Sei sulla pagina 1di 12

550.

46 -TG1Y (196)

SPLIT-SYSTEM
CONDENSING UNITS

10.00 SEER
HRA018 thru 060
(1.5 thru 5 Nominal Tons)

DESCRIPTION • LOWER INSTALLED COST - Installation time and costs are


reduced by easy power and control wiring connections. Dis-
The HRA Series condensing unit is the outdoor part of a versatile charge line heat exchanger knockouts are provided,if re-
system of air conditioning. It is designed to be custom-matched quired. Available in sweat connect models only. The unit
with one of our complete line of evaporator sections, each de- contains enough refrigerant for matching indoor coils and 15
signed to serve a specific function. Matching Air Handlers are feet of interconnecting piping. The small base dimension
available for upflow, downflow or horizontal application to provide means less space is required on the ground or roof.
a complete system. Electric heaters are available if required.
Add-On coils are available for use with upflow, downflow or • TOP DISCHARGE - The warm air from the top mounted fan
horizontal furnaces. is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.
FEATURES • LOW OPERATING SOUND LEVEL - The upward air flow
• QUALITY CONDENSER COILS - The coil is constructed of carries the normal operating noise up away from the living
copper tube and hardened aluminum fins for durability and area. The rigid top panel effectively isolates any motor sound.
long lasting efficient operation. The decorative 2" X 4" grille Isolator mounted compressor and the rippled fins of the
backed by the black coated fins, enhances appearance and condenser coil muffle the normal fan motor and compressor
protects the unit. operating sounds.

• PROTECTED COMPRESSOR - The compressor is inter- • LOW MAINTENANCE - Long life permanently lubricated
nally protected against high pressure and temperature. This motor- bearings need no annual servicing.
is accomplished by the simultaneous operation of high pres- • EASY SERVICE ACCESS - Fully exposed refrigerant con-
sure relief valve and a temperature sensor which protect the nections, a single panel covering the electrical controls and
compressor if undesirable operating conditions occur. A the molex plug in the control box connecting the condenser
liquid line filter-dryer further protects the compressor. fan, make for easy servicing of the unit.
• DURABLE FINISH - Cabinet is made of pre-painted steel. • SECURED SERVICE VALVES - Secured re-usable service
The pre-treated flat galvanized steel provides a better paint valves are provided on both the liquid and vapor sweat connec-
to steel bond, which resists corrosion and rust creep. Special tions for ease of evacuating and charging.
primer formulas and glossy earth tone finish insure less
fading when exposed to sunlight.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


550.46-TG1Y

COOLING CAPACITY - With Air Handler Coils


AIR HANDLER COOLING
UNIT COIL2
2 ELECTRIC RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
HEAT KW CFM TOTAL SENS. TXV1
1 Phase HRA / NMB & NBF
H1RA018 N2AHD10 5,8,10,13,15 16 G3HC024 650 18.0 12.6 1.97 10.0 — 9.20
H1RA024 N2AHD10 5,8,10,13,15 16 G3HC030 800 24.0 16.9 2.67 10.3 — 9.00
H1RA030 N4AHD14 5,10,15,20,25 22 G3HC036 1000 28.5 19.3 3.17 10.0 — 9.00
H1RA036 N4NHD14 5,10,15,20,25 22 G3HC042 1250 35.5 26.2 3.83 10.3 — 9.30
N2AHD14 5,10,15,20,25 22 G3HC042 1400 40.5 30.0 4.43 10.0 — 9.15
H1RA042
N4AND16 8,10,15,20,25,30 26 G3HC048 1400 41.0 29.4 4.48 10.0 10.3 9.15
N4AHD16 8,10,15,20,25,30 G3HC048 1600 45.0 32.8 4.84 10.3 — 9.30
H1RA048 26
N4AHD20 8,10,15,20,25,30 G3HC060 1600 47.0 34.9 4.95 10.0 — 9.50
H1RA060 N4AHD20 8,10,15,20,25,30 26 G3HC060 1800 56.5 40.3 5.95 — 10.3 9.50

