The cabinet control unit (CCU) processes the environment information collected from relevant
sensors to monitor the environment parameters, including temperature in the cabinet, door
status, smoke and water. The CCU communicates with the network management center
through a network interface, and reports the data to the network management system.
Upgrade Overview
The CCU monitors the environment parameters collected by the sensors in real
time, and reports the alarm information to the control system. Therefore, make sure
that the connections from the sensors to the CCU, from the CCU to the control
system are correct.
Upgrade Overview
MA5600T(config)#meth l2-forward vlan 10 enable // Enable the Layer 2 forwarding function on the meth port
NOTE:
Some details for the snmp profile: Testname, C0mm1ss10n@1 , C0mm1ss10n@2 should be the same with
which on U2000 when add SNMP profile, the port select 161 on U2000.
MA5600T(config)#nac enable master meth // Enable the Neighbor Automatic Communication (NAC)
function of meth port and indicating that the MSAN is the master node.
MA5600T(config)#nac config master meth slave vlan 10 ip-address 172.20.31.3 mask 255.255.255.0
gateway 172.20.31.1 snmp-profile-id 1 //The nac config command is used to send settings to a slave
node (CCU) supporting the NAC function.
Upgrade Overview
1. File--->New-->Create NE
2. Input the correct CCU IP address: 172.20.31.3
3. Select the SNMP Parameters
testccu Step 1
Step 2
Step 3
Step 4
Step 5
C0mm1ss10n@2 C0mm1ss10n@1
C0mm1ss10n@2 C0mm1ss10n@1
5. Perform the following step 1 with clicking the button, if CCU is displayed on
device name list, then confirm with OK, finally the CCU will be normal on the
Main Topology.
Step 1
testccu
Step 2
Upgrade Overview
During the setting, you are required to specify the slot ID and senor ID. You can run the display
sensor number command to query the sensor IDs.
2. Run the set sensor alarm enable command to enable the sensor to report alarms. The
alarms of a sensor can be reported only after the sensor is enabled to report alarms. By
default, the sensor is disabled from reporting alarms except the analog parameter
threshold-crossing alarms.
3. (Optional) Run the set sensor alarm level command to set the alarm level of the sensor.
NOTE: Only dry contact sensors require the setting of the alarm level. By default, the system
deems the high level as an alarm being generated. It is not advisable to change the system
default alarm level.
4. Run the set analog sensor fault alarm enable command enable the analog sensor to report its
fault alarms.
5. Run the set fan alarm enable command enable alarm reporting for a fan.