Chapter four
Over head insulator
The overhead line conductors should be supported on the poles or towers
in such a way that currents from conductors do not flow to earth through
supports i.e., line conductors must be properly insulated from supports.
This is achieved by securing line conductors to supports with the help of
insulators.
The insulators provide necessary insulation between line conductors and
supports and thus prevent any leakage current from conductors to earth.
1- Insulate the conductors from each other and from the towers under
highest voltage and under bad air estimate circumstance
2-Carry the conductors under the bad estimate mechanical stresses
*The materials that used for made the insulators of overhead line are
1- porcelain
2-Tougheneed glass.
Although the two above materials are brittle and inelastic but it are the
best materials that used to insulate the conductors.
Types of insulator:
3. Strain insulators.
When there is a dead end of the line or there is corner or sharp curve, the
line is subjected to greater tension. In order to relieve the line of
excessive tension, strain insulators are used. For low voltage lines (< 11
kV), shackle insulators are used as strain insulators. However, for high
voltage transmission lines, strain insulator consists of an assembly of
suspension insulators as shown in Fig. 8.8. The discs of strain insulators
are used in the vertical plane. When the tension in lines is exceedingly
high, as at long river spans, two or more strings are used in parallel.
4. Shackle insulators.
In early days, the shackle insulators were used as strain insulators. But
now a days, they are frequently used for low voltage distribution lines.
Such insulators can be used either in a horizontal position or in a vertical
position. They can be directly fixed to the pole with a bolt or to the cross
arm. The conductor in the groove is fixed with a soft binding wire.
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
1- C ( self capacitance )
Between the cap of insulator and the pin in the bottom of insulator and its
value of about 30 pf
2- Ce ( air capacitance )
Where Ce is another capacitance between the tower and the connection
point between the pin of each insulator and the cap of the next insulator
and it is have a value of about ( K where k (0.1
The insulator make the distribution of voltage through the insulator of the
string is different (where the insulator that nearest to the conductor has a
higher voltage then the next and up)
(1)
At point B
(2)
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
At point C
(3)
At point D
(4)
If we have n insulator
(5)
(6)
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
(7)
(8)
Where X is the number of insulator that you need to get the voltage across
it.
The voltage across the capacitors ( insulator) are equally ( uniformly). But
this case is a theoretical case because of the air capacitance (ce) that make
the voltage across the insulator are not uniformly. Also the string
efficiency decrease if the number of insulator (n) increase because of the
not equally .
Distribution voltage across the insulators. Many method are used to
increase the string efficiency such as :.
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
2-Grading of units :.
This method depend on the change
Of the self capacitance where
The capacitance that near to
The conductor is greater than
The others due to the location
Of insulator in the string and
The capacitance (self capacitance)
That near to the cross-arm is
Less than the others
If we have four insulator (n =4) and the self capacitance that nearest to
the cross- arm is C then we make a grading for self capacitance in order to
get an equal voltage across the insulators (maximum efficiency)
(
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
At point A
(9)
At point B
(10)
At point C
Ƶ= y+3kc
Ƶ= c(1+3k)+3kc
(11)
And so on
This method is difficult in practical application because of different value
of the capacitance .
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
3) Guard Ring :.
It is possible to make the voltage distribution across the units of string of
insulator uniformly by a guard ring which is a ring of conductor put or
placed across or around the nearest insulator to the conductor .
The main reason of different the Voltage across the insulator of The
string is the air capacitance (Ce) And so that the guarding reduce Ce by
adding a number of Air capacitance between the Conductor or guard ring
and Metal point of insulator and these air capacitances are in opposite by
the effect with Ce and make the voltage across the insulators more
uniformly .
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
Ex1) Over string of five insulator and the ratio of Ce/C=0.1. If the string
is connected to line of voltage 33kv.
1- What is the voltage distribution over the unit of string and what
will be the string efficiency.
2- When the string is supplied by a guard Ring and this lead to add a
two air capacitance of value 0.2c,0.1c respectively to the nearest to
the conductor. Find the new voltage distribution and the new
efficiency.
So1)
0.1c
A
0.1c cc
B
(1) 0.1c
C
c
0.1c
D
c
(2)
Conductor
(3)
(4)
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
c
0.1c
A
At point C
c
0.1c
B
0.1c c
C 0.1c
c
0.1c
D 0.2 c
c
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
At point D
1.299
Now
After guard Ring Before guard Ring
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
C
0.6C
A cf
3C=5Ce
Calculator cd, cf, cg in 0.6C C cg
B
0.6C C cd
C
Conductor
So1) at point A
At point B
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
At point C
So1)
0.15c C V
*1
C
*2
conductor
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
V
C
conductor
Then
The string failed to insulator the conductor from the tower
2) at point A
0.15C C 0.15C
C 0.15C
B
0.15C
C
At point B
conductor
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
1- Find the voltage distribution across the insulators and what is the
string efficiency
2- If the string is supplied by a guard ring and this lead to add a two
Air capacitance of o.2C, 0.1 C respectively to the nearest to the
conductor. Find the new voltage distribution and the new string
efficiency
So1)
C
0.12c
C
0.12c
V
0.12c C
K= 0.12
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
KV
At point B
(1)
POWER SYSTEM ANALYSIS MISSAN UNIVERSITY\ COLLEGE OF ENGINEERING /ELECTRICAL DEP.
C
0.12C
A
0.12C C
B 0. 1C
0.12C C
0. 2C
C
At point C
Also as F before