Sei sulla pagina 1di 20

Intelligent Site

Cabinet Control Unit


CCU05D-02

www.huawei.com

Name: Abdellah TADJINE


ID: 00319643

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential


Contents

The Cabinet Control Unit CCU05D-02

Checking Environment Monitoring Cables

CCU configuration on MA5600T

Adding CCU on U2000

Configuration of CCU environment monitoring

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 2


The Cabinet Control Unit CCU05D-02

The cabinet control unit (CCU) processes the environment information collected from relevant
sensors to monitor the environment parameters, including temperature in the cabinet, door
status, smoke and water. The CCU communicates with the network management center
through a network interface, and reports the data to the network management system.

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 3


Contents

Upgrade Overview

Checking Environment Monitoring Cables

CCU configuration on MA5600T

Adding CCU on U2000

Configuration of CCU environment monitoring

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 4


Checking Environment Monitoring Cables (1/2)

The CCU monitors the environment parameters collected by the sensors in real
time, and reports the alarm information to the control system. Therefore, make sure
that the connections from the sensors to the CCU, from the CCU to the control
system are correct.

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 5


Checking Environment Monitoring Cables (2/2)

The below picture shows the connections of environment monitoring cables in


the F01T500 cabinet

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 6


Contents

Upgrade Overview

Checking Environment Monitoring Cables

CCU configuration on MA5600T

Adding CCU on U2000

Configuration of CCU environment monitoring

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 7


CCU configuration on MA5600T (1/2)

MA5600T(config)#meth l2-forward vlan 10 enable // Enable the Layer 2 forwarding function on the meth port

MA5600T(config)#snmp-profile add profile-name testccu //name of the SNMP management profile.


{ profile-id<K>|v1<K>|v2c<K>|v3<K> }:v3 // SNMP version V3
{ username<S><Length 1-32> }:Testname //Uniquely identifies an SNMPv3 user
{ authentication-mode<E><hmac-sha,hmac-md5>|des-ip<I><X.X.X.X> }:hmac-sha // Authentication mode
{ authkey<S><Length 8-64> }:C0mm1ss10n@1 // Authentication password
{ des-ip<I><X.X.X.X>|privacy-mode<E><aes256,aes192,aes128,3des168,des56> }:aes128 // Encryption mode
{ prikey<S><Length 8-64> }:C0mm1ss10n@2 // Encryption password
{ des-ip<I><X.X.X.X> }:192.168.116.3 // Destination address for trap (U2000 server)
{ dest-port<U><1,65535> }:162 //UDP port
{ securitylevel<E><privacy,authentication,noauthnopriv> }:privacy // Trap security level

snmp-profile add profile-name testccu v3 Testname hmac-sha C0mm1ss10n@1 aes128 C0mm1ss10n@2


192.168.116.3 162 privacy
Adding a SNMP profile succeeded
Profile ID : 1
Profile name: testccu

NOTE:
Some details for the snmp profile: Testname, C0mm1ss10n@1 , C0mm1ss10n@2 should be the same with
which on U2000 when add SNMP profile, the port select 161 on U2000.

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 8


CCU configuration on MA5600T (2/2)

MA5600T(config)#nac enable master meth // Enable the Neighbor Automatic Communication (NAC)
function of meth port and indicating that the MSAN is the master node.

MA5600T(config)#nac config master meth slave vlan 10 ip-address 172.20.31.3 mask 255.255.255.0
gateway 172.20.31.1 snmp-profile-id 1 //The nac config command is used to send settings to a slave
node (CCU) supporting the NAC function.