AIR HANDLER COOLING


UNIT COIL
2ELECTRIC RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
HEAT KW CFM TOTAL SENS. TXV1
1 Phase HRA / F1RP or F1RC
F1RC024 5, 7.5, 10 18 — 650 17.5 12.3 1.95 10.0 — 9.00
H1RA018
F1RP024 5, 7.5, 10 18 — 650 17.5 12.3 1.95 10.0 — 9.00
F1RP024 5, 7.5, 10 18 — 800 23.4 16.5 2.60 10.0 — 9.10
H1RA024
F1RP030 5, 7.5, 10, 15 18 — 800 23.6 16.5 2.59 10.0 — 9.00
H1RA030 F1RP036 5, 7.5, 10, 15 21 — 1000 28.0 19.0 3.11 10.0 — 9.40
H1RA036 F1RP036 5, 7.5, 10, 15 21 — 1250 34.0 25.0 3.86 10.0 — 8.80
Rated in accordance with DOE test procedures (Federal Register 12-27-79) and ARI Standards 240.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.

SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1
TXV = Use 1TV0604 TXV kit (for 060 model start assist component not required, due to scroll compressor).
2
To meet Florida R=4.2 insulation code requirements, substitute N1FA for N2AH, N3FA for N4AH, G1FC for G3HC, F1FP for F1RP, and F1FC for F1RC
models. All ratings remain the same.
3
P2MP, P2MPV, and P2UR furnaces and F1RP / F1RC air handlers have B.O.D. standard. P1SP furnace requires B.O.D. accessory (2FD06700224).

** Field transition may be required.

— = Not Applicable.

SOUND RATINGS
SOUND
UNIT MODEL RATINGS
HRA BELS
H1RA UNIT
018 7.6
024 7.8 CERTIFICATION APPLIES ONLY
WHEN USED WITH PROPER
030 8.2 COMPONENTS AS LISTED WITH
ARI
036 8.2
042 8.2
048 8.2
060 8.0

2 Unitary Products Group


550.46-TG1Y

COOLING CAPACITY - With 80% Furnace and Coils


FURNACE COOLING
UNIT COIL
MODEL RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
# MBH CFM TOTAL SENS. TXV1
1 Phase H1RA / UPFLOW FURNACE & COILS
P2MPD083 32 12 G3UA030 650 18.0 12.8 1.96 10.0 — 9.20
H1RA018 P2MPD083 48 G3UA024 18.0 12.8 1.96 10.0 9.20
16 650 —
P2MPD123 48 M3UF032 18.4 13.4 2.04 10.0 9.00
P2MPD083 32 12 G3UA030 800 23.6 17.6 2.62 10.0 — 9.00
P2MPD083 48
G3UA036 24.0 18.2 2.61 10.0 9.20
P2MPD123 48 16 800 —
H1RA024 M3UF032 23.4 17.5 2.60 10.0 9.20
P2MPD123 64
G3UA037 24.0 18.2 2.61 10.0 9.20
P2MPD143 80 22 800 —
M3UF044 24.0 18.2 2.55 10.3 9.40
P2MPD123 48
16 G3UA036 1000 28.5 21.1 3.17 10.0 — 9.00
P2MPD123 64
H1RA030
G3UA037 28.5 21.1 3.17 10.0 9.00
P2MPD143 80 22 1000 —
M3UF044 28.0 20.7 3.11 10.0 9.00
P2MPD123 48
16 G3UA036 1250 34.4 25.4 3.82 10.0 — 9.00
P2MPD123 64
H1RA036 P2MPD163 64
G3UA037 35.0 25.8 3.89 10.0 9.00
P2MPD143 80 22 1250 —
M3UF044 34.0 25.0 3.78 10.0 9.00
P2MPD163 96
P2MPD163 64
P2MPD143 80 G3UA048 41.0 31.0 4.48 10.0 — 9.15
22
P2MPD163 96
H1RA042 1400
P2MPD203 96 G3UA060 42.0 32.1 4.52 10.0 — 9.30
3 G3UA061 42.0 32.1 4.52 10.0 9.30
P2MPD20 112 26 —
M3UF052 40.0 30.6 4.44 10.0 9.00
3
P2MPD16 64
P2MPD203 80
G3UA048 45.0 34.0 4.84 10.0 — 9.30
P2MPD163 96
P2MPD203 96 22
H1RA048 P2MPD163 64 1600
P2MPD163 96 G3UA060 47.0 35.4 4.95 10.0 — 9.50
P2MPD203 96
G3UA061 47.0 35.4 4.95 10.0 9.50
P2MPD203 112 26 —
M3UF052 44.0 32.1 4.78 10.0 9.20
P2MPD203 80
22 G3UA060 56.5 39.9 5.95 — 10.0 9.50
H1RA060 P2MPD203 96 1800
P2MPD203 112 26 G3UA061 56.5 39.9 5.95 — 10.0 9.50
See Notes on Page 2

