no 7 E

Ind8 ABB_v1SPS General indication no 8 E

Ind9 ABB_v1SPS General indication no 9 E

Ind10 ABB_v1SPS General indication no 10 E

Ind11 ABB_v1SPS General indication no 11 E

Ind12 ABB_v1SPS General indication no 12 E

Ind13 ABB_v1SPS General indication no 13 E

Ind14 ABB_v1SPS General indication no 14 E

Ind15 ABB_v1SPS General indication no 15 E

Ind16 ABB_v1SPS General indication no 16 E

3.2.30 SPC8GGIO

GGIO class

M/O/E
Attribute DATA Explanation Remarks
/C

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 46
Name Type

GGIO Single point command

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

SPCSO1 ABB_v2SPC Single Point Controllable 1 E Controllable

SPCSO2 ABB_v2SPC Single Point Controllable 2 E Controllable

SPCSO3 ABB_v2SPC Single Point Controllable 3 E Controllable

SPCSO4 ABB_v2SPC Single Point Controllable 4 E Controllable

SPCSO5 ABB_v2SPC Single Point Controllable 5 E Controllable

SPCSO6 ABB_v2SPC Single Point Controllable 6 E Controllable

SPCSO7 ABB_v2SPC Single Point Controllable 7 E Controllable

SPCSO8 ABB_v2SPC Single Point Controllable 8 E Controllable

3.2.31 STSGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Startupscheme function
GGIO
for Differential protection

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 47
Startup ABB_v1_dSPS Startup signal output E

StUpCV1 ABB_v1_dSPS Startup for current E


variation phase 23

StUpCV2 ABB_v1_dSPS Startup for current E


variation phase 31

StUpCV3 ABB_v1_dSPS Startup for current E


variation phase 12

StUpZroA ABB_v1_dSPS Startup for zero seq E


current

StUpLoVol ABB_v1_dSPS Startup for Low voltage E


signal

StUpLoCurr ABB_v1_dSPS Startup for Low current E


signal

3.2.32 SWSGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Switch status used for


GGIO
Busbar protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Alm ABB_bSPS General single alarm O

Fcd ABB_v1SPS Primary object status forced E


to open or closed by setting

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 48
3.2.33 TMAGGIO

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Signal matrix

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Out1 ABB_v1SPS OR function between E


inputs 1 and 16

Out2 ABB_v1SPS OR function between E


inputs 17 and 32

Out3 ABB_v1SPS OR function between E


inputs 1 and 32

3.2.34 VSGGIO Revision 1

GGIO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

GGIO Versatile switch

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

DPCSO ABB_d_dDPC Double point controllable O Controllable

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 49
status output

3.2.35 ETPMMTR

MMTR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Energy Three Phase


MMTR
Measurement

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_aINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

SupRs ABB_v1SPC Reset of accumulated E Controllable


energy

MaxDmdRs ABB_v1SPC Reset maximum demands E Controllable

StrAcc ABB_v1SPS Start of accumlating E


energy values

WhFwdAlm ABB_v1SPS Alarm of energy active E


forward for exceeding the
limit

WhRvAlm ABB_v1SPS Alarm of energy active E


reverse for exceeding the
limit

VArhFwdAlm ABB_v1SPS Alarm of energy reactive E


forward for exceeding the
limit

VArhRvAlm ABB_v1SPS Alarm of energy reactive E


reverse for exceeding the
limit

VArsAccFwd ABB_v2MV Accumulated forward E


reactive energy

VArsAccRev ABB_v2MV Accumulated reverse E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 50
reactive energy

WsAccFwd ABB_v2MV Accumulated forward E


active energy

WsAccRev ABB_v2MV Accumulated reverse E


active energy

MaxVArFwdD ABB_v2MV Maximum reactive power E


demand value in forward
direction

MaxVArRvDm ABB_v2MV Maximum reactive power E


demand value in reverse
direction

MaxWFwdDmd ABB_v2MV Maximum active power E


demand value in forward
direction

MaxWRvDmd ABB_v2MV Maximum active power E


demand value in reverse
direction

3.2.36 CVMMXN Revision 1

MMXN class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Service value reading of


MMXN
power

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 51
NamPlt ABB_a_dLPL Name plate M

Status Information

Amp ABB_a_dMV Current I (rms) not allocated O


to a phase

Vol ABB_a_dMV Voltage V (rms) not allocated O


to a phase

Watt ABB_a_dMV Power (P) not allocated to a O


phase

VolAmpr ABB_a_dMV Reactive Power (Q) not O


allocated to a phase

VolAmp ABB_a_dMV Apparent Power (S) not O


allocated to a phase

PwrFact ABB_a_dMV Power Factor not allocated to O


a phase

Hz ABB_a_dMV Frequency O

ALd ABB_v1_dSPS Current is leading voltage E

ALg ABB_v1_dSPS Current is lagging voltage E

3.2.37 GF2MMXN Revision 3

MMXN class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Non phase related


MMXN measurements for General
Multipurpose protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 52
Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Amp ABB_bMV Measured current value O

Vol ABB_bMV Measured voltage value O

AmpPwrFact ABB_v2MV Measured current multiplied E


with cos (Phi)

VolAmpAng ABB_v2MV Angle between voltage and E


current

3.2.38 CBPMMXU

MMXU class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

MMXU Current monitoring

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

APeakPhA ABB_v2MV Peak value of current for E


phase L1

APeakPhB ABB_v2MV Peak value of current for E


phase L2

APeakPhC ABB_v2MV Peak value of current for E


phase L3

VArPhA ABB_v2MV Reactive power value for E


phase L1

VArPhB ABB_v2MV Reactive power value for E


phase L2

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 53
VArPhC ABB_v2MV Reactive power value for E
phase L3

VRMSPhA ABB_v2MV Calculated voltage for phase E


L1

VRMSPhB ABB_v2MV Calculated voltage for phase E


L2

VRMSPhC ABB_v2MV Calculated voltage for phase E


L3

3.2.39 CMMXU

MMXU class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

MMXU Current monitoring

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

A ABB_aWYE Phase currents (IL1, IL2, IL3) O

3.2.40 VMMXU

MMXU class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

MMXU Voltage monitoring

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 54
Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

PPV ABB_aDEL Phase to phase voltages O


(VL1VL2, …)

3.2.41 VNMMXU

MMXU class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

MMXU Voltage monitoring Ph-Gnd

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

PhV ABB_aWYE Phase to ground voltages O


(VL1ER, …)

3.2.42 CMSQI Revision 1

MSQI class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 55
Current monitoring,
MSQI
sequence values

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

SeqA ABB_aSEQ Positive, Negative and Zero C


Sequence Current

3.2.43 VMSQI Revision 1

MSQI class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Voltage monitoring,
MSQI
sequence values

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

SeqV ABB_aSEQ Positive, Negative and Zero C


Sequence Voltage

3.2.44 BCZTPDIF

PDIF class

Attribute DATA Explanation M/O/E Remarks

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 56
/C
Name Type

Busbar differential protection


PDIF
check zone, 3 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate M

3.2.45 BCZSPDIF

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential protection


PDIF
check zone, 1 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 57
3.2.46 BZNTPDIF

