DESIGN CALCULATIONS
Capacity = 1TR = 3.5 KW
Concentration of NH3 in refrigerant, Xr = 0.98
Concentration of NH3 in solution, Xs = 0.42
Concentration of NH3 in absorbent, Xw = 0.38
Temperature of the evaporator, TE = -15℃
Generator or condenser pressure, PH = 10.7 bar
Evaporator pressure, PL = 2.4 bar
Temperature of the condenser, TC = 54℃
Temperature of the absorber, TA = 52℃
Temperature of the generator, TG = 120℃
State Points Pressure in Temperature in Specific enthalpy
bars ℃ (h) in KJ/Kg
1 10.7 54 1200
2 10.7 54 330
3 2.4 - 15 330
4 2.4 - 15 1450
5 2.4 52 - 110
6 10.7 52 180
P2 = 10.7 bar
X2 = 0.98
T2 = 54℃
h2 = 330 KJ/Kg
@ point 3
h2 = h3 = 330 KJ/Kg
T3 = - 15℃
P3 = 2.4 bar
@point 4
P4 = 2.4 bar
T4 = - 15℃
h4 = 1450 KJ/Kg
QE = mr (h4 – h3)
3.5 = mr (1120)
mr = 3.125 gm/s
Using mass balance equation
ms = m w + mr
mw = 43.75 gm/s
Design of Evaporator
θ1 = 45℃ θ2 = 5℃
45−5
θm = ¿ ln 45
( )
5
θm = 18.205℃
U = 1000 W/m2
QE = FUAEθm
AE = 0.3845 m2
0.39 = nπDL ; D = 0.008 m
nL = 15.51 m
Design of condenser
Xr = 0.98 θ2 = 9℃
Tc1 = 30C
24−9
Tc2= 45C θm = ¿ ln 24
( )9
QC = mr (h1 – h2)
QC = 2.718 KW
U = 1000 W/m2
F=1
QC = FUACθm
AC = 0.266 m2
AC = n π D L
nL = 10.58 m
Design of Generator
= 15125 – 8437.5
= 6687.5 = 6.687 KW
Design of absorber
QA = 21.062 KW
QE
COP = QG
3.5
=
6.687
COP = 0.523