Unitary Products Group 3


550.46-TG1Y

COOLING CAPACITY - With 90% Furnace and Coils


FURNACE COOLING
UNIT COIL
MODEL RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
# MBH CFM TOTAL SENS. TXV1
1 Phase HRA / UPFLOW FURNACE & COILS
P2URD083 37 14 G3UA030 18.0 12.8 1.96 10.0 — 9.2
H1RA018 P2URD103 55 G3UA024 650 18.0 12.8 1.95 10.0 9.2
17 G1UA024S17 18.0 13.8 1.96 10.0 —
P2URD123 74 M3UF032 18.4 13.4 2.04 10.0 9.0
3
P2URD08 37 14 G3UA030 23.6 17.6 2.62 10.0 — 9.0
P2URD103 55 G1UA024S17 23.8 17.6 2.60 10.0 9.2
G3UA036 24.0 18.2 2.61 10.0 9.2
17 —
H1RA024 P2URD123 74 G1UA036S17
800
24.0 17.2 2.68 10.0 9.0
M3UF032 23.4 17.5 2.60 10.0 9.2
P2URD163 76 G1UA036S21 24.0 17.2 2.68 10.0 9.0
21 G3UA037 24.0 18.2 2.61 10.0 — 9.2
P2URD143 98 M3UF044 24.0 18.2 2.55 10.3 9.4
P2URD103 55 G3UA036 28.5 21.1 3.17 10.0 9.0
17 —
P2URD123 74 G1UA036S17 28.0 20.2 3.15 10.0 8.9
H1RA030 G3AU037 1000 28.5 21.1 3.17 10.0 9.0
P2URD143 98 21 G1UA036S21 28.0 20.2 3.15 10.0 — 8.9
M3UF044 28.0 20.7 3.11 10.0 9.0
G3AU036 34.4 25.4 3.82 10.0 — 9.0
P2URD123 74 17
G1AU036S17 33.4 24.2 3.84 10.0 — 8.8
H1RA036 1250
P2URD163 76 21 G3UA037 35.0 25.8 3.89 10.0 9.0