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential protection


PDIF
zone, 3 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate M

DifAClc ABB_aWYE Differential Current O

RstA ABB_aWYE Restraint Current O

IndOpExBay ABB_v1SPS Zone trip due to external trip E


from one of the connected
bays

IndOpExZn ABB_v1SPS Zone trip due to external E


input signal

IndOpSen1 ABB_v1SPS Sensitive differential function E


trip phase 1

OpnCTAlm ABB_v1SPS General open CT alarm E

ADifAlm1 ABB_v1SPS Differential current alarm E


phase 1

OpRs ABB_v1SPC Trip reset used by command E Controllable


handling

OpnCTRs ABB_v1SPC Open CT reset used by E Controllable


command handling

IndOpDif1 ABB_v1SPS Differential trip phase 1 E

IndOpDif2 ABB_v1SPS Differential trip phase 2 E

IndOpDif3 ABB_v1SPS Differential trip phase 3 E

IndOpSen2 ABB_v1SPS Sensitive differential function E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 58
trip phase 2

IndOpSen3 ABB_v1SPS Sensitive differential function E


trip phase 3

ADifAlm2 ABB_v1SPS Differential current alarm E


phase 2

ADifAlm3 ABB_v1SPS Differential current alarm E


phase 3

3.2.47 BZNSPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential protection


PDIF
zone, 1 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate M

DifAClcS ABB_v1_dMV Differential Current, non E


phase related

Amp ABB_a_dMV Sum of incomming currents, E


RMS value

IndOpExBay ABB_v1SPS Zone trip due to external trip E


from one of the connected
bays

IndOpExZn ABB_v1SPS Zone trip due to external E


input signal

IndOpSen ABB_v1SPS Sensitive differential function E


start

OpnCTAlm ABB_v1SPS General open CT alarm E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 59
ADifAlm ABB_v1SPS Differential current alarm E

OpRs ABB_v1SPC Trip reset used by command E Controllable


handling

OpnCTRs ABB_v1SPC Open CT reset used by E Controllable


command handling

IndOpDif ABB_v1SPS Differential trip E

3.2.48 GENPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Generator Differential
PDIF
Protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate M

Str ABB_aACD Start O

BlkHPhA ABB_v1SPS Harmonic block L1 E

BlkHPhB ABB_v1SPS Harmonic block L2 E

BlkHPhC ABB_v1SPS Harmonic block L3 E

OpRst ABB_v1SPS tripRestrained E

OpUnRst ABB_v1SPS tripUnrestrained E

OpNSUnRst ABB_v1SPS tripNegSeqUnrestrained E

OpNSSen ABB_v1SPS tripNegSeqSensitive E

ItrFlt ABB_v1SPS InternalFault E

ExFlt ABB_v1SPS ExternalFault E

BlkH ABB_v1SPS harmonicBlock E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 60
DifANS ABB_v2MV currDiffNegSeq E

RstMaxA ABB_v2MV currBias E

OpnCT ABB_v1SPS An open CT was detected E

OpnCTVal ABB_v1INS Open CT side : 1 -> Terminal E


side, 2 -> Neutral side

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay

3.2.49 HZRPDIF

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Classic restricted earth fault


with harmonic filtered
PDIF
overcurrent, high impedance
measuring, external VDR

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Trip signal M

Alm ABB_v1SPS Alarm signal E

3.2.50 L3CPDIF Revision 1

PDIF class

Attribute DATA Explanation M/O/E Remarks


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 61
/C
Name Type

Line differential protection,


PDIF
phase segregated

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Common, main, trip output M


signal

Str ABB_aACD Common, main, start output O


signal

OpCrv ABB_aCURVE 19 curve types. Example: 15 E


for definite time delay.

Blk2HPhA ABB_v1SPS Block signal due to 2nd E


harmonic, phase L1

Blk2HPhB ABB_v1SPS Block signal due to 2nd E


harmonic, phase L2

Blk2HPhC ABB_v1SPS Block signal due to 2nd E


harmonic, phase L3

Blk5HPhA ABB_v1SPS Block signal due to 5th E


harmonic, phase L1

Blk5HPhB ABB_v1SPS Block signal due to 5th E


harmonic, phase L2

Blk5HPhC ABB_v1SPS Block signal due to 5th E


harmonic, phase L3

Blk2H ABB_v1SPS Common, block, due to 2-nd E


harmonic

Blk5H ABB_v1SPS Common, block, due to 5-th E


harmonic

ExFlt ABB_v1SPS External fault has been E


detected

ItrFlt ABB_v1SPS Internal fault has been E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 62
detected

OpNSUnRst ABB_v1SPS Trip by enhanced restrained E


differential protection

OpRst ABB_v1SPS Trip by restrained differential E


protection

OpUnRst ABB_v1SPS Trip by unrestrained E


differential protection

OpnCT ABB_v1SPS Open Current Transformer E

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay ...

3.2.51 L6CPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Line differential protection,


PDIF
phase segregated

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Common, main, trip output M


signal

Str ABB_aACD Common, main, start output O


signal

OpCrv ABB_aCURVE 19 curve types. Example: 15 E


for definite time delay.

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 63
Blk2HPhA ABB_v1SPS Block signal due to 2nd E
harmonic, phase L1

Blk2HPhB ABB_v1SPS Block signal due to 2nd E


harmonic, phase L2

Blk2HPhC ABB_v1SPS Block signal due to 2nd E


harmonic, phase L3

Blk5HPhA ABB_v1SPS Block signal due to 5th E


harmonic, phase L1

Blk5HPhB ABB_v1SPS Block signal due to 5th E


harmonic, phase L2

Blk5HPhC ABB_v1SPS Block signal due to 5th E


harmonic, phase L3

Blk2H ABB_v1SPS Common, block, due to 2-nd E


harmonic

Blk5H ABB_v1SPS Common, block, due to 5-th E


harmonic

ExFlt ABB_v1SPS External fault has been E


detected

ItrFlt ABB_v1SPS Internal fault has been E


detected

OpNSUnRst ABB_v1SPS Trip by enhanced restrained E


differential protection

OpRst ABB_v1SPS Trip by restrained differential E


protection

OpUnRst ABB_v1SPS Trip by unrestrained E


differential protection

OpnCT ABB_v1SPS An open CT was detected E

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay ...

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

3.2.52 LDLPDIF

PDIF class

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 64
Attribute DATA M/O/E
Explanation Remarks
Name Type /C

Logical element for line


PDIF
differential function

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate M

OpLoc ABB_v1ACT Operation local differential E


function

OpRem ABB_v2ACT Operation from remote E


differential function

LocDifBlk ABB_v1SPS Local differential function E


blocked

3.2.53 LT3CPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Line differential protection,


phase segregated including
PDIF
add-on for transformer in
protected zone

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 65
NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Common, main, start output O


signal

Op ABB_aACT Operate M

OpCrv ABB_aCURVE 19 curve types. Example: 15 E


for definite time delay.

Blk2HPhA ABB_v1SPS Block signal due to 2nd E


harmonic, phase L1

Blk2HPhB ABB_v1SPS Block signal due to 2nd E


harmonic, phase L2

Blk2HPhC ABB_v1SPS Block signal due to 2nd E


harmonic, phase L3

Blk5HPhA ABB_v1SPS Block signal due to 5th E


harmonic, phase L1

Blk5HPhB ABB_v1SPS Block signal due to 5th E


harmonic, phase L2

Blk5HPhC ABB_v1SPS Block signal due to 5th E


harmonic, phase L3

Blk2H ABB_v1SPS Common, block, due to 2-nd E


harmonic

Blk5H ABB_v1SPS Common, block, due to 5-th E


harmonic

ExFlt ABB_v1SPS External fault has been E


detected

ItrFlt ABB_v1SPS Internal fault has been E


detected

OpNSUnRst ABB_v1SPS Trip by enhanced restrained E


differential protection

OpRst ABB_v1SPS Trip by restrained differential E


protection

OpUnRst ABB_v1SPS Trip by unrestrained E


differential protection

OpnCT ABB_v1SPS An open CT was detected E

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay ...