MA5600T(config)#display nac slave info


{ <cr>|detail<K>|master<K> }:
Command:
display nac slave info
-----------------------------------------------------------------------------
F/S/P Auto-find-result Config-result Slave-type
-----------------------------------------------------------------------------
MEth0 Found Added successfully CCU
-----------------------------------------------------------------------------
Total: 1

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 9


Contents

Upgrade Overview

Checking Environment Monitoring Cables

CCU configuration on MA5600T

Adding CCU on U2000

Configuration of CCU environment monitoring

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 10


Adding CCU on U2000 (1/3)

1. File--->New-->Create NE
2. Input the correct CCU IP address: 172.20.31.3
3. Select the SNMP Parameters

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 11


Add CCU on U2000 (2/3)
4. Set Default SNMP Parameters window, and perform step 1~step 5, then OK

testccu Step 1

Step 2
Step 3

Step 4
Step 5
C0mm1ss10n@2 C0mm1ss10n@1
C0mm1ss10n@2 C0mm1ss10n@1

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 12


Add CCU on U2000 (3/3)

5. Perform the following step 1 with clicking the button, if CCU is displayed on
device name list, then confirm with OK, finally the CCU will be normal on the
Main Topology.

Step 1

testccu

Step 2

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 13


Contents

Upgrade Overview

Checking Environment Monitoring Cables

CCU configuration on MA5600T

Adding CCU on U2000

Configuration of CCU environment monitoring

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 14


Configuration of CCU environment monitoring
data (1/5)

During the setting, you are required to specify the slot ID and senor ID. You can run the display
sensor number command to query the sensor IDs.

CCU(config-if-ccu)#display sensor number


CCU Sensor Number:
*************************************************************
Sensor Sensor Number
TEM0 1
TEM1 2
TEM2 3
WATER 4
SMOKE 5
GATE 6
IN0 7
IN1 8
IN2 9
IN3 10
IN4 11
IN5 12
IN6 13
*************************************************************
EEU Sensor Number:
*************************************************************
Sensor Sensor Number
ALM_IN 1
DI0 2
DI1 3
DI2 4
DI3 5
DI4 6
A0 7
A1 8
A2 9
A3 10
*************************************************************

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 15


Configuration of CCU environment monitoring data
(2/5)

1. Log in to the CCU CLI.


The access to CCU is through SSH. From MSAN use the command stelnet to log into CCU.
The default user name is root and password is Huawei@ccu123.

2. Run the set sensor alarm enable command to enable the sensor to report alarms. The
alarms of a sensor can be reported only after the sensor is enabled to report alarms. By
default, the sensor is disabled from reporting alarms except the analog parameter
threshold-crossing alarms.

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 16


Configuration of CCU environment monitoring data (3/5)

CCU(config-if-ccu)# set sensor alarm enable 0 1 0


CCU(config-if-ccu)# set sensor alarm enable 0 2 0
CCU(config-if-ccu)# set sensor alarm enable 0 3 0
-slot num
CCU(config-if-ccu)# set sensor alarm enable 0 4 0 -Indicates the sensor ID (5: SMOKE)
CCU(config-if-ccu)# set sensor alarm enable 0 5 0 -Enables or disables alarm reporting for the sensor
(0: Enable 1: Disable)
CCU(config-if-ccu)# set sensor alarm enable 0 6 0
CCU(config-if-ccu)# set sensor alarm enable 0 6 0
CCU(config-if-ccu)# set sensor alarm enable 0 7 0
CCU(config-if-ccu)# set sensor alarm enable 0 8 0

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 17


Configuration of CCU environment monitoring data (4/5)

3. (Optional) Run the set sensor alarm level command to set the alarm level of the sensor.
NOTE: Only dry contact sensors require the setting of the alarm level. By default, the system
deems the high level as an alarm being generated. It is not advisable to change the system
default alarm level.

4. Run the set analog sensor fault alarm enable command enable the analog sensor to report its
fault alarms.

CCU(config-if-ccu)#set analog sensor fault alarm enable 0 1 0


CCU(config-if-ccu)#set analog sensor fault alarm enable 0 2 0
CCU(config-if-ccu)#set analog sensor fault alarm enable 0 3 0

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 18


Configuration of CCU environment monitoring data (5/5)

5. Run the set fan alarm enable command enable alarm reporting for a fan.

CCU(config-if-ccu)#set fan alarm enable 0 0


CCU(config-if-ccu)#set fan alarm enable 1 0
CCU(config-if-ccu)#set fan alarm enable 2 0
CCU(config-if-ccu)#set fan alarm enable 3 0

HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Confidential 19


Thanks!
www.huawei.com

Potrebbero piacerti anche