P2URD143 98 21 G1UA036S21 33.4 24.2 3.82 10.0 8.8
P2URD163 76 21 G3UA048 41.0 31.0 4.48 10.0 — 9.2
P2URD143 98 21 G1UA048S21 41.0 31.5 4.44 10.0 — 9.2
H1RA042 P2URD203 94 21 G3UA060 1400 32.1 4.52 10.0 — 9.3
P2URD203 112 24 G1UA060S24 42.0 32.4 4.44 10.0 — 9.5
P2URD203 130 24 G3UA061 32.1 4.52 10.0 — 9.3
P2URD163 76 21
G3UA048 45.0 34.0 4.84 10.0 — 9.3
P2URD143 98 21
G1UA048S21 45.5 35.0 4.81 10.0 — 9.5
H1RA048 P2URD203 94 21 1600
P2U5D203 112 24 G3UA060 47.0 35.4 4.95 10.0 — 9.5
P2URD203 130 24 G1UA060S24 47.0 36.2 4.85 10.4 — 9.7
P2URD203 94 21 G3UA060 39.9 5.95 9.5
H1RA060 P2URD203 112 24 G1UA060S24 1800 56.5 40.6 6.35 — 10.0 8.9
P2URD203 130 24 G3UA061 39.9 5.95 9.5
See Notes on Page 2

4 Unitary Products Group


550.46-TG1Y

COOLING CAPACITY - With 78% Furnace and "UA" Coils


FURNACE COOLING
UNIT COIL**
MODEL RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
# MBH CFM TOTAL SENS. TXV1
1 Phase HRA / UPFLOW FURNACE & COILS
G1UA024S17 18.0 13.8 1.96 10.0 9.2
H1RA018 P1SPD10 40 17 650 —
G3UA024 18.0 12.8 1.96 10.0 9.2
P1SPD10 40 17 G1UA024S17 23.8 17.6 2.60 10.0 9.2
40 17 G1UA036S17 24.0 17.2 2.68 10.0 — 9.0
P1SPD12 G3UA036 24.0 18.2 2.61 10.0 9.1
H1RA024 60 17 850
60 20 G1UA036S24 24.0 17.2 2.68 10.0 9.0
P1SPD16 —
80 20 G3UA037 24.0 18.2 2.61 10.0 9.2
40 17 G1UA036S17 28.0 20.2 3.15 10.0 8.9
P1SPD12 —
60 17 G3UA036 28.5 21.1 3.17 10.0 9.0
H1RA030 1000
60 20 G1UA036S24 28.0 20.2 3.15 10.0 8.9
P1SPD16 —
80 20 G3UA037 28.5 21.1 3.17 10.0 9.0
40 17 G1UA036S17 33.4 24.2 3.82 10.0 8.8
P1SPD12 —
60 17 G3UA036 34.4 25.4 3.82 10.0 9.0
H1RA036 60 20 G1UA036S24 1250 33.4 24.2 3.82 10.0 8.8
P1SPD16 G3UA037 35.0 25.8 3.89 10.0 — 9.0
80 20 G1UA048S21 35.0 26.6 3.87 10.0 9.1
60 20
P1SPD16
80 20 G1UA048S21 41.0 31.6 4.43 10.0 9.3
H1RA042 80 20 G3UA048 1400 41.0 31.0 4.48 10.0 — 9.2
P1SPD20 100 23 G1UA048S24 42.0 32.4 4.44 10.0 9.5
120 23
60 20
P1SPD16
80 20 G1UA048S21 45.5 35.0 4.81 10.0 9.5
80 23 G3UA048 1600 45.0 32.1 4.84 10.0 — 9.3
P1SPD20 100 23 G1UA048S24 47.0 36.2 4.85 10.4 9.7
H1RA048
120 23
80 23
P1SPD20 100 23 G3UA061 1600 47.0 35.4 4.95 10.0 — 9.6
120 23
80 23
G1UA024S24 56.5 40.6 6.35 10.0 8.9
H1RA060 P1SPD20 100 23 1800 —
G3UA060 56.5 39.9 5.95 10.0 9.5
120 23
See Notes on Page 2