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 66
OpnCTIn ABB_v1INS Open CT on Input : 1 for E
input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

3.2.54 LT6CPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Line differential protection,


phase segregated including
PDIF
add-on for transformer in
protected zone

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Common, main, start output O


signal

Op ABB_aACT Operate M

OpCrv ABB_aCURVE 19 curve types. Example: 15 E


for definite time delay.

Blk2HPhA ABB_v1SPS Block signal due to 2nd E


harmonic, phase L1

Blk2HPhB ABB_v1SPS Block signal due to 2nd E


harmonic, phase L2

Blk2HPhC ABB_v1SPS Block signal due to 2nd E


harmonic, phase L3

Blk5HPhA ABB_v1SPS Block signal due to 5th E


harmonic, phase L1

Blk5HPhB ABB_v1SPS Block signal due to 5th E


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 67
harmonic, phase L2

Blk5HPhC ABB_v1SPS Block signal due to 5th E


harmonic, phase L3

Blk2H ABB_v1SPS Common, block, due to 2-nd E


harmonic

Blk5H ABB_v1SPS Common, block, due to 5-th E


harmonic

ExFlt ABB_v1SPS External fault has been E


detected

ItrFlt ABB_v1SPS Internal fault has been E


detected

OpNSUnRst ABB_v1SPS Trip by enhanced restrained E


differential protection

OpRst ABB_v1SPS Trip by restrained differential E


protection

OpUnRst ABB_v1SPS Trip by unrestrained E


differential protection

OpnCT ABB_v1SPS An open CT was detected E

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay ...

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

3.2.55 REFPDIF

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Restricted earth fault


PDIF
protection

Data

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 68
Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start by restricted earth fault O


protection function

Op ABB_bACT Trip by restricted earth fault M


protection function

Blk2H ABB_v1SPS Block due to 2-nd harmonic E

ItrFlt ABB_v1SPS Directional Criteria has E


operated for internal fault

3.2.56 T2WPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Transformer Differential
PDIF
protection, two winding

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Main, common start signal O

Op ABB_bACT Main, common trip command M

Blk2HPhA ABB_v1SPS Second harmonic block E


signal, phase L1

Blk2HPhB ABB_v1SPS Second harmonic block E


signal, phase L2
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 69
Blk2HPhC ABB_v1SPS Second harmonic block E
signal, phase L3

Blk5HPhA ABB_v1SPS Fifth harmonic block signal, E


phase L1

Blk5HPhB ABB_v1SPS Fifth harmonic block signal, E


phase L2

Blk5HPhC ABB_v1SPS Fifth harmonic block signal, E


phase L3

BlkWavPhA ABB_v1SPS Block signal, waveform E


criterion, phase L1

BlkWavPhB ABB_v1SPS Block signal, waveform E


criterion, phase L2

BlkWavPhC ABB_v1SPS Block signal, waveform E


criterion, phase L3

OpRst ABB_v1SPS Trip request signal from E


restrained differential
protection

OpNSSen ABB_v1SPS Trip request from negative E


sequence sensitive
differential protection

OpNSUnRst ABB_v1SPS Trip request from negative E


sequence unrestrained
differential protection

OpUnRst ABB_v1SPS Trip request signal from E


unrestrained differential
protection

Blk2H ABB_v1SPS Common second harmonic E


block signal

Blk5H ABB_v1SPS Common fifth harmonic block E


signal

BlkWav ABB_v1SPS Common block signal, E


waveform criterion

ExFlt ABB_v1SPS Binary output signal, external E


fault detected

ItrFlt ABB_v1SPS Binary output signal, internal E


fault detected

OpnCT ABB_v1SPS An open CT was detected E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 70
OpnCTVal ABB_v1INS Open CT side : 1 -> W 1 E
(pri), 2 -> W 2 (sec), 3 -> W 3

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E


2 for L2, 3 for L3

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay

DifAlm ABB_v1SPS Alarm for sustained E


differential current

3.2.57 T3WPDIF Revision 1

PDIF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Transformer Differential
PDIF
protection, three winding

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Main, common start signal O

Op ABB_bACT Main, common trip command M

Blk2HPhA ABB_v1SPS Second harmonic block E


signal, phase L1

Blk2HPhB ABB_v1SPS Second harmonic block E


signal, phase L2

Blk2HPhC ABB_v1SPS Second harmonic block E


signal, phase L3

Blk5HPhA ABB_v1SPS Fifth harmonic block signal, E


phase L1

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 71
Blk5HPhB ABB_v1SPS Fifth harmonic block signal, E
phase L2

Blk5HPhC ABB_v1SPS Fifth harmonic block signal, E


phase L3

BlkWavPhA ABB_v1SPS Block signal, waveform E


criterion, phase L1

BlkWavPhB ABB_v1SPS Block signal, waveform E


criterion, phase L2

BlkWavPhC ABB_v1SPS Block signal, waveform E


criterion, phase L3

OpRst ABB_v1SPS Trip request signal from E


restrained differential
protection

OpNSSen ABB_v1SPS Trip request from negative E


sequence sensitive
differential protection

OpNSUnRst ABB_v1SPS Trip request from negative E


sequence unrestrained
differential protection

OpUnRst ABB_v1SPS Trip request signal from E


unrestrained differential
protection

Blk2H ABB_v1SPS Common second harmonic E


block signal

Blk5H ABB_v1SPS Common fifth harmonic block E


signal

BlkWav ABB_v1SPS Common block signal, E


waveform criterion

ExFlt ABB_v1SPS Binary output signal, external E


fault detected

ItrFlt ABB_v1SPS Binary output signal, internal E


fault detected

OpnCT ABB_v1SPS An open CT was detected E

OpnCTVal ABB_v1INS Open CT side : 1 -> W 1 E


(pri), 2 -> W 2 (sec), 3 -> W 3

OpnCTIn ABB_v1INS Open CT on Input : 1 for E


input 1, 2 for input 2

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 72
OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, E
2 for L2, 3 for L3

OpnCTAlm ABB_v1SPS Open CT Alarm output E


signal. Issued after a delay

DifAlm ABB_v1SPS Alarm for sustained E


differential current

3.2.58 FDPSPDIS Revision 2

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Combined phase selection


and general fault-criteria,
PDIS
impedance and current
based

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_bACT Operate M

StrFwdPhA ABB_v1SPS Fault detected in phase L1 - E


forward direction

StrFwdPhB ABB_v1SPS Fault detected in phase L2 - E


forward direction

StrFwdPhC ABB_v1SPS Fault detected in phase L3 - E


forward direction

StrFwdGnd ABB_v1SPS Earth fault detected in E


forward direction

StrRvPhA ABB_v1SPS Fault detected in phase L1 - E


reverse direction

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 73
StrRvPhB ABB_v1SPS Fault detected in phase L2 - E
reverse direction

StrRvPhC ABB_v1SPS Fault detected in phase L3 - E


reverse direction

StrRvGnd ABB_v1SPS Earth fault detected in E


reverse direction

StrNDPhA ABB_v1SPS Fault detected in phase L1- E


non directional

StrNDPhB ABB_v1SPS Fault detected in phase L2- E


non directional

StrNDPhC ABB_v1SPS Fault detected in phase L3- E


non directional

StrNDGnd ABB_v1SPS Earth fault detected- non E


directional

Str1Ph ABB_v1SPS Single-phase fault detected E


in forward direction

Str2Ph ABB_v1SPS Two-phase fault detected in E


forward direction

Str3Ph ABB_v1SPS Three-phase fault detected in E


forward direction

RelGnd ABB_v1SPS Current conditions release of E


phase-to-earth measuring
elements

RelPP ABB_v1SPS Current conditions release of E


phase-to-phase measuring
elements

StrCndZ ABB_v1INS Start condition (PHS,LE and I E


based)

