Sei sulla pagina 1di 1

1 General data

1.1 Details of the project


Rating of the Line = 400 kV,Double Circuit
Type of Monople = PB+9M, Base Extension

1.2 Reference documents


Design document:-
Drawing No.:-
Soil Report No.:-

2 Details of Super Strcuture


2.1 Dimensional details
Height of the monopole = 46 m
Base diameter of the pole = 1.85 m

PCD of the pole = 2.43 m


Outer diameter of the base plate = 2.65 m
Inner diameter of the base plate = 1.7 m

1.4 Unit weight of the soil & concrete


Weight of reinforced dry concrete = 2.4 t/m3
Weight of reinforced wet concrete = 1.4 t/m3
Weight of dry soil = 1.6 t/m3
Weight of wet soil = 0.94 t/m3

1.3 Soil & SBC


Net safe bearing capacity of the soil = 35 t/m2
Net safe bearing capacity of the soil = 43.75 t/m2
(25% increase for wind structures)
Overburden pressure = 3.2 t/m2
Safe bearing capacity=Net safe bearing capacity + Overburden pressure
Safe bearing capacity(Gross bearing capacity) = 46.95 t/m2

Depth of water table from the G.L = 1 m

Soil details
Depth of foundation = 2.0 m
Upper Layer
Thickness of upper layer = 1.20 m
Density of soil = 1.6 t/m3
Density of concrete = 2.4 t/m3
Lower Layer
Thickness of lower layer = 0.80 m
Density of soil = 1.6 t/m3
Density of concrete = 2.4 t/m3