COOLING CAPACITY - With 78% Furnace and "UF" Coils


FURNACE COOLING
UNIT COIL**
MODEL RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
# MBH CFM TOTAL SENS. TXV1
1 Phase HRA / UPFLOW FURNACE & COILS
H1RA018 P1SPD10 40 17 M3UF024 650 18.4 13.4 2.04 10.0 — 9.0
P1SPD10 40 17
40 17 M3UF032 23.4 17.5 2.61 10.0 — 9.2
P1SPD12
H1RA024 60 17 850
60 20
P1SPD16 M3UF044 24.0 18.2 2.55 10.3 — 9.4
80 20
60 20
H1RA030 P1SPD16 M3UF044 1000 28.0 20.7 3.11 10.0 — 9.0
80 20
60 20
H1RA036 P1SPD16 M3UF044 1250 34.0 25.0 3.78 10.0 — 9.0
80 20
See Notes on Page 2

Unitary Products Group 5


550.46-TG1Y

COOLING CAPACITY - With 80% Furnace and Coils


FURNACE COOLING
UNIT COIL
RATED NET MBH SEER/
MODEL MODEL MODEL# MBH W MODEL KW SEER EER
CFM TOTAL SENS. TXV1
1 Phase HRA / HORIZONTAL FURNACE & COILS
40 **
P2HED12
60 ** M3HD024 23.4 17.4 2.60 10.0 10.3
H1RA024 800 9.0
47 ** M3HD036 24.0 17.8 2.67 10.3 —
P1HDD12
69 **
40 **
P2HED12
60 **
H1RA030 M3HD036 1000 28.0 20.8 3.15 10.0 — 8.9
47 **
P1HDD12
69 **
40 **
P2HED12
60 **
P2HED16 80 **
H1RA036 M3HD048 1250 35.0 25.2 3.76 10.3 — 9.3
47 **
P1HDD12
69 **
P1HDD16 92 **
P2HED16 80 **
P2HED20 100 **
H1RA042 M3HD060 1400 41.0 29.4 4.48 10.0 — 9.15
P1HDD16 92 **
P1HDD20 115 **
P2HED16 80 **
P2HED20 100 **
H1RA048 M3HD060 1600 47.0 33.3 4.95 10.3 — 9.5
P1HDD16 92 **
P1HDD20 115 **
P2HED20 100 **
H1RA060 M3HD060 1800 55.6 39.2 5.95 — 10.0 9.5
P1HDD20 115 **
1 Phase HRA/ HORIZONTAL FURNACE AND COILS
P2MPD08 32 16 G3HC024 650 18.0 12.6 1.97 10.0 — 9.2
H1RA018
P2MPD12 48 16 G3HC024 650 18.0 12.6 1.97 10.0 — 9.2
H1RA024 P2MPD12 48 16 G3HC030 800 24.0 16.9 2.67 10.3 — 9.0
H1RA030 P2MPD14 80 22 G3HC036 1000 28.5 19.3 3.17 10.0 9.0
P2MPD14 80 22
H1RA036 G3HC042 1250 35.6 26.2 3.83 10.3 — 9.3
P2MPD16 64, 96 22
P2MPD16 64, 96 22
P2MPD14 80 22 G3HC042 40.5 30.0 4.43 —
H1RA042 1400 10.0 9.15
P2MPD20 80, 96 22
P2MPD20 112 26 G3HC048 41.0 29.4 4.48 10.3
P2MPD16 64, 96 22 G3HC048 45.0 32.8 4.84 10.3 — 9.4
P2MPD20 80, 96 22 G3HC060 47.0 34.9 4.95 10.3 — 9.5
H1RA048 1600
G3HCO48 45.0 32.8 4.84 10.3 — 9.4
P2MPD20 112 26
G3HC060 47.0 34.9 4.95 10.3 — 9.5
P2MPD20 80, 96 22
H1RA060 G3HC060 1800 56.5 40.3 5.95 — 10.0 9.5
P2MPD20 112 26
See Notes on Page 2.