StrCndA ABB_v1INS Start condition (LE and I E


based)

3.2.59 FMPSPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PDIS Phase selection logic

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 74
Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

EFlt ABB_v1SPS Ground fault detected E

3.2.60 FPSRPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Combined phase selection


and general fault-criteria,
PDIS
impedance and current
based

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_bACT Operate M

StrFwdPhA ABB_v1SPS Fault detected in phase L1 - E


forward direction

StrFwdPhB ABB_v1SPS Fault detected in phase L2 - E


forward direction

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 75
StrFwdPhC ABB_v1SPS Fault detected in phase L3 - E
forward direction

StrFwdGnd ABB_v1SPS Earth fault detected in E


forward direction

StrRvPhA ABB_v1SPS Fault detected in phase L1 - E


reverse direction

StrRvPhB ABB_v1SPS Fault detected in phase L2 - E


reverse direction

StrRvPhC ABB_v1SPS Fault detected in phase L3 - E


reverse direction

StrRvGnd ABB_v1SPS Earth fault detected in E


reverse direction

StrNDPhA ABB_v1SPS Fault detected in phase L1- E


non directional

StrNDPhB ABB_v1SPS Fault detected in phase L2- E


non directional

StrNDPhC ABB_v1SPS Fault detected in phase L3- E


non directional

StrNDGnd ABB_v1SPS Earth fault detected- non E


directional

Str1Ph ABB_v1SPS Single-phase fault detected E


in forward direction

Str2Ph ABB_v1SPS Two-phase fault detected in E


forward direction

Str3Ph ABB_v1SPS Three-phase fault detected in E


forward direction

RelGnd ABB_v1SPS Current conditions release of E


phase-to-earth measuring
elements

RelPP ABB_v1SPS Current conditions release of E


phase-to-phase measuring
elements

StrCndZ ABB_v1INS Start condition (PHS,LE and I E


based)

StrCndA ABB_v1INS Start condition (LE and I E


based)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 76
3.2.61 LEXPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PDIS Under and Loss of Excitation

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

OpZ1 ABB_v1SPS Trip signal from impedance E


zone Z1

OpZ2 ABB_v1SPS Trip signal from impedance E


zone Z2

StrZ1 ABB_v1SPS Start signal from impedance E


zone Z1

StrZ2 ABB_v1SPS Start signal from impedance E


zone Z2

PriRis ABB_v2MV Resistance in Primary Ohms E

PriReact ABB_v2MV Reactance in Primary Ohms E

3.2.62 ZMCPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
measuring zone for series
PDIS
compensation, quadrilateral
characteristic, Zone 1

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 77
Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.63 ZMCAPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
measuring zone for series
PDIS
compensation, additional
zones

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 78
3.2.64 ZMHPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PDIS Mho Distance function

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrPP ABB_v1SPS Phase - phase start signal E

StrPh ABB_v1SPS Phase - earth start signal E

OpPP ABB_v1SPS Phase - phase trip signal E

OpPh ABB_v1SPS Phase - earth trip signal E

3.2.65 ZMMPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
PDIS measuring zone,
quadrilateral characteristic

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 79
Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.66 ZMMAPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
PDIS
measuring zone, additional

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.67 ZMQPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
measuring zone,
PDIS
quadrilateral characteristic,
Zone 1

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 80
Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.68 ZMQAPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
PDIS measuring zone, additional
zones

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 81
Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.69 ZMRPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
PDIS
measuring zone,Quadilateral

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.70 ZMRAPDIS

PDIS class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Full-scheme distance
PDIS
measuring zone,Quadilateral

Data

Common Logical Node Information

Beh ABB_aINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 82
Health ABB_cINS Health M

Mod ABB_aINC Mode M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate M

Str ABB_aACD Start M

StrNDir ABB_v1SPS Non-directional start, issued E


from any phase or loop

3.2.71 GOPPDOP

PDOP class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Generator power protection,


PDOP
reverse

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

OpZ1 ABB_v1SPS Trip of stage 1 E

OpZ2 ABB_v1SPS Trip of stage 2 E

StrZ1 ABB_v1SPS Start of stage 1 E

StrZ2 ABB_v1SPS Start of stage 2 E

MW ABB_v2MV Active Power in MW E

MVAr ABB_v2MV Reactive power in MVar E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 83
3.2.72 RP3PDOP

PDOP class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PDOP Reactive Power Protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

3.2.73 GUPPDUP

PDUP class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Generator power protection,


PDUP
forward

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

OpZ1 ABB_v1SPS Trip of stage 1 E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 84
OpZ2 ABB_v1SPS Trip of stage 2 E

StrZ1 ABB_v1SPS Start of stage 1 E

StrZ2 ABB_v1SPS Start of stage 2 E

MW ABB_v2MV Active Power in MW E

MVAr ABB_v2MV Reactive power in MVar E

3.2.74 LAPPPDUP

PDUP class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Low Active power and power


PDUP factor protection for under
power

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_b_dACT Operate M

3.2.75 SAPFRC

PFRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Frequency gradient
PFRC
protection

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 85
Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start/pick-up signal for M


frequencyGradient

Op ABB_bACT Operate/trip signal for M


frequencyGradient

BlkLoMg ABB_v1SPS Signal indicating internal E


blocking due to low amplitude
of signal from which
frequency is calculated

RestLd ABB_v1SPS Restore signal for frequency E

3.2.76 GEN4PHAR Revision 1

PHAR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Harmonic restraint for 4-


PHAR
stage protection function

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_bACD Start (active when restraint is M


needed)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 86
3.2.77 GF2PHAR

PHAR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Harmonic restraint used in


PHAR General MultiPurpose
protection function

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_bACD Start (active when restraint is M


needed)

3.2.78 ROTIPHIZ

PHIZ class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

100% Rotor earthfault


PHIZ
protection by using injection

Data

Common Logical Node Information

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

Mod ABB_aINC Mode M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate O

Str ABB_bACD Start O

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 87
Alm ABB_v1SPS Alarm rotor E

Error ABB_v1SPS Error rotor E

ErrorSt ABB_v1INS Error status rotor (change E


description)

OpAC ABB_v2ACT Trip for ground fault on AC- E


side of exciter

OpDC ABB_v2ACT Trip for rotor ground fault (on E


DC-side of exciter)

OpnCir ABB_v1SPS Open rotor injection circuit E

StrAC ABB_v2ACD Start for ground fault on AC- E


side of exciter

StrDC ABB_v2ACD Start for rotor ground fault E


(on DC-side of exciter)

3.2.79 STEFPHIZ Revision 1

PHIZ class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

100% Stator Earth Fault


PHIZ
Protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start O

Op ABB_bACT Operate O

Op3rdH ABB_v1SPS Trip by one of two 3rd E


harmonic voltage

OpUN ABB_v1SPS Trip by fund. freq. neutral E


over-voltage

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 88
Str3rdH ABB_v1SPS Start by one of two 3rd E
harmonic voltage

