MiCOM P115
Numerical CT and auxiliary voltage
powered overcurrent
relays
AREVA T&D
APPLICATION GLOBAL FUNCTIONS
MiCOM P115 numerical overcurrent protection relays The power supply to the electronic circuits of the
provide optimized and cost efficient solution where no MiCOM P115 has been optimised so that it can trigger
external auxiliary power supply is available or the circuit-breaker with a load current of 0.2 In on at
guaranteed. least one phase.
> Retrofit of old technology relays > Two types of case (HxWxD): flush (183x160x107)
or wall (203x138x95) mounting
> Settings referred to nominal current.
FUNCTIONS OVERVIEW
The hardware architecture and software algorithms > Three-Phase Overcurrent protection (50/51)
have been studied to operate on very short failure
detection times. MiCOM P115 relays provide three phase current
inputs. Three independent stages are available
P115 relay is optional equipped with circuit breaker trip (I>, I>>, I>>>).
output (24VDC, 0.1J) or striker output (12VDC, 0.02J) For I> and I>> the user may independently select
(the striker K1 is offered by Areva). A capacitance definite time delay or inverse time delay with different
discharge output capable of putting out sufficient power type of curves IDMT (IEC SI, VI, EI, UK LTI, STI, RI,
to low energy trip CB coil. Rect, IEEE: MI, VI, EI, US: CO2, CO8).
I>>> can be configured with definite time only.
Thanks of changeover outputs and self-supplying
facility P115 can be used in tripping current transformer
application (current tripping CB coil). > Earth Fault Overcurrent protection (50N/51N)
An external Flag Indicator can be connected to MiCOM P115 relays provide two independent stages
independent energy output (24VDC, 0.01J). earth fault current input (IN> and IN>>).
Communication via USB (Modbus RTU protocol) and For the first stage (IN>) the user may independently
rear RS485 port (Modbus RTU or IEC 103 protocol) select definite time delay or inverse time delay with
allows to download information about settings, different type of curves IDMT (IEC SI, VI, EI, UK LTI,
measurements and inputs, outputs, starting, tripping, STI, RI, Rect, IEEE: MI, VI, EI, US: CO2, CO8).
LEDs status. The second stage (IN>>) can be with definite time only
IDMT (IEC, IEEE, US) time characteristics can be with E/f input, depends on the way of connection
instantaneous, time delayed or IDMT reset. (terminals), can supply or not supply P115.
FUNCTIONAL OVERVIEW
Local Remote
Communication Communication
Event records
Communication 100 Contact output RL4
Binary Input L2
CBF
50BF Binary Input L1
MiCOM P115
Innovative Solution with Compact Design
> Assymetry Overcurrent Protection AREVA Track Record -
MiCOM powered overcurrent relay
Asymmetry overcurrent stage (DT) is based on
>> MiCOM P124 (P124S & P124D)
difference between phase currents and average current
First released in September 2000. Over 13 000 devices installed.
in three phases.
> Circuit Breaker Failure (50BF) > Blocking and Selective Scheme Logic
The circuit breaker failure verifies the effective opening When the P115 relays are used in critical networks,
of CB by dedicated undercurrent threshold. management of protection relays must take
The CBF can be used for tripping upstream circuit too. surrounding devices into consideration. Two digital
inputs can be independently configured to lock any
combination of selected elements (i.e. current stages or
> Two Setting Groups AUX timers)
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
The last 5 faults and 100 logic events are stored in
> I/O Configuration FRAM memory. All events are time stamped to 1ms.
AUTOMATION-L3-P115-BR-04.08-1813-EN - © - AREVA - 2008. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
MiCOM S1 is fully Windows TM compatible.
> Remote trip via Binary Input This Support Software allows to set all parameters in
P115 or download settings parameters, fault and event
Opto isolated binary input can be freely configured to records.
timers AUX1 or/and AUX2. Timers can be used for PC connection with P115 is available via USB port.
ALARM signalling or TRIP of circuit breaker. This
function works if powering of relay is assured.