6 Unitary Products Group


550.46-TG1Y

COOLING CAPACITY - With 80% / 90% Furnace and Coils (continued)


FURNACE COOLING
UNIT COIL
MODEL# RATED NET MBH SEER/
MODEL MODEL W MODEL KW SEER EER
MBH CFM TOTAL SENS. TXV1
1 Phase HRA / DOWNFLOW FURNACE & COILS
P2DPD10 48 G3CN030 18.4 13.4 2.00 10.0 9.3
H1RA018 16 650 —
P2CDD10 57 M3CF032 18.4 13.4 2.04 10.0 9.0
P2DPD10 48
P2CDD10 57 G3CN030 24.0 17.9 2.67 10.0 9.0
H1RA024 16 800 —
P2DPD12 64 M3CF032 23.4 17.5 2.60 10.0 9.2
P2CDD12 76
P2DPD10 48
P2DPD12 64
H1RA030 16 G3CN030 1000 28.5 20.5 3.17 10.0 — 9.0
P2CDD10 57
P2CDD12 76
P2DPD12 64
P2CDD12 76 G3CN042 35.6 26.2 3.88 10.0 9.3
H1RA036 22 1250 —
P2DPD16 80 M3CF044 34.0 25.0 3.78 10.0 9.0
P2CDD16 97
80
P2DPD16
H1RA042 92 22 G3CN042 1400 40.5 29.0 4..43 10.0 — 9.15
P2CDD16 97
80
P2DPD16
92 26 M3CF052 44.0 32.1 4.78 10.0 9.2
H1RA048 1600 —
P2DPD20 104 G3CN060 47.0 34.3 4.95 10.0 9.5
P2CDD16 97 22
P2DPD20 104
H1RA060 26 G3CN060 1800 56.5 39.5 5.95 — 10.0 9.5
P2CDD20 114

See Notes on Page 2

Unitary Products Group 7


550.46-TG1Y

COOLING PERFORMANCE
SUCT. T/P AIR TEMP ON CONDENSER SUCT. T/P AIR TEMP ON CONDENSER
MODEL @ COMPR. 75°F 95°F 115°F MODEL @ COMPR. 75°F 95°F 115°F
TEMP. PSIG MBH KW MBH KW MBH KW TEMP. PSIG MBH KW MBH KW MBH KW
35 61.5 16.2 1.66 13.1 1.84 11.0 1.96 35 61.5 35.8 3.83 28.9 4.25 24.2 4.53
40 68.5 17.7 1.67 14.9 1.88 12.8 2.04 40 68.5 39.1 3.86 32.9 4.34 28.2 4.72
H1RA018 H1RA042
45 76.0 19.3 1.69 16.7 1.92 14.2 2.11 45 76.0 42.6 3.90 36.8 4.44 31.3 4.87
50 84.0 20.8 1.70 18.5 1.96 15.9 2.18 50 84.0 45.8 3.93 40.8 4.53 35.0 5.03
35 61.5 21.0 2.23 17.0 2.46 14.2 2.63 35 61.5 39.9 4.18 32.3 4.63 27.0 4.94
40 68.5 22.9 2.24 19.3 2.52 16.5 2.74 40 68.5 43.6 4.21 36.7 4.73 31.4 5.14
H1RA024 H1RA048
45 76.0 25.0 2.27 21.6 2.58 18.3 2.83 45 76.0 47.6 4.26 41.1 4.84 34.9 5.32
50 84.0 26.8 2.28 23.9 2.63 20.5 2.92 50 84.0 51.1 4.28 45.5 4.94 39.0 5.48
35 61.5 25.1 2.68 20.3 2.97 17.0 3.17 35 61.5 49.7 4.85 44.1 5.83 38.5 7.04
40 68.5 27.4 2.70 23.1 3.04 19.7 3.30 40 68.5 54.3 4.89 48.5 5.84 42.6 7.05
H1RA030 H1RA060
45 76.0 29.9 2.74 25.8 3.10 21.9 3.41 45 76.0 58.7 4.97 52.7 5.95 46.6 7.17
50 84.0 32.1 2.75 28.6 3.17 24.5 3.51 50 84.0 63.0 5.02 57.2 6.08 50.5 6.81
35 61.5 30.5 3.28 24.7 3.64 20.6 3.88
40 68.5 33.3 3.31 28.1 3.72 24.0 4.04
H1RA036
45 76.0 36.4 3.35 31.4 3.80 26.7 4.18
50 84.0 39.1 3.36 34.8 3.88 29.9 4.31
NOTES: 1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15° superheat and 15° sub-cooling at condensing unit.
a. Increase capacity 1% for each 2° increase in sub-cooling.
b. Decrease capacity 1% for each 2° decrease in sub-cooling.
3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°.
Maximum recommended condensing temperature is 140°F.