StrUN ABB_v1SPS Start by fund. freq. neutral E


over-voltage

VT3rdH ABB_v2MV Magnitude of 3rd harmonic E


voltage at generator terminal
side

VN3rdH ABB_v2MV Magnitude of 3rd harmonic E


voltage at generator neutral
side

E3 ABB_v2MV Total induced (source) stator E


3rd harmonic voltage

VolAngClc ABB_v2MV Angle between E


voltT3rdHarmonic and
voltN3rdHarmonic

VDif3rdH ABB_v2MV Diff. between E


voltT3rdHarmonic,
voltN3rdHarmonic

VBias3rdH ABB_v2MV Bias voltage, a part of E


voltN3rdHarmonic

UN ABB_v2MV Fund. frequency voltage at E


generator neutral

3.2.80 STTIPHIZ

PHIZ class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

100% Stator earthfault


PHIZ
protection by using injection

Data

Common Logical Node Information

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

Mod ABB_aINC Mode M

NamPlt ABB_aLPL Name plate M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 89
Status Information

Op ABB_bACT Operate O

Str ABB_bACD Start O

Alm ABB_v1SPS Alarm stator E

Error ABB_v1SPS Error stator E

ErrorSt ABB_v1INS Error status stator (change E


description)

OpnCir ABB_v1SPS Open stator injection circuit E

3.2.81 EFPIOC

PIOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Instantaneous non-directional
PIOC residual overcurrent
protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate M

3.2.82 PHPIOC

PIOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Instantaneous non-directional
PIOC
phase overcurrent protection

Data

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 90
Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate M

3.2.83 PSPPPAM Revision 1

PIOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PPAM Pole slip generator protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

Gen ABB_v1SPS Generator E

Mot ABB_v1SPS Motor E

N2SlpDet ABB_v1SPS Trip 2 E

SlpZ1 ABB_v1SPS First slip in zone1 region E

SlpZ2 ABB_v1SPS First slip in zone2 region E

N1SlpDet ABB_v1SPS Trip 1 E

SlpHz ABB_v2MV slipFrequncy E

SlpZOhm ABB_v2MV slipImpedance_Ohm E

CosUkV ABB_v2MV uCosPhi_KV E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 91
3.2.84 ECPSCH

PSCH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Scheme communication logic


PSCH for residual overcurrent
protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Teleprotection signal M


transmitted

ProRx ABB_aSPS Teleprotection signal M


received

Str ABB_bACD Carrier Send M

Op ABB_bACT Operate M

CarRx ABB_bACT Carrier Signal received signal O


from Communication Logic

LosOfGrd ABB_aSPS Loss of carrier guard signal O

3.2.85 ECRWPSCH Revision 1

PSCH class

Attribute DATA Explanation M/O/E Remarks

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 92
/C
Name Type

Current reversal and weak-


PSCH end infeed logic for residual
over-current protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Teleprotection signal M


transmitted

ProRx ABB_aSPS Teleprotection signal M


received

Str ABB_bACD Carrier Send M

Op ABB_bACT Operate M

Echo ABB_bACT Carrier send by WEI logic O

WeiOp ABB_bACT Trip of WEI logic O

RvABlk ABB_bACT Operation of current reversal O


logic

3.2.86 ZCPSCH

PSCH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Scheme communication logic


PSCH for residual overcurrent
protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 93
Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Teleprotection signal M


transmitted for a forward fault

ProRx ABB_aSPS Teleprotection signal M


received for a forward fault

Str ABB_bACD Carrier Send by M


Communication Scheme
Logic

Op ABB_bACT Trip by Communication M


Scheme Logic-Residual

CarRx ABB_bACT Carrier Signal received or O


missing carrier guard signal

LosOfGrd ABB_aSPS Loss of carrier guard signal O

3.2.87 ZCRWPSCH Revision 1

PSCH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Current reversal and weak-


PSCH end infeed logic for distance
protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Carrier send by WEI logic M

ProRx ABB_aSPS Carrier signal received from M


remote end

Str ABB_bACD Carrier send by WEI logic M


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 94
Op ABB_aACT Trip of WEI logic M

Echo ABB_bACT Carrier send by WEI logic O

WeiOp ABB_bACT Trip of WEI logic O

RvABlk ABB_bACT Operation of current reversal O


function

3.2.88 ZPCPSCH

PSCH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Phase segregated
PSCH
communication logic function

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Teleprotection signal M


transmitted

ProRx ABB_aSPS Teleprotection signal M


received

Str ABB_aACD Carrier Send M

Op ABB_aACT Operate M

CarRx ABB_aACT Carrier received after unblock O


logic

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 95
3.2.89 ZPCWPSCH

PSCH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Phase Segregated Current


PSCH reversal and weak-end infeed
logic for distance protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

ProTx ABB_aSPS Teleprotection signal M


transmitted

ProRx ABB_aSPS Teleprotection signal M


received

Str ABB_aACD Carrier Send M

Op ABB_aACT Operate M

RvABlk ABB_aACT Block signal from current O


reversal function

3.2.90 SDEPSDE

PSDE class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Sensitive Directional earth


PSDE
Fault Protection WEF

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 96
Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate O

OpResA ABB_v1SPS Operate for non directional E


residual over current
protection

OpResV ABB_v1SPS Operate for non directional E


residual over voltage
protection

StrResA ABB_v1SPS Start for non directional E


residual over current
protection

StrResV ABB_v1SPS Start for non directional E


residual over voltage
protection

AngAV ABB_v2MV Angle between residual E


current and polarizing
compensate voltage

ResA ABB_v2MV Measured magnitude of the E


residual current

ResV ABB_v2MV Measured magnitude of the E


residual voltage

ResP ABB_v2MV Magnitude of 3I03U0cosFi E


the active power due to
residual current

StrDirResA ABB_v1SPS Start of directional residual E


over current protection

OpDirResA ABB_v1SPS Operate of directional E


residual over current
protection

TypInCrv ABB_v1CURVE Operation curve selection for E


IDMT operation

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 97
3.2.91 BRCPTOC Revision 2

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOC Broken conductor monitoring

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

UnbA ABB_v2MV Current Unbalance E

StrDur ABB_v2MV Start Duration E

3.2.92 LCNSPTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Negative Sequence over


PTOC
current for local criteria

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_d_dACD Start M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 98
Op ABB_b_dACT Operate M

3.2.93 LCP3PTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Three phase over current LN


PTOC
for Local Criterion Check

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate M

3.2.94 LCZSPTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Zero sequence over current


PTOC
for local criteria

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 99
Status Information

Str ABB_d_dACD Start M

Op ABB_b_dACT Operate M

3.2.95 NS2PTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Negativ phase sequence


PTOC overcurrent protection, 2
Steps

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

TmACrv ABB_aCURVE Operating Curve Type O

3.2.96 PH1BPTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Single phase over-current


PTOC
protection 4 stages for Busbar

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 100


Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

TmACrv ABB_aCURVE Operating Curve Type O

3.2.97 PH1PTOC Revision 1

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Overcurrent function used in


PTOC four-stage protections, one
phase

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

TmACrv ABB_aCURVE Operating Curve Type O

3.2.98 PH3PTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOC Overcurrent function used in

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 101


four-stage protections, three
phase

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate M

TmACrv ABB_aCURVE Operating Curve Type O

3.2.99 SCCVPTOC

PTOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Sudden change in current


PTOC
variation

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_b_dACD Start M

Op ABB_b_dACT Operate M

3.2.100 STBPTOC

PTOC class

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 102


Attribute DATA M/O/E
Explanation Remarks
Name Type /C

PTOC STUB protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Trip M

3.2.101 SAPTOF

PTOF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOF Over-frequency protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start/pick-up signal for M


frequency.

Op ABB_bACT Operate/trip signal for M


frequency.

