Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
GA 90 – 160 A/W
Introduction:
Good product performance is dependent on a good installation. Poor installation can
affect machine performance. It can also create costly service problems.
Storage instructions:
(Valid for 3 months)
Don’t store the machine out in the air. Store the compressor, preferably indoors, in a
clean dry place.
Cover up the unit with tight fitting plastic or canvas, so as to avoid ingression of dust and
moisture.
Place the unit on a clean and level floor. The floor should be well ventilated. The floor
should be free from vibration or pulsation emanating from nearby machinery.
Make sure all coolant is drained and all connections closed off in water cooled units.
Avoid extreme ambient conditions (Temperature and moisture)
Min/Max ambient temperature during storage is 0 and 45 deg cel.
Once every two weeks, turn the motor/compressor coupling 10 turns by hand in order to
redistribute the oil (or grease) film on all moving parts.
4 slotted hole (small) provided in compressor frame which can be used for horizontally
pulling compressor out of container.
Compressor can be moved by lift truck using the slots (big) in the frame and ensure that
the folks protrude from the other side of the frame.
Compressor can also be lifted after inserting beams in the slots and ensure that beams
cannot slide and that they protrude from frame equally.
The chains must be held parallel to the bodywork by chain spreaders in order not to
damage the compressor.
The lifting equipment must be placed in such a way that the compressor will be lifted
perpendicularly.
Foundation:
Foundation bed should be flat surface and should have sufficient bearing capacity.
For ventilation proposal, minimum distance between the top of the body work and the
ceiling is 1200 mm.
If more compressor (Air cooled) in one room, it is advisable to provide ducting even
distance between top of the compressor body work and ceiling is around 1200 mm.
Distance between two compressors should be minimum of 1600 mm and distance
between compressor & wall should be minimum of 1600 mm.
Ventilation:
Air cooled machines must be installed in such a way that an adequate flow of cooling air
is available and that the exhausted air doesn’t recirculate to the compressor air inlet or
cooling air inlet.
Inlet grid (s) and ventilation fan should be installed in such a way that any recirculation
of cooling air to the compressor is avoided.
The air velocity to the grid (s) has to be limited to 5 m/s
For alt. 2, 3, 4 the maximum allowable pressure drop over cooling air duct is 30 Pa
For alt. 1, 3, required ventilation to limit the compressor room temperature can be
calculated from
Qv = 0.1 N/Delta T
Qv is the required ventilation capacity (m3/sec)
N is the shaft pf the compressor (kw)
Delta T is the compressor room temperature over the outdoor temperature
Ducting procedure:
Ducting should be individual and it should not be connected together between
compressors.
Compressor suction should not have any obstruction and if any suction duct provided,
Hot air exhaust ducting should not reduce from compressor grating. Poorly designed
ducting can lead to overheating of compressor.
Piping:
In system with a large distribution network it is preferable to have the compressor located
centrally in order to minimize piping between the compressor and the farthest work
station in the plant.
The compressor system should be arranged to minimize the number of valves, fittings
and flow obstruction in order to reduce pressure drops.
Isolation valve should be installed (Not in ACIL scope) in compressor discharge air
outlet line. It should be closed whenever compressor not in operation.
For water cooled compressor, shut off valves should be provided in water line (in and
out) pipes (Not in ACIL scope) and water drain valve should be provided in water in &
out pipe.
Delivery pipe:
Maximum length of pipe can be calculated from,
L = (Delta P * d5 * p) / 450 * (Qc power of 1.85)
Where,
L : length of pipe in meter
Delta P : max allowable pressure drop in bar (recommended is 0.1 bar)
d : inner dia of pipe in mm
p : absolute pressure at the compressor outlet in bar
Qc : Compressed FAD in l/s
Pressure drop over the air outlet pipe can be calculated as follows
It is recommended that the connection of the compressor air outlet pipe is made on top of
the main air net pipe to minimize carry over of possible remainder of condensate
When air receiver is placed after the compressor air outlet, the air receiver will act as
safety buffer which will prevent condensate from flowing back into the compressor.
Piping has to be aligned properly in the compressor. There should not be any stress on the
piping.
Technical data’s:
Compressor Pressure ranges Oil capacity Cooling water flow (l/s) –
model (bar) (liter) (temp rise 10 deg cel)
GA 90 A 7.5 /8.5 /10 /13 69
GA 110 A 7.5 /8.5 /10 /13 75
GA 132 A 7.5 /8.5 /10 /13 93
GA 160 A 7.5 /8.5 /10 /13 100
GA 90 W 7.5 /8.5 /10 /13 63 2
GA 110 W 7.5 /8.5 /10 /13 63 2.5
GA 132 W 7.5 /8.5 /10 /13 85 3
GA 160 W 7.5 /8.5 /10 /13 85 3.6
Commissioning procedures:
Gearbox, Motor is fixed with two metal spacers for transit purpose. Remove the metal
spacers before commissioning the compressor. Don’t start the compressor without
removing metal spacers.
Ensure installation as mentioned above
For water cooled compressors, flush the water line pipes before connecting. Check that
the cooling water drain valves (customer installation) in the inlet and outlet lines are
closed and that the water shut off valves (customer installation) are open and check for
water flow
On full feature compressor check that the dryer by-pass valve is closed and that the dryer
inlet and outlet valves are open.
Ensure the oil level is proper in oil tank
Check whether proper lugs are provided in electric cable and confirm the tightness of
electrical cables. Check that earthing connection provided properly and megger the
motor.
Check incoming voltage and Transformer T1 & T2
Check wirings and ensure that there are no loose connections
Ensure the main fuses are as mentioned above
Check the motor rotation direction by bumping the motor. On air cooled compressor,
check rotation direction of the cooling fan motor.
Ensure the discharge pressure settings as required
Set the drive motor OLR, cooling fan motor OLR and ensure the correctness of the same
Ensure the compressor discharge valve in open condition
Start the compressor and run at unload for few minutes. Stop the compressor and top up
the oil if required.
Run the compressor at unload and check that it operates normally.
Load the compressor and observe running parameters and ensure that it operates
normally.
Check the current of main drive motor and compare with the limit ranges
Check correctness of sensors, electrical interlocking
Observe compressor running parameters for at least 2 to 3 hours
Ensure there are no air/oil leakages
Check and confirm loading/unloading cycle
Check whether manual/auto drains are working properly
Customer should be informed to monitor whether condensate is draining automatically
SPM values:
Alert level: reference level during limit for new unit +20 dB
SPM Measurement points:
Service schedule:
Service activities
Pre commissioning report
Commissioning report