8 Unitary Products Group


550.46-TG1Y

DIMENSIONS
REFRIGERANT
UNIT DIMENSIONS CONNECTION
MODEL
LINE SIZE
HRA
A1 B C LIQUID VAPOR All dimensions are in inches. They are subject
018 17 35 23 5⁄ to change without notice. Certified dimensions
8 will be provided upon request.
024 17 35 23
030 17 35 23
036 19 35 23 3⁄ 3⁄
8 4
042 25 35 23
048 27 37 27 7⁄
8
060 29 37 27
1
B
Includes fan guard
C

1/2", 3/4", 1" DIA.


HOLE OPTIONS 1/2" DIA. HOLE / FINGERED BUSHING
FOR POWER WIRING FOR CONTROL WIRING

LIQUID CONNECTION VAPOR CONNECTION

PHYSICAL AND ELECTRICAL DATA - (1 Phase)


H1RA H1RA H1RA H1RA H1RA H1RA H1RA
MODEL
018 024 030 036 042 048 060
UNIT SUPPLY VOLTAGE 208/230-1-60
NORMAL VOLTAGE RANGE1 187 to 252
MIN. CIRCUIT AMPACITY 12.5 15.6 17.8 21.5 25.5 25.9 36.3
MAX. OVERCURRENT DEVICE AMPS2 20 25 30 35 40 45 60
COMPRESSOR TYPE RECIP RECIP RECIP RECIP RECIP RECIP SCROLL
RATED LOAD 8.5 11.4 13.8 16.1 19.3 20.0 28.0
COMPRESSOR AMPS LOCKED
54 57 75 82 97 110 170
ROTOR
CRANKCASE HEATER NO NO NO NO NO NO NO
FAN MOTOR AMPS RATED LOAD 0.5 0.5 0.5 1.4 1.4 0.9 1.3
MIN. FIELD WIRE SIZE -AWG/LENGTH (ft) 12 / 0-55 10 / 0-83 10 / 0-55 10 / 0-51 10 / 0-49 10 / 0-43
8 / 0-50
75°C COPPER CONDUCTORS, 230V 10 / 56-88 8 / 84-132 8 / 56-89 8 / 52-81 8 / 50-78 8 / 44-68
FAN DIAMETER INCHES 18 18 18 18 18 22 22
RATED HP 1/12 1/12 1/12 1/4 1/4 1/6 1/4
FAN MOTOR NOMINAL RPM 1,100 1,100 1,100 1,100 1,100 850 850
NOMINAL CFM 1,850 1,850 1,850 2,750 2,750 3,250 3,400
FACE AREA SQ. FT. 8.00 8.00 8.00 9.15 12.58 15.72 17.03
COIL ROWS DEEP 1 1 1 1 1 1 1
FIN / INCH 18 18 18 22 20 22 22
LIQUID LINE OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8
VAPOR LINE OD 5/8 5/8 3/4 3/4 3/4 7/8 7/8
UNIT CHARGE, (LBS - OZ)3 3-6 3 - 11 3 - 14 4-5 5-4 7-5 7 - 12
CHARGE PER FOOT, OZ 0.66 0.66 0.68 0.68 0.68 0.70 0.70
OPERATING WEIGHT, LBS. 118 123 132 137 161 176 200
1
Utilization range “A” in accordance with ARI standard 110.
2
Dual element fuses or HACR circuit breaker.
3
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other
than 15 feet, add or subtract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.