BlkLoMg ABB_v1SPS Signal indicating internal E


blocking due to low amplitude
of signal from which

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 103


frequency is calculated

3.2.102 COUVPTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Over voltage for MAF of


PTOV Compensated over and
under voltage

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name Plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate O

3.2.103 GF2PTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Over-voltage function for


PTOV General Multipurpose
protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 104


Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate O

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.104 HOLPTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOV for Harmonic over load


PTOV
in IDMT stage capbankprot

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_aACD Start M

Op ABB_bACT Operate O

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.105 HPH1PTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOV for Harmonic over load


PTOV
in DT stage capbankprot

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 105


Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_aACD Start M

Op ABB_bACT Operate O

TmVCrv ABB_dCURVE Operating Curve Type O

3.2.106 LCNSPTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Negatavie sequence over


PTOV
voltage for Local criteria

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name Plate M

Status Information

Str ABB_d_dACD Start M

Op ABB_b_dACT Trip Signal E

3.2.107 LCZSPTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Zero sequence over voltage


PTOV
for local criteria

Data

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 106


Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name Plate M

Status Information

Str ABB_d_dACD Start M

Op ABB_b_dACT Operate O

3.2.108 OV2PTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Overvoltage function for two-


PTOV
step overvoltage protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_aACD Start M

Op ABB_aACT Operate O

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.109 ROV2PTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTOV Overvoltage function for two-

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 107


step overvoltage protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate O

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.110 VDCPTOV

PTOV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Voltage differential function


PTOV
(for US)

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name Plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate O

3.2.111 BUSPTRC

PTRC class

Attribute DATA Explanation M/O/E Remarks

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 108


/C
Name Type

Busbar differential protection


PTRC
bay unit, 1 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Tr ABB_bACT Trip C

Zn1 ABB_v1SPS Bay is connected to zone A E

Zn2 ABB_v1SPS Bay is connected to zone B E

3.2.112 BUTPTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Busbar differential protection


PTRC
bay unit, 3 Phases

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Tr ABB_bACT Trip C

Zn1 ABB_v1SPS Bay is connected to zone A E

Zn2 ABB_v1SPS Bay is connected to zone B E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 109


3.2.113 EF4PTRC Revision 1

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTRC Trip logic for EF4

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate (combination of C


subscribed Op from
protection functions)

Str ABB_bACD Sum of all starts of all O


connected Logical Nodes

OpSOF ABB_v2ACT Trip signal from earth fault E


switch onto fault function

StrSOF ABB_v2ACD Start signal from earth fault E


switch onto fault function

3.2.114 LCCRPTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTRC Carrier receive logic for DTT

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 110


NamPlt ABB_a_dLPL Name plate M

Status Information

Op ABB_a_dACT Operate (combination of C


subscribed Op from
protection functions)

Str ABB_a_dACD Sum of all starts of all O


connected Logical Nodes

3.2.115 NS2PTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Trip logic for Negativ phase


PTRC sequence overcurrent
protection, 2 Steps

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate (combination of C


subscribed Op from
protection functions)

Str ABB_bACD Sum of all starts of all O


connected Logical Nodes

3.2.116 PH1PTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 111


Trip logic for aggregated
PTRC
functions, one phase

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate (combination of C


subscribed Op from
protection functions)

Str ABB_bACD Sum of all starts of all O


connected Logical Nodes

3.2.117 PH3PTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Trip logic for aggregated


PTRC
functions, three phase

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate (combination of C


subscribed Op from

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 112


protection functions)

Str ABB_aACD Sum of all starts of all O


connected Logical Nodes

3.2.118 SMPPTRC

PTRC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTRC Trip logic

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_aACT Operate (combination of C


subscribed Op from
protection functions)

LORs ABB_v1SPC Reset Lockout E Controllable

SPTr ABB_v1SPS Single Pole Trip E

TwoPTr ABB_v1SPS Two Pole Trip E

TPTr ABB_v1SPS Three Pole Trip E

ClsLO ABB_v1SPS Close Lockout E

3.2.119 LPTTR Revision 4

PTTR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Thermal overload, one time


PTTR
constant

Data

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 113


Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Trip M

Str ABB_bACD Start Signal O

AlmThm ABB_aSPS Alarm signal O

BlkRecSt ABB_v1SPS Block AR start E

SenFlt ABB_v1SPS Error signal from the E


temperature sensor

TmmOp ABB_v1_dINS Estimated time to trip E

TmmRsLO ABB_v1_dINS Estimated time to reset of E


lockout

Tmp ABB_bMV Calculated temperature E

TmpAmb ABB_v2MV Ambient temperature E

TmpRl ABB_bMV Temperature relative to E


operate temperature

3.2.120 TRPTTR Revision 3

PTTR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Thermal overload, two time


PTTR
constants

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 114


NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Thermal Overload trip M

Str ABB_bACD Start signal O

AlmThm ABB_aSPS Thermal Alarm O

AlmThm2 ABB_v1SPS Second level Thermal E


overload alarm

LO ABB_v1SPS Thermal Overload lockout E

Wrn ABB_v1SPS Warning signal: Trip within E


set warning time

AClcPct ABB_v2MV Current measured by the E


function in % of rated current

TmmOp ABB_v2MV Estimated time to trip (in min) E

TmmRsLO ABB_v2MV Estimated time to reset of E


lockout (in min)

TmpPct ABB_v2MV Percentage of the E


heatcontent of the
transformer

3.2.121 GF2PTUC

PTUC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Undercurrent for General


PTUC
Multipurpose protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 115


Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

3.2.122 LCP3PTUC

PTUC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Under Current Protection LN


PTUC for Local criterion check in
DTT

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate M

3.2.123 PH3PTUC

PTUC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Three phase undercurrent


PTUC
protection

Data

Common Logical Node Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 116


Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate M

StrDur ABB_v2_dMV Start Duration E

3.2.124 SAPTUF

PTUF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTUF Under frequency protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start/pick-up signal for M


frequency.

Op ABB_bACT Operate/trip signal for M


frequency.

BlkLoMg ABB_v1SPS Signal indicating internal E


blocking due to low amplitude
of signal from which
frequency is calculate

RstLd ABB_v1SPS Restore signal for load E


restoring purposes.

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 117


3.2.125 COUVPTUV

PTUV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Under voltage for MAF of


PTUV Compensated over and
under voltage

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate M

3.2.126 GF2PTUV

PTUV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Undervoltage function for


PTUV General Multipurpose
protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 118


Op ABB_bACT Operate M

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.127 LOVPTUV

PTUV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PTUV Loss of voltage check

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

3.2.128 UV2PTUV

PTUV class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Two step undervoltage


PTUV
protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 119


Str ABB_aACD Start M

Op ABB_aACT Operate M

TmVCrv ABB_aCURVE Operating Curve Type O

3.2.129 LAPPPUPF

PUPF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Under power factor


PUPF
protection LN for LAPP

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Str ABB_a_dACD Start M

Op ABB_a_dACT Operate M

3.2.130 GF2PVOC

PVOC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Overcurrent function for


PVOC General Multipurpose
protection

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 120


Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Start M

Op ABB_bACT Operate M

TmACrv ABB_aCURVE Operating Curve Type (for O


current)

IvdCrv ABB_v1SPS Invalid coefficients for user E


programmable curve

3.2.131 OEXPVPH Revision 2

PVPH class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

PVPH Overexcitation protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Overexcitation alarm limit M


exceeded (instantaneous)

Op ABB_bACT Common trip overexcitation M

OpCrv ABB_aCURVE Time characteristic selection, E


IEE/Tailor rmade

VHzRat ABB_v2_dMV Relative voltage to frequency E


ratio

GenFctFlt ABB_v1SPS General function error E

Alm ABB_aSPS Overexcitation alarm limit E


exceeded (delayed)