Unitary Products Group 9


550.46-TG1Y

TYPICAL INSTALLATION - HRA018 THRU 060

TO FURNACE OR
18" SERVICE THERMOSTAT AIR HANDLER
ACCESS CLEARANCE TERMINAL BLOCK
60" OVERHEAD
CLEARANCE WEATHERPROOF
DISCONNECT
SWITCH NEC CLASS 1 WIRING
NEC CLASS 2 WIRING

10" CLEARANCE TO INDOOR COIL


COIL AREA

SEAL OPENING(S) WITH PERMAGUM


OR EQUIVALENT

CONTROL ACCESS NOTE: ALL OUTDOOR WIRING MUST


PANEL BE WEATHERPROOF

TYPICAL FIELD WIRING

ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60 POWER
FURNACE OR AIR HANDLER CONTROL
TERMINAL BLOCK
24 VOLT FACTORY
CONTROL
C Y R G W
WIRING

CONTACTOR
TERMINALS

GROUND COIL * * Terminal W is only required on


Y R G W
SCREW systems with heat.
HRA CONDENSING UNIT ROOM THERMOSTAT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

10 Unitary Products Group


550.46-TG1Y

ACCESSORIES
Refer to Price Manual for specific model numbers. Hard Start Kit (Single Phase Units) - provides required start-
ing torque for used with thermal expansion valve.
Compressor Blanket - Designed to further reduce the normal
operating sound and is required to meet Canadian sound levels Outdoor Thermostat - 2TD06700124 - Consists of an adjust-
for units of three tons and below. able outdoor thermostat and relay in a vented enclosure. It
provides additional second stage control of the supplemental
Stub Adapters - Available to adapt sweat connect units to quick resistance heat. (balance point control)
connect coils or sweat connect coils to quick connect units.
Room Thermostats - One of the following thermostats may be
Precharged Line Sets - Available in 15, 25, 35 and 50 foot used with these systems.
lengths for connection of quick connect models. Outdoor liquid
ends have F-6 connectors, vapor ends have F-11 connectors. 2ET07700324 - Programmable electronic, One Stage Heat /
Indoor liquid ends have M-6 connectors, vapor ends have M-11 One Stage Cool, Manual change over.
connectors. All indoor vapor ends are provided with a 90° bend.
2TH07700124 - One Stage Heat / One Stage Cool, manual
A 30 foot line set with straight ends is available for splicing to
other lines for longer runs. All vapor lines are insulated with 1/2 changeover, non-programmable
sponge rubber.
Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for
approximately one minute after cooling thermostat has been
satisfied.

Unitary Products Group 11


MATCHING INDOOR COMPONENTS
Add-On Coils - For Furnace Application


UPFLOW
G1UA,
3 6
G3UA or
G2UT

1 4

2 5


UPFLOW
M3UF

Air Handlers - For Non-Furnace Application

F1RP / F1RC
FAN COIL UNITS

HORIZONTAL
M3HD
N1VS, N2AH
N4AH
or
N1FA, N3FA
BLOWER

➁ G3HC
DOWNFLOW or
G3CN G1FC
COIL

➃ UPFLOW ➃ UPFLOW
➅ HORIZONTAL ➄ DOWNFLOW
➁ ➅ HORIZONTAL
DOWNFLOW
G3CF

Unitary Products Group


P.O. Box 1592, York, Pennsylvania USA 17405-1592
Subject to change without notice. Printed in U.S.A.
Copyright  by York International Corporation 1996. All Rights Reserved. 550.46-TG1Y
Supersedes: 550.46-TG1Y(1095)

Potrebbero piacerti anche