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 121


3.2.132 EF4RDIR Revision 4

RDIR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RDIR Directional element for EF4

Data

Common Logical Node Information

Mod ABB_cINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Dir ABB_bACD Direction M

3.2.133 DRPRDRE

RDRE class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RDRE Disturbance recorder

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

RcdMade ABB_a_dSPS Recording made M

FltNum ABB_b_dINS Fault Number M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 122


3.2.134 CCRBRF

RBRF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RBRF Breaker failure protection

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

OpEx ABB_bACT Breaker failure trip (external C


trip)

OpIn ABB_aACT Operate, retrip (internal trip) C

OpEx2 ABB_v2ACT Extarnal trip E

3.2.135 CCSRBRF

RBRF class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Breaker failure protection


RBRF
single phase function

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 123


NamPlt ABB_aLPL Name plate M

Status Information

OpEx ABB_bACT Breaker failure trip (external C


trip)

OpIn ABB_bACT Operate, retrip (internal trip) C

OpEx2 ABB_v2ACT Extarnal trip E

3.2.136 LMBRFLO

RFLO class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RFLO Fault locator

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

FltZ ABB_bCMV Fault Impedance M

FltDiskm ABB_bMV Fault Distance in km M

FltLoop ABB_eINS Fault loop O

FltDisRl ABB_v2MV Distance to fault, relative E

ClcFlt ABB_v1SPS Fault calculation made E

3.2.137 ZMRPSB Revision 1

RPSB class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RPSB Power swing detection

Data

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 124


Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Str ABB_bACD Power swing detected C

BlkZn ABB_aSPS Blocking of correlated PDIS C


zone

ZOuter ABB_v1SPS Measured impedance within E


outer impedance boundary

ZInner ABB_v1SPS Measured impedance within E


inner impedance boundary

3.2.138 SMBRREC Revision 1

RREC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

RREC Autorecloser

Data

Common Logical Node Information

Mod ABB_aINC Mode M

Beh ABB_aINS Behaviour M

Health ABB_cINS Health M

NamPlt ABB_aLPL Name plate M

Status Information

Op ABB_bACT Operate (used here to M


provide close to XCBR)

AutoRecSt ABB_dINS Auto Reclosing Status M

BlkRec ABB_bSPC Block AR/The AR is in O Controllable


blocked state

OpRs ABB_v1SPC Reset counters E Controllable

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 125


RdyRec ABB_v1SPS Indicates that the AR function E
is ready for a new sequence

ActRec ABB_v1SPS Reclosing sequence in E


progress

SucRec ABB_v1SPS Activated if CB closes during E


the time tUnsucCl

UnsRec ABB_v1SPS Reclosing unsuccessful, E


signal resets after the reclaim
time

PrgRec ABB_v1SPS Reclosing shot in progress, E


activated during open time

PrgRec11 ABB_v1SPS Single-phase reclosing is in E


progress, shot 1

PrgRec21 ABB_v1SPS Two-phase reclosing is in E


progress, shot 1

PrgRec31 ABB_v1SPS Three-phase reclosing is in E


progress, shot 1

PrgRec32 ABB_v1SPS Three-phase reclosing is in E


progress, shot 2

PrgRec33 ABB_v1SPS Three-phase reclosing is in E


progress, shot 3

PrgRec34 ABB_v1SPS Three-phase reclosing is in E


progress, shot 4

PrgRec35 ABB_v1SPS Three-phase reclosing is in E


progress, shot 5

Prm1PhOp ABB_v1SPS Permit single-phase trip, E


inverse signal to PREP3P

Prp3PhOp ABB_v1SPS Prepare three-phase trip, E


control of the next trip
opreation

WtMst ABB_v1SPS Signal to Slave issued by E


MAster for sequential
reclosing

Rec1PhCnt ABB_v1INS Counting the number of E


single-phase reclosing shots

Rec2PhCnt ABB_v1INS Counting the number of two- E


phase reclosing shots

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 126


Rec31Cnt ABB_v1INS Counting the number of E
three-phase reclosing shot 1

Rec32Cnt ABB_v1INS Counting the number of E


three-phase reclosing shot 2

Rec33Cnt ABB_v1INS Counting the number of E


three-phase reclosing shot 3

Rec34Cnt ABB_v1INS Counting the number of E


three-phase reclosing shot 4

Rec35Cnt ABB_v1INS Counting the number of E


three-phase reclosing shot 5

TotRecCnt ABB_v1INS Counting total number of E


reclosing shots

EnaRec ABB_v1SPS Reclose enabled E

3.2.139 AUT1RSYN Revision 2

RSYN class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Auto control of synchrocheck


RSYN
and energizing check

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Rel ABB_a_dSPS Release M

VInd ABB_a_dSPS Voltage Difference Indicator O

AngInd ABB_a_dSPS Angle Difference Indicator O

HzInd ABB_a_dSPS Frequency Difference O

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 127


Indicator

DifVClc ABB_b_dMV Calculated Difference in O


Voltage

DifHzClc ABB_b_dMV Calculated Difference in O


Frequency

DifAngClc ABB_b_dMV Calculated Difference of O


Phase Angle

EnOK ABB_v1_dSPS Auto energizing check OK E

TestSCOK ABB_v1_dSPS Auto synchro check OK test E


output

VBus ABB_v2_dMV Voltage amplitude for Bus E


voltage

VLin ABB_v2_dMV Voltage amplitude for Line E


voltage

3.2.140 MAN1RSYN Revision 2

RSYN class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Manual control of
RSYN synchrocheck and energizing
check

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Rel ABB_a_dSPS Release M

VInd ABB_a_dSPS Voltage Difference Indicator O

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 128


AngInd ABB_a_dSPS Angle Difference Indicator O

HzInd ABB_a_dSPS Frequency Difference O


Indicator

EnOK ABB_v1_dSPS Manual energizing check OK E

TestSCOK ABB_v1_dSPS Manual synchro check OK E


test output

3.2.141 SYNRSYN Revision 3

RSYN class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

Auto control of synchrocheck


RSYN
and energizing check

Data

Common Logical Node Information

Mod ABB_c_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Rel ABB_a_dSPS Release M

SynPrg ABB_a_dSPS Synchronising in progress O

FailSyn ABB_v1_dSPS Synchronizing failed E

TestSynOK ABB_v1_dSPS Synchronizing OK test output E

VHiAlmSyn ABB_v1_dSPS Voltage amplitudes for E


synchronizing above set
limits

VIndSyn ABB_v1_dSPS Voltage difference out of limit E


for synchronizing

HzIndSyn ABB_v1_dSPS Frequency difference out of E


limit for synchronizing

HzInBndSyn ABB_v1_dSPS Frequency difference in band E


for synchronizing

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 129


HzRCIndSyn ABB_v1_dSPS Frequency derivative out of E
limit for synchronizing

3.2.142 SXCBR Revision 1

XCBR class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

XCBR Circuit breaker

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Loc ABB_a_dSPS Local operation (local means M


without substation
automation communication,
hardwired direct control)

OpCnt ABB_b_dINS Operation counter M

Pos ABB_c_dDPC Switch position M Controllable

BlkOpn ABB_a_dSPC Block opening M Controllable

BlkCls ABB_a_dSPC Block closing M Controllable

CBOpCap ABB_h_dINS Circuit breaker operating M


capability

BlkUpd ABB_v1_dSPC Block update E Controllable

3.2.143 SXSWI Revision 1

XSWI class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

XSWI Circuit switch

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 130


Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

Loc ABB_a_dSPS Local operation M

OpCnt ABB_b_dINS Operation counter M

Pos ABB_c_dDPC Switch position M Controllable

BlkOpn ABB_a_dSPC Block opening M Controllable

BlkCls ABB_a_dSPC Block closing M Controllable

SwTyp ABB_g_dINS Switch type M

SwOpCap ABB_f_dINS Switch operating capability M

BlkUpd ABB_v1_dSPC Block update E Controllable

3.2.144 TCLYLTC Revision 3

YLTC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

(large) Load Tap Changer,


YLTC
32 Binary Input for tap

Data

Common Logical Node Information

Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 131


Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

EndPosR ABB_a_dSPS End position raise reached M

EndPosL ABB_a_dSPS End position lower reached M

TapChg ABB_b_dBSC Change tap position stop, C Controllable


higher, lower

OpCnt ABB_b_dINS Operation counter value O

CLCnt ABB_v2_dMV Contact life counter value E

CLRs ABB_v1_dSPC Reset contact life counter E Controllable

OpRs ABB_v1_dSPC Reset operation counter E Controllable

CmdFlt ABB_v1_dSPS Alarm for a command without E


an expected position change

ConvFlt ABB_v1_dSPS General tap position E


conversion error

InvPosChg ABB_v1_dSPS Last position change was an E


invalid change

TapChgFlt ABB_v1_dSPS Alarm for none or illegal tap E


position change

TapPosFlt ABB_v1_dSPS Alarm that indicates a E


problem with the position
indication

HiTapPos ABB_v1_dINS High tap position E

LoTapPos ABB_v1_dINS Low tap position E

3.2.145 TCMYLTC Revision 4

YLTC class

Attribute DATA M/O/E


Explanation Remarks
Name Type /C

(mini) Load Tap Changer, 6


YLTC
Binary Input for tap

Data

Common Logical Node Information

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 132


Mod ABB_a_dINC Mode M

Beh ABB_a_dINS Behaviour M

Health ABB_c_dINS Health M

NamPlt ABB_a_dLPL Name plate M

Status Information

EndPosR ABB_a_dSPS End position raise reached M

EndPosL ABB_a_dSPS End position lower reached M

TapChg ABB_b_dBSC Change tap position stop, C Controllable


higher, lower

OpCnt ABB_b_dINS Operation counter value O

CLCnt ABB_v2_dMV Contact life counter value E

CLRs ABB_v1_dSPC Reset contact life counter E Controllable

OpRs ABB_v1_dSPC Reset operation counter E Controllable

CmdFlt ABB_v1_dSPS Alarm for a command without E


an expected position change

ConvFlt ABB_v1_dSPS General tap position E


conversion error

InvPosChg ABB_v1_dSPS Last position change was an E


invalid change

TapChgFlt ABB_v1_dSPS Alarm for none or illegal tap E


position change

TapPosFlt ABB_v1_dSPS Alarm that indicates a E


problem with the position
indication

HiTapPos ABB_v1_dINS High tap position E

LoTapPos ABB_v1_dINS Low tap position E

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 133


4 Common Data Class Extensions

Redundancy supervision CDC (RSS)

The RSS (Redundancy Supervision Status) is used for two purposes:


 Provide supervision information about a supervised IED
 Provide supervision information on the input channels of the supervising IED
For both cases it shall have the following attributes (i.e. the same CDC is used), although their
interpretation is slightly different for each case:

RSS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C
Name
DataName Inherited from Data Class (see below)
DataAttribute
status
stValA BOOLEAN ST dchg TRUE | FALSE: channel A is working M
stValB BOOLEAN ST dchg TRUE | FALSE: channel B is working M
q Quality ST qchg Bad(invalid), if supervision is not working M
t TimeStamp ST Time stamp of last value change of M
stValA or stValB
errRateA INT32U ST Synch or telegram error rate in channel C_O
A, errors per 10 4 telegrams
errRateB INT32U ST Synch or telegram error rate in channel C_O
B, errors per 10 4 telegrams
configuration, description and extension
addr VISIBLE STRING255 CF IP address of supervised source, or M
empty
d VISIBLE STRING255 DC Text, e.g. IED name of supervised O
source
dU UNICODE DC Unicode text O
STRING255
cdcNs VISIBLE STRING255 EX ABB-TN PTUTT05/3201 M
cdcName VISIBLE STRING255 EX RSS M
dataNs VISIBLE STRING255 EX ABB-TN PTUTT05/3201 M
Services
As defined in Table 12 of IEC 61850-7-3, with exception of Substitution
C_O = optional; if one is there, then all must be there
Table 1 Attributes of CDC RSS

The attribute addr contains the IP address of the source to be supervised. At initialisation stValX (X =
A or B) are set to FALSE, q to invalid,and all counters to 0. When supervision starts, stValA and
stValB are set to TRUE when messages arrive on / for this channel.
Attributes errRateA and errRateB contain the rate of messages lost to messages transmitted on the
appropriate channel as telegram error count per 10000 received telegrams, as long as there is no
permanent interruption of the channel. If a permanent interruption (several losses in sequence, or
arrival timeout) appears, then the appropriate stValX is set to FALSE, counting of lost messages
stops, and the rate is set to 100 % (10000). If communication resumes on this channel, then stValX is
again set to TRUE, and counting of messages and erroneous messages continues, starting with rate 0.

Attributes cdcNs and dataNs indicate that this is ABB defined data, and where the definition can be
found.
Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 134


Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 135


5 Enum types Extensions
No Enum types extensions have been made.

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 136


6 Control Block Extensions

No Control block extensions have been made.

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 137


REVISION

Rev. ind. Page (P) Description Date


Chapt. (C) Dept./Init.
A All Initial version TP/TA/RP
B 3.2.16, DO Types changed TP/TA/RP
3.2.37,
3.2.91,
3.2.132,
3.2.141,
3.2.145
C 3.1.1, DO Type changed in chapter 3.1.1, 3.1.3, 3.1.8, 3.2.15, 3.2.79, 091201/
3.1.3, 3.2.144. TP/TA/RP
3.1.8, DO Name changed from Ang to DifAngClc in chapter 3.2.37 and
3.2.15, 3.2.79 and from ImbA to UnbA in chapter 3.2.91
3.2.37,
3.2.79,
3.2.91,
3.2.144
D 3 RSS CDC is added 091209 TP/T
RoSi
E 3.2.15, DO Name changed from TotW to LodW and from TotVAr to 100112/
3.2.16, LodVAr in chapter 3.2.15 and 3.2.16. TPTA/RP
3.2.27, DO Name changed from Ang to VolAmpAng in chapter 3.2.37.
3.2.37,
DO Name changed from DifAClc to DifAClcS and from RstA to
3.2.47,
Amp in chapter 3.2.47.
3.2.79,
3.2.144, DO Name changed from DifAngClc to VolAngClc in chapter
3.2.145 3.2.79.
DO Type changed in chapter 3.2.15, 3.2.16, 3.2.27, 3.2.47.
HiTapPos and LoTapPos deleted in chapter 3.2.144 and
3.2.145
F 3.2.15, LN revision number changed in chapter 3.2.15, 3.2.16, 3.2.37, 100215/
3.2.16, 3.2.119, 3.2.132, 3.2.141, 3.2.144 and 3.2.145. TPTA/RP
3.2.37, DO types changed in chapter 3.2.119
3.2.119,
Attribute Op removed in chapter 3.2.132 and 3.2.141
3.2.132,
3.2.141,
3.2.144,
3.2.145
G 3.2.15, LN revision number changed 100412/
3.2.16, TPTA/RP
3.2.144,
3.2.145

Doc. no. Lang. Rev. ind. Page

ABB AB 1MRK117-